| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹1.2 Cr | L1 | Accepted-Finance Lowest Bidder |
| 2 | L2₹1.4 Cr+₹20.2 L (17.0%)Rejected-Finance CHANDAN NAGAR OPP IOCL PERTROL PUMP RAMPUR ROAD BAREILLY UP 243001 | BAREILLY | BAREILLY | UTTAR PRADESH | 243001 | ₹1.4 Cr+₹20.2 L (17.0%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹1.5 Cr+₹32.8 L (27.6%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹1.5 Cr+₹32.8 L (27.6%) | L3 | Rejected-Finance Not Lowest |
| Sl No | Description | Qty | Unit | BHARAT ELECTRICAL TRADERS L2 | Raman Electric Trading Co L1 | R D Bansal L3 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed. | 918.24 | Cum | 100 ₹91,824 Lowest | 140 ₹1,28,553.6 | 150 ₹1,37,736 |
| 2.00 | Add to item No 1 above for each additional 1.5m or part there of in depth beyond the first 1.5 mtr complete all as specified and directed. | 4 | Cum | 250 ₹1,000 | 200 ₹800 Lowest | 300 ₹1,200 |
| 3.00 | Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed. | 680.54 | Cum | 50 ₹34,027 | 30 ₹20,416.2 Lowest | 100 ₹68,054 |
| 4.00 | Removing of excavated soft/loose soil not exc 50m & depositing where as directed at a level n.exc 1.5 m above from starting point complete all as specified and directed. | 232.34 | Cum | 40 ₹9,293.6 | 30 ₹6,970.2 Lowest | 60 ₹13,940.4 |
| 5.00 | M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches complete all as specified and directed and sand cover to under ground cable complete all as specified and directed. | 176.81 | Cum | 400 ₹70,724 | 350 ₹61,883.5 Lowest | 800 ₹1,41,448 |
| 6.00 | Supply and laying un-reinforced precast concrete cable cover class HVP type I flat of size 300mm x 180mm x 40mm complete all as specified and directed. | 9,438 | Each | 15 ₹1,41,570 Lowest | 20 ₹1,88,760 | 20 ₹1,88,760 |
| 7.00 | Laying Only Precast concrete cable cover of size 300 x 180 x 40mm complete all as specified and directed. | 4,250 | Each | 0.5 ₹2,125 Lowest | 1 ₹4,250 | 1 ₹4,250 |
| 8.00 | Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair in replacement of broken/worn out components and insulators etc complete all as specfied and directed. | 6 | Each | 100 ₹600 Lowest | 200 ₹1,200 | 200 ₹1,200 |
| 9.00 | Supply installed testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 12 nos including 400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed | 6 | Each | 12,000 ₹72,000 Lowest | 17,000 ₹1,02,000 | 15,000 ₹90,000 |
| 10.00 | Taking down existing damage/unsv/faulty PVC insulated, armoured, aluminium conductor 11000V grade cable of any size and core from trenches, pipe, ducts, pole etc. Testing for serviceability of cable, cutting and segregating serviceable portion for relaying serviceable cable where directed. | 2,710 | RM | 20 ₹54,200 Lowest | 20 ₹54,200 Lowest | 50 ₹1,35,500 |
Tender Value
₹1.3 Cr
EMD Value
₹2 L
Closing Date
1 Dec 2025, 6:00 pmClosed
CWE Bareilly
HEADQUARTERS, COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, STATION ROAD, BAREILLY CANTT, PIN 243001
CA NO.CWE BLY/GE (E)/93 OF 2025- 2026REPAIR/MAINT OF HT DISTRIBUTION SYSTEM AND ITS CONNECTED WKS OF EAST AREA, REPAIR/MAINT OF DISTRIBUTION TRANSFORMER, CONTROL PANEL AND CONNECTED WKS OF EAST AREA, REPAIR /MAINT/REPLACEMENT OF HT CABLE
2025_MES_737062_1
8200/B/903/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (East) Bareilly
As per NIT
7 documents required · 7 mandatory
₹1,000
GE (West) Bareilly
₹2 L
Yes
19 Dec 2025
27 Oct 2025
8 Dec 2025
27 Oct 2025
1 Dec 2025
17 Nov 2025
Amount
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed.
Add to item No 1 above for each additional 1.5m or part there of in depth beyond the first 1.5 mtr complete all as specified and directed.
Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed.
Removing of excavated soft/loose soil not exc 50m & depositing where as directed at a level n.exc 1.5 m above from starting point complete all as specified and directed.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches complete all as specified and directed and sand cover to under ground cable complete all as specified and directed.
Supply and laying un-reinforced precast concrete cable cover class HVP type I flat of size 300mm x 180mm x 40mm complete all as specified and directed.
Laying Only Precast concrete cable cover of size 300 x 180 x 40mm complete all as specified and directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair in replacement of broken/worn out components and insulators etc complete all as specfied and directed.
Supply installed testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 12 nos including 400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed
Taking down existing damage/unsv/faulty PVC insulated, armoured, aluminium conductor 11000V grade cable of any size and core from trenches, pipe, ducts, pole etc. Testing for serviceability of cable, cutting and segregating serviceable portion for relaying serviceable cable where directed.
Supply, laying, connecting and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11 KV grade earthed laid in trenches/ducts/encased in GI pipe/fixed to pole including jointing and testing complete all as specified and directed of size 95 sqmm 3 core complete all as specified and directed.
Supply, laying, connecting and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11 KV grade earthed laid in trenches/ducts/encased in GI pipe/fixed to pole including jointing and testing complete all as specified and directed of size 120 sqmm 3 core complete all as specified and directed.
Relaying only serviceable 11 KV XLPE insulated armoured cable obtained from item Ser No 10 above all as specified and directed by Engr-in-Charge.Note : Excavation and earth work will be paid and measured sepertely in relevant items.
Dismantling of PCC/steel tubular pole incl coping, insulators from poles complete all as specified and as directed
M&L for steel tubular sewaged poles of complete with cast iron base plate, finial taper plate, bolts, nuts and screws, as specified type 410 SP-55 11 Mtrs long all as specified and directed.
M&L for PCC type B1 (1:2:4) using 20 mm graded aggregate as in coping to the poles complete all as specified and directed.
M&L for PCC (1:3:6) type C2 using (40 mm graded aggregate in foundation, filing and mass concrete complete all as specified and directed.
S&F in repair GI tube 100 mm bore light grade with all fittings and fixed complete for road crossing /on wall/floor and crossing culvert or laid in floor complete all as specified and directed.
M&L in repair for horozontal boring and inserting casing pipe with all fitting and fixture with material of HDPE pipe size 150 mm of pressure rating 6 Kg/Cm2 along road and under pavements/hard standing/railway/road crossing in all type of soils at prescribed depth of boring not less than 1.75 Mtr from the raod surface including making PCC Chamber with cover at both ends of road.
M&L for painting the external exposed surfaces of steel tubular swaged/rail poles of HT alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 lines around the pole complete all as specified and directed.
M&L Cleaning of surrounding areas from large grass weeds ,vegetation, shrubs branches of trees at substations, near Transformers, near RMU panel , near Electric pole structures by manual /Electric Grass cutting machine/JCB etc with complete grass and vegetation clearance from ground and leveling if required without any damage to the electric cables and items complete all as specified and as directed by Engr-in-Charge.Notes: Rates of T&P must be included in the quoted rates
S&F in repair Cable end termination 11 KV HT (heat shirnkable) cable jointing kit for 11 KV (Earthed) grade cable for indoor /outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
All as per above here-in-before but size of 120 to 185 sqmm complete all as specified and directed.
S&F Danger notice plate of 1.6 mm thick mild steel sheet vitreous enanelled white of size 20 x25 cm with figures letters and conventional skull bones in signal red colour and fixed with mild steeel clamps made of flat iron nuts bolts and washers etc for HT poles with voltage and danger indicated in hindi and english and local vernacular complete.
S&F of Cable route markers made of galvanised iron with embossing of HT Cable of 11 KV, supporting MS angle of 75 cm long, for HT/LT cable route marking duly embedded in and incl PCC (1:3:6) foundation up to 30 cm incl excavation and earth work complete all as specified and directed. .
M&L for servicing and greasing GOD (gang operated air break switch) 200 Amps triple pole 11 KV including replacement of the following unserviceable parts :- (a) ACSR Jumper with RYB, PVC sleaves 1.5 m to 2.0 m long – 03 Nos (b) Brass connector brackets with bolts, nuts etc - 3 sets (c) Aluminium lugs of suitable size
M&L for maintenance & Overhauling of 11 KV VCB of existing make/ type/mode/ capacity including dismaintling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts re-assembling of parts including well cleaning and greasing of all mechanical parts .The complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented in service by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert complete all as specified and directed.Note:- Spare parts required to make VCB functional will be measure and paid separately under respective items.
Supply only the following spare parts of HT 11 KV VCB for replacement under relevant items above.Spares as approved by GE and Engg in charge all as directed.
NO volt coil 30 V DC complete all as specified and directed.
Shunt Tripping coil 30V DC complete all as specified and directed.
Vaccum interupter for indoor VCB complete all as specified and directed.
Spout incomming side complete all as specified and directed.
Spout outgoing side complete all as specified and directed.
Multifunction meter suitable for 11 KV panel for measuring Voltage, Amp, Frequency and PF complete all as specified and directed.
Breaker control switch 10A 660V complete all as specified and directed.
Electronic hooter 40v DC 96 x 96mm
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NO blockl, 22mm dia Red colour complete all as specified and directed.
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NC blockl, 22mm dia Green colour complete all as specified and directed.
Spring charging motor to match with existing complete all as specified and directed.
Closing coil to match with existing 30/110 Volt complete all as specified and directed.
Coil to match with existing complete all as specified and directed.
Supplying, installation, commissioning and testing of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type set of three, of 13.1 KA/Sec having ratio 200/100/5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering and associated wiring including taking down old UNSV CTs complete all as specified and directed
Supplying, installation, commissioning and testing of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type set of three, of 13.1 KA/Sec having ratio 100/50/5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering and associated wiring including taking down old UNSV CTs complete all as specified and directed
Supplying, installation, commissioning and testing of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type set of three, of 13.1 KA/Sec having ratio 50/25/5+5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering and associated wiring including taking down old UNSV CTs complete all as specified and directed
Integrated LED pilot lamp suitable for operating at 24V/36V ( AC/DC) red/Yellow/Green/Blue /White colour
Toggle switch assembly complete all as specified and directed.
Fuse holders for british pattern fuse links complete all as specified and directed.
S&F of 11 KV VCB trolly aluminium busbar incoming side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV VCB trolly aluminium busbar outgoing side suitable for crompton make VCB complete all as specified and directed.
Spring charging gear to match with existing complete all as specified and directed.
Strip type heater 40/60 watt approx 4"/6" in length complete all as specified and directed
S&F of 11 KV VCB trolly fixed contact of spout incoming/ outgoing side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV VCB trolly female jaw incoming/ outgoing side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV PT spout suitable for 11 KV crompton potential transformer complete all as specified and directed.
M & L for Copper bus bar of size 50 X6 mm with heat shrinkable PVC HT sleeves with nut bolts and washer of brass and fixing arrangement as required at site complete all as specified and directed.
M & L for repair of battery bank float cum booster charger by filling up distilled water in lead acid battery , cleaning of battery terminal, including repairing variable type rotary transformers (automatic battery charging system) suitable for input of 230 Volts AC 50 Hz single phase and having adjustable charging rate up to 100 AH at 110 V DC complete as specified and directed. Note :Batteries shall be measured & paid separetly under respective item of this schedule.
Taking out unserviceable batteries from system and S&F with 12 Volts 160 AH new maintenance free batteries dry type complete all as specified and directed.
Supply & Fix battery bank variable type rotary transformers ( automatic battery charging system) suitable for input of 230 Volts AC 50 Hz single phase and having adjustable charging rate up to 40 AH at 30V DC complete with charger as specified and directed. Note :Batteries shall be measured & paid separetly under respective item of this schedule.
Repairing of DC Battery charger suitable for recharge of batteries 12 Volt 160 AH for supply to relays for smooth functioning of control relay including replacement of worn out wiring and replacement of other defective parts complete all as specified and directed.
Taking out unserviceable batteries from DC battery bank float cum boost charger and S&F with 2 Volts 100 AH new maintenance free batteries dry type complete all as specified and directed.
M & L for repair of Potential Transformer (PT) 11 KV/110 V and suitable to match the existing system including overhauling , replacement of burnt winding of primary & secondary , replacement of oil etc and reinstall after repair & testing on load complete as specified and directed .
M&L for repair and servicing of strip heater/ thermostat assembly of VCB panels of 11 KV of existing make/ type/mode/ capacity including dis-assembling of strip heater / thermostat and replacing unserviceable spare parts, wiring, cable, including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar by using blow lamp to ensure proper function of strip heater complete all as specified and directed .Note:- Spare parts required to make strip heater/thermostat assembly , functional will be deemed to be included in quoted rate.
M&L for sign board complete made out of stainless steel sections of round/square as required at site and indicated of size (1.80 x 1.50 M) incl supporting legs made out of same material and hight of complete board not less than 2.80 Mtr with best quality ACP sheet and luminous letter writing size of letter and colours of back gound and letters will be indicated by Engr-in-Charge. All earth and PCC work as reqd at site for fixation of board is incl in quoted rates.
Supply and fix HT PVC tape roll of size 38 mm width in 09 Mtr roll complete all as specified and directed.
Supply and fix HT Fuse wire of capacity 5 Amp/10 Amp/30 Amp/100 Amp complete all as specified and directed.
Opening the front and rear cabinate of the RMU 3/4 way 630/800 Amps 11 KV, de-carbonizing and replacement of moving and fixed contacts if required, lubricating, checking the pressure of SF-6 gas, wiring with suitable size of copper conductor cable, checking of micro processor EF/ OC relay, tripping coil electrical and checking for manual/auto tripping system complete and placing the SF-6 RMU and isolating unit in its original position as per OEM all as specified and as directed.
Material and Labour of plug in voltage presence indicator system (VPIS) type WIM for Ring Main Unit SF-6 of capacity 11 KV, 630/800 Amps complete all as specified and as directed.
Material and Labour of Bushing assembly for Ring Main Unit SF-6 of capacity 11 KV, 630/800 Amps complete all as specified and as directed.
Material and Labour of terminal contact piece with silicone coupling by opening the terminal cover for Ring Main Unit SF-6 of capacity 11 KV, 630/800 Amps complete all as specified and as directed.
Material and Labour of Trifurcation boot 11 KV capacity for cable termination joint of RMU incoming and outgoing terminals including taking out old defective trifurcation boot for Ring Main Unit SF-6 of capacity 11 KV, 630 Amps complete all as specified and as directed.
Callibration of microproccessor E/F and O/C relay of Ring Main Unit SF-6 of capacity 11 KV, 630/800 Amps complete and calibrating with portable relay test kit to set time and fault level and adjustment of setting with according to load & time with main Power Supply incl replacement of relay battery for proper functioning complete all as specified and directed.
M & L PCC 1:4:8 type D2 (using 40 mm graded aggregate) as in foundation filling and mass concrete complete all as specified and directed.
M&L Brick work with fly ash old size bricks, straight or curved on plan exc 6m mean radius, built in CM 1:4 complete all as specified and directed.
M&L rendering 15 mm thick on fair faces of brick work/concrete surfaces in CM 1:4, finished fair & even & smooth without using extra cement complete all as specified and directed
M&L for 100 mm thick PCC type D2 1:4:8 (40 mm graded stone aggregate), complete all as specified and directed.
M&L for 100 mm thick PCC 1:2:4 (using 20 graded stone aggregate) finish even and smooth w/o using extra cement complete all as specified and directed.
Excavating in post holes (or similar holes) each n. exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance n. exc 50 mtr and making good surface in soft/loose soil complete all as specified and as directed.
M&L PCC 1:2:4 type B2 (using 40 mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed.
S&F mild steel angle iron work, as in fencing post and strut, flat iron fillets for securing wire mesh etc including cutting, drilling, bending, bolting etc and similar work complete all as specified and directed.
S&F for Framed work such as grills, gratings etc, with ends of bars shouldered and/or riveted or forget into spikes, framed guard bars, barred iron doors, ladders, framed balusters, walk ways, railings, framework of water tanks and similar work conforming to Fe 410-0 or 310-0, and for portions framed and hung as gates, including pintle hinges, stops, hand-made sliding bolts,etc complete all as specified.
S&F PVC coated chain link fencing 3 mm dia galvanised wire mesh (mesh size 50 mm x 50 mm) made up to tapped wire and laid on portion/fixed on poles complete all as specifed and directed.NOTE : MS Post, MS round bars, flat iron, nuts & bolts shall be measured and paid seperately.
S&F MS 10 mm dia round bar and fixed independently to angle iron for chain link fencing cut to length, bend to shape required, complete all as specified and as directed.
M&L for preperation of new steel and iron surfaces of any description over 10cm in width or girth not otherwise described and applying two coats of synthetic enamel paint over a coat of primer complete all as specified and directed.
M&L for preperation of new steel and iron surfaces of any description n. ecx 10cm in width or girth not otherwise described and applying two coats of synthetic enamel paint over a coat of primer complete all as specified and directed.
M&L for preperation of new surfaces and applying three coats of white wash on walls complete all as specified and directed.
M&L for preperation of new surfaces and applying two coats of white wash on ceiling complete all as specified and directed.
Maintenance of 33 KV indoor control and relay panel of 33 KV by checking wiring from outdoor VCB to indoor control panel, tightening of loose connections, U/S indicator with holder, thimble, replacement of unserviceable wiring/part including testing, calibration and checking of tripping system of 33 KV control panel through all protective relays installed on each C&R panel including testing and adjust/ repair the alarm circuit as per time current characteristics by primary injuction test at 60%, 75%, 100% plug including well cleaning and decarbonizing of relay contacts complete all as specified and directed.
Overhauling and servicing of 33 KV VCB including repair and setting of operating mechanism parts, spring charging material mechanism, well cleaning with petrol and CRC-226 and replacing unserviceable parts/ accessories, oiling/ greasing of moving parts, dismantling, checking and well cleaning of pole insulator, checking of vaccum, interupters well cleaning mechanism links fibre reinforced plastic frame around the vaccum interupters including routine and periodical test complete all as specified and directed. Note:- Spare parts required to make VCB functional replaced wih SCADA compatible parts/ accessories will be measured and paid separately under respective items.
Supply only control motor as existing SCADA compatible in replacement of 33 KV, VCB type 036, 1.3 A, 220/260 V, O/PO, 1 KWM/Y06/08, 350/Min complete all as specified and directed.
Supply only Spring charging gears as per existing type and Make complete all as specified and directed.
Supply and fixing in replacement of Red Colour indicator lamp LED 24 Volt and also 110 Volt (AC/DC) with holder suitable for Vacuum Circuit Breaker 11 KV of capacity 400/ 630/ 800 Amps complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply and fixing in replacement of Yellow Colour indicator lamp LED 24 Volt and also 110 Volt (AC/DC) with holder suitable for Vacuum Circuit Breaker 11 KV of capacity 400/ 630/ 800 Amps complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply and fixing in replacement of Blue Colour indicator lamp LED 24 Volt and also 110 Volt (AC/DC) with holder suitable for Vacuum Circuit Breaker 11 KV of capacity 400/ 630/ 800 Amps complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply and fixing in replacement of Green Colour indicator lamp LED 24 Volt and also 110 Volt (AC/DC) with holder suitable for Vacuum Circuit Breaker 11 KV of capacity 400/ 630/ 800 Amps complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply and fixing in replacement of White Colour indicator lamp LED 24 Volt and also 110 Volt (AC/DC) with holder suitable for Vacuum Circuit Breaker 11 KV of capacity 400/ 630/ 800 Amps complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply only Auxillary relay for buchholz relay, oil temp, winding temp trip 24/110V DC as per exsting complete all as specified and directed.
Supply only Master relay 24/110VDC as per exsting complete all as specified and directed.
Supply and fixing Multi Function Meter LCD Display with Parameters - Amp, Volt, Freq, PF, RPM, % Load, % Unbal, Amp phase angle, Maximum Demand including Taking down/ out Unserviceable Multi Function Meter, complete all as specified and as directed. Make- As per existing OEM or approved by GE.
Supply only TNC switch as per exsting complete all as specified and directed.
Supply only Remote local switch as per exsting complete all as specified and directed.
Supply only Control Relay of model CGI 14 C , 50/24 Volt DC in control panel including wiring complete all as specified and directed
Supply, installation,testing and commisioning of 33 KV, outdoor PT, Oil cooled 33KV/110 Volt. complete all as specified and directed.
Material and labour for Preparation of old painted surfaces of steel by brushing/cleaning stain, greasy spots with thinner, applying two coats of spray painting (synthetic enamel paint) on all sides of 33 KV outdoor brakers with spraying machine including writing description of equipment in block English letter 50 mm high with white /black synthetic enamel paint complete all as directed by Engr -in-Charge.
Material and labour for spreading of crushed stone aggregate of nominal size not more than 40mm from the bay/yard manually without damaging any equipments, cable or parts of the 33 KV Grid bays, spreading & levelling of finished gravel uniformaly in layers n. exc. 15 cm thick to true surface all as specified and directed including taking out of old material.
M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petrolium jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
Supplying and Fixing in repairs, male/moving contact/ rotating blade of HDE copper silver plated of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc complete all as specified and directed.
Supplying and Fixing in repairs, Fixed Contacts, made of HDE copper, silver plated, of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc. complete all as specified and directed.
Supplying and fixing of terminal pad for Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity complete all as specified and directed.
M&L for lightining arrester expulsion type ( set of three as per existing make/model/capacity to be fixed on existing structure) complete with all fitting, transmission class, discharge capacity 65 kilo amps suitable for 33000 volts incl taking down old one etc complete as specified and directed
Supply & fix Current transformer (CT) of 33 KV Single Phase, outdoor type, CT ratio 200/1 Amps and 100/1 (dual core one for metering and other for protection) having 16 VA burden and class 5P-10 protection complete all as specified and directed.Make : AE/PRAGATI/KAPPA
Supply, installation, testing and commissioning in replacement of air- breake off load line isolator switch rotating type manually gear drive mechanism operated highest system voltage 36 KV rated current 1250 Amps triple pole with earthing device each pole consist of insulating pedestals 03 Nos on galvanized steel base as per BSS /IS incuding rotating blade of HDE copper and fixed contacts of same material , spring loaded arcing horns of adequate section to brake magnetizing current of transformer as directed with adequate 50mm dia GI operating pipe for operation from ground level and operating handle complete with both off and on positions complete all as specified and directed.
Supply and laying in replacement PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded Copper conductor of size 2.5 sq mm 10 core 1100 Volts grade complete all as specified and directed.
All as per item No. 85 above but 2.5 sqmm 6 core copper conductor complete all as specified and directed.
Supplying, installation, commissioning and testing of SCADA compatible 3 o/c + 1 EF relay RS 485 port compatible for SCADA operation with IEC 61850 incl taking out of existing of complete all as specified and directed
S&F in replacement of vacuum interrupter suitable for 1250 amps, 11 KV HT VCB complete all as specified and directed
Supply and fixing Power Pack 110 V AC/110 V DC on VCB panel as per site requirement complete all as specified and directed . Make - as approved by GE.
Dismantling/ Disconnecting electric connection of underground HT, XLPE Cable, 33/11 KV upto 95 to 300 Sqmm from both sides and locating the fault in HT cable upto 01 KM with fault locating machine in the entire length complete testing after reconnecting and commissioning of cable complete all as specified and as directed. NOTE :- (a) The work will be executed after obtaining proper shutdown from 33 KV MRS liase with JE E/M. (b) Excavation and earth work & Joints will be paid and measured separtely in relevent item. (c) If the complaint not attended within one hour contractor shall be liable to penalty of Rs. 1000/- per hour per complaint.
Supplying, laying, jointing testing and connecting in replacement , XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 33 KV (E) grade, of size 240 Sq mm, 3 core, laid in trenches complete all as specified & directed.
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240/300 Sqmm incl taking down of existing complete.
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm 3 core incl taking down of existing complete.
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system laid in trenches fixed to pole, including jointing & testing of size 300 Sqmm 3 core complete all as specified and directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm incl taking down of existing complete.
Opening up the top cover of power transformer of 5 MVA out door type and taking out the transformer Oil in a separate container (arranged by contractor with in day )after disconnecting the HV/LV side electric connections from both the primary & secondary side of the transformer, for carrying out necessary repair & testing like leakage arresting ,Visual inspection of Tap etc or visual inspection of core/ winding at site including taking out complete core assembly, Megger the defective winding portion/taking out ,cleaning the laminated core,cleaning the tank including minor repair ( ie brazing, soldering, adjusting of coil, packaging ) or as directed if reqd for transformer including assembling & testing & installation the same at the site all as specified and directed by the Engineer-In-Charge,.Note:- (a) All T&P charges etc shall be deemed to be inclusive in the above quoted rate.(b) The cost of insulation material such as paper,cotton tape, latheriod sheet, cork sheet and minor repair wk etc are inclusive in the quoted rates. (c ) Cost of cleaning are included in quoted rates.
M&L for shifting of transformer 5 MVA from 33 Yard to workshop for repairing purpose with suitable T&P and Vehicle safely and revert back from wksp to original place incl connection installation and charging complete.
M&L for Dehydration and filtering the transformer oil with dehydration machine to achieve required di-electric strength of the oil up to 60 KV at 2.5 mm gap complete all as specified and directed. Note 1 :- Dehydration machine and other required equipments shall be arranged by the contractor and no extra cost shall be paid to the contractor on this effect. Note2 : BDV Test certificate shall be submitted by contractor after dehydration.
Supply and filling transformer oil in sealed container for topping up the level of oil having dielectric strength 60 KV during filling after initial filtration, Make -:POWER/ INSOLE/ UNIVERSAL conforming to relevant IS-335 complete all as specified and directed.
M& L for opening up the top cover of transformer and taking out the transformer oil in a separate container after disconnecting the HT/LT side electric connections from both the primary & secondary side of the transformer of any type/description (indoor/out door type) installed on pole/floor, for carrying out necessary repair/rewinding to HT/LT side after shifting the transformer to contractors work shop including taking out complete core assembly, megger testing the defective winding portion/taking out , cleaning the laminated core and rewinding with appropriate gauge/winding wire/strip winding of existing description for transformer of capacity 50 to 100 KVA including assembling & testing on completion & installation the same at the site complete all as specified and directed.Note:- (a) Winding of coil shall be measured and paid seperately under respective item.(b) Transportation charges are deemed to be included in the quoted rate.(c) The cost for the dehyderation of transformer oil if required shall be measured and paid seperately.(d) The cost of insulation material such as paper, cotton tape, latheriod sheet, cork sheet etc are included in the quoted rate. (f) Proper shut down shall be taken by the contractor before execution of the work.
All as above Srl item No 100 in before but of capacity exceeding 100 KVA and upto 200 KVA complete all as specified and directed.
All as above Srl item No 100 here in before but of capacity exceeding 200 KVA and upto 1000 KVA.
M&L for replacement of copper winding wire of any size/description suitable for step down transformer of any capacity, including winding of coil of HT side as per manufacturers design and specification to obtain rated KVA complete all as specified and directed.
All as above Srl item No 103 here in before but for strip winding of LT side complete all as specified and directed.
All as above Srl item No 103 here in before but for aluminium strip winding of HT side complete all as specified and directed.
All as above Srl item No 103 here in before but for aluminium strip winding of LT side complete all as specified and directed.
Shifting only of trolly mounted transformer upto 400 KVA from one location to another location after carefully disconnecting from existing location and connecting at new location complete all as specified and directed
M&L for Replacement of existing defective drain out oil outlet valve of any type & size suitable for outdoor/ indoor transformer complete all as specified and directed .
M&L for Replacement of synthetic rubberised cork sheet gasket, 1/4" thick suitable for main body top cover of transformer of capacity up to 1000 KVA incl opening and lifting of top cover complete all as specified and directed.
M&L for air breather assembly complete with fresh blue colour silica gel suitable for indoor/outdoor transformer capacity upto 200 KVA of 11/0.415 KV Tfr connected to air column with conservator tank complete all as specified and as directed.
All as above Srl item No 110 here in before but for capacity above 200KVA and upto 1000 KVA
S&F in replacement transformer oil temperature gauge 0 - 100, graduated, analogue dial type complete all as specified and directed.
S&F in replacement HT porcelain bushing (set of three) of suitable size for transformer upto 250 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement of HT porcelain bushing (set of three) of suitable size for transformer above 250KVA and upto 1000 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer upto 250 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer above 250KVA and upto 1000 KVA including washers nuts, bolts & complete all as specified and directed.
S&F in replacement HT bush rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer upto 200 KVA capacity complete all as specified and directed.
S&F in repairs HT bush rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer above 200KVA upto 1000 KVA capacity complete all as specified and directed.
S&F in repairs LT bush rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer upto 200 KVA capacity complete all as specified and directed.
S&F in repairs LT bush rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer above 200KVA and upto 1000 KVA capacity complete all as specified and directed.
S & F rubber seal for transformer HT/LT studs complete for any capacity of transformer complete all as specified and directed.
Supply and filling in replacement of silica gel inside the breather assembly and fixing properly with transformer complete all as specified and directed.
M&L for cutting worn out aluminium cable terminal lugs from the HT cable of size 120 to 300 Sqmm and S&F of new aluminium cable lugs of suitable size and reconnecting the cable with transformer, terminal stud including dressing of cable, excavation & surface dressing after providing sand cushioning and brick protection to match with the existing complete all as specified and directed.
M&L in replacement Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised iron side complete all as specified, including testing and commissioning complete all as directed. Note :-(a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in soft/loose soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 type C2 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement 6mm dia both ways as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply installation,testing and commissioning of chemical earthing maintenace free with electrode of size 85 mm dia x 300 mm long with 17.2 mm Cu bonded MS conductor pre cast or in situ cast in high purity electrically conductive granular material having ultra low resistive value . Electrode made of conductive earth enhancing material mixed wirth cement in ratio 3:1 to encase or back fill the voids surrounded the 17.2 mm cu bonded MS conductor or other metal components places in augured bore hole of 85 mm diax3000 mm depth, resulting to increase in the effective surface area of the earth electrode or grids to lower the resistance permanently with no further maintenance, like periodic, re- watering or recharge of salt or earth enhancing compound for a long period in dry soil or rocks, earth enhancing material should not leach chemicals in to the adjacent soil or underground water chanels and should be pH neutral range. Earth enhancing material should permanently protect the encased metal compound of earthing system. All hardware like nuts, bolts and washers should be stainless steel Electrode top terminal be sealed permanently packed with conductive concrete and Cu bonded MS/ copper extension strip taken out be terminated on to the earth bus bar complete all as spd and directed.
M&L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint completeall as spd and directed.
M&L Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp for 11000 V grade complete all as spd and directed.
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25x4mm dia galvanised iron or strip complete all as specified and directed.
Dismantling of PCC/steel tubular pole incl coping, foundation etc complete all as specified and as directed
M&L for steel tubular sewaged poles of complete with cast iron base plate, finial taper plug, bolts, nuts and screws, as specified type 410 SP-55 11 Mtrs long all as specified and directed.
M&L in repair for boring of holes under road /pavement/hard standing or any other situation by mannual means for 100 mm bore for crossing the cable and making good both the ends all as specified and directed at site. Note :- GI pipe shall be measure and paid separately under respective item.
M&L for painting the external exposed surfaces of steel tubular swaged/rail poles of HT alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters(length of each letter 40mm) on black back ground and pasting radium red strickers/paint with 3 lines alternative layers of 30 cm width around the pole complete all as directed.
M&L for cleaning the area around the sub station including two pole/four pole structures premises, trimming the trees, complete all as specified and as directed.
Looping /prooning of tree branches upto the extend to obtain clearance all around the OH lines conductor upto 3 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed. Note : (a) The tree branches etc will be left as it is and will not be carried away by the contractor / DEL as wood belongs to CEO/DEO and they will be responsible to lift the wood. (b) Prooning of all tree branches in one tree shall be measured as one job. (c) Contractor will employ sufficient labour to complete the job with in time as required. (d) Contractor will be responsible for any type of mishapening / accident while proning the trees. (e) Contractor supervisor will take proper shut down from the MES installations before starting the work and clear it before resuming power supply. However full assistance will be provided by MES Staff. (f) The contractor will provide proper tools and safety devices to his staff for prooning of trees.
M&L for hiring of cable fault locator machine for HT cables working voltage 11 KV to find out the fault in underground trench at different location up to 500 RM after locating the fault the contractor has to provide megger and test the faulty cable complete all as specified and directed. Note : (a) Excavation and earth work will be paid and measured seperately in relevant item. (b) Jointing kit for above job will be paid and measured seperately. (c) The contractor shall be provide fault locator and test the cable immediately after getting complaint within stipulated time , In case of failure on the part of contractor to attend the complaint penalty of Rs 1000/-per hour shall be imposed from the contractor.
S&F in repair Cable end termination 11 KV HT (heat shirnkable) cable jointing kit for 11 KV (Earthed) grade cable for indoor type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
All as per Sl item No 136 here-in-before but size of 120 to 185 sqmm complete all as specified and directed.
S&F in repair Cable end termination 11 KV HT (heat shirnkable) cable jointing kit for 11 KV (Earthed) grade cable for outdoor type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
S&F in repair Straight through 11 KV HT (heat shirnkable) cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of of size 120 to 185 sqmm complete all as specified and directed.
All as per Sl item No 139 here-in-before but size of 95 sqmm complete all as specified and directed.
Dismantling of cross arms of MS channel or angle sections etc complete and setting aside for re-use with in 50 m complete all as specified and as directed.
Dismantling of ACSR from the poles all as specified and directed by Engineer -in-Charge.
M&L for aluminium conductor, steel reinforced incl stringing in position all as specified and directed by Engineer -in-Charge.
Dismantling insulators any type any size from HT poles complete all as specified and directed.
M&L for Pin type , porcelain, vitreous, white , borwn or green insulator including one galvanised mild steel spindle , two galvanised mild steel spindle, two galnvanised iron wahers and one galvanised iron nut, 150 mm height,150 mm dia for 11000 volts grade complete all as specified and directed.
S&F in repair loop type insulator with complete fitting porcelain, vitreous white or brown large sizewith over all dismensions 90x140mm , clearance of hole 25.5mm complete all as specified and directed.
Dismantling stay assembly complete from the pole complete all as specified and directed.
M&L for stay assembly complete with accessories of diameter of stay rod in 20 mm all as specified and directed by Engineer -in-Charge.
S&F in repair galvanised steel stranded stay wire size 7/4mm for stay assembly complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 KV for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed.
M&L in repair Earthing complete with copper earth plate 60cm x 60cm x 3.15mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to 20x3mm copper strip as earthing lead by means of bolts, nuts, check nuts and washer of brass all as shown in electrical plate No 3 of SSR Part-I connected to continuous earth wire/lead all as specified and testing on completion, including provision of earth strip protected by 40 mm dia GI light grade protection pipe from test point to main board and 40mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as directed at site.
M&L for glow sign board LED of required size (180 x 80 x 30 cm) made out of steel frame ame with MS sheet of suitable size with flex sheet marked with details of sub station on front with different colours including provision of LED power-fittings & fixtures in equal distance to illuminate board including connections with 2.5 sqmm stranded copper conductor cable all as specified and directed by Engr in Charge.
Supply and Fix HT Aluminium Lugs of size 95 sqmm complete all as specified and directed.
Supply and Fix HT Aluminium Lugs of size 120 sqmm complete all as specified and directed.
Supply and fix fuse wire of capacity 5A to 50 A as required for above Job complete all as specified and directed.
Supply and fix Insulating ACSR conductor jumpher for 11 kv HT line min length of 2.0 mtr including thimble of sutable size for both ends and binding properly complete all as specified and directed.
S&F in replacement latest electronic over current and earth fault relay three phase, 03 OC and 1 EF, auxillary supply as per existing DC supply with 2 No + 2 NC contact suitable for SCADA compatible 11 KV VCB/OCB complete all as specified and directed.
M&L for repairing of 11 KV indoor PT with replacement of all damaged parts all male and female spouts and SRC fuses complete all as specified and directed.
S&F in replacement phase barriors support including brass bolt/washer for holding copper bus bar in the HT panel of existing type/size/capacity complete all as specified and directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm incl taking down of existing complete.
M&L for Dehydration and filtering the transformer oil with dehydration machine to achieve required di-electric strength of the oil up to 40 KV at 2.5 mm gap complete all as specified and directed. Note 1 :- Dehydration machine and other required equipments shall be arranged by the contractor and no extra cost shall be paid to the contractor on this effect. Note2 : BDV Test certificate shall be submitted by contractor after dehydration.
Supply and filling transformer oil in sealed container for topping up the level of oil having dielectric strength 60 KV during filling after initial filtration,complete all as specified and directed.
M& L for opening up the top cover of transformer and taking out the transformer oil in a separate container after disconnecting the HT/LT side electric connections from both the primary & secondary side of the transformer of any type/description (indoor/out door type) installed on pole/floor, for carrying out necessary repair/rewinding to HT/LT side after shifting the transformer to contractors work shop including taking out complete core assembly, megger testing the defective winding portion/taking out , cleaning the laminated core and rewinding with appropriate gauge/winding wire/strip winding of existing description for transformer of capacity 50 to 100 KVA including assembling & testing on completion & installation the same at the site complete all as specified and directed. Note:- (a) Winding of coil shall be measured and paid seperately under respective item. (b) Transportation charges are deemed to be included in the quoted rate. (c) The cost for the dehyderation of transformer oil if required shall be measured and paid seperately. (d) The cost of insulation material such as paper, cotton tape, latheriod sheet, cork sheet etc are included in the quoted rate. (f) Proper shut down shall be taken by the contractor before execution of the work.
All as above Srl item No 163 here in before but of capacity exceeding 100 KVA and upto 200 KVA.
All as above Srl item No 163 here in before but of capacity exceeding 200 KVA and upto 400 KVA.
M&L for replacement of copper winding wire of any size/description suitable for step down transformer of any capacity, including winding of coil of HT side as per manufacturers design and specification to obtain rated KVA complete all as specified and directed.
All as above Srl item No 166 here in before but for strip winding of LT side
All as above Srl item No 166 here in before but for aluminium strip winding of HT side
All as above Srl item No 166 here in before but for aluminium strip winding of LT side
M&L for Replacement of existing defective drain out oil outlet valve of any type & size suitable for outdoor/ indoor transformer complete all as specified and directed .
M&L for air breather assembly complete with fresh blue colour silica gel suitable for indoor/outdoor transformer capacity upto 200 KVA of 11/0.415 KV Tfr connected to air column with conservator tank complete all as specified and as directed.
All as above Srl item No 171 here in before but for capacity above 200KVA and upto 400 KVA
S&F in replacement transformer oil temperature gauge 0 - 100, graduated, analogue dial type complete all as specified and directed.
S&F in replacement HT porcelain bushing (set of three) of suitable size for transformer upto 250 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement of HT porcelain bushing (set of three) of suitable size for transformer above 250KVA and upto 400 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer upto 250 KVA including nuts, bolts & washers complete all as specified and directed.
S&F in replacement LT porcelain bushing (set of four) of suitable size for transformer above 250KVA and upto 400 KVA including washers nuts, bolts & complete all as specified and directed.
S&F in replacement HT bush rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer upto 200 KVA capacity complete all as specified and directed.
S&F in repairs HT bush rod (set of three) made out of copper with brass nuts and washers of required length including connecting up with HT coil of transformer above 200KVA and upto 1000 KVA capacity complete all as specified and directed.
S&F in repairs LT bush rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer upto 200 KVA capacity complete all as specified and directed.
S&F in repairs LT bush rod (set of four) made out of copper with brass nuts and washers of required length including connecting up with LT coil of transformer above 200KVA and upto 400 KVA capacity complete all as specified and directed.
S & F rubber seal for transformer HT/LT studs complete for any capacity of transformer complete all as specified and directed.
Cutting worn out aluminium cable terminal lugs from the HT cable of size 120 to 300 Sqmm and S&F of new aluminium cable lugs of suitable size and reconnecting the cable with transformer, terminal stud including dressing of cable, excavation & surface dressing after providing sand cushioning and brick protection to match with the existing complete all as specified and directed.
Looping/Prunning of tree branches to obtain clearance all around the 11 KV line including removing of cut branches and cleaning of site complete all as specified and directed. Note:- (a) The tree branches etc willl be left as it as and will not be carried away by the contractor as wood belongs to CEO/DEO and they will be responsible to lift the wood.However the same shall be stacked properly to avoid any inconvience to traffic etc. (b) Prunning of all tree branches of one tree shall be measured as one Job. (c) Contractor shall employ sufficient labour to complete the job within time as required. (d) Contractor shall be responsible for any type of mishappeing/accident while prunning of the trees. (e) Contractor's supervisor will take proper shut down from the MES installations before starting the work and clear it before resuming power supply. However full assistance will be provided by MES Staff. (f) The contractor will provide proper tools and safety devices to his staff for carrying out prunning of trees
M&L for disconnecting the input and output electric supply from automatic voltage stablizer upto 100 KVA capacity and taking out from site and shifting to civil workshop for carrying out repair works including servicing of dimmer and gears and refixing the same after repair complete all as specified and directed. Note:- The rate quoted by the contractor shall include the rate of T&P, transportation and necessary man power required during loading and unloading.
Opening the top cover of voltage stablizer taking out the complete servo stablizer oil and keep it for reuse and taking out dimmer assembly and transformer assembly for checking the defects and carrying necessary repair work complete all as specified and directed.
Copper wound dimmer state unit of capacity 100KVA servo voltage stablizer complete all as specified and directed
S&F in replacement electronic cards including replacement of all worn out parts complete all as specified and directed.:-
Servo motor complete with RC network complete all as specified and directed
Micro switch complete all as specified and directed
RC Network for motor complete all as specified and directed
Carbon bushes complete all as specified and directed
M&L for construction brick masonry platform in replacement of for mounting transformer of 200 KVA to 400 KVA capacity of overall finish size 3mx3mx1.25 mtr high above ground level with sub class 'B' bricks wall 230mm in CM 1:4 PCC 1:4:8 type D2 (using 40mm graded stone agregate) top of the platform finished even and fair without using extra cement including necessary form work, excavation in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtr and rendering 10 mm thick in CM 1:4 on all exposed vertical surfaces of platform including complete fancing of the transformer base as per existing fancing wtih MS angle iron frame 50x50x6mm as in posts at an interval 1.2 mtr centre to centre and 2.25 mtr height duly grouted in PCC 1:3:6 type C-2 (using 40mm aggregate stone and painted with two coats of synthetic enamel paint over a coat of red oxide primer) alongwith 3 Nos Steps, complete all as specified and directed.
Repairing of DC battery charger suitable forrecharge of batteries 12 V 160AH for supply to relays for smooth functioning of control relay including replacement of worn out wirinf and replacement of other deffective parts complete all as specified and as directed.
Taking out unservicable batteries from DC Battery bank folat cum boost charger and S&F with 2 volt 100 AH new maintenance free batteries dry type complete all as specified and directed
S & Fix in repair lightning arresters expulsion type complete with all fittings ,30 KA discharge capacity ,distribution class complete all as specified and directed.
Taking down transformer of any capacity from plinth including disconnecting from HT and LT connection and reinstallation in specified near by area complete and Remounting on plinth and Reinstallation complete all as specified and directed.NOTE:Cost of crane/hydra and labour included in quoted rate.
Shifting of trolly mounted transformer upto 400 KVA from one location to another location after carefully disconnecting from existing location and connecting at new location complete all as specified and as directed.
Note : (i) Complaints pertaining to External Electric Supply shall be resolved by the contractor immediatelly after getting complaints. In case of failure on the part of contractor to resolve to the complaints within stipulated time, a penalty of Rs 5000/- per day per complaint shall be imposed from the contractor. (ii) The contractor or his authorised representative shall report to the concerned JE E/M / Engr -in-Charge during the time of breakdown. A register shall be maintained to record all orders & instructions and their complaints and is to be signed by the contractor/his representative and the Engineer-in-charge/JE E/M concerned. (iii) Work done register to be maintained by the contrator.
BHARAT ELECTRICAL TRADERS (BID ID -3480883)
R D Bansal (BID ID -3487111)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQ_825277.xls
BOQ • 0.43 MB
TD93.pdf
Tender Documents • 2.82 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .