Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 LAccepted-AOC | L1 | Accepted-AOC aoc | |
| 2 | Rejected-Technical | - | Rejected-Technical above quoted rate | |
| 3 | Rejected-Technical | - | Rejected-Technical above quoted rate |
Tender Value
₹1.9 L
EMD Value
₹4,688
Closing Date
15 Dec 2023, 6:00 pmClosed
Assistant Engineer, LSGD Section, Cherpu
Assistant Engineer, LSGD Section, Cherpu
Construction of Smart Anganwadi Building for Anganwadi No.21 ward 19 cherpu GP
2023_LSGD_629199_1
155/TS/118902/AE/LSGD/CHP
Open Tender
Electrical Works
Item Rate
180 days
Cherpu
Please refer Tender documents.
9 documents required · 9 mandatory
₹555
Yes
₹4,688
Yes
24 Feb 2024
7 Dec 2023
18 Dec 2023
7 Dec 2023
15 Dec 2023
7 Dec 2023
Amount
Electrification
90.2.2.1:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
90.2.2.2:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Twin control light point with 6A, 3 plate ceiling rose -Short point
90.2.2.3:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Single control light point without ceiling rose - Short point
90.2.2.4:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point
90.2.2.6:Supply and wiring points according to IS 732-1989 through the existing conduit with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (Group B/ RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.
90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
OD253781/2023-2024:Supply and providing 12 W, LED, out door bulk head fittings on wall/ceiling and giving connections with required length of 16/0.20 mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire etc as required. ( LUKER eco LBKOVSL12 or equivalent make)
OD253782/2023-2024:Supply and providing and fixing 7 W LED indoor wall bracket and giving connections etc as required. (luker LWL111-1 or equivalent make)
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD253783/2023-2024:Supply and fixing shades of the following types on existing batten/ pendent/ bracket fittings as required -200 mm plastic sill shade
OD253784/2023-2024:Supply and providing 9/11 Watts LED lamp on existing batten/ pendent/ bracket holder as required
OD253812/2023-2024:Supply ofindirect LED mirror light 6W Luker LIMR6/equivlent make etc as required
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.17.1:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.32 mm dia GI pipe
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD253785/2023-2024:Conveyance installation, testing and commissioning of exhaust fan 200 mm light duty in metal frame in the existing opening, fixing necessary anchor bolts, nuts etc as required including giving connection with the supplied wire along with the fan
90.4.10:Conveyance, installation , testing and commissioning of exhaust fans of size up to 450mm in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
OD253786/2023-2024:Supply and providing 305mm sweep heavy duty exhaust fan in metal frame in the existing opening, fixing necessary anchor bolts, nuts, washer etc as required including giving connection with the supplied wire along with the fan.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.47:Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.14:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm
90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm
1.17.2:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm
1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm
1.17.13:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
1.17.29:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 6 sq. mm
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD253787/2023-2024: Supply and provding test joint for earthing system using 2 nos of the following strips including cutting and bending to shape ,drilling necessary holes and fixing to the watering pipe etc as required .2x25x6 mm GI strip
OD253788/2023-2024: Supply and providing earth lead from test joint to earth electrode using the following strips including cutting and bending to shape ,drilling necessary holes and fixing to the earth plate to test joint etc as required 25x6mm GI strip
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD253789/2023-2024:Supply and providing the following sizes of bolt and nut with washers on the existing M.S box/ earth bus etc. as required including drilling necessary holes as required. 25x6mm brass nut and bolt .
OD253790/2023-2024:Supply and providing the following sizes of bolt and nut with washers on the existing M.S box/ earth bus etc. as required including drilling necessary holes as required. 12x3mm brass nut and bolt .
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
OD253791/2023-2024:Supply and providing good quality nylon rope 16 mm/nearest with require object outside the well for hanging the motor pumpset
OD253792/2023-2024: Charges for installation of 0.5/1 H.P. submersible motor pumpset into well after connecting the delivery pipes, and lead cable to motor and hanging the unit on rope and setting into trouble free operation and conducting trail run satisfactorily.
OD253793/2023-2024: Supply and providing 25/32 mm dia reflex/nonreturn valve
OD253795/2023-2024: Supply and providing special make SS connector with steel clamp suitable for 25/32 mm PVC fexible pipe.
OD253796/2023-2024: supply and providing dry run protection relay curren based in the existing starter and giving conection etc as required (L&T make i-AD
OD253797/2023-2024: Supply and providing 25/32 mm heavy duty duro flex/canoflex PVC flexible pipe as delivery pipe
OD253798/2023-2024: Supply and providing submersible motor controller suitable for 0.5 H.P.Submersible motor pump including Ammeter,Volt meter etc L&Tmake MR-G2/equivlent make .
90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
OD253799/2023-2024: Supply of 0.5 H.P,Single phase open well submersible motor pumpset suitable for operation of 230V,50Hz a.c. supply having 8 mtrs to 20 mtrs head range , capable of discharge 6180ltrs/Hr of clear water at 12 Mtrs head (Kilosker KOSi.0520/equivlant make Akash/Texmo/Deccan) etc as requird .
OD253800/2023-2024:Supply and fixing the following accessories in the existing board and giving connections etc. 32A 2 way Neutral link mounted on DMC/ SMC base
OD253801/2023-2024:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and padlocking arrangement on existing angle ion frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc as required. Switch disconnector unit 32 A SPN AC 23A.
OD253802/2023-2024:Supply and fixing the following accessories in the existing board and giving connections etc. 32A HRC Fuse Base with HRC Fuse link
OD253803/2023-2024:Supply and installation of dust and vermin proof wall mounting SMC Meter box suitable for fixing KSEB Meter, cut out Neutral link etc, hinged door construction for the front side , providing vision panel, for the meter compartment, knock out for cable entry and exit. GS-MB 4537(inside 450x370x200 mm) Sintex or its equivalent.
OD253814/2023-2024:Supply and providing type1+2 , I 12.5KA Imax 50KA 2pole (1p+1) surge Protection Device in the existing box and giving connection etc as required.
OD253804/2023-2024:Supply and providing MS eye bolt hook in wall/parapet for binding support for KSEB service wire connection
OD253805/2023-2024:Preparing completion and test certificates for KSEB connection
KIRAN MG
SHARJAS A
Bidder Name
KIRAN MG
SHARJAS A
BASTIN VINCENT
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_950730.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .