Sh K A Vardhan, IDSE
Office of the GE (Army) Camp Hanuman, Ahmedabad - 380 004
SPECIAL REPAIR TO LT CABLE PANEL AT DIV HQ PS LINE AND NGV SUBSTATION ALONGWITH UG CABLE AND CERTAIN MINOR WORKS UNDER AGE EM AOR UNDER GE A AHMEDABAD
2020_MES_385912_1
8132/E8
Open Tender
Civil Works
Item Rate
180 days
GE (Army) Ahmedabad
AS PER NIT
9 documents required · 9 mandatory
₹500
GE (Army) Ahmedabad
₹26,400
Yes
2 Feb 2021
13 Oct 2020
12 Nov 2020
13 Oct 2020
10 Nov 2020
27 Oct 2020
13 Oct 2020 - 27 Oct 2020
Amount
M&L for taking down of old unserviceable LT panel any type any size any capacity including all accessories after disconnecting elect cable connection from MCCB/MCB/Capacitor/Earthing terminals from existing site and dismantaling of foundation without damaging of LT cables and keep aside complete all as directed.
Supply, errect, test and commissioning LT feeder pillar box out door type, standing top, from CPRI type tested approved manufacturer fabricated, powder coated, dust & vermin proof, air vent gasket for natural air flow including removal cable entry gland plate, powder coated 440 volts, 3 phase, 4 pole, 50 cycles outdoor type weather proof made out of 3mm thick CRCA sheet, seperated chamber will be made with 2mm thick CRCA for each switch gear and bus bar with MS Channel base frame of size 75mmx75mmx6mm, hinged door, double locking arrangement with 'U' shape gasket on door panel with aluminium bus bar 800 Amps capacity insulated, Digital ammeter 0-500 amps, with CTs, Digital voltmeter 0-500 volts , LED indicating lamp with Kit-Kat control fuses for RYB installed and including on PCC 1:3:6 type C1 as per OEM drawing size of foundation comprising the following:- (Drg / design of Panel need to be approved by Engr-in-charge before given order to concern factory ). (Loc - Div HQ)
Incoming (Main) :- One number MCCB 250 amp, 4 pole, Ics 35 KA, 415 volts, 50 Hz with thermal magnetic release adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420219 or equivalent in Havells or Hager as approved.
Outgoing:- (i) Six Numbers MCCB 100 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420015 or equivalent in Havells or Hager as approved.
(ii) Two Numbers MCCB 63 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420013 or equivalent in Havells or Hager as approved.
(iii) Six Numbers of panel mounted on-load AC changeover connected through suitable size of copper bus bar coated with insulating sleeves capacity of 100 Amps, 415 Volt, 4 pole, 50 Hz with advance neutral conforms to IS : 13947-3 including pahse barrier & handle with door interlock kit complete all as directed. Make : Standard, Cat ref No ISCNFO 0100 or equivalent in Havells / Hager.
Note:-(i) All internal connections of changeover/MCCBs shall be with suitable size of copper bus bar/copper cable (ii) The foundation of panel board shall be above 60 cm fromground level. (iii) All incoming and outgoing cables will be provided with suitable size of cable glands (iv) The design drawing of panel to be submitted with copy of genuine CPRI type test certificate of panel manufacturer. Any confirmation of genuiness of CPRI type test required at later stage, the same will be produced by contractor without any extra expenduture due to department. (v) Antirust paint will be provided on external surface of panel.
All as per item No 2 above but comprising with the following incoming and out going accessories:- (Loc : P S Line)
Incoming (Main) :- One number MCCB 400 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz with thermal magnetic release adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 422007 or equivalent in Havells or Hager as approved.
Outgoing:- (i) One Number MCCB 200 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420208 or equivalent in Havells or Hager as approved.
(ii) Two Numbers MCCB 160 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420207 or equivalent in Havells or Hager as approved.
(iii) Two Numbers MCCB 100 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bas coated with insulating sleeves. Make : Legrand cat ref no. 420205 or equivalent in Havells or Hager as approved.
(vi) One Number MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420003 or equivalent in Havells or Hager as approved.
All as per item No 2 above but comprising with the following incoming and out going accessories:- (Loc : P S Line)
Incoming (Main) :- One number MCCB 320 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz with thermal magnetic release adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 422006 or equivalent in Havells or Hager as approved.
Outgoing:- (i) One Number MCCB 200 amp, 4 pole, Ics 25 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420208 or equivalent in Havells or Hager as approved.
(ii) Two Numbers MCCB 160 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420207 or equivalent in Havells or Hager as approved.
(iii) Two Numbers MCCB 100 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420205 or equivalent in Havells or Hager as approved.
(iv) One Number MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420003 or equivalent in Havells or Hager as approved.
All as per item No 2 above but comprising with the following incoming and out going accessories:- (Loc : NGV Sub Station)
Incoming (Main) :- One numbers MCCB 250 amp, 4 pole, Ics 36 KA, 415 volts, 50 Hz with thermal magnetic release adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420249 or equivalent in Havells or Hager as approved.
Outgoing:- (i) Three Numbers MCCB 160 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420207 or equivalent in Havells or Hager as approved.
(ii) One Number MCCB 100 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420205 or equivalent in Havells or Hager as approved.
(iii) One Number MCCB 63 amp, 3 pole, Ics 16 KA, 415 volts, 50 Hz, thermally adjustable lcs=100% lcu against overload setting connected through suitable size copper bus bar coated with insulating sleeves. Make : Legrand cat ref no. 420003 or equivalent in Havells or Hager as approved.
Supply, installation, testing and commissioning out door type APFC correction panel for power factor correction , manufactured by CPRI type tested approved panel manufacturer, compartmentalised made out of 3mm thick CRCA sheet, front and back open double door system locable and air vent gaskets for natural flow of air, powder coated, dust and vermin proof, with MS Channel base frame of size 75mmx75mmx6mm complete of capacity 70 KVAR distributed in steps of 5 steps (2x5 KVAR, 2x10 KVAR 1x40KVAR) with manufacturer configuration having auto switching system for each stage as per the varying load sensed by the APFC relay. Each switching stage shall carry back up, protection in the form of MCB TP, ON/OFF indication lamps etc complete with PCC 1:3:6 foundation as per OEM drawing and comprising with following items : (Loc : P S Line)
APFC RELAY :- Microprocessor based APFC relay flush mounted, on site programmable capable for detecting wrong current transformer connections with following specification:-
Programmable - at site
Protection Class - IP 64 front & IP 31 rear
Working temperature - (-) 10 to (+) 500 C
Over voltage trip point - ± 15%
Alarm contact - One
Harmonics O/L - Available
Low current release - Less than 50 mA
Voltage release - 35 milli seconds
Switching sequence - Self adjusting
PF adjusting range - 0.8 lag to 0.95 lead by digital setting keys
C/K adjustment - Auto calculation of C/K value
Voltage burden - 5 VA
Current burden - 0.5 VA
Stages - Minimum 12
Frequency - 50 Hz
Voltage inputs - 415 ± 15%
Current inputs - 5A
Alarm - 4
Contact function - Alarm
Switching pattern - Programmable
CAPACITOR: The capacitors shall be housed in self-extinguishing insulating material operated on 3 phase 415 volts AC. The dielectric should be mixed dielectric type, with built in over pressure safety device. Capacitors should carry the following technical specifications:-
Dielectric construction - Mixed dielectric (MDXL)
Voltage - 415 volts only
Rated frequency - 50 Hz
No of phases - 3
Output capacitance tolerance - 0% to 10%
Dielectric loss - Less than 0.50 watt / KVAR
Capacitor loss - Less than 1.0 watt / KVAR
Protection degree - IP 30
Temperature (Max) - 550 C
Container type - MS sheet
Make - L&T MD XL Ultra or equivalent in Siemens or Schneider or ABB or Neptune as approved.
INCOMING MCCB :- MCCB 125 amp 3 pole, Ics 25 KA, 415 volts, 50 Hz with thermal magnetic release lcs = lcs 100% against overload setting. Make - Legrand equivalent in Schneider or Hager or L&T as approved
CTs/Voltmeter/Ammeter:- Suitable rating CTs/ digital voltmeter & ammeter shall be provided.
Busbars:- Copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB.
Note for APFC Panels :- All items / components / accessories which are useful and necessary for efficient working of the APFC panel to achieve power factor 0.99 shall deemed to be included in the item irrespective of the fact whether such items are specifically mentioned in it or not.
All as per item No 6 above of APFC panel but capacity of 50 KVAR distributed in steps of 3 steps (1x5 KVAR, 1x15 KVAR , 1x30 KVAR) complete all as directed.
Supply, laying & testing LT cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 120 Sqmm complete all as directed. Make : Havells/ Polycab/ RR kabel
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specifed and punned thickness shall be measured and paid.
Supply and laying sub class 'B' bricks of old size (230x115x75 mm) or of size locally available , laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge
S&F steel tubes light grade galvanized 100 mm bore ISI marked with all fittings fixed to walls / floors / road crossing, poles as required. Make : Tata / Jindal / Surya Prakash
Labour & tools for horizontal boring 100mm using trenchless technology under road / path / floor for passing UG cables through GI pipe as required.
Supply and fix refrigerator ,electric driven (single phase) ,capacity 253 Litres Double door. Make:- Samsung cat ref No RT28T312258/HL) or LG/ Haier as approved.
Supply and fix Deep Freezer glass top of 320 litres capacity having single door,BEE 5 star rated . Make:- Voltas cat ref No HC-320GTDD or Daikin or Bluestar as approved.
Supply and fix refrigerator electric driven (single phase) capacity 195 litre .BEE 5 star rated. Make:- Haier cat ref No 1953CRS-E or Samsung or LG as approved.
Supply and fix refrigerator ,electric driven (single phase) ,capacity more than 324 litres .BEE 5 star rated. Make:- Samsung cat ref No HC324GTRF or equivalent in LG or Haier as approved.
BABBAR ENGINEERS
RISING ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .