| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹71.4 LAccepted-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L1 | Accepted-AOC LOWEST BID | |
| 2 | L2₹71.4 L+₹5,545.19 (0.08%)Rejected-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-Finance HIGHER BID | |
| 3 | L3₹71.7 L+₹31,516.35 (0.44%)Rejected-Finance 300 GOPAL NIWAS 3 A ROAD SARDARPURA JODHPUR CITY RAJASTHAN 342003 | JODHPUR | RAJASTHAN | 342003 | L3 | Rejected-Finance HIGHER BID | |
| 4 | L4₹78.0 L+₹6.6 L (9.28%)Rejected-Finance | L4 | Rejected-Finance HIGHER BID | |
| 5 | L5₹78.4 L+₹7.0 L (9.82%)Rejected-Finance | L5 | Rejected-Finance HIGHER BID |
Tender Value
₹72.8 L
EMD Value
₹1.3 L
Closing Date
28 Feb 2023, 6:00 pmClosed
CWE AF JODHPUR
HQ CWE AF JODHPUR 342011 RAJASTHAN
PROVN OF STAND BY POWER SUPPLY, DE-HUMIDIFIER AND ACS FOR FMS AF STN JODHPUR
2023_MES_578035_1
85972/E8
Open Tender
Electrical and Maintenance Works
Item Rate
GE AF JODHPUR
As per NIT
7 documents required · 7 mandatory
₹1,000
GE AF JODHPUR
₹1.3 L
Yes
6 Jul 2023
31 Jan 2023
2 Mar 2023
31 Jan 2023
28 Feb 2023
14 Feb 2023
Amount
Supplying, installing, testing & commissioning of factory assembled Diesel Engine driven generating set including acoustic enclosure as per current CPCB norms automatic mains faillure panel fully wired alternator AC to give an output of 320 KVA /256 KW,continuously rating at a PF of 0.8 lagging, 415 volts , AC 3 phase 4 wire 50 HZ ,1500 RPM, Governing class (As per ISO 8528 Part-V) directly coupled with diesel engine water cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads & other accessories etc comprising of following:- Diesel engine : Water cooled turbocharger of suitable BHP at 1500 RPM confirming to BS 5514 & ISO 3046 with an overload capacity of 10 % for one hour in any 12 continuous hours operation and designed and tested for 50°C ambient temperature with standard fittings. Alternator:- 320 KVA alternator, 3 phase, Power factor:- 0.8, Rated generating voltage:- 230/415V, screened protected, revolving field, self excited, self regulated through an AVR, the alternator has following features:-(i) 'H' class insulation (ii) IP23 protection with insulation class H (iii) +/- 1.0% voltage regulation (maximum) in static condition (iv) permissible overload of 10% for one hour in 12 hours of operations Control Panel : Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish. including the following:- PowerCommand Controller Aluminum bus bars with suitable capacity with incoming/ outgoing terminals Indicating lamps for ‘Load ON’ and ‘Set Running’ Instrument fuses duly wired and ferruled MCCB of suitable rating with overload and short circuit protections
AMF panel: AMF Panel outdoor type, 320 KVA DG Set with alluminium busbar of capacity 800 Amps, TPN powder coated (coloured ) heat shrinkable sleeves, 3.15 mm CRCA sheet steel enclosure duly powder coated and inbuilt on load change over switch of 600Amps consisting the following:- INCOMING from 320 KVA(i) MCCB 600 Amp thermal magnetic release type FP 36 KA - 01 No(ii) Spreaders 600 Amps FP - 01 Set(iii) Extended Rotary handle 600 Amps FP - 01 No (iv) Earth fault module - 01 No (v) Power Contactor 600 Amp FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 Volts AC - 01 No (vi) C.T. 600/5A CL-1.0 10 VA - 03 Nos (vii) Digital MF meter 96 x 96 mm with 485 Port CL 1.0 - 01 No (viii) Indicating lights (Red-4, Yellow-2. Green-2) (ix) Control MCB 6A SP 10 KA C curve (x) VMR - 01 No (xi) In built on load change over switch 600 A for bypassing of AMF panel - 01 No Outgoing (i) MCCB 600 Amp FP 36 KA - 01 No (ii) Power Contactor 600 Amps FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 V AC - 01 No (iiI) AMF relay (iv) SMPS 12/24V, DC, 10A - 01 No (v) Emergency stop P.B - 01 No (vi) Digital Amp meter 12, DC - 01 No (vii) Digital Volt meter 12/24V, DC - 01 No (viii) Control MCB 6A SP 10 KA C Curve (ix) Hooter - 01 No (x) PROCOM UNIT (DGC6D) FOR control - 01 No Acoustic Enclosure : Powder coated weather proof canopy. Engine and alternator mounted on AVM mounts, with silencer and SS exhaust below optimised to meet stringent CPCB norms for sound and emission, Baserail with drawout type fuel tank, drain plug, inlet and outlet connections, airvent, level gauge etc PCC Plateform : size as per OEM recommendation Batteries : Volts and AH as per OEM.
Material & labour for earthing complete with galvanised steel earth electrode 60cmx60cmx6mm buried directly in ground vertically to depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth not less than 1.5m below ground level connected to and including GI earth strip 32mm x 6mm, by means of nuts, bolts, check nuts and washer etc, made of GI and connected to test point and earth dolly all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of soil PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with cast iron frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 40 mm bore light grade GI protection pipe, test point etc. complete all as specified and directed. NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. GI strip beyond 7.5 Metre shall be measured and paid for separately
Material & labour for earthing complete with copper earth plate electrode 60cmx60cmx3.15mm buried directly in ground vertically to depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth not less than 1.5m below ground level connected to and including copper earth strip 20mm x 3mm, by means of nuts, bolts, check nuts and washer etc, made of copper and connected to test point and earth dolly all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of soil PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with cast iron frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 40 mm bore light grade GI protection pipe, test point etc. complete all as specified and directed. NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. Copper strip beyond 7.5 Metre shall be measured and paid for separately.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 Sqmm, 3.5 core all as specified and directed by Engineer-in-Charge.
Excavating in trenches,in soft/loose soil n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. Or for shafts, wells, cesspits, manholes, pier holes, etc. N exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and directed by Engineer-in-Charge .
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed by Engineer-in-Charge.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge.
Material & labour for Tibba sand filling/clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed by Engineer-in-Charge.
Material & labour for stone slab 40mm to 50mm thick rough dressed Jodhpur stone patties/ slab cover in trenches for protection of cable 25 cm to 30 cm wide and not less than 50cms in length laid dry abutting each other with gap between adjacent slab not exceeding 10mm over sand cushioning complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core Complete all as specified and directed by Engineer-in-Charge.
S&F MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA With MCCB box, 2mm thick duly powder coated all as specified and directed by Engineer-in-Charge.
Supply, installation, commissioning and testing LT panel board of suitable shape and size for 3 phase, 4 wire,415 Volts AC, 50 Hz supply, outdoor cubical type, dust and vermin proof, pedestal mounting type suitable for outdoor applications having suitable shape, size canopy on top, made out of 3.15 mm thick MS sheet with using 40mmX40mmX5mm angle iron frame and supports, duly finished with powder coated using two coats of synthetic enamel paint of approved colour over a coat of red oxide primer all over steel surfaces complete with separate compartment of suitable shape and size with shutter and locking arrangement for each switchgear and including PCC work for fixing panel legs and copper bus bar 3 phase rating of 300 Amps conforming of following:- (i) Incomming :- (a) MCCB , 4 P, 200 Amp,25 KA thermal magnetic release type-01 No (b) Digital voltmeter (0-500 V)-01 No. (c) Ampear meter (0-500 V), with CT -01 No. (d) LED phase indicator lamp-01 (Set of three) (ii) Outgoing :- (a) MCCB 4 P, 125 Amp, 16 KA thermal magnetic release type-03 Nos (b) MCB SPN,32 Amp-04 Nos
Supply, installation, testing and supervision of commissioning of Dessiccant based dehumidifier, complete with procces blower, Reactivation blower, Dehumidifier section, Heaters with, Bird Gauge & Digital Humidstat. The dehumidifier casing shall be made in single skin and material will Carbon steel with power coated finish. The process air should be passed through dehumidifier process section, Reactivation section consist of reactivation Blower with motor, Electric heater. High efficiency Desiccant rotors suitable for 140 to 180 deg C regenration temperature, the "Ecodry" desiccant honeycomb rotor media shall be adsorbent, non toxic, non flammable,fully water washable,having metal silicate desiccant synthesized in-situ, on an inorganic fibre substrate, with net organic less than 2%. Rotor shall be manufactured in India all as specified and directed by Engineer-in-Charge and as per following specification:-COMPACT DESICCANT DEHUMIDIFIER 4500 CMH with humidstat (01nos) (i) Designated to supply 2700CFM of dehumidifier air (ii) Desiccant rotor (iii) Suitable for continuous operation (iv) Reactivation heaters (v) power and cabling upto the control panels (vi) Supply and return air ducting with necessary duct materials as per suggested by OEM up to 15 mtrs. (vii) High efficiency and reliability (viii) High temperature safety thermostat cut out (ix) MOS (material of construction) Mild steel with power coating from heavy gauge sheet (x)High capacity filters (xi) Energy efficient Technical Specification : (i) Process Air flow-4500 CMH (ii) Process motor-2.2 KW (iii) Power required- 415 V/ 3 phase/ 50 Hz (iv) Reactivation motor-1.1 KW (v) Reactivation Heater-42 KW (vi) Process Air flow- 1400 CMH Desiccant Rotor (i) Rotor type-Rotary flutted honey comb media (ii) Rotor Bearing-Inbuilt (iii) Rotar casing-With perimeter flange (iv) Desiccant-in-situ synthesized Metal Silicate (v) Active Desiccant on rotor- above 82% (vi) Net organic of the rotor medialess than2% Air Circulation type :- 100% Recirculation
Supply, fixing, installation, testing & commission air cooled inverter type with non CFC gas split air conditioner capacity 2 TR, BEE 5 star rating comprising of indoor & outdoor unit. The evaporator & condenser coil shall be made of copper, including control wiring, stand for fixing outdoor unit on wall/floor insulated copper tubing for connection the indoor and outdoor. Note:- The cost of copper tubing & control wire upto 3 Mtr shall deemed to be included in quoted rate.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 05 KVA all as specified and directed by Engineer-in-Charge.
M & L for submain wiring alongwith earth wire with the2x4.0 sq. mm + 1x2.5 sq. mm earth wire of FRLS PVC insulated copper conductor, multi stranded IS-694 marked cable in surface/ recessed in PVC conduit as required all as specified and directed by Engineer-in-Charge.
Supply and fix Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amps,240 volts all as specified and directed by Engineer-in-Charge.
SANJOLI CONSTRUCTION COMPANY
UTSAV INDIA LIMITED
RISING ELECTRICALS
SHISHODIA ENTERPRISES
Leo Network power systems
Vijaypower Generators Limited
M/s Chopra Associates
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .