| Sl No | Description | Qty | Unit | HNS Barq Electric L1 |
|---|---|---|---|---|
| 1.00Part - "B" NON BSR Item | ||||
| 1.01 | Over all maintenance with material of 11KV, 400 amp Isolator including fabricating of copper pipe/conductor, setting of operable pipe connecting copper pipe/blade/U clamp nut bolts complete maintenance so that Isolator should be in smooth operation. (i) 11/0.4 KV Distribution transformer upto 500KVA capacity | 12 | Nos | 3,400 ₹40,800 |
| 1.02 | Supply and fixing of strut made out of ‘B’ Class GI pipe 80mm. having base plate of size 300mm×300mm×6mm. (10.0 Mtr. long) by fixing on the pole at top by clamping within position with M.S. flat 50mm×6mm. Clamps and M.S. nuts & bolts and grouting in ground as required (0.4 Mtr.) (a) GI pipe Strut 8 Mtr. | 6 | Nos | 2,500 ₹15,000 |
| 1.03Repairing charges of LED Street Light / Flood Light | ||||
| 1.04 | (a) LED Street Light 90 watt | 5 | Nos | 500 ₹2,500 |
| 1.05 | (b) LED Flood Light 150 | 5 | Nos | 500 ₹2,500 |
| 10.00 | The Total value of Schedule4 | 1 | Nos | - |
Tender Value
₹18.1 L
EMD Value
₹36,140
Closing Date
6 Mar 2026, 5:00 pmClosed
VMOU, Kota
VMOU, Kota
Annual Rate Contract for Electrical Maintenance work in University Campus.
2026_VMOU_541652_1
NIB No. 38/2025-26
Open Tender
Electrical Works
365 days
Kota
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
VMOU, Kota
₹36,140
25 Mar 2026
25 Feb 2026
7 Mar 2026
25 Feb 2026
6 Mar 2026
25 Feb 2026
Part - "B" NON BSR Item
Over all maintenance with material of 11KV, 400 amp Isolator including fabricating of copper pipe/conductor, setting of operable pipe connecting copper pipe/blade/U clamp nut bolts complete maintenance so that Isolator should be in smooth operation. (i) 11/0.4 KV Distribution transformer upto 500KVA capacity
Supply and fixing of strut made out of ‘B’ Class GI pipe 80mm. having base plate of size 300mm×300mm×6mm. (10.0 Mtr. long) by fixing on the pole at top by clamping within position with M.S. flat 50mm×6mm. Clamps and M.S. nuts & bolts and grouting in ground as required (0.4 Mtr.) (a) GI pipe Strut 8 Mtr.
Repairing charges of LED Street Light / Flood Light
(a) LED Street Light 90 watt
(b) LED Flood Light 150
The Total value of Schedule4
Percentage BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part - "A" Electric Work
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked (IS:14927 P - II) virgin material UPVC trunking & it's accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal/ Surface Moulded virgin material UPVC Modular Box, 10 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose/holder /3 way Connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/Wiring accessories refer Chapter E-04, E-05 & E-07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
Short Point (upto 3 mtr.)
Medium point (up to 6 mtr.)
Long point (up to 10 mtr.)
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked (IS:14927 P - II) virgin material UPVC Trunking & it's accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal/ Surface Moulded virgin material UPVC Modular Box, modular 10A switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E-04, E-05 & E-07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
On Board
Short Point (upto 3 mtr.)
Medium point (up to 6 mtr.)
Long point (up to 10 mtr.)
S&F following sizes of ISI marked (IS:14927 P - II) virgin material UPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
Supplying and Drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade. Wire should be made from 99.90% purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss, oxygen free for less chances of oxidization, insulation PVC type A/C/D, flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828 (1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism, energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm, conductor line load reversibility, IP-20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20000 upto 20 A rating and 10000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accredited lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
Single pole MCB (With B/C curve tripping Characteristics) 6A to 32A Rating
Double pole MCB (With B/C curve tripping Characteristics) 6A to 32A Rating
Providing & Fixing of 240/415 V isolator ISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation, two position din rail mounting, minimum phase termination capacity of 35sq.mm IP-20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
Double pole Isolator 63 A Rating.
Four pole Isolator 40 A Rating.
80 A / 100 A Rating.
Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only) 100 amp. insulated copper bus bar/shorting link, copper neutral link, copper earth link, color coded interconnecting wire set of suitable rating and din bar, masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Metal door (single phase) IK-09 and IP-43 with Metal end box
Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB and SP / TP MCB as outgoing, made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only) complete with insulated 100 A rating copper bus bar, neutral bars with shrouds, earth bar , color coded interconnecting wire set of suitable rating and din bar, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Double door IK-09 & IP-43 with Metal end box 6 Way (8+18)
P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
Providing & Fixing of 16 amp. Combined flush type non modular socket and switch set with indicator and fuse set as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Providing & Fixing of ISI marked (IS:3854) twin control non modular 6A switch flush type as per PWD specification for electrical Works, made out from industrial grade Polycarbonate or fire resistant ABS material, including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
Providing & Fixing of 3/5 pin 6 amp. flush type non modular socket made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Providing & Fixing of IS 11037:1984 marked non modular socket size flush type 120 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material including making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, minimum width of switch toggle (PUSH PART) should not less then 20mm, including all as per pre approved by Engineer in charge, making connections, testing etc. as required. For additional technical parameters of product/work refer Annexure 'A' attached with this BSR.
10 A One way switch
10 A Two way switch
10 A bell push
16 Amp. One way switch with Led Indicator
Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including all as per pre approved by Engineer in charge, making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
6 A 3/5 pin shuttered socket
6/16 A shuttered socket
Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including all as per pre approved by Engineer in charge, making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
5 step fan regulator 2 Module 360 degree rotating
Providing & Fixing of Wiring Accessories OEM fabricated following size virgin material UPVC modular boxes on surface suitable for modular accessories as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
1-2-3 Module
6-8 Module
10-12 Module
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalized cubical panel as specifications and Other parameters required as per point (a), (b), (c), (d), (e), (f), (g), (h) as below :
(a) Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3mm thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness, required hardware, concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
(c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp) and by solid bus bar (>63 amp). Control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned. Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves. Earth and Neutral bus bar shall be half of the size of phase bus bar. (Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra)
(d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
(e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100×50×5 mm (to be paid Extra)
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Supplying and Fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending, cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Electrolytic grade Aluminium bus bar 6010 grade
Electrolytic grade (Cu-ETP) Tin Coated annealed copper bus bCaSrs IA 100% grade
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings, conforming to IS/IEC 60947 P -2 :2003 with front face & centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree & without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. Provision for UVR, shunt trip, earth fault trip, door interlock, pad lock & rotary handle, including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution all as per pre approved by Engineer in charge. For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR. 4 pole MCCB with Thermal Magnetic release
125 Amp, 25 kA, adjustable O/L & adjustable S/C setting,
200 Amp, 25 kA, adjustable O/L & adjustable S/C setting,
Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 including connections, testing etc. as required .in the following rating. Appropriate type test certificate / OEM test report shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. With sheet steel enclosure made out from CRCA sheet door 1.2mm & body 1.6mm thick, powder quoted, door locking system allow opening of door in OFF position only with 2 nos external earthing points.
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P-I of 1.1 KV with H4-Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6%, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
4.0 Sq. mm - 2 Core
4.0 Sq. mm - 3 Core
6.0 Sq. mm - 2 Core
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P-I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6%, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
10 sq.mm - 4 core
25.0 Sq.mm - 3.5 core
35.0 Sqmm. - 3.5 core
50.0 Sq.mm - 3.5 core
70.0 Sqmm. - 3.5 core
95.0 Sq.mm - 3.5 core
120.0 Sqmm. - 3.5 core
185.0 Sqmm. - 3.5 core
Supplying and making end termination with heavy aluminium lugs (Pin / ring type) confirming to IS 8309-1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
P/L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted. (Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS:7098 P-2 with H4 - Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6%, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables, Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
3 core 95.0 Sq.mm
3 core 185.0 Sq.mm
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, preparation of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for straight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
11 KV end Termination Kit Indoor type, 3 core 120/150/185 Sq.mm
11 KV Straight Through Joint Kit, 3 core 120/150/185 Sq.mm
Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm × 600mm × 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia G.I. 'B' class watering Pipe, including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurement book. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm × 600mm × 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia G.I. 'B' class watering Pipe, including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top dia 225 to 260 mm, Bottom dia 300 to 350 mm and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurement book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Supply & Laying following size earth wire in horizontal or vertical run in ground/ surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
8 SWG copper Wire
8 SWG G.I. (Hot Dipped) Wire
Supply & Laying following size 'B' class, G.I. Pipe confirming to IS : 1239 P-1 (2004) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in charge. (Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
25 mm dia
50 mm dia
100 mm dia
Providing & Fixing of IP20, 2'×2' LED Surface/ Recessed mounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non-yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt, THD < 10 %, p.f. ≥ 0.95, CRI > 80, life time of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures.
(LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. Minimum lumen output 4200 lm
Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 × 3.25 mm) with cap (400 × 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Single arm overhang
Double arm overhang
Supply and erection of Mild steel Swaged tubular pole conforming to IS: 2713-1980 (part I to II) with base plate, the pole shall be made from steel tube & Pipe (IS:1141, Fe 410) including excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50 cm above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals, cable entry with 32 mm dia 'B' class GI cable sleeves. After erection pole shall be painted with two coat of red oxide primer and two quote of enamel paint of silver colour as per the direction of Engineer-in-charge complete as required of following height & designation. (See Table P - 02 for specs) All as per pre approved by Engineer-in-charge. For additional technical parameters of products/work, refer Annexure "A" attached with this BSR.
7.5 Mtr. (410 SP – 5)
9.0 Mtr. (410 SP – 28)
Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety. Power Factor >0.95, THD(I) <10%, driver current <=750mA driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved / Embossing / Screen printing on die cast housing to allow traceability/authenticity.
Fixture shall be IS 10322 Complianced. OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. High Power LED Flood Light Minimum lumen output 14800 lm
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stabilization report submitted for UV cover) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each. The System efficacy >=125 lm/ wt. & potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety, Power Factor >0.95 driver Efficiency >85%, THD(I) <10% Humidity 10% to 90% RH Working Temp -5ºC to 45ºC driver current <750mA. The luminaire shall be BIS certified & Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintained, CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment driver should be Phase to phase protection of 440V for 4Hrs.
Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. LED Street Light fixture with Minimum lumen output 8700 lm
Providing & Fixing of Street light bracket made out from following size of 'B' class, Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR. 32 mm dia
Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
8.0 Mtr long PCC pole of 200 Kg Working Load
9.0 Mtr long PCC pole of 200 Kg Working Load
Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 × 380 × 4.0 mm
Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
LT cross arm 600 mm long with clamp
LT cross arm 1200 mm long with clamp
Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 100 mm x 70 mm
Supply and Fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 75mm x 90mm
Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked (IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT
Supply and fixing of 'V' type cross arms with top hamper and clamps as per latest Discom specifications made of MS angle on the existing poles complete including all necessary nut and bolt, clamps with two coats of Red oxide and two coats of Aluminium paint etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product/work refer Annexure 'A' attached with this BSR.
Supply and fixing of top hamper on the existing pole as per latest Discom specifications complete including nut bolts with two coats of Red oxide and two coats of Aluminium paint etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. Vertical type 11 kV (.7m long) (65×65×6mm angle)
Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486 (Part-I) / 1993 & IS:2486 (Part-II) / 1989 with latest amendment and as per latest Discom specs etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product/work refer Annexure 'A' attached with this BSR.
Supply and Fixing of 11kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest amendment and as per latest Discom Specs on existing bracket including all accessories etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR.
B & S type hardware 45 KN
B & S disc insulator 45 KN
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt, one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR.
Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be leveled and neatly dressed:
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Item Wise BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Part - "C" Labour Work [Based on Minimum wages (1 Electrician + 1 Helpar on each in three shifts)]
Providing qualified / Experienced Electrician & Helper sufficient members for round the clock electrical maintenance in University campus (24 hours × 7 days). The maintenance work includes from main meter point to upto end user points, street lights, D.O. fuse etc. Complete in all respect. (L.T. Line & H.T. Lines).
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
TenderDocElectric.pdf
Tender Documents • 1.06 MB
BOQ_965572.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid