Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.4 LAccepted-AOC HOUSE NO 01 B JANANA DODI OPP AKSHAY HOTEL RAI KA BAGH JODHPUR RAJASTHAN 342010 | 342010 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹24.0 L+₹1.8 L (7.99%)Rejected-AOC | L2 | Rejected-AOC Not Lowest Bidder | |
| 3 | L3₹24.3 L+₹2.1 L (9.38%)Rejected-AOC MANOBAL 236 VARDMAN NAGAR SHOBAWATO KI DHANI PAL ROAD JODHPUR | L3 | Rejected-AOC Not Lowest Bidder | |
| 4 | L4₹25.4 L+₹3.2 L (14.4%)Rejected-AOC | L4 | Rejected-AOC Not Lowest Bidder |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
28 May 2025, 6:00 pmClosed
GE (AF) No 02 Jodhpur
GE (AF) No. 2 Jodhpur AF Stn Jodhpur
Repair replacement of Street light fitting security light fitting high mast flood light fittings and allied work at 750 SU under AGE E/M GE AF No 2 Jodhpur, Repair maint of LT cable LT Panel, MCCBs and GI earthing chemical earthing pits surge protec
2025_MES_706179_1
8529/E8
Open Tender
Construction Works
Item Rate
180 days
Mandore
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) No 02 Jodhpur
₹60,000
Yes
21 Jun 2025
1 May 2025
30 May 2025
1 May 2025
28 May 2025
15 May 2025
1 May 2025 - 8 May 2025
Amount
Excavation in trenches n.exc 1.5 Mtr wide and n.exc 1.5 Mtr in depth in hard/dense soil and getting out complete all as directed.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers n.exc 25cm complete all as directed.
Removal of excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed.
M&L sand cushioning / filling for underground cable protection, filling under floors ,consolidated and compacted with clean dry sand complete all as specified and as directed.
M & L stone Slab 40 to 50 mm thick rough dressed jodhpur stone patties/ slab cover in trenches for protection of cable 25 to 30 CM wide and thickness not less than 50 mm in length lay dry abutting each other with gap between adjacent slab not exceeding 10 mm over sand cushioning.
Supplying and fixing in replacement of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with standed aluminium conductor 4 core 16 sqmm laid in trenches/ duct/ pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge.
All as per itme No 06 above but 3.5 core 25 Sqmm
All as per itme No 06 above but 3.5 core 35 Sqmm
All as per itme No 06 above but 3.5 core 50 Sqmm
All as per itme No 06 above but 3.5 core 240 Sqmm
S&F in replacement LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 25-50 Sqmm 3.5 core all as directed.
S&F in replacement LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 70-120 Sqmm 3.5 core all as directed.
S&F in replacement LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 150-185 Sqmm 3.5 core all as directed.
Supply and fixing MCCB in replacement of 100 Amps, 3 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
Supply and fix MCCB in replacement with thermal magnetic release adustable type DU 160, 160A, 36KA, 415 Volts 3 pole all as specified & directed.
Supply and fix MCCB in replacement with thermal magnetic release adustable type DN2-250D, 250A, 415 Volts 4 pole 36KA all as specified & directed.
Supply and fix MCCB in replacement with thermal magnetic release adustable type DN3-400D, 400A, 415 Volts 4 pole 36KA all as specified & directed.
M & L in repair GI tubing Light grade 80mm incl all accessories for protection cable complete all as specified and directed in engr-in-chage
M & L in repair GI tubing Light grade 50mm incl all accessories for protection cable complete all as specified and directed in engr-in-chage
S&F double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to ISI 14930 (Part I and II ) for protection of underground cable .Outer dia of pipe 50 mm with all fitting laid in trenches/road/nallah or fixed along wall ,poles or laid under floor (including cutting floor /Road and making good to match with existing adjointing surface etc for cable protection all as specified and as directed.
PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregates as in foundation of poles etc filling and mess concrete complete all as specified.
PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregates as in foundation of poles etc filling and mess concrete complete all as specified.
Checking of earth registance of 80 earthing (copper earth pits/ chemical earth pits/GI earth pits) and E-N voltage monthly with calibrated earth tester meter and multimeter including recharging of earthing with chemical ,maintaing of earth testing record and rectification of blockage earth pits ,rectification of earthing related fault also complete all as specified and as directed by engr in charge. Note:- (a) Chemical required for recharging of earthing shall be paid separtely. (b) Measurment of one month shall be treated as one job.
S&F in replacement galvanized iron strip of size 32 x6 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
S&F in replacement copper strip of size 32 x6 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
S&F in replacement copper strip of size 20 x3.15 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
M&L for carrying out brazing to existing earthing strip joint in between earthpit to test point after removing the nut bolt ,scraping the strip,preparing the hole and fix new copper bolt and nut the surface all as specified by Engr-in-charge Note - length of brazing 75mm minimum for jointing of strip.
Material and labour in repairs for electric Welding of existing GI strip of any size, any height (on roof/ on wall) at various places complete all as specified and directed by Engr in Charge.
M& L in repairs for porcelin insulater fixing on wall for supporting the copper strip at distance 45 cm including nut bolt drilling hole etc complete all as specified and directed by Engineer-in-charge.
M & L in repairs for GI funnel and wire mesh for earth pits complete all as specified & directed by Engr in Charge.
Material and labour for Test point terminal block in repairs as made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & directed by Engr in Charge.
Taking down old broken and damaged earth pit chamber and M & L for construction of new earth pit chamber of size 600 X 600 X 300 mm of PCC 1:2:4 Type B-1including colour of earth pit chamber red/green/yellow/white all as specified and directed by Engineer-in-charge.
M/L air termination single pointed copper rod of 12 mm dia and 300 mm long.
M & L for PCC 1:2:4 with 20 mm grade aggregate including demolation of existing foundation all as specified and as directed by Engineer in charge.
Material and labour in repairs for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground, vertically to a dpeth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not lss than 1.5 mtr below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead GI strip 32 x 6mm by means of bolts, nuts, check-nuts and wahsers of galvanised iron and thimbles and of earth wire protected by galvanised iron pipe light grade 40mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh complete 1:3:6 type C-1 using 20mm graded stone aggregate in lieu of CI cover and frame etc all as specified and shown in electrical plate No 3 of SSR- 2009 (Part-1)
Material & Labour in repairs for Chemical Earthing complete with copper earth plate electrode 90cm x 60cm x 5mm thickness burried directly in ground (earth pit not less than 2.5mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl copper strip 32x6mm by means of nuts & bolts, check nuts and washers of brass made of copper and connected to test point and earth dolly al as shown in electrical plate no 3 SSR part I 2009 ans specified or indicating including providing charcoal dust 100 kgs ,common salt 150 kgs ,magnisum sulphate 200 kgs and all around the plate 15CM depth and wide upto 650mm height in continuous layer ,balance pit will be filled with vegaetable soil upto groundlevel including excavation and earth work in any type of soil PCC (1:3;6) type C1 in chamber ,precast concrete (1:2:4) type B1,reinforced with welded steel wire fabric or XPM weight not less than 4 Kg/Sqm with cast iron frame ,funnel with wire mesh 40 mm bore light grade GI watering pipe all as specified and testing on completion.(Note:- the earth resistance should be less than one ohms and GI protection pipe and earth lead more than 7.5 RM shall be measure and paid separately)
Supply, and fixing in repair of wall mounted sounder with strobe lights, back plate, control module complete all as specified and as directed..
Supply and fixing in repairs addressable manual call point resattable type complete all as specified and directed.
Supply and fixing in repairs fire alarm sounders/sirens electronic type horizantal two stage continous normal operation atleast 50 minutes with sound level 65 db to 120 db measured at 1.5 m with sound output variation of + 5 db 2000 m range complete all as specified and directed.
Supply and laying in repair of GI pipes medium grade with fitting laid in trenches/wall /ground surface complete for the 20 mm sizes for eathing pits water connection complete all as specified and as directed.
Material and labour of topup of potassium nitrate (commerical name Kalmi Shora) in the earthing chambers for improvement existing of earthing registance vlaue complete all as specified and as directed.
Material and labour of topup of common salt in the earthing chambers for improvement existing of earthing registance vlaue complete all as specified and as directed.
Material and labour of 20-25 mm thick Kota stone earth pit cover of size 2 ft X 2 ft complete all as specified and as directed.
Material and labour in repair of bib tap 20 mm dia standered of PTMT any colour high pressure screwed for iron pipe complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 60 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 70/72 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 90 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED street light fitting of 120 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection complete all as specified and as directed.
S&F and testing in replacement of energy efficient LED Flood light fitting of 150 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection of complete all as specified and directed .
S&F and testing of energy efficient LED Flood light fitting of 200 watt pole mounting comprising a diecast aluminium houing with heat resistant toughened glass with frame IP 66 protection of complete all as specified and directed .
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver50/ 60 watt complete all as specified and as directed.
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 70/72 watt complete all as specified and as directed.
M&L for disconnecting electric connection and dismantling U/S LED driver form led light fittings and fixed new driver 90/100 watt complete all as specified and as directed.
M&L for repair of mechanism of highmast and rewinding of three phase high mast tower motor 440 volt AC 1HP 1425 RPM if burnt and incl dismantling form highmast transportation to workshop for rewinding with existing size of super enamlled copper wire replacing of gear,bearing bush ,greashing varnishing etc for running of rope at satisfactory level and reinstalation complete all as specified and as directed.
M & L for PVC insulated copper conductor 4 sqmm 10 core complete all as specified and as directed.
Supply and fixing in replacement of high mast panel with complete copper wiring ,ML contractor 4 pole AC3 18Amp 9 KW -03 Nos ,Timer 32 Amp , TPN MCB 63 Amp with complete busbar and including taking down old panel complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCCB in replacement of 63 Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
Supply and fixing MCCB in replacement of 160Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 36KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
S & F in repair GI Bracket for mounting street light fittings made out of light grade 32mm GI pipe and have angle of 120 degree incl fixing arrangement complete all as specified and as directed by engr-in-charge.
Supply and fix single core PVC insulated FR cable with multi stranded copper conductor 1.5 sq mm cross sectional area 3 core ,1100 volts grade all as specified and as directed.
Supply and fixing in replacement of automatic street light switch using Nature switch for automatic switching of street light based on LUX level of natural light. The sensor (nature switch) along with suitable power contactor , MCB and support terminals should be encloused in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC juction box (sintex make) conorming to IP 54. The contactor, MCB and copper circuit should suitable enough to take 3 phase load of 5 KW, contactor rating 25-32 Amps per phase, MCB SP rating of 32 Amps (03 Nos)
M/L for Repairs to out door LT panel including taking down for repair as follows :-( a ) Supply and fixing of MS sheet 16 SWG( 1.6 mm ) and fabrication of back side cover of LT panel including cutting to required size and shape fixing in position by bending, welding all as required for proper functioning of LT panel shutters including two coats of coats of synthetic enamel paint over a coat of red oxide.(b ) Supply and fixing of hinges , tee type stove enamelled black medium weight , cold rolled and mild steel 30 mm size and fixed door shutters .( c ) Supply and fixing of locking arrangement with MS sliding door bolts hasp and suitable for use with pad lock of size 200 mm.( d ) Mild steel work conforming to Fe-410-0 or Fe-310-0 as in angle iron frame work , cut to size including bending and welding angles as necessary and re -fixing of MS sheet of panel including a shop coat of red oxide primer.
M&L in replacement HERITAGE LED Post Ideal to lit up parks, garden ways and heritage sites 20 Watts complete all as directed by Engr-in -Charge Make :Crompton cat pat no -LPTH-20-CDL or eqult Havells/Bajaj/Surya
M&L in replacement of Inverted Tripod type LED bollard light 10 watt with soft light disturbution complete all as directed by Engr-in -Charge Make :Crompton cat pat no -LBLSN-10-CDL or eqult Havells/Bajaj/Surya
Supply and fixing in Replacement Digital Ammeter and Voltmeter set with connected wiring complete all as directed by Engr-In-Charge
Supply and fixing of copper thimbles using crimping tool for electrical connections with cable and connecting with suitable size of nuts / bolts and washers of size 120 sqmm to 185 sqmm LT cable size.
Supply and fixing of copper thimbles using crimping tool for electrical connections with cable and connecting with suitable size of nuts / bolts and washers of size 25 sqmm to 95 sqmm LT cable size.
S & F in replacement Change over main switch, on load, four poles, 100 Amps, 415 Volts, with enclosure, fixed in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
Material and labour for painting above the copping upto 1.5 mtr in alternatively black and white strips of 30 cm each & rest of the portion with two coats of silver/aluminium paint on steel tubular LT pole of any height after scrapping/removing the existing paint and the preparation the surface of steel tubular pole LT including painting of the channel cross arms, nut, bolts & washer, street light bracket and clamps complete all as specified and directed
S & F in repairs Mild steel work in framed work such as grills, Gates, Framed guard bars, gratings, ladders, Cable trays, Fencing etc., with ends of bars soldered/welded and/ or riveted, or forged into spikes, and similar work confirming to Fe 410 - O or Fe 310 - O incl two coats of mettallic paint over a coat of mettallc primer incl taking down old rusted steel work as directed.
Supplying and fixing in replacement of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with standed aluminium conductor 2 core 10 sqmm laid in trenches/ duct/ pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge.
S&F double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to ISI 14930 (Part I and II ) for protection of underground cable .Outer dia of pipe 50 mm with all fitting laid in trenches/road/nallah or fixed along wall ,poles or laid under floor (including cutting floor /Road and making good to match with existing adjointing surface etc for cable protection all as specified and as directed.
S&F in replcement FRP junction box for street light central with linked door control incl 6 amp MCB SP with aluminium bus bar-04 nos for controling street light/garden light complete as directed by Engr-in-Charge.
Supply and fixing LED Solar street light fitting 36 Watt including galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor complete.
Material and labour for substation yard spreading levelling with 20 mm graded coarse aggregate /gravells laid approximately 75 mm thick layer near VCB/Transformer /2/4 pole structure and plateform etc complete all as specified and as directed.
Surface cleaning by removing the roots completely from the earth, shrubs, vegetation, grass, bushes, weeds by excavation not exceeding 15cm deep including sweeping removing the same to distance not exceeding 50m away from the installation and burning the same all as specified and directed by Engr-in-Charge.
Periodical maintenance and inspection/checking of following size /capacity of DG sets and ensuring smooth functioning of DG sets and replacements of unsv parts of DG sets of following capacities : - Note:- Spare parts required shall be measured and paid separately
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement bypass filter element with O ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for the following capacities of DG Sets :-
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement luberication oil filter element with 'O' ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for following capacities of DG Sets :-
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement Air filter element inner and outer as required at site with 'O' ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for following capacities of DG Sets :-
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement fuel filter element with 'O' ring of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for following capacities of DG Sets :-
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement fan belt of Kirloskar /Crompton greeves/Mahindra DG Sets as required at site as per make and model for the following capacities of DG Sets :-
40 KVA DG SET
30 KVA DG SET
20 KVA DG SET
Supply and fixing in Replacement distilled water to be filled in batteries ,complete all as specified and directed by Engineer-in-charge.
Supply and fixing in Replacement ignition switch with key in repair for DG sets of any capacities, complete all as specified and directed by Engineer-in-charge.
Material & Labour for replacement of battery cable of size 40 sqmm PVC insulated multi stranded copper conductor single core cable with necessary lugs, complete all as specified and directed by Engineer-in-charge.
Supply and filling in Replacement top up coolent for DG set radiator
Supply and fixing in Replacement Water temperature gauge for 20 KVA to 40 KVA DG set complete all as specified and as directed.
Supply and fixing in Replacement oil pressure gauge assembly for 20 KVA to 40 KVA DG set complete all as specified and as directed.
Supply and fixing in Replacement oil temperature gauge for 20 KVA to 40 KVA DG set complete all as specified and as directed.
Supply and fixing in Replacement cable for Techno meter for 20 KVA to 40 KVA DG set complete all as specified and as directed.
Supply and fixing in Replacement Techno meter assembly for 20 KVA to 40 KVA DG set complete all as specified and as directed.
Supply and fixing in Replacement flexible braided hydraulic hose 5/8" dia x 600 mm length including suitable check nuts & washers, complete all as specified and directed by Engineer-in-charge.
Supply and fixing in Replacement RPM metre with cable (0-3000 RPM),, complete all as specified and directed by Engineer-in-Charge.
Supply and filling in Replacement lube oil SAE 15 W - 40 for Top up and filling up the oil in the sump after completely flushing the old oil out of the tank and cleaning of the tank for fresh filling, complete all as specified and directed by Engineer-in-charge. Make : Castrol/Power Supreme
Supply and fixing in Replacement battery terminal heavy duty as per sample made of brass with bolts and washers all as required at site,, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in Replacement complete 12 V 180 AMPH maintenance free battery and initial charging complete including inbuilt charger including required electrolyte /distilled water etc and fixing as required at site to the concerned DG Set, complete all as specified and directed by Engineer-in-charge.
Supply and fixing in Replacement of self starter assembly for DG set for 20 KVA to 40 KVA 12 volts DC including, complete fixing and testing, complete all as specified and directed by Engineer-in-charge. Make:-Lucas-TVS
Supply and fixing in Replacement Rubber hose set for DG set radiator by replacing the unserviceable hose set ,for 20 KVA to 40 KVA DG set complete all as specified as directed by Engineer-in-charge.
Supply and fixing in Replacement PLC system for DG sets of 20 KVA to 40 KVA capacities , complete all as specified as directed by Engineer-in-charge.
Supply and fixing in Replacement of turbo charger,320 complete all as specified as directed by Engineer-in-charge. Make:- Holest or equivalent as approved.
Material and labour for dismantling of radiator from engine taking it to work shop repair of leakage pipes, cleaning the radiator with cleaning agents, re-assembling to the engine completely to enting satisfaction of Engineer-in-Charge
Inspection/checking of AMF panel of DG set of capacity 20 KVA to 40 KVA installed at various installations of any make and shape and rectify the defects, replacement of unserviceable part as required at site and cleaning of AMF panel as detecting during inspection or pointed out by users/department and carry out maintenance , complete all as specified as directed by Engineer-in-charge. Note:- Spare parts required shall be measured and paid separately .
Supply and fixing in Replacement 4 Pole power contactor with AC coil 80 Amps, 3 phase 415 volt 50 HZ suitable for AMF panels complete all as specified as directed by Engr-in-Charge Make:-Havells model No-IHPAC065500 or equivalent as approved
Supply and fixing in Replacement engine start relay 12 volt DC suitable for AMF panels Complete all as specified as directed by Engr-in-Charge Make:- Eagle Man/PIC or equivalent as approved
Supply and fixing in Replacement frequency meter 45 to 55 HZ AC 415 volt of size Sqmm suitable for AMF panels complete all as specified as directed by Engineer-in-Charge. Make:- AE/Premier.or equivalent as approved
Supply and fixing in Replacement cranking relay 12/24 volts DC 8/11 stage suitable for AMF panels complete all as specified as directed by Engineer-in-Charge. Make:- Eagle Man or equivalent as approved
Supply and fixing in Replacement indicator lamp assembly LED type with red/green/blue for phases R,Y,B suitable for AMF panels complete all as specified as directed by Engineer-in-Charge.
Supply and fixing MCCB in replacement of 100 Amps, 3 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
S & F Change over main switch, on load, four poles, 630 Amps, 415 Volts, 36 KA ,50 Hz, with enclosure, fixed in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. Make: Havells model No-IHCNF00250 or equivalent as approved
M/L for Repairs to out door LT panel including taking down for repair as follows :-( a ) Supply and fixing of MS sheet 16 SWG( 1.6 mm ) and fabrication of back side cover of LT panel including cutting to required size and shape fixing in position by bending, welding all as required for proper functioning of LT panel shutters including two coats of coats of synthetic enamel paint over a coat of red oxide.(b ) Supply and fixing of hinges , tee type stove enamelled black medium weight , cold rolled and mild steel 30 mm size and fixed door shutters ( c ) Supply and fixing of locking arrangement with MS sliding door bolts hasp and suitable for use with pad lock of size 200 mm( d ) Mild steel work conforming to Fe-410-0 or Fe-310-0 as in angle iron frame work , cut to size including bending and welding angles as necessary and re -fixing of MS sheet of panel including a shop coat of red oxide prime
Material and labour in repair for earthing complete with copper plate electrode 60cmx60cmx3.15mm thick, buried directly in ground, vertically to a dpeth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not lss than 1.5 mtr below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead copper strip 20 x 3 mm by means of bolts, nuts, check-nuts and wahsers of galvanised iron and thimbles and of earth wire protected by galvanised iron pipe light grade 40mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh complete 1:3:6 type C-1 using 20mm graded stone aggregate in lieu of CI cover and frame etc all as specified and directed.
S&F copper strip of size 20 x3 mm as earth continuity conductor buried in ground or fixed to wall/floor/ground provided with porcelain insulators space no less than 0.5 mtrs complete all as specified and directed.
Shiv Shakti Enterprises (BID ID -3302125)
AMAN ASSOCIATES (BID ID -3307248)
L C ASSOCIATES (BID ID -3307113)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .