Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹33.9 L+₹7.6 L (28.8%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical not qualified in Technical evaluation | |
| 4 | Not Admitted-Fee/PreQual/Technical 108 3 CHANDAR NAGAR DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | - | Not Admitted-Fee/PreQual/Technical Others-Original Bid documents not received. | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-सà¥à¤Ÿà¤¾à¤®à¥à¤ª पेपर/affidavit वांछित पà¥à¤°à¤¾à¤°à¥‚प में न होने के कारण(à¤à¤•ल सà¥à¤Ÿà¤¾à¤®à¥à¤ª संलगà¥à¤¨) निविदा non responsive पायी गयी। |
Tender Value
Refer Docs
EMD Value
₹74,000
Closing Date
11 Dec 2023, 5:00 pmClosed
Executive Engineer
Executive Engineer E/M Division P.W.D., Dehradun
S.I.T.C. of 60 KW Solar power Plant under RCS UDAAN-2 at Sahastradhara Road, Dehradun, Uttarakhand.
2023_pwd_65818_1
2081/Nivida Dt. 14.11.2023
Open Tender
Solar Power Plants
Item Rate
120 days
Dehradun
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,950
Executive Engineer E/M Division P.W.D., Dehradun
₹74,000
Dehradun
30 Jan 2024
23 Nov 2023
13 Dec 2023
23 Nov 2023
11 Dec 2023
23 Nov 2023
30 Nov 2023
Amount
Supply, Installation, Testingand Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- a)Solar Photovoltaic Module of capacity 330Wp or above, manufactured in India, conforming to IS14286/IEC61215, IS/IEC61730-Part-1, IS/IEC61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 18.5%. PV modules used in solar power plants/ systems must be warranted for their out put peak watt capacity, which should not be less than 90%at the end of 10 years and 80% at the end of 25 years. b)Power Conditioning Unit(PCU)of 350-800 VDC Input voltage range and 400 VAC, three phase, 4wire, 50Hz+/-2.5Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d)Fixing of Array junction box & Main junction box with IP65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor1.1kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.
SONIC ENGINEERING & AUTOMATION
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .