Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹86.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹87.5 L+₹70,756 (0.82%)Rejected-Finance CHAKKALAKKAL H KOTTAT P O | L2 | Rejected-Finance L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical L3 |
Tender Value
₹88.5 L
EMD Value
₹50,000
Closing Date
12 Mar 2025, 4:00 pmClosed
Executive Engineer Thrissur corporation
Executive Engineer Thrissur corporation
Annual Plan-TC- Ayyanthole, Tagore hall Electrification work S1967/25, Part-A-General Electrical Work
2025_LSGD_746388_8
PW2-17409/18,14.3.25EE2
Open Tender
Electrical Works
Item Rate
270 days
Superintending Engineer Thrissur corporation
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,760
₹50,000
26 Jul 2025
5 Mar 2025
14 Mar 2025
5 Mar 2025
12 Mar 2025
5 Mar 2025
5 Mar 2025 - 10 Mar 2025
Amount
electrical
90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
90.2.1.8:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Medium Point
90.2.1.10:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Medium point
90.2.1.12:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Call bell point with piano type 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Medium point
90.2.1.14:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent Plug - Medium Point
90.2.2.9:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Twin control light point with 6A, 3 plate ceiling rose -Medium point
90.2.1.2:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Twin Control light point with 6A, plate ceiling rose - Short point
90.2.1.3:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Short point
90.2.1.4:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point
90.2.1.11:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator - Medium Point.
90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.2.1.7:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.5.1.9:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Gong bell 225mm-without MS box
90.5.1.4:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Musical bell with bird sound
90.5.1.10:Gong bell 300mm-without MS box
OD454815/2024-2025:Supply and providing 230V, 24 watts, 4 feet, Aluminum/ CRCA housing, integrated electronic driver, batten LED tube light fittings directly on wall/ceiling with screws/ nut bolts and giving connections with 3 core flexible copper wire etc as required.(Havells/Crompton/Bajaj/Philips)
OD454806/2024-2025:Supply and providing 230V, 40 watts, high lumen, 4 feet, THD < 10%, batten LED tube light fittings directly on wall/ceiling with screws/ nut bolts and giving connections with 3 core flexible copper wire etc as required.(Havells/Crompton/Philips/Bajaj)
OD454814/2024-2025:Supply and providing 230V, 60 watts, high lumen, 4 feet, THD<10%, batten LED tube light fittings directly on wall/ceiling with screws/ nut bolts and giving connections with 3 core flexible round copper wire etc as required.(Luker/Halonix/Philips or equivalent)
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD454770/2024-2025:Supply and providing 5/7 Watts LED lamp on existing batten/ pendent/ bracket holder as required
OD454820/2024-2025:Supply and providing 230V, 12 watts, recess mounting, (3 IN 1, WH, WW, NW)LED down light with heat sink and PC diffuser, integral high efficiency driver, powder coated finish, THD less than 10%, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells, Crompton, Luker, Philips make)
OD454797/2024-2025:Supply and providing 230V, 12 watts, recess mounting, LED down light with heat sink and PC diffuser, integral high efficiency driver, powder coated finish THD less than 10%, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells, Crompton, K-Lite, Philips make)
OD454777/2024-2025:Supply and providing 230V, 18 watts, recess mounting, integral high efficiency driver, LED down light with heat sink and PC diffuser, powder coated finish THD less than 10%, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells, Crompton, K-Lite, Philips make)
OD454792/2024-2025:Supply and providing 230V, 24/26 watts, recess mounting LED down light with heat sink and PC diffuser, integral high efficiency driver, pressure die-cast aluminum heat sink, powder coated finish THD less than 10%, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells Integra Neo, K-Lite Diva7, Crompton, Keslec, Philips make)
OD454809/2024-2025:Supply and providing 230V, 40 watts, recess mounting LED down light with heat sink and PC diffuser, integral high efficiency driver, pressure die-cast aluminum heat sink, powder coated finish THD less than 10%, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells, K-Lite, Crompton, Keslec, Philips make)
OD454776/2024-2025:Supply and providing 230V, 30 watts, recess mounting cob LED down light with heat sink and PC diffuser, integral high efficiency driver, pressure die-cast aluminum heat sink, powder coated finish THD less than 10%, beam angle 36/40 degree, minimum 100L/watt, cutting hole on false ceiling, fixing and giving connections etc as required. (Havells Unico, Crompton fame spot, Keslec, Philips make)
OD454786/2024-2025:Supply and providing 12 W, LED out door bulk head fittings on wall/ceiling and giving connections with required length of 16/0.20 mm PVC insulated and sheathed 3 core round copper conductor flex wire etc as required. (LBKOVSL12 or equivalent make)
OD454767/2024-2025:Supply and providing 18 W, LED out door bulk head fittings on wall/ceiling and giving connections with required length of 16/0.20 mm PVC insulated and sheathed 3 core round copper conductor flex wire etc as required. (LUKER eco LBKOVSL18 or equivalent make).
OD454785/2024-2025:Supply and providing 230V, 6 W, LED mirror light fittings on wall and giving connections etc as required. (LUKER LIMR6, or equivalent make).
OD454816/2024-2025:Supply and providing 230V, 12 W, LED mirror light fittings on wall and giving connections etc as required. (LUKER LIMR12, or equivalent make).
OD454787/2024-2025:Supply and providing 230V, 2x3 W, LED out door wall light fittings on wall and giving connections etc as required. (LODARCD-6D, or equivalent make).
OD454784/2024-2025:Supply and providing 230V, 3 W, LED foot light fittings concealed on wall / step and giving connections etc as required. (LUKER LODFTW3 or equivalent make).
OD454796/2024-2025:Supply and providing 230 V, 18/15 W,LED bulb, E-27, minimum 100L/W, in existing post top/gate lamp etc as required.
OD454789/2024-2025:Supply and providing 230V, 70 W, integrated, energy saving, long life, corrosion resistant, diecast, LED well glass Luminaire fitting, aesthetically designed with symmetrical light distribution, fixing / hanging from ceiling / stress work with fixing bracket and nut bolt, giving connections etc as required. (Luker Faro LW0705Y / Havels AltezaWGS40W / Philips/Keslec/K-Lite make).
OD454790/2024-2025:Supply and providing 230V, 5W, LED out door wall light fitting fixing on wall and giving connections etc as required. (Luker ORA OW1 or equivalent reputed make).
OD454817/2024-2025:Supply and providing PVC/SMC round black base for fixing gate lights, fixing on wall as required.
OD454794/2024-2025:Supply and providing 230V, with E27 holder, 340mm dia and 520 mm height, out door gate light fittings on base pipe and giving connections with 3 core flexible copper wire etc as required.(K-Lite Light House Mini or equivalent Kesslec/Havells/bajaj /Crompton Make)
OD454821/2024-2025:Supply and providing 230V, integral 40W, IP65, aesthetically designed, symmetrical light distribution, clear cover, out door gate light fittings on base pipe and giving connections with 3 core flexible copper wire etc as required.(K-Lite double standard/ Crompton chaplet/ Havells Ruby/ Kesslec Make)
OD454788/2024-2025:Supply and providing 12V, heavy duty, 30 Amps or nearest size LED strip driver unit, fixing in control box and giving connections etc as required.
OD454800/2024-2025:Supply and providing 12V, 14/12 watt/meter or nearest size, LED profile strip light (5mtr roll length) fixing through the cove on false ceiling with connector, end cap, double sided adhesive form tape and giving connections etc as required.
90.15.4.7:Supply Conveyance, installation, testing and commissioning of 100W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.9:Supply Conveyance, installation, testing and commissioning of 150W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD454783/2024-2025:Supply conveyance and providing of 75 mm dia or nearest size, B class GI pipe in single section for fixing post top lantern/flood lights, cutting/welding MS brackets, fixing with existing concrete base, and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, 2.5 mtr length etc as required.
90.3.17.3:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.50 mm dia GI pipe
OD454811/2024-2025:Supply and providing 240V, 450 mm, 18 inch, energy efficient, Heavy duty, wall mounting fan with 3 speed setting, oscillation, adjustable/tilting, fixing on wall and giving connection etc as required . (Almonard/Crompton high speed torpido or equivalent reputed make)
OD454813/2024-2025:Supply and providing 240V, 400 mm, 16 inch, energy efficient, Heavy duty, wall mounting fan with 3 speed setting, oscillation, adjustable/tilting, fixing on wall and giving connection etc as required . (Almonard/Crompton high speed torpido or equivalent reputed make)
OD454769/2024-2025:Supply and providing, fixing, 240 V, 400 mm size wall mounting fan with standard accessories and giving connections as required. (Havells/Crompton/Bajaj/Usha)
OD454775/2024-2025:Supply and providing 200 mm sweep light duty exhaust fan in plastic body with self opening lowers working on 230V single phase AC, in the existing opening, fixing necessary anchor bolts, nuts, washer etc including giving connections with wire supplied with the exhaust fan as required.
OD454798/2024-2025:Supply and providing 250 mm sweep light duty exhaust fan in plastic body with self opening lowers working on 230V single phase AC,in the existing opening, fixing necessary anchor bolts, nuts, washer etc including giving connections with wire supplied with the exhaust fan as required.
OD454819/2024-2025:Supply and providing 300/305 mm sweep 1400 rpm, heavy duty exhaust fan in metal frame working on 230V single phase AC, in the existing opening, fixing necessary anchor bolts, nuts, washer etc including giving connections with wire supplied with the exhaust fan as required.
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.6:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
OD454781/2024-2025:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. 3 x 1.0 sq. mm
1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.13:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.2:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.7:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 1.5 sq. mm
1.17.4:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
OD454764/2024-2025:Supply and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface /recessed steel/PVC conduit as required. 2 x 1.00 sq mm
90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm
90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm
90.6.10.3:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm
OD454771/2024-2025:Supply and providing 25 mm corrugated PVC flexible conduit as required.
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.3:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 Degree /Tee
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
OD454807/2024-2025:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, single door.
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.12:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.16:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.20:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD454795/2024-2025:Supply and providing 415 V, 50 Amps, TP MCB, C-curve, on existing DB/enclosure and giving connections etc as required.
OD454773/2024-2025:Supply and providing 2 pole enclosure for independent mounting of MCB/RCCB/Isolator etc. as required.
OD454808/2024-2025:Supply and providing 4 pole enclosure with mounting rail for independent mounting of MCB/RCCB/Isolator etc, fixing on panel/wall as required.
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
OD454793/2024-2025:Supply and providing 600/5A, 15 VA, accuracy class 1, resin cast metering CT in the existing panel board and giving connections etc as required.
OD454799/2024-2025:Supply and providing 800/5A, 15 VA, accuracy class 5P/10P 10, protection CT Tape wound in the existing panel board and giving connections etc as required.
OD454802/2024-2025:Supply and providing 400/5A, 15 VA, accuracy class 1, resin cast metering CT in the existing panel board and giving connections etc as required.
OD454782/2024-2025:Supply and providing 8 stage 440V/110V 5A/1A intelligent power factor controller (IPFC), in APFC panel and giving connections as required.
OD454812/2024-2025:Supply and providing 3 pole capacitor duty contactors for switching capacitor banks up to 50 kVAR with AC coil, in APFC panel and giving connections as required.
OD454779/2024-2025:Supply and providing 3 pole capacitor duty contactors for switching capacitor banks up to 25 kVAR with AC coil, in APFC panel and giving connections as required.
OD454801/2024-2025:Supply and providing 3 pole capacitor duty contactors for switching capacitor banks up to 10 kVAR with AC coil, in APFC panel and giving connections as required.
90.14.24.44:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.47:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.51:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.25 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.54:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.50 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N
2.2.14:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp, 36 KA
2.2.15:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200 Amp, 36 KA
2.2.17:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.250 Amp, 50 KA
2.2.18:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.400 Amp, 50 KA, 4 pole
2.2.3:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.160 Amp, 16KA,TPMCCB
2.2.13:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 30 KA 4 Pole
2.2.5:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200 Amp, 25 KA,TPMCCB
2.2.7:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.250 Amp, 35 KA,TPMCCB
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.7.1:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp
90.12.7.30:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
90.12.7.32:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm
90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
90.12.7.35:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 240 sq mm
90.12.7.39:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.5.13:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 6 sq mm
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
OD454766/2024-2025:Supply and providing earth clamp for cable gland earthing up to 4x16/25 sq mm AYFY cables with 20x1 mm copper strip and 12X3 mm brass bolt and nut etc as required.
OD454804/2024-2025:Supply and providing dust and vermin proof, wall mounting, Hot press moulded SMC Cable junction Box of following sizes suitable for fixing switch board, mcb DB, contactor, timer, relay etc, with hinged door construction for the front side knock out for cable entry and exit, 450x370x200 mm or nearest size. (Sintex GS-JB 4537 or equivalent make).
OD454818/2024-2025:Supply and providing 220/415V,30A(AC1) , 3 Pole , power contactor for high mast lighting and giving connections etc as required.(L&T MNX22 3P or equivalent make)
OD454805/2024-2025:Supply and providing earth clamp for cable gland earthing up to 4x6 sq.mm AYFY cable with 20x1 mm copper strip and 12x3 mm brass bolt and nut etc as required.
OD454803/2024-2025:Supply and providing dust and vermin proof, wall mounting, Hot press moulded SMC Cable junction Box of following sizes suitable for fixing switch board, mcb DB, contactor, timer, relay etc, with hinged door construction for the front side knock out for cable entry and exit, 400x300x150 mm or nearest size. (Sintex GS-JB 4030 or equivalent make).
OD454778/2024-2025:Supply and providing dust and vermin proof, wall mounting, Hot press moulded SMC Cable junction Box of following sizes suitable for cable termination, knock out for cable entry and exit, including 32 Amps 4way connector terminal, 200x140x95 mm or nearest size. (Sintex GS-JB2014 or equivalent make).
OD454791/2024-2025:Supply and providing dust and vermin proof, wall mounting, Hot press moulded SMC Cable junction Box of following sizes suitable for cable termination, knock out for cable entry and exit, 250x200x100 mm or nearest size. (Sintex GS-JB2520 or equivalent make).
4.5.3:Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
4.5.4:Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
4.5.6:Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 2.0 mm thickness
90.16.3.2:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm GI strip
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD454768/2024-2025:Supply and providing Test joint for earthing made up of 2 nos, 25x5 mm GI strip, 25 cm long placed on either sides of earth leads and watering pipe, bending, drilling and tightening with 4 sets of brass/SS nut, bolt, washer etc as required.
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD454772/2024-2025:Supply and providing 25X6 mm brass bolt and nut with washers on the existing MS box/earth bus etc as required including drilling necessary holes as required.
OD454765/2024-2025:Supply and providing 12X3 mm brass bolt and nut with washers on the existing MS box/earth bus etc as required including drilling necessary holes as required.
OD454774/2024-2025:Supply and providing 25X3 mm brass bolt and nut with washers on the existing MS box/earth bus etc as required including drilling necessary holes as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
OD454780/2024-2025:Supply and providing tor steel rod for reinforced cement concrete including cutting bending and tying in shape as required.
OD455044/2024-2025:Supply and providing instant water heater (3/5) ltr, Rust and shock proof with iSI mark, indicator temperature sensor, cut off, flexible pipes, 3 KW, multi layered tank, fixing on wall and and giving all connections etc as required. (V-guard Zio / Crompton Rapid jet ? Bajaj Flora / Havells instanio)
OD454810/2024-2025:Supply and installation and commissioning of Pure sine wave inverter with UPS mode including 12V, 180 Ah tall tubular inverter battery with water level indicators, protection for over load, deep discharge, short circuit, reverse polarity, input mains etc. and display/indicators for ON/OFF overload, low battery, UPS mode, charging, mains etc having a minimum load capacity of 1 KVA continuously , giving connections etc as required (Hykon SD+1200VA, or equivalent Numeric make with Exide/Hykon/Numeric-180 Ah tall tubular inverter battery, with water level indicators)
Lightning Protection
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD454822/2024-2025:Supply and providing Test joint for earthing made up of 2 nos, 25x5 mm GI strip, 30 cm long placed on either sides of earth leads and watering pipe, bending, drilling and tightening with 4 sets of brass/SS nut, bolt, washer etc as required.
5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
6.12:Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
6.2:Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube,having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
90.16.3.18:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm aluminium strip
90.16.4.15:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm aluminium strip
OD454823/2024-2025:Supply and providing dust and vermin proof, wall mounting, Hot press molded SMC Junction box of following sizes suitable for fixing Test joit of lightning conductor strip / cable termination, hinged door construction for the front side, knock out for cable entry and exit, 300x200x1105 mm or nearest size. (Sintex GS-JB3020 or equivalent make).
BIJU JOSE (BID ID -2150660)
E R ANANDAN (BID ID -2150731)
Bidder Name
SABI ENGINEERING COMPANY
BIJU JOSE
E R ANANDAN
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1205575.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .