Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹28.2 L+₹10,650 (0.38%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L2 | Rejected-Finance Not being L1 | |
| 3 | L3₹30.2 L+₹2.1 L (7.47%)Rejected-Finance | L3 | Rejected-Finance Not being L1 | |
| 4 | L4₹35.6 L+₹7.5 L (26.9%)Rejected-Finance INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | L4 | Rejected-Finance Not being L1 |
Tender Value
₹25.0 L
EMD Value
₹49,940
Closing Date
25 Mar 2024, 6:00 pmClosed
GE (I) Navy Jamnagar
INS Valsura, Jamnagar - 361 150
Special repairs/ replacement to LT ACBs and LT Panels including connecting items at certain locations under GE (I) Navy Jamnagar
2024_MES_637016_3
8719/VAL/E8
Open Tender
Miscellaneous Works
Item Rate
150 days
GE (I) Navy Jamnagar
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (I) Navy Jamnagar
₹49,940
Yes
2 Apr 2024
5 Mar 2024
27 Mar 2024
5 Mar 2024
25 Mar 2024
13 Mar 2024
Amount
Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new indoor type, LT Panel Box cubical type of suitable size (minimum depth 900mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 2 mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-54 with coloured insulation sleeve, rubber gasket, insulators, indoor type, totally enclosed, weather, dust and vermin proof as per IS, Front & Rear opening with double door shutters having suitable aldrop bolt locking arrangement, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground/floor level and 30cm below ground/floor level, comprising & including the following accessories complete all as specified and as directed :- description of item contd....
Description of serial item No. 1 contd… (a) INCOMING (i) Air Circuit Breaker (ACB), 800 Amp, 4 Pole, 50 kA, 415 Volts, 50 HZ, AC Supply, Drawout version, single frame, Electrical Version, including advanced self powered electronic protection unit with LSIg and shunt coil, Closing coil, Shunt Trip, Motor operator, working on 220-250 V AC, Neutral Overload protection OFF-50%-100%, inbuilt temperature protection, LCD Display, fast operation type connecting with proper size link set. ACB shall comply with IS/IEC 60947-1&2. ACB shall have ready to close indication contact operational voltage 415V AC, insulation voltage 1000 AC, impulse voltage 12 KV breaking performance Icu=Ics=Icw (1Sec) in KA, including all accessories like shunt release, under voltage release, closing coil, two key locks to ensure safety, protected by electronic protection unit (self powered type) with batteries, ACB shall have inbuilt protection for Adjustable over load current (Ir) from 40% to 100% rating of ACB (in),overload time setting from 1.5 to 10 times of Ir setting, short circuit time delay from (0 to 1 Sec), inbuilt Earth fault setting from (20% to 100%) with time delay setting, over temperature protection inside ACB with alarm generation, programmable pre-alarm for overload protection over temp & trip function with counter facility & trip history with EMC/EMI tested, ACB comply with generate reports based on data stored with USB port. Make : Legrand ‘ACB : Cat No. 6695 43’, ‘Electronic Protection Unit LSIg : Cat No. 0281 66’, ‘Motor operator 220-250 V AC/DC : Cat No. 0281 23’, ‘Closing coil 220-250 V AC/DC : Cat No. 0281 29’ & ‘Shunt release 220-250 V AC/DC : Cat No. 0281 34’ or equivalent in makes mentioned in Appendix 'B' here-in-after. description of item contd....
Description of serial item No. 1 contd… (x) CT Short Link - 06 Nos. (xi) E-Stop Push Button - 01 No. Make: L&T Cat No. EMNRMH1 or equivalent in makes mentioned in Appendix 'B' here-in-after. (b) OUTGOING NO. 01 (i) MCCB 630 Amp, 3 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. Make: Legrand Cat Part No. 4220 04 or equivalent in makes mentioned in Appendix 'B' here-in-after (ii) Spreader Terminal, 3 Pole, Set of Three, suitable for MCCB 630 Amp - 2 Sets. Make: Legrand Cat Part No. 6250 04 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (iii) Rotary Handle, Vary Depth type, suitable for MCCB 630 Amp - 1 No. Make: Legrand Cat Part No. 4201 63 or equivalent in makes mentioned in Appendix 'B' here-in-after. (c) OUTGOING NO. 2 (i) MCCB 250 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. Make: Legrand Cat Part No. 4202 49 or equivalent in makes mentioned in Appendix 'B' here-in-after (ii) Spreader Terminal, 4 Pole, Set of Four, suitable for MCCB 250 Amp - 2 Sets. Make: Legrand Cat Part No. 6250 18 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (iii) Rotary Handle, Vary Depth type, suitable for MCCB 250 Amp - 1 No. Make: Legrand Cat Part No. 4201 61 or equivalent in makes mentioned in Appendix 'B' here-in-after. description of item contd....
Description of serial item No. 1 contd… (d) OUTGOING NO. 3 & 4 (i) MCCB 125 Amp, 3 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 02 Nos. Make: Legrand Cat Part No. 4200 86 or equivalent in makes mentioned in Appendix 'B' here-in-after (ii) Spreader Terminal, 3 Pole, Set of Three, suitable for MCCB 125/160 Amp - 4 Sets. Make: Legrand Cat Part No. 6250 02 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (iii) Rotary Handle, Vary Depth type, suitable for MCCB 125/160 Amp - 2 Nos. Make: Legrand Cat Part No. 4201 61 or equivalent in makes mentioned in Appendix 'B' here-in-after. (e) OUTGOING NO. 5 & 6 (i) MCCB 100 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 02 Nos. Make: Legrand Cat Part No. 4200 95 or equivalent in makes mentioned in Appendix 'B' here-in-after (ii) Spreader Terminal, 4 Pole, Set of Four, suitable for MCCB 100/160 Amp - 4 Sets. Make: Legrand Cat Part No. 6250 06 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (iii) Rotary Handle, Vary Depth type, suitable for MCCB 100/160 Amp - 2 Nos. Make: Legrand Cat Part No. 4201 61 or equivalent in makes mentioned in Appendix 'B' here-in-after. (f) FOR 200 KVAR (i) MCCB 400 Amp, 3 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. Make: Legrand Cat Part No. 4220 02 or equivalent in makes mentioned in Appendix 'B' here-in-after description of item contd....
Description of serial item No. 1 contd… (ii) Spreader Terminal, 3 Pole, Set of Three, suitable for MCCB 400/630 Amp - 2 Sets. Make: Legrand Cat Part No. 6250 04 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (iii) Rotary Handle, Vary Depth type, suitable for MCCB 400/630 Amp - 1 No. Make: Legrand Cat Part No. 4201 63 or equivalent in makes mentioned in Appendix 'B' here-in-after. (iv) APFC controller for Contactor switching with 1 CT input, 12 No. of steps (For Contactor Switching), size 144 x 144, 1/5 Amp single CT input, Voltage input - 415 V - 01 No. Make; L&T Cat No. “etaSMART R” CS90903OOOO or equivalent in makes mentioned in Appendix 'B' here-in-after. (v) MCB SP 6 Amp, 240 V, 50 Hz, AC supply, 10 kA, 'C' Curve - 04 Nos. Make: Legrand Cat Part No. 4085 87 or equivalent in makes mentioned in Appendix 'B' here-in-after. (g) FOR 25 KVAR (i) MCB TP 63 Amp, 10 kA, ‘C’ Curve, 415 Volt grade, AC, 50 Hz - 04 Nos. Make: Legrand Cat Part No. 4086 61 or equivalent in makes mentioned in Appendix 'B' here-in-after. (ii) Capacitor duty Contactor, 25 kVAr Rating @ 440V, 3Ph, 50 Hz, 1NO built-in Auxiliary Contacts - 04 Nos. Make: L&T “Type MO C25” Cat Part No. CS96322 or equivalent in makes mentioned in Appendix 'B' here-in-after. (iii) 25 kVAR Capacitors Heavy Duty Cylindrical type (ISI marked) 440 V - 04 Nos. description of item contd....
Description of serial item No. 1 contd… (h) FOR 20 KVAR (i) MCB TP 50 Amp, 10 kA, ‘C’ Curve, 415 Volt grade, AC, 50 Hz - 02 Nos. Make: Legrand Cat Part No. 4086 60 or equivalent in makes mentioned in Appendix 'B' here-in-after. (ii) Capacitor duty Contactor, 20 kVAr Rating @ 440V, 3Ph, 50 Hz, 1NO built-in Auxiliary Contacts - 02 Nos. Make: L&T “Type MO C20” Cat Part No. CS90021 or equivalent in makes mentioned in Appendix 'B' here-in-after. (iii) 20 kVAR Capacitors Heavy Duty Cylindrical type (ISI marked) 440 V - 02 Nos. description of item contd....
Description of serial item No. 1 contd… (j) FOR 15 KVAR (i) MCB TP 32 Amp, 10 kA, ‘C’ Curve, 415 Volt grade, AC, 50 Hz - 02 Nos. Make: Legrand Cat Part No. 4086 58 or equivalent in makes mentioned in Appendix 'B' here-in-after. (ii) Capacitor duty Contactor, 15 kVAr Rating @ 440V, 3Ph, 50 Hz, 1NO built-in Auxiliary Contacts - 02 Nos. Make: L&T “Type MO C15” Cat Part No. CS90019 or equivalent in makes mentioned in Appendix 'B' here-in-after. (iii) 15 kVAR Capacitors Heavy Duty Cylindrical type (ISI marked) 440 V - 02 Nos. (k) FOR 10 KVAR (i) MCB TP 25 Amp, 10 kA, ‘C’ Curve, 415 Volt grade, AC, 50 Hz - 02 Nos. Make: Legrand Cat Part No. 4086 57 or equivalent in makes mentioned in Appendix 'B' here-in-after. (ii) Capacitor duty Contactor, 10 kVAr Rating @ 440V, 3Ph, 50 Hz, 1NO built-in Auxiliary Contacts - 02 Nos. Make: L&T “Type MO C10” Cat Part No. CS96156 or equivalent in makes mentioned in Appendix 'B' here-in-after. (iii) 10 kVAR Capacitors Heavy Duty Cylindrical type (ISI marked) 440 V - 02 Nos. description of item contd....
Description of serial item No. 1 contd… Notes : (i) Old existing serviceable ACB 630 Amp fixed in the existing Panel shall be taking down carefully and deposited to Store Yard of AGE E/M (N) Jamnagar. (ii) Vertical height of legs of LT panel base frame shall be not less than 45 cm from top of nearest road level / PCC floor finish. Legs shall be grouted in ground minimum 30cm in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). (iii) The contractor shall produce and get the detailed (GD) drawings of LT Panel approved from GE through Engineer-in-Charge before fabrication and placing the order to the approved manufacturer. (iv) MS frame work shall be painted with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer. (v) Cost of internal wiring, MS frame work, painting, platform, MCCB spreaders, cable glands, locking arrangement with aldrop bolt and any minor addition/alteration where required at site (the decision of GE shall be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new indoor type, LT Panel Box cubical type of suitable size (minimum depth 900mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 2 mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-54 with coloured insulation sleeve, rubber gasket, insulators, indoor type, totally enclosed, weather, dust and vermin proof as per IS, Front & Rear opening with double door shutters having suitable aldrop bolt locking arrangement, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground/floor level and 30cm below ground/floor level, comprising & including the following accessories complete all as specified and as directed :- description of item contd....
Description of serial item No. 2 contd… (a) Air Circuit Breaker (ACB), 1000 Amp, 4 Pole, 50 kA, 415 Volts, 50 HZ, AC Supply, Drawout version, single frame, Electrical Version, including advanced self powered electronic protection unit with LSIg and shunt coil, Closing coil, Shunt Trip, Motor operator, working on 220-250 V AC, Neutral Overload protection OFF-50%-100%, inbuilt temperature protection, LCD Display, fast operation type connecting with proper size link set. ACB shall comply with IS/IEC 60947-1&2. ACB shall have ready to close indication contact operational voltage 415V AC, insulation voltage 1000 AC, impulse voltage 12 KV breaking performance Icu=Ics=Icw (1Sec) in KA, including all accessories like shunt release, under voltage release, closing coil, two key locks to ensure safety, protected by electronic protection unit (self powered type) with batteries, ACB shall have inbuilt protection for Adjustable over load current (Ir) from 40% to 100% rating of ACB (in),overload time setting from 1.5 to 10 times of Ir setting, short circuit time delay from (0 to 1 Sec), inbuilt Earth fault setting from (20% to 100%) with time delay setting, over temperature protection inside ACB with alarm generation, programmable pre-alarm for overload protection over temp & trip function with counter facility & trip history with EMC/EMI tested, ACB comply with generate reports based on data stored with USB port. Make : Legrand ‘ACB : Cat No. 6695 44’, ‘Electronic Protection Unit LSIg : Cat No. 0281 66’, ‘Motor operator 220-250 V AC/DC : Cat No. 0281 23’, ‘Closing coil 220-250 V AC/DC : Cat No. 0281 29’ & ‘Shunt release 220-250 V AC/DC : Cat No. 0281 34’ or equivalent in makes mentioned in Appendix 'B' here-in-after. description of item contd....
Description of serial item No. 2 contd… (m) Voltage Monitoring Relay, 415 V, AC, 3Ph, 4 W, 2 C/O - 01 No. Make: L&T Cat No. MAC04 or equivalent in makes mentioned in Appendix 'B' here-in-after. (n) Bus bar minimum 1200 Amp aluminium with R/Y/B coloured for three Phases and 600 Amp for Neutral Black colour insulation sleeves with insulators - 01 Set Notes : (i) Vertical height of legs of LT panel base frame shall be not less than 45 cm from top of nearest road level / PCC floor finish. Legs shall be grouted in ground minimum 30cm in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). (ii) The contractor shall produce and get the detailed (GD) drawings of LT Panel approved from GE through Engineer-in-Charge before fabrication and placing the order to the approved manufacturer. (iii) MS frame work shall be painted with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer. (iv) Cost of internal wiring, MS frame work, painting, platform, MCCB spreaders, cable glands, locking arrangement with aldrop bolt and any minor addition/alteration where required at site (the decision of GE shall be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new indoor type, LT Panel Box cubical type of suitable size (minimum depth 500mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 2mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-54 with coloured insulation sleeve, rubber gasket, insulators, indoor type, totally enclosed, weather, dust and vermin proof as per IS, front & Rear opening with double door shutters having suitable aldrop bolt locking arrangement, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground/floor level and 30cm below ground/floor level, comprising & including the following accessories complete all as specified and as directed :- (a) Automatic Transfer Switch (ATS) 630 Amp, 4 Pole with Controller, 415 V, 50 Hz, Open Execution - 01 No. Make: Havells Cat No. IHYFCDO630 or equivalent in L&T/ABB/other makes mentioned in Appendix 'B' here-in-after. (b) Indication Lamp – 2 Nos description of item contd....
Description of serial item No. 3 contd… (c) Control Fuse - 02 Nos. (d) Aluminium Bus bar minimum 800 Amp with R/Y/B coloured for three Phases and 400 Amp for Neutral Black colour insulation sleeves - 01 Set Notes : (i) Vertical height of legs of LT panel base frame shall be not less than 45 cm from top of nearest road level / PCC floor finish. Legs shall be grouted in ground minimum 30cm in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). (ii) The contractor shall produce and get the detailed (GD) drawings of LT Panel approved from GE through Engineer-in-Charge before fabrication and placing the order to the approved manufacturer. (iii) MS frame work shall be painted with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer. (iv) Cost of internal wiring, MS frame work, painting, platform, MCCB spreaders, cable glands, locking arrangement with aldrop bolt and any minor addition/alteration where required at site (the decision of GE shall be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new indoor type, LT Panel Box cubical type of suitable size (minimum depth 500mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 2mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-54 with coloured insulation sleeve, rubber gasket, insulators, indoor type, totally enclosed, weather, dust and vermin proof as per IS, front & Rear opening with double door shutters having suitable aldrop bolt locking arrangement, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground/floor level and 30cm below ground/floor level, comprising & including the following accessories complete all as specified and as directed :- (a) MCCB 630 Amp, 3 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. Make: Legrand Cat Part No. 4220 04 or equivalent in makes mentioned in Appendix 'B' here-in-after description of item contd....
Description of serial item No. 4 contd… (b) Spreader Terminal, 3 Pole, Set of Three, suitable for MCCB 630 Amp - 2 Sets. Make: Legrand Cat Part No. 6250 04 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (c) Rotary Handle, Vary Depth type, suitable for MCCB 630 Amp - 1 No. Make: Legrand Cat Part No. 4201 63 or equivalent in makes mentioned in Appendix 'B' here-in-after. (d) Indicator Set RYB, “LED” type (set of three) -01 Set (e) Control Fuse - 03 Nos. (f) Aluminium Bus bar minimum 800 Amp with R/Y/B coloured for three Phases and 400 Amp for Neutral Black colour insulation sleeves - 01 Set Notes : (i) Vertical height of legs of LT panel base frame shall be not less than 45 cm from top of nearest road level / PCC floor finish. Legs shall be grouted in ground minimum 30cm in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). (ii) The contractor shall produce and get the detailed (GD) drawings of LT Panel approved from GE through Engineer-in-Charge before fabrication and placing the order to the approved manufacturer. (iii) MS frame work shall be painted with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer. (iv) Cost of internal wiring, MS frame work, painting, platform, MCCB spreaders, cable glands, locking arrangement with aldrop bolt and any minor addition/alteration where required at site (the decision of GE shall be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new indoor type, LT Panel Box cubical type of suitable size (minimum depth 300mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 2mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-54 with coloured insulation sleeve, rubber gasket, insulators, indoor type, totally enclosed, weather, dust and vermin proof as per IS, front opening with double door shutters having suitable aldrop bolt locking arrangement, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground/floor level and 30cm below ground/floor level, comprising & including the following accessories complete all as specified and as directed :- (a) MCCB 250 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. Make: Legrand Cat Part No. 4202 49 or equivalent in makes mentioned in Appendix 'B' here-in-after description of item contd....
Description of serial item No. 5 contd… (b) Spreader Terminal, 4 Pole, Set of Four, suitable for MCCB 250 Amp - 2 Sets. Make: Legrand Cat Part No. 6250 18 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL. (c) Rotary Handle, Vary Depth type, suitable for MCCB 250 Amp - 1 No. Make: Legrand Cat Part No. 4201 61 or equivalent in makes mentioned in Appendix 'B' here-in-after. (d) Indicator Set RYB, “LED” type (set of three) -01 Set (e) Control Fuse - 03 Nos. (f) MCB DP 32 Amp, 10 kA, ‘C’ Curve, 415 Volt grade, AC, 50 Hz - 24 Nos. Make: Legrand Cat Part No. 4086 36 or equivalent in makes mentioned in Appendix 'B' here-in-after. (g) Aluminium Bus bar minimum 300 Amp with R/Y/B coloured for three Phases and 150 Amp for Neutral Black colour insulation sleeves - 01 Set Notes : (i) Vertical height of legs of LT panel base frame shall be not less than 45 cm from top of nearest road level / PCC floor finish. Legs shall be grouted in ground minimum 30cm in PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate). (ii) The contractor shall produce and get the detailed (GD) drawings of LT Panel approved from GE through Engineer-in-Charge before fabrication and placing the order to the approved manufacturer. (iii) MS frame work shall be painted with two coats of synthetic enamel paint of approved tint over a coat of red oxide primer. (iv) Cost of internal wiring, MS frame work, painting, platform, MCCB spreaders, cable glands, locking arrangement with aldrop bolt and any minor addition/alteration where required at site (the decision of GE shall be final and binding regarding extent to which the change can be considered as minor addition/alteration) shall be deemed to be included in the quoted rates.
Note applicable to serial item No. 1 to 5.01 : All MCCBs of capacity 160 Amp & above shall also have adjustable overload current, overload time setting, Ics=100%Icu, short circuit setting including all accessories.
M&L for filling approved dry river sand for cushioning and cover for protection of under ground electric cable in trenches/duct 8 cm before laying cable and 15 cm thickness over the cable and punning to 18 cm total thickness complete all as specified and as directed. Notes :- (i) Approved dry sand free from vegetations, grass and other deleterious substances shall be used. (ii) For the purpose of payment, only punned thickness shall be measured.
S&F rolled mild steel work as in Plates (plain or chequered) channels. Square cut or notched (ordinary and counter sunk) forming holes, without any attachment, including necessary welding etc. conforming to Fe-410-W (Gde E-250) quality `A’, fixed in repairs, complete all as specified and as directed.
M&L for Earthing with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to Panel / transformer / GOD / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing of any type. Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner.
JAYESH TRADING CORPORATION
M/s. Vimal Enterprise
JAMNAGAR ELECTRIC AND MACHINERY CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .