Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.6 LAccepted-AOC 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | L1 | Accepted-AOC You are placed in L1 | |
| 2 | Rejected-Technical | - | Rejected-Technical You are not placed in L1 | |
| 3 | Rejected-Technical | - | Rejected-Technical You are not placed in L1 | |
| 4 | Rejected-Technical 1ST COMPLEX RADHANPUR ROAD NEAR BYPASS CIRCLE OPP 1SQUARE MARKET MAHESANA GUJARAT 384002 | MAHESANA | GUJARAT | 384002 | - | Rejected-Technical You are not placed in L1 | |
| 5 | Rejected-Technical | - | Rejected-Technical You are not placed in L1 |
Tender Value
Refer Docs
Closing Date
28 Aug 2020, 9:00 amClosed
Maj V E Pawar, GE
Garrison Engineer (AF) Jamnagar No2, Air Force Station-2, PIN-361004
REPAIR/REPLACEMENT OF LT CABLE OF SIZE 120 SQMM X 3.5 CORE AND LT CABLE OF SIZE 70 SQMM X 3.5 CORE AT KHAMBHALIYA AIR FORCE STATION-I UNDER GE(AF0 JAMNAGAR NO2
2020_MES_371289_1
3010/16/E3
Limited
Job Works
Works
60 days
GE(AF) Jamnagar No.2
Please refer Tender documents.
1 document required · 1 mandatory
₹0
Exempted
4 Sept 2020
22 Aug 2020
29 Aug 2020
22 Aug 2020
28 Aug 2020
22 Aug 2020
REPAIR/REPLACEMENT OF LT CABLE OF SIZE 120 SQMM X 3.5 CORE AND LT CABLE OF SIZE 70 SQMM X 3.5 CORE AT KHAMBHALIYA AIR FORCE STATION-I UNDER GE(AF) JAMNAGAR NO2 1. M&L for disconnection electric connection from LT panel taking out old/unsv/damaged LT cable of size 120 Sqmm x 3.5 core and 70 Sqmm x 3.5 core along with PCC cable cover from trenches, megger testing of cable & placed at site for repair/replacement -01 Job. 2. Laying only XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT underground cable ISI marked with aluminiummulitistranded conductor 1100 volt grade of size 120 Sqmm 3.5 core laid in treanches/duct passing through pipe/duct or fixed on pole and connecting complete using suitable size lugs and nuts/bolts complete all as specified & directed by Engr-in-charge - 340 RM, Note : XLPE cable shall be issued under sch 'B' free for fixing only. 3. Laying only XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT underground cable ISI marked with aluminiummulitistranded conductor 1100 volt grade of size 70 Sqmm 3.5 core laid in treanches/duct passing through pipe/duct or fixed on pole and connecting complete using suitable size lugs and nuts/bolts complete all as specified & directed by Engr-in-charge - 184 RM, Note : XLPE cable shall be issued under sch 'B' free for fixing only. 4. Excavation in tranches hot exc 1.5m wide and n.exc 1.5m in depth for foundation/fixing pole /laying cable and pipe line etc or for man hole etc not exc 10 sqm on plan and getting out in soft /loose soil complete all as specified and directed - 138.78 CUM 5. M &L for providing dry river sand as in sand cushioning below and above cable of the thickness specified in SSR to under ground electric cable incuding punning down of sand in layer all as specified and directed - 46.26 CUM. Note : For measurement purpose punned thickness of sand only will be considered, Supply and return Air ducting. 6. Supplying and laying reiforced precast concrete cable cover, class LV Type 2 flat, size 300mm x 180mm x 40mm thick all as specified and directed - 2356 Nos. 7. Laying only PCC cable cover of size 300mm x 180mm x 40mm thick after sorting out serviceable/ undamaged using from trenches all as specified and directed - 500 Nos. 8. Returning filling in including spreading, leveling, watering and well ramming in layers, not exceeding 25 cm thick using excavated soil complete all as specified and directed - 77.72 CUM. 9. Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed - 61.06 CUM. 10. S&F in repair and replacement for MCCB 160 amp 4 pole 25 KA(TMD), lcs=100% lcu with fixed magnetic and thermal release adjustable overload 80-100% and adjustable short ckt 5 to 10 in setting complete with phase separator - 01 Nos Make:- L&T/ABB/Schnieder.
11. S&F in repair and replacement for MCCB 125 amp 4 pole 25 KA(TMD), lcs=100% lcu with fixed magnetic and thermal release adjustable overload 80-100% and adjustable short ckt 5 to 10 in setting complete with phase separator - 01 Nos Make:- L&T/ABB/Schnieder. 12. Testing and commissioning on load complete - 01 Job.
MADHAV ENTERPRISE
Krishna Bhoomi Enterprise
Navdurga Engineering
Nirmal Construction
Indice Technologies
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_414199.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .