Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.3 LAccepted-AOC AMBALA CANTT | L1 | Accepted-AOC awarded | |
| 2 | L2₹12.4 L+₹8,420 (0.68%)Rejected-AOC DOON PUBLIC SCHOOL NEAR HOUSE NO 838 P SECTOR 21 PANCHKULA 134112 | PANCHKULA | PANCHKULA | HARYANA | 134112 | L2 | Rejected-AOC r | |
| 3 | L3₹13.5 L+₹1.1 L (9.32%)Rejected-AOC | L3 | Rejected-AOC r |
Tender Value
₹12.7 L
EMD Value
₹25,300
Closing Date
5 Aug 2019, 3:00 pmClosed
Executive Engineer
Executive Engineer Mech Public Health Engineering Division Ambala Cantt
Providing installing of 3 Nos Twell in place of failed tubewell in village Sabhapur Safilpur Laharpur Consty Sadhaura Tehsil Bilaspur Distt Yamuna Nagar and 1 no twell at village Kot Kachwa Khurd Distt Ambala
2019_HRY_89740_1
SE Mech. Memo No. 2058 Dated 18-07-2019 Mech
Open Tender
Water Equipments/ Meter/ Drilling/ Boring
Works
10 days
Yamuna Nagar
as per DNIT
4 documents required · 4 mandatory
₹1,000
Mech PHE Division Ambala Cantt
₹25,300
6 Feb 2020
26 Jul 2019
5 Aug 2019
26 Jul 2019
5 Aug 2019
26 Jul 2019
Amount
Drilling of 609.60 mm dia bore by hydraulic rotary drilling (Reverse Circulation method) according to ISI specification No. 2800-1991 (Part-I) and IS No. 2800-1979 (Part-II) as amended upto date and modified to extent of the specification attached with this schedule of items of work in all kinds of soils and boulders upto 125mm dia except rocky strata including the cost of all consumable stores, fuel, oil soil stabilizing material and transportation of rig and other accessories to the site of proposed bore and extracting the same against earth frictions etc. complete in satisfaction of the Engineer-In-Charge. (Drilling with Private Rig) Vill. Sabhapur = 1 x 220 = 220 mtrs. Vill. Sabhapur = 1 x 220 = 220 mtrs. Vill. Laharpur = 1 x 220 = 220 mtrs. Vill. Kot Kachwa Khurd = 1 x 300 = 300 mtrs.
Labour for fixing for lowering 273.10 mm i/d dia ERW steel pipes as per IS 4270/2001 as amended upto date, duty ISI marked for casing pipe in 4 to 7 meters random length manufactured out of 8 mm thick MS plates with required number of M.S socket 177.80mm length with inside thread to pmatch the pipe threads and made out of MS plate in to borehole in vertical position including cost of all scaffolding, derricks, Jim, poles, tools and plants, ropes gays MS clamp embedded in foundation etc. complete in all respects to the satisfaction of the Engineer-in-charge of the work including cost of all cutting, threading of pipe where required and all sockets. The pipes shall be painted with anti-corrosive paints and covered tightly polythene.10” i/d M.S. Pipe. (Supplied by the Deptt.) Vill. Sabhapur = 1 x 100 = 100 mtrs. Vill. Safilpur = 1 x 100 = 100 mtrs. Vill. Laharpur = 1 x 100 = 100 mtrs. Vill. Kot Kachwa Khurd = 1 x 120 = 120 mtrs.
Labour for fixing and lowering 219.10 Providing and fixing of lowering 219.10 mm outer dia ERW steel pipes as per IS 4270/ 2001 as amended upto date duly ISI marked for housing pipe in 4 to 7 meters random length manufactured out of 6.4 mm M.S plates with required number of M.S socket 177.80mm with inside thread to match the pipe threads and made out of M.S plate in to borehole in vertical position, including cost of all scaffolding, derricks, Jim, poles, tools and plants, ropes, gays M.S clamp embedded in foundation etc. complete in all respects to the satisfaction of the Engineer-in-charge of the work including cost of all cutting, threading of pipe where required and all sockets. The pipe shall be painted with anti corrosive paint & covered tightly with polythene. (Supplied by the Deptt.) Vill. Sabhapur = 1 x 100 = 100 mtrs. Vill. Safilpur = 1 x 100 = 100 mtrs. Vill. Laharpur = 1 x 100 = 100 mtrs. ill. Kot Kachwa Khurd = 1 x 160 = 160 mtrs.
Labour for fixing and lowering 200mm i/d ISI marked stainless steel (SSC) cage as including M.S. Socket with welding material ISI marked Stainless Steel (V-wire welding ) cage as per code No. IS 110:2000 (200 x 8.00 x 0.50 mm).(Supplied by the Deptt.) Vill. Sabhapur = 1 x 20= 20 mtrs. Vill. Safilpur = 1 x 20= 20 mtrs. Vill. Laharpur = 1 x 20= 20 mtrs. Vill. Kot Kachwa Khurd = 1 x 20= 20 mtrs.
Labour for fixing of M.S. bail plug end cap. (Supplied by the Deptt.)
Labour for fixing of Center Guides. (Supplied by the Deptt.) (i) 250mm ø ( 4 x 3 = 12 Nos.)
Labour for fixing of Center Guides. (Supplied by the Deptt.) (ii) 200mm ø ( 4 x 3 = 12 Nos.)
Labour for fixing of M.S. cap 250mm ø. (Supplied by the Deptt.)
Labour for fixing of M.S. Reducing socket 250mm ø x 200mm ø..
Labour for packing of Pea Gravel (A-Grade) for use as pack in tubewells size of over 2.00mm to 3.35mm with uniformity coefficient Not to exceed 2.00. The Gravel should be confirming To requirement of ISI, 4097-1967 regarding its physical Characteristic quarry at Panchkula/Chandi Mandir. (Supplied by the Deptt.) Vill. Sabhapur = 1 x 58 = 58 Cum Vill. Safilpur = 1 x 58 = 58 Cum Vill. Laharpur = 1 x 58 = 58 Cum Vill. Kot Kachwa Khurd = 1 x 80 = 80 Cum
Providing clay seal of thickness 4.0mm or above consisting of balls of local lay or bentonite mud to be placed in the annular space around the assembly the clay seal should be provided at a level of minimum 25.00m above the top most screens depending onthe logging result.
according to clause 9.3 of IS: 2800 - 1991 (Part-I) as amended upto date and specifications attached and as directed by the Engineer-in-Charge of the work including the cost of all consumable stores, fuel, oil, compressors and machinery etc. as required for this work. Developed by Air Compressor of 250 PSI 450 CFM. (4 x 10 = 40 Hrs.)
Electric logging of Tubewell
BIS SPECIFICATION No. 8034 - 1989 (as amended up to date for pumps ) and IS 9283 – 1979 (as amended up to date for motor ) the pump motor sets should be capable of pumping clear fresh cold water having characteristics as specified in Clause – 4 of IS 8034 – 1989 and clause 4.1 of IS 9283 – 1979 . 450 LPM /110 M Head (V-8) 20 BHP Each Make Grundfoss, calama , KSB , Franklin , Texmo. ( Village Sabhapur, Safilpur & Laharpur ).
Prov. and fixng M.S. Base Plate
Prov. and fixng M.S. Clamp
Prov. and fixing CI Bend 90° (3 x 30 = 90)
Bidder Name
Amount
SANDEEP KUMAR CONTRACTOR
arvind kumar contractor
charan singh tubewell company
SANDEEP KUMAR CONTRACTOR
charan singh tubewell company
charan singh tubewell company
arvind kumar contractor
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .