Executive Engineer, District R and B Division, Vadodara
Taluka Sevasadan at Karjan, Dist. Vadodara (Providing and Fixing of Fire Hydrant System and Implementation of Fire Sprinkler Systems with Conventional Alarm and Detection System with Fire pump etc.)
307946
02 of 2026-2027
Open
Civil - All
Works
Vadodara
7 documents required · 6 mandatory · 1 optional
₹1,500
Executive Engineer, District (R and B) Division, Vadodara
₹50,000
22 May 2026
22 May 2026
22 May 2026
30 May 2026
22 May 2026
Name of Work: Taluka Sevasadan at Karjan, Dist. Vadodara (Providing and Fixing of Fire Hydrant
System and Implementation of Fire Sprinkler Systems with Conventional Alarm and Detection
System with Fire pump etc.)
BILL OF QUANTITIES
It. No. Description of Item Quantity Unit Rate in Figure Total
1 (A) Supplying, installation, testing and commissioning of Electric 1.00 Set 328966.95
Driven Main Fire Pump suitable for automatic operation and
consisting of following, complete in all respects, as required:
(B) Horizontal type, single Stage, centrifugal, End suction pump of
cast iron & bronze impeller with stainless steel shaft, Gland Pack
conforming to IS
(C) Suitable HP Squirrel cage induction motor, TEFC, synchronous
speed 2900 RPM, suitable for operation on 415 volts, 3 phase
Hz, AC supply with IP 55 protection for enclosure, horizontal foot
mounted type with Class-'F' insulation, conforming to JS-325.
(D) M.S. fabricated Common base plate, coupling, coupling guard,
foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered with anti
vibration pads.
2280 LPM at 70 m Head
2 (A) Supplying, installation, testing and commissioning of Diesel 1.00 Set 544162.71
Engine Driven Fire Pump suitable for automatic operation and
consisting of following, complete in all respects, as required: (Diesel
(B) Horizontal type, Single stage, centrifugal pump of cast of iron
body and bronze impeller with stainless steel shaft, mechanical seal
conforming to IS
(C) Suitable HP, 1500/2300 RPM water cooled with radiator, diesel
engine conforming to relevant IS standard
complete with auto starting mechanism, 12 /24 volts electric starting
equipment, 125 Ltrs diesel tank, exhaust pipe extended upto 10 m
outside pump house duly insulated with 50 mm thick glass wool with
1.0 mm thick aluminium sheet cladding, residential silencer,
instruments and protection as per standard specification, stop
solenoid for auto stop in the event of fault with audio indications,
painted with post office red colour etc. as required.
(D) M.S fabricated, common base plate, coupling, coupling guard,
foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered and with
anti vibration pads.
2280 LPM at 70 m head
3 (A) Supplying, installation, testing and commissioning of Electric 1.00 Set 92588.14
Driven Pressurisation Pump suitable for automatic operation and
consisting of following, complete in all respects, as required:
(B) Horizontal type/Vertical Inline type, Single Stage/Multi Stage,
centrifugal End suction pump of cast iron body and bronze impeller
with stainless steel shaft, mechanical seal conforming to IS:
(C) Suitable HP squirrel cage induction motor TEFC type suitable
for operation on 415 volts, 3 phase 50 Hz AC supply with IP
class of protection for enclosure, horizontal foot mounted type with
Class-'F' insulation, conforming to IS:
(D) M.S. fabricated Common base plate, coupling, coupling guard,
foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered and with
anti vibration pads.
180 LPM at 60 m Head
It. No. Description of Item Quantity Unit Rate in Figure Total
4 Fabrication, Supply, Installation, testing & commissioning of 1.00 Set 254917.80
Electrical Control Panel of cubical construction, floor mounted type,
fabricated out of 2mm thick CRCA sheet, compartmentalised with
hinged lockable doors, dust and vermin proof, powder coated of
approved shade after 7 tank treatment process, cable alley, inter
connection with suitable size copper conductor cable/solid copper
strip, having switchgears and accessories, mountings and internal
wiring, earth terminals, numbering etc. complete in all respect,
suitable for main fire pump. pressurisation pump & diesel pump set
complete as per CPWD specification with following in coming and
Outgoings, suitable for operation on 415V, 3 phase, 50Hz AC
supply with enclosure protection class IP 42 as required: for all
suitable AMP fire pump and Disel Pump in one cubical construction
400A. 50kA 4 Pole MCCB, lcs=100% Icu rating
Digital Voltmeter 0-500 V with selector switch
Digital Ammeter (0-250A) with selector switch & CTs etc.
LED type RYB phase indicating lamps, ON, OFF, trip indicating
Set of Copper Bus Bar 300A
(Note: All outgoing feeders for pumps should have digital Ammeter
with selector switches, and LED type ON, OFF, trip indicating
125 A, 50kA TPN MCCB, lcs=l00% lcu, with fully automatic
Star/Delta starter suitable for 60 HP pump with overload protection,
current sensing type single phase preventor complete with all
accessories and internal wiring required for automatic operation,
selector switch for local/remote,auto / manual /OFF operation.
63 A, 50kA TPN MCCB, lcs=100% lcu, with suitable HP fully
automatic Star/Delta starter with overload protection, current
sensing type single phase preventor complete with all accessories
and internal wiring required for automatic operation, selector switch
for local/remote, auto / manual / OFF operation.
DIESEL ENGINE CONTROL
Control for diesel engine comprising -
Automatic/Manual selector switch & 3 attempts starting device,
timers and relays as required, push buttons, start/stop in manual
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp
and Engine on indication
Battery charger suitable for 12V/24 V DC with boost and trickle
selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter.
All standard relays and accessories for automatic operation of
System Controller
Designing, Supply, Installation, Testing and commisioning of system
controller to control operation of main electric fire pump, diesel
pump, Pressurization pump, Terrace pump in sequence as per
specification consisting of relays, timers. Sensors, annunciation
window for fault indication, complete as per specification.
5 Supply Installation Testing and commissioning of Zincalvalume 58000.00 Ltr 9.22
sheet Modular tank having size Dia 3.22 x Ht. 6.05mtr with gross
volume of Tank is 50 KL and Effective Volume is 50 KL. Rates are
including of supply and erection of required Fittings & accessories
like Internal & External Ladder, Level indicators, Air Vent, Manhole,
Food Grade Liner & roof Railing as per manufacaturing standard
with required Nozzles for Supply and descharge of Fire water as per
site situation and as directed by EIC.
It. No. Description of Item Quantity Unit Rate in Figure Total
6 Providing, laying, testing & commissioning of 'B' class Medium duty 985.00 Mtr. 602.54
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with painting with two or more coats of
synthetic enamel paint of required shade complete as required:
excluding the cost of Excavation, refilling, demolition of RCC work
and demolition of paver block. 25 mm
7 Providing, laying, testing & commissioning of 'B' class Medium duty 72.00 Mtr. 818.64
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with painting with two or more coats of
synthetic enamel paint of required shade complete as required:
excluding the cost of Excavation, refilling, demolition of RCC work
and demolition of paver block. 40 mm
8 Providing, laying, testing & commissioning of 'B' class Medium duty 36.00 Mtr. 903.39
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with painting with two or more coats of
synthetic enamel paint of required shade complete as required:
excluding the cost of Excavation, refilling, demolition of RCC work
and demolition of paver block. 50 mm
9 Providing, laying, testing & commissioning of 'B' class Medium duty 36.00 1127.12
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with painting with two or more coats of
synthetic enamel paint of required shade complete as required:
excluding the cost of Excavation, refilling, demolition of RCC work
and demolition of paver block. 65 mm
10 Providing, laying, testing & commissioning of 'B' class Medium duty 66.00 Mtr. 1283.05
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with painting with two or more coats of
synthetic enamel paint of required shade complete as required:
excluding the cost of Excavation, refilling, demolition of RCC work
and demolition of paver block. 80 mm
11 Providing, laying, testing & commissioning of 'B' class Medium duty 98.00 Mtr. 1631.36
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with suitable clamp/support frame and
painting with two or more coats of synthetic enamel paint of required
shade complete as required: excluding the cost of Excavation,
refilling, demolition of RCC work and demolition of paver block.
12 Providing, laying, testing & commissioning of 'B' class Medium duty 26.00 Mtr. 2231.36
G.l. pipe conforming to IS 1239 including welding, fittings like
elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the
pipe on the wall ceiling with suitable clamp/support frame and
painting with two or more coats of synthetic enamel paint of required
shade complete as required: excluding the cost of Excavation,
refilling, demolition of RCC work and demolition of paver block.
13 Supplying and fixing single headed internal/External hydrant valve 10.00 Each 6955.93
with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia
with cast iron wheel ISI marked conforming to IS 5290 (Type -A)
with blank Gunmetal/Stainless Steel cap and chain as required:
Single Headed Stainless Steel
14 Supplying & fixing 63 mm dia. Stainless Steel (Grade 304) short 10.00 Each 2883.05
branch pipe with 20 mm nominal internal diameter size nozzle
conforming , to IS:903 suitable for instantaneous connection to
interconnect hose pipe coupling as required: Stainless Steel (Grade
It. No. Description of Item Quantity Unit Rate in Figure Total
15 Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 18.00 Each 3955.08
mm dia male and female couplings duly bound with GI wire, rivets
etc. conforming to IS 636 (type-A) as required: Stainless Steel
16 Supplying and fixing first-aid Hose Reel Drum with MS construction 10.00 Each 8000.00
spray painted in post . office red, conforming to IS 884 complete
with the following as required. 20/25 mm nominal internal dia water
hose thermoplastic (Textile reinforced) type -2 as per IS: 12585
mm nominal internal dia gun metal globe valve & nozzle. Drum and
brackets for fixing the equipments on wall. Connections from riser
with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
17 Supplying, fixing, testing and commissioning of butterfly valve of PN 7.00 Each 4581.36
1.6 rating with bronze/gunmetal seat duly ISI marked complete with
nuts, bolts, washers, gaskets conforming to IS: 13095 of following
sizes as required: 80 mm dia
18 Supplying, fixing, testing and commissioning of butterfly valve of PN 9.00 Each 6161.86
1.6 rating with bronze/gunmetal seat duly ISI marked complete with
nuts, bolts, washers, gaskets conforming to IS: 13095 of following
sizes as required: 100 mm dia
19 Supplying, fixing, testing and commissioning of butterfly valve of PN 6.00 Each 8251.69
1.6 rating with bronze/gunmetal seat duly ISI marked complete with
nuts, bolts, washers, gaskets conforming to IS: 13095 of following
sizes as required: 150 mm dia
20 Providing, installation, testing and commissioning of non-return 1.00 Each 6995.76
valve of following sizes confirming to IS: 5312 complete with rubber
gasket, GI bolts, nuts, washers etc.as required: 80 mm dia.
21 Providing, installation, testing and commissioning of non-return 4.00 Each 10044.92
valve of following sizes confirming to IS: 5312 complete with rubber
gasket, GI bolts, nuts, washers etc.as required: 100 mm dia
22 Supplying installing testing & commissioning of 100 mm dia. 9.00 Each 1783.94
Pressure gauge 1% Accuracy direct bottom 3/8" BSP connection in
brass socket & Range 0 to 16 Kg/Cm2 etc. necessary as directed
by Engineer in Charge.
23 Providing and Fixing pressure switch in M.S. Pipe line including 2.00 Each 1415.25
connection etc. as required.
24 Providing and Installation SS 304 male to male siphone tube size 9.00 Each 1150.03
3/8 inch dia for pressure gauge.
25 Providing and Installation SS 304 male to male siphone tube size 2.00 Each 1150.03
1/4 inch dia for pressure switch.
26 Providing and Fixing 25 mm dia. Air valve of Raising Main Line. For 3.00 Each 970.73
Air Release including supply, installing, testing and commissioning
etc. complete as directed by Engineer in charge.
27 Supply Installing Testing & Commissioning of following dia. Y - 2.00 Each 9900.00
Strainer with gasket, Nut-bolts etc. necessary complete as directed
by Engineer in charge. 150 mm dia
28 Supply Installing Testing & Commissioning of following dia. Y - 1.00 Each 6161.02
Strainer with gasket, Nut-bolts etc. necessary complete as directed
by Engineer in charge. 100 mm dia
29 Supplying and fixing of fire brigade connection of cast iron body with 2.00 Each 6154.24
gun metal male instantaneous inlet couplings complete with cap and
chain as reqd. for suitable dia MS pipe connection conforming to IS
904 as required: 2 way
30 Steel work, welded in built up sections framed work including 115.00 Kg. 91.08
cutting, hoisting, fixing in position and applying a priming coat of red
lead paint. (A) In neams and joints, channels angles Tees, flats,
with connecting plates or angles cleats as in main and cross
beams. Hip and jack rafters, purlins connected to common rafters
31 Supply & installation ISI marked (IS:15683) Fire Extinguisher, 14.00 Each 6058.28
Carbon-di-oxide type capacity 4.5 Kgs. flat base including valve,
discharge hose of not less than 10mm dia., 1M long and complete
in all respects including initial fill with CO2 gas conforming to IS:307-
1966 filled to a filling rate of not more than 0.667 and wall
suspension bracket. (LMR) etc completed as directed EIC.
It. No. Description of Item Quantity Unit Rate in Figure Total
32 Supplying & fixing 6 Kg. Capacity ABC Dry Chemical powder Stored 14.00 Each 3188.57
Pressure type fire Extinguisher As per I.S-15683 having ISI marked
Etc. complete as Directed by EIC
33 Supplying & fixing 9 ltr. Capacity WCO2 Stored Pressure type fire 6.00 Each 4949.00
Extinguisher As per I.S-15683 having ISI marked Etc. complete as
Directed by EIC
34 Design, Supply & Installation of Safety Signage approved make 22800.00 Sq.cm. 2.65
made of zinc sulphide based glow in the dark rigid sheet with high
luminous property enclosed in a transparent weather proof U/V
stabilized plastic pasted on 3mm thick clear acrylic sheet/ foam
sheet such as ASSEMBLY POINT, EXIT, EMERGENCY EXIT, DO
NOT USE LIFT IN CASE OF FIRE, FLOOR MARKINGS, FIRE
LIFT, STAIRCASE EXIT, STAIRCASE STRIP, FIRE ALARM CALL
POINT, FIRE EXTINGUISHER, FLOOR EVACUATION PLAN etc.
completed as directed by engineer in charge.
35 Supplying, installation, testing and commissioning of micro 1.00 Set 212220.34
processor based intelligent addressable main fire alarm panel,
central processing unit with the following loop modules and capable
of supporting not less than 240 devices (including detectors) and
minimum 120 detectors per loop and loop length upto 2 km, network
communication card, minimum 320 character graphics/ LCD display
with touch screen or other keypad and minimum 4000 events
history log in the non volatile memory (EPROM), power supply unit
(230 +- 5% V, 50 hz), 48 hrs back-up with 24 volt sealed
maintenance free batteries with automatic charger. The panel shall
have facility to have seamless integration with analog/digital voice
evacuation system and shall be complete with aa accessories. The
panel shall be compatible for open protocol BACnet/ Modbus over
IP complete as per specifications. Single / Two Loop Panel
36 Supplying, installation, testing & commissioning of intelligent analog 90.00 Each 2545.76
addressable photothermal detector complee with mounting base
complete as required.
37 Supplying, installation, testing & commissioning of addressable 6.00 Each 3443.22
manual call point complete as required
38 Supplying, installation, testing & commissioning of intelligent 6.00 Each 2361.86
addressable programmable sounder complete as required.
39 Supplying, installation, testing & commissioning of response 9.00 Each 259.32
indicator on surface/recessed MS Box having two LED, metallic
cover complete with all connections as required.
40 Supplying & Laying of 2 x 1.5 sq., mm fire alarm armoured cable, 2930.00 Mtr. 162.71
600 / 1000 V rated with annealed copper conductor having XLPE
insulation, steel wire armouring & FRLS outer sheath complete as
41 Providing, Fixing & installation PVC 100x100mm junction box for 92.00 Each 212.10
smoke detector including fixing in ceiling with all labour & materials
as directed by engineer in charge.
It. No. Description of Item Quantity Unit Rate in Figure Total
42 Labour charges for Professional & Administrative Charges for 1.00 Job 50500.00
engaging manpower for giving testing in front of Fire Department
and Fire Testing & Liasoning with Fire Department to getting Fire
and Safety Certificate for existing Fire Fighting System include.
engaging skilled labour & skilled supervisor for testing of all fire
system on site with operating pump/panel & existing FA system.
The testing should be done in the presence of PWD authority as
well as Fire Department with required pressure of 3.5 KG pressure
at farthest point. Also testing should be done at every floor with all
installed equipment before final testing. As built fire drawing to be
submitted by bidder to PWD Authority after completion of the work.
Manufacturer Test Certificate attached at the time of RA Bill and
Note - Goverment Official fees and hidden charges shall be extra at
actual to getting fire NOC
43 Providing and fixing SS - 304 Crome Finished Ball valve 25mm dia. 9.00 Each 1069.92
44 Providing, lifting (Terrace Floor) & fixing PVC Three /Four layer 5000.00 Liter 12.88
water tank of required capacity with all necessary fitting and
connection etc. Complete on terrace cabin at any level and at any
height as directed by engineer in charge.
45 Providing laying and jointing in true line and level 25mm dia. 24.00 Mtr. 148.12
U.P.V.C. Pipe ( SCH- 40) for cold water including fittings make
PRINCE / SUPREME / ASTRAL / FINOLEX or equivalent as
approved by Engineer In Charge. Pipe shall be fixed on the wall
with the help of clamp at every two metre C/C or shall be concelled
as directed including necessary fittings etc. including testing of pipe
and joints and fixing the same with adhesive solvent, including cost
of all materials.
46 Providing laying and jointing in true line and level 50mm dia. 8.00 Mtr. 195.67
U.P.V.C. Pipe ( SCH- 40) for cold water including fittings make
PRINCE / SUPREME / ASTRAL / FINOLEX or equivalent as
approved by Engineer In Charge. Pipe shall be fixed on the wall
with the help of clamp at every two metre C/C or shall be concelled
as directed including necessary fittings etc. including testing of pipe
and joints and fixing the same with adhesive solvent, including cost
of all materials.
47 Providing and fixing UPVC check or ball valve 25mm dia 1.00 Each 339.56
48 Providing and fixing UPVC check or ball valve. 50mm dia. 6.00 Each 418.24
49 Supply Installing Testing & Commissioning of M. S. 18 guage hose 10.00 Each 4411.74
box to accommodate of 2-Nos 15-Mtrs. Length Hose Box pipe &
No. of branch pipe with Nozzle, With necessary fabrication support
and joints and 3 mm glass shutter including poweder coating etc.
complete as directed by engineer in charge.
50 Excavation for foundation upto 1.5 m depth including sorting out 30.50 Cum 120.01
and stacking of useful materials and disposing off the excavated
stuff upto any lead. (A) Loose or soft Soil
51 Filling in plinth with sand under floors including watering ramming, 3.50 Cum 471.69
consolidating and dressing complete.
52 Supplying and Laying, Spreading and Compacting of hard stone of 3.50 Cum 1024.93
following nominal size including carriage of material spreading in
uniform layers manually on prepared base and compacted
consolidation using 40 to 63mm size BT metal and 25% sand for
binding material, labours etc. completed as directed Engineer in
53 Providing and laying cement concrete 1:2:4 (1- Cement : 2 Coarse 9.20 Cum 3656.13
sand : 4- graded stone aggregates 20 mm nominal size) and curing
complete excluding cost of formwork in (A) Foundation and Plinth
54 Providing and Laying ordinary cement concrete 1:2:4 (1-Cement 2- 18.50 Cum 6888.15
coarse sand : 4- graded stone aggregates 20 mmnominal size) and
finishing smooth with curing etc.completeincluding the cost of
formwork but excluding thecost of reinforsement for R.C.C work in
It. No. Description of Item Quantity Unit Rate in Figure Total
55 Providing TMT Bar FE 500D reinforcement for R.C.C. work 1000.00 Kg. 76.21
including bending, binding and placing in position complete upto
floor two level
Rs. Fourty Nine Lakhs, Seventeen Thousand Six Hundred Eleven and Twenty Three Paisa Only
I/We am/are willing to carry out the work @ ______________ % ______________ percent
(should be written in figures and words) below / above, the estimated rates mentioned above, amount of
my/our tender works out as under :
Above all items of "Bill of Quantities" with Item Description, Unit, Qty, Rate & Amount have verified by me and
1 The Contractor shall exhibit a board with detailed specification and details of work as directed by the
Engineer-In-Charge for which no extra payment shall be made.
2 The labour cess will be deducted as per prevailing rules i.e. 1% of the work done.
3 GST and Income tax TDS will be deducted at a source while making payments of bills.
4 In all R.C.C. Items in Rate Analysis Standard Cement Consumption has been taken as per Govt. G.R.: PRC-
10/2017 Cement Consumption/16/C, Date:11/05/2017 as stated in S.O.R. therefore in R.C.C. items where
there is a change as per actual mix design the cost of difference of cement consumption have been deducted
from the rate of original item at the rate of input rate mentioned in all the tender.
5 The contractor will have to submit the mix design for different grades of cement concrete and asphalt
at his own cost before execution as directed and to be approved from the engineer in charge.
Deputy Executive Engineer Executive Engineer
District (R&B) Sub Dn. No.1 District (R & B) Division
Vadodara Vadodara
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2. NIT.pdf
3. SBD Form.pdf
4. BOQ.pdf
4.1. Make List.pdf
5. Specification Index.pdf
6. Tech Specifications.pdf
7. Index - GRs - Govt.pdf
8. GRs - 2.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .