| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.5 LAccepted-AOC 59 NEW MARKET CLOCK TOWER DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | L1 | Accepted-AOC Accept due to being L1 | |
| 2 | L2₹14.2 L+₹1.6 L (12.9%)Accepted-AOC PREM NAGAR GALI NO 3 RAJPUTANA SALEMPUR ROORKEE DISTT HARIDWAR UK | ROORKEE | HARIDWAR | UTTARAKHAND | L2 | Accepted-AOC Reject due to not being L1 | |
| 3 | L3₹14.9 L+₹2.4 L (18.8%)Accepted-AOC 52 VIJAY COLONY NEW CANTT ROAD DEHRADUN UK | L3 | Accepted-AOC Reject due to not being L1 | |
| 4 | L4₹16.3 L+₹3.7 L (29.7%)Accepted-AOC | L4 | Accepted-AOC Reject due to not being L1 |
Tender Value
₹14.5 L
EMD Value
₹29,000
Closing Date
12 May 2021, 6:00 pmClosed
GE MES Roorkee
Garrison Engineer Military Engineer Services Roorkee Cantt
SPECIAL REPAIR REPLACEMENT OF 28 X 1.5 TON WINDOW AC ALL WEATHER WITH VOLTAGE STABILIAZER AT OT BLDG NO T 30 P 1 FAM WD AND LABOUR ROOM AT MH ROORKEE UNDER GE MES ROORKEE
2021_MES_440355_1
8392/27/E8
Limited
Electrical and Maintenance Works
Item Rate
45 days
Roorkee
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer MES
₹29,000
Yes
29 May 2021
4 May 2021
14 May 2021
4 May 2021
12 May 2021
5 May 2021
Amount
Suppy and fixing installation and commissioning Window type Air Conditioner, 1.5 Ton Capacity of Hot and Cold (all weather) electric driven single phase complete all as specified and directed. Make: Voltas Series - Classic, and model No Voltas WAC 18H CZP or equivalent in LG/Samsung/Hitachi Note:- 1. Tenderor should confirm availability from market before quoting the rates, as this item is required to be installed for Covid facilities on urgent basis II. The rate quoted shall deemed to be include for the cost of cutting holes in the brick masonry wall / stone masonry wall as required for installation including making good and finishing to match with the adjoining surfaces and covering with water proof ply wood 8mm thick duly painting two coats of synthetic enamel paint as required at site. III. Old unserviceable/serviceable window ACs removed from the existing position shall be deposited to MES store yard. The quated rates shall deem to include the provision.
Supply and fixing of Voltage stabilizer for automatic operation , single phase naturally air cooled indoor type & designed for input variation between 130V to 280V with out put voltage between 200-240 V with low / high cut & TDR facility and of capacity 4.0 KVA Make: Model No PEARL EM 4130+ 130V to 300V up to 1.5 Ton of Make Microtek or equivalent in Luminous/Voltas/V-Guard .
Supply and fixing in Replacement single pole and neutral metal sheet enclosure with a two pin and earth plug and socket complete with one single pole MCB 240V 20 Amps. Make: Cat part No-5068 11 of make Legrand or equivalent in Indo Asian/C&S,
Material and labour in replacement of Sub main wiring with two runs of single core FRLS PVC insulated and unsheathed multistranded, copper conductor cable of size 4.0 sqmm LT, 1100V grade, drawn trhough and incl adequate sizes PVC non metallic conduit of 20mm or more approprite dia with accessories and fittings and one run of 4.0 sq mm single core multi stranded copper conductor cable as earth continuity conductor complete all as specified and as directed. Note: Two runs of cable one run of earth wire and one run of PVC non metallic conduit of 20 mm or more approprite dia shall be measured as one run length of submain wiring.
Material and labour in replacement of Sub main wiring with two runs of single core FRLS PVC insulated and unsheathed multistranded, copper conductor cable of size 6.00 sqmm LT, 1100V grade, drawn trhough and incl adequate sizes PVC non metallic conduit of 20 mm or more approprite dia with accessories and fittings and one run of 6.00 sq mm single core multi stranded copper conductor cable as earth continuity conductor. Note: Two runs of cable one run of earth wire and one run of PVC non metallic conduit of 20 mm or more approprite dia shall be measured as one run length of submain wiring.
S&F in replacement of MCB TPN 63 Amps AC 230 Volts, 'C' curve series with 10 KA breaking cpacity including necessary lugs/ thimbles complete all as specified and as directed. Make : Cat part No 4086 83 of Legrand or equivalent in Indo Asian/C&S
S&F in replacement of MCB SPN 63 Amps AC 230 Volts, 'C' curve series with 10 KA breaking cpacity including necessary lugs/ thimbles complete Make : Cat Part No 4086 20 of make of Legrand or equivalent in Indo Asian/C&S
S & F in replacement of unserviceable TPN DB- VTPN for independent mounting fixed on wall duly flush mounted, 4 way, IP 43, IK 09 with 250 Amp Bus bar complete all as specified and as directed. Make : Legrand cat part No .5077 40 or equivalent model in ABB/ Havells/C&S
S & F in replacement of unserviceable MCCB 100 Amp four pole, 415 volt, 25kA adjustable thermal and magnetic setting including necessary connection complete all as specified and directed. Make: : Legrand cat part No.420055 or equivalent model in ABB/C&S/Havells
S&F in replacement of MCB SP 6 to 32 Amps AC 230 Volts, 'C' curve series with 10 KA breaking cpacity including necessary lugs/ thimbles completeall as specified and as directed. Make : Legrand/Indo Asian
M/S Konark Electric Sales Corporation
nautiyalandcompany
SHRI RAM ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .