Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.0 LAccepted-AOC | L1 | Accepted-AOC Lowset1 | |
| 2 | L2₹11.3 L+₹24,440 (2.21%)Rejected-Finance | L2 | Rejected-Finance Rejected | |
| 3 | L3₹12.5 L+₹1.4 L (12.8%)Rejected-Finance | L3 | Rejected-Finance Rejected | |
| 4 | L4₹13.0 L+₹1.9 L (17.5%)Rejected-Finance | L4 | Rejected-Finance Rejected | |
| 5 | L5₹14.9 L+₹3.8 L (34.8%)Rejected-Finance VILLAGE P O MANSIMBLE TEHSIL PALAMPUR DISTRICT KANGRA HP | KANGRA | HIMACHAL PRADESH | 175013 | L5 | Rejected-Finance Rejected |
Tender Value
₹14.8 L
EMD Value
₹29,660
Closing Date
17 Aug 2020, 11:00 amClosed
Executive Engineer
Jal Shakti Division Fatehpur
Sub Head Supply and Erection of submersible /centrifugal pumping machinery 2 sets 10 HP with allied accessories, centrifugal pumping machinery with its allied accessories, laying jointing testing of Rising main 100 mm dia of GI pipe (Medium Class)
2020_HPIPH_39640_1
EE/JSD/FTR/EA/T/2020-4187-4237
Open Tender
Civil Works
Item Rate
120 days
Tehsil Fatehpur
As per notice inviting tender
10 documents required · 10 mandatory
₹400
Executive Engineer, Jal Shakti Division Fatehpur
₹29,660
Yes
18 Dec 2020
7 Aug 2020
17 Aug 2020
7 Aug 2020
17 Aug 2020
7 Aug 2020
Amount
Supply of submerssible puming set of KSB/Kirloskar/Lubi/Sabar/Calama/ SU/Crompton /Johnston/ Worthington/ BS make confirming to BIS:8034-1974/5660-1970 (latest) suitable for lifting clear, cold & fresh water fitted with bronze impellers or suitable allow directly coupled to squirrel cage electric induction motor of same make as that of pump confirming to BIS:9283-1979 (latest with upto date ammendments) and totally water proof for submerssible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand non-vertical loads with minimum wear and tear. It should also be fitted with a device to take up expension of water with the heating of motor including water level guard, errection clamps, cable clips & depth guage etc. The pump shall be suitable for operation on data give below:-
Location of site :-The site is located at a distance of 25 Kms.from Pathankot Railway Station.
The altitude of place in which :-Altitude of place is 435 Metres above Mean Sea Level. The motor is intended to work:-
Type of current :-A.C.Three phase supply with frequency 50 cycles per second.
Rated Voltage :-415 Vvolts (+/-) 10%
Characterstics of water :-(a).Temperature = 20oC (f) PH =_____
(b).Turbidity =Upto 10NTU (g) Total solids____Mg/Litre
©. Hardness =__Mg/Litre(as CaCo3) (h). Others_____
(d).Alkalinity =__Mg/Litre(as CaCo3)
Depth of Well Assembly :- 125 Metres.
L.W.L.in Tube-Well :- Metres
Maximum draw down :- Metres
Centre line level of Pump :- 211 Metres
Discharge level of highest point:- 255 Metres
Nos.of Pumps required :-2 No.Pump.
Capacity :- 5.10 L.P.S.
Total head in Metres :-35.92 Metres
Length of Rising Main :- 50 Metres
Dia of Rising Main :- 100 mm ( GI. Medium Class)
No.of working hours per day :16.00 Hours.
Limits of pump operation :- ( - ) 15% ( + ) 10% of total head.
H.P.of Motor/Drive unit :-Required H.P.of Pump at ( + ) 10% and ( - ) 15% of total head.
BHP.with following margins/multiplying factor at duty point,whichever is higher.
a).Upto 2 H.P. =1.5 (d) 10 to 20 H.P. =1.2
b).2 to 5 H.P. =1.4 (e) 20 to 100 H.P. =1.15
c) 5 to 10 H.P. =1.3 (f) Above 100 H.P. =1.10
Test Run :-16 Hours continueously for 7 days.
Providing and fixing automatic pannel borad including auto start, auto stop and restart facility single phase of phase reversal imbalance and overload and fixed with compatible starter in sheet enclosure with cabling of phase reversal imbalance and overload and fixed with compatible starter in sheet enclosure with cabling complete in all respect to deliver results.
Providing C.I.double flanged sluice valve of Kirloskar/Kilburn/IVC.\/Fouress/Gled/BHEL/Leader make of size dia as per offered pump and Class PN 1.0 having one size higher to delivery size of Pump and capable of dia as per offered pump and Class PN 1.6 having one size higher to delivery size of Pump and capable of with standing nominal seat pressure of 10.20 Kgs/Cm2. conforming to IS 780-1984 (P-I)
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make C.I. double flanged swing Check type Reflux Valve having bye pass arrangement and one size higher to delivery size of pump (size --dia and clasas PN 1.0 and shall be suitable for withstanding nominal seat pressure of 10.20Kgs.cm<2)conforming to IS: 5312-1984 (Note:- The size of valve specified by the tenderer)
Supply of Kirloskar/Kilburn/IVC/Foluress/Gled/BHEL/Leader make C.I. double flanged Swing check Type Reflux Valve having bye pass arrangement and of size equal to dia of Rising Main & class PN 1.0 shall be suitable for withstanding nominal seat pressure of 10.20Kgs./Cm<2).(Note:- The size of valve specified by the tenderer)
Providing and laying suitable size copper PVC.insulated armoured power 3.5 core cable conforming to BIS-1554-Part-I -1988 or latest with uptodate ammendments Siemen/Gloster/ICC make from Meter of HPSEB. to MCB/OCB & from OCB to Busbar Switch & Starter(One cable carrying all three phases) including all other elecrc equipments/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc.laid in pipers or trenches size and make will be subject to approval of HPSEB.authorities. In case of non-acceptance by HPSEB.auithority shall have to bereplaced by the tenderer free of cost. Supply side .(Note:- The size of cable specified by the tenderer)
Providing and laying PVC.jointless flat water proof cable as per BIS-694-1990(Latest with uptodate ammendments) suitable for the pump set offered from OCB to Motor, Motor to Starter including all other electric equipment such as;thimbles,flexible pipe,solder,nuts & bolts,cable glands etc.laid in pipes or trenches under floor The type & make will be subject to approval of HPSEB.authorities. In case of non-acceptance by HPSEB .authoirity,it shall have to be replaced by the tenderer free of costmotor side (Note:- The size of cable specified by the tenderer)
Providing and laying doub le loop earthing with copper plate 600x600x3mm.thick electrode complete with material such as;char coal,common salt,G.I.Pipes,thimbles,nuts & bolts,digging of pits,G.I.wiring and 25x5mm.copper stripsw of required capacity conforming to BIS-3043-1987 latest with uptodate ammendments for above motors and other electrical equipments.
Supply and erection of floor/wall mounted power factor shunt capacitor conforming to BIS-2834-1986 latest with uptodate ammendments BHEL/GEC/Machneil/Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to Induction Motor individually of required KVAR according to H.P.of Motor offered including Siemens/Gloster/ICC make from Busbar chamber to capacitor and also including LT/LK/ Kilburn make ICTP.Switchesconforming to BIS-4064-1978 or latest with HRC fuses(Range to be specified by the tendere
Supply of standard make circular dial pressure gauge of suitable range of Fiebeg/Bourden/Precision make with all accessories such as;stop cock,copper tubing etc.conforming to BIS-3624-1987 latest with uptodate ammendments
Lowering of Column Assembly of 100 mm.dia and common header 80 mm.dia Confirmng to IS-1239 or MSERW pipe 4.80 mm.thick conforming BIS-1978-82 considering site requirement duly flanged at every 3 Metre length with flanges conforming to BIS-6392-1971(Table-17) including tapers,flanges,rubber gaskets 3mm.thick as as per BIS-2712-1978,nuts & bolts as per 1364-1983 and specials upto collection tank as per directions of Engineer-in-Charge /as per layout approved by the Engineer-in-Charge. The pipes shall be capable of withstanding 1.5 times the total pressure indicated in item No.1(xii). NOTE:- Actual laying tobe done as per final drawings to be approved by the Engineer-in-Charge.
Erection of all equipments from S.No. 1 to 5. and 6 ncluding cost of tees, bends,tapers and any other fittings required as per conditions and as per directions of the Engineer-in-Cha
Providing horizontal spindle, horizontal/radial split casing/and suction (backfull out arrangement) single/ double/ multistage centrifugal pump or combination of pumps, in series/parallel of recommended make such as BS/SABAR/LUBI/Calama/KSB/Crompton/SU/Johnston/Kirloskar /BE/Jyoti as per BIS-1520-1980 with upto date ammendments, read with IS:9137-1978 or latest edition suitable for lifting water for under mentioned characterstics with bronze, impellers, priming funnels, casing ring and shaft sleaves of bronze, shaft of steel grade with cast iron casing coupled directly through a flexible coupling on a common CI/cast steel base plate(base plate to be from the manufacturer of the pumping set) to slipring/squirrel cage screen protected drip proof induction motor of Kirloskar/ BHEL/Crompton /NGEF/GEC/ Siemen/ Jyoti/BHEL/ GEC/ABB confirming to BIS-325-1978 read wih BIS:900-1978 (latest with upto date ammendments) It should be include the cost of bearing, nuts & bolts painting etc and shall be suitable for operation as per data given below :-
The pumping machinery shall be installed on properdised baseplate , which is to befrom the principal manufacturer of pumping set. The foundation of the machinery should be designedandanchored properly.
Location of site :-The site is located at a distance of 25 Kms.from Nurpur Road Railway Station.
The altitude of place in which :-Altitude of place is 460 Metres above Mean Sea Level.
the Motor is intended to work
Type of current :-A.C.Three phase supply with frequency 50 cycles per second.
Rated Voltage :-415 Vvolts (+/-) 10%
Characterstics of water :-(a).Temperature = 20oC (f) PH =_____
(b).Turbidity =Upto 10NTU (g) Total solids____Mg/Litre
©. Hardness =__Mg/Litre(as CaCo3) (h). Others_____
(d).Alkalinity =__Mg/Litre(as CaCo3)
Depth of Well Assembly :- Metres.
L.W.L.in Tube-Well :- 250 Metres
Maximum draw down :- Metres
Centre line level of Pump :-1251 Metres
Discharge level of highest point:-376 Metres
Nos.of Pumps required :-2 No.Pump.
Capacity :- 5.10 L.P.S.
Total head in Metres :-152.62 Metres
Length of Rising Main :- 2380 Metres
Dia of Rising Main :- 100 mm dia GI Medium Class
No.of working hours per day :-16 Hours.
Limits of pump operation :- ( - )15% ( + ) 10% of total head.
H.P.of Motor/Drive unit :-Required H.P.of Pump at ( + ) 10% and ( - ) 15% of total head.
BHP.with following margins/multiplying factor at duty point,whichever is higher.
a).Upto 2 H.P. =1.5 (d) 10 to 20 H.P. =1.2
b).2 to 5 H.P. =1.4 (e) 20 to 100 H.P. =1.15
c) 5 to 10 H.P. =1.3 (f) Above 100 H.P. =1.10
Test Run :-8 Hours continueously for 7 days.
Providing C.I.double flanged sluice valve of Kirloskar/Kilburn/IVC.\/Fouress/Gled/BHEL/Leader make of size dia as per offered pump and Class PN 1.6 having one size higher to delivery size of Pump and capable of with standing nominal seat pressure of 16.00 Kgs/Cm2. conforming to IS 780-1984 (P-I)
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make C.I. double flanged swing Check type Reflux Valve having bye pass arrangement and one size higher to delivery size of pump (size --dia and clasas PN 1.6 and shall be suitable for withstanding nominal seat pressure of 16.00 Kgs.cm<2)conforming to IS: 5312-1984 (Note:- The size of valve specified by the tenderer)
Supply of Kirloskar/Kilburn/IVC/Foluress/Gled/BHEL/Leader make C.I. double flanged Swing check Type Reflux Valve having bye pass arrangement and of size equal to dia of Rising Main & class PN 1.6 shall be suitable for withstanding nominal seat pressure of 16.00Kgs./Cm<2).(Note:- The size of valve specified by the tenderer)
Providing and laying suitable size copper PVC.insulated armoured power 3.5 core cable conforming to BIS-1554-Part-I -1988 or latest with uptodate ammendments Siemen/Gloster/ICC make from Meter of HPSEB. to MCB/OCB & from OCB to Busbar Switch & Starter(One cable carrying all three phases) including all laid in pipers or trenches other elecrc equipments/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc.size and make will be subject to approval of HPSEB.authorities. In case of non-acceptance by HPSEB.auithority shall have to be replaced by the tenderer free of cost. Supply side (Note:- The size of cable specified by the tendere
Providing and laying PVC.jointless flat water proof cable as per BIS-694-1990(Latest with uptodate ammendments) suitable for the pump set offered from OCB to Motor, Motor to Starter including all other electric equipment such as;thimbles,flexible pipe,solder,nuts & bolts,cable glands etc.laid in pipes or trenches under floor The type & make will be subject to approval of HPSEB.authorities. In case of non-acceptance by HPSEB.authoirity,it shall have to be replaced by the tenderer free of costmotor side (Note:- The size of cable specified by the tenderer)
Providing and laying doub le loop earthing with copper plate 600x600x3mm.thick electrode complete with material such as;char coal,common salt,G.I.Pipes,thimbles,nuts & bolts,digging of pits,G.I.wiring and 25x5mm.copper stripsw of required capacity conforming to BIS-3043-1987 latest with uptodate ammendments for above motors and other electrical equipments.(6x2 =12)
Supply and erection of floor/wall mounted power factor shunt capacitor conforming to BIS-2834-1986 latest with uptodate ammendments BHEL/GEC/Machneil/Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to Induction Motor individually of required KVAR according to H.P.of Motor offered including Siemens/Gloster/ICC make from Busbar chamber to capacitor and also including LT/LK/ Kilburn make ICTP.Switchesconforming to BIS-4064-1978 or latest with HRC fuses(Range to be specified by the tenderer).
Supply of standard make circular dial pressure gauge of suitable range of Fiebeg/Bourden/Precision make with all accessories such as;stop cock,copper tubing etc.conforming to BIS-3624-1987 latest with uptodate ammendments.
Laying jointing of Delivery/sunction pipe conforming to BIS:1978-82/BIS-1239-1990 of suitable size of suction, delivery and common header considering site requirement & NPSH required/available. The pipe size for suction and delivery shall as per the requirement of offered pump and common header shall be3 equal to dia of Rising main icnluding cost of tappers, flanges Table-17 (confirming to relevant table of BIS-6392-1971) bends, rubber gasket, 3mm thick nuts, & bolts and specials upto 5 mtrs away from the outer wall of pump house as per layout drawing approved by Engineer-in-charge. Pipe & material shall be capable of with standing field test pressure equal to 1.5 times the operating pressure.
The complete arrangement shall be comprise of: (a) Suction pipe ---mm dia GI Pipe (Medium Class)
(b) Delivery pipe ----mm dia GI Pipe ( Medium Class)
( c) Common header -- mm dia GI Pipe (Medium class)
Erection of all equipments from S.No. 8 to 12 and 13 including cost of tees, bends,tapers and any other fittings required as per conditions and as per directions of the Engineer-in-Charge.
Excavation in foundation treanches(Pipe & Pits) up to all depths in all classification of earth work such as pick work,jumper work,saturated soil including bailing or pumping out water,blasting soft /hard rock where blasting is prohibited in all lifts including trimming & dressing of sides leveling of beds to correct grade i/c shoring/strutting planking,timbering & dewatering wherever required stacking the usable & unusable material/soil separately & after laying,jointing & testing of pipes,returning the useable soil in trenches in 15cm layers including consolidating of such deposited layer by raming & watering & then disposing of all surplus excavated soil/unusable material as directed with in all leads & lifts including restoration of unmetalled surface to its original condition & including cost of diversion for traffic,night signals,fixing caution boards,crossing over trenches for access to houses,fencing etc.completein all respects with in all leads & lifts as per directions of Engineer-in-Charge.
Laying and jointing in trenches to be levelled to grade, BIS marked GI flanged pipes confirming to BIS:1239 (latest with upto date ammendments) of 100 mm dia (Medium class) duly flanged to be welded after 66 mtr. ,interval of pipe with intermediate butt welded joints including the cost of flanges, bends/short pieces made from parent tubes of diferent degrees cutting welding and jointing with flanges conforming to tables as specified below of BIS: 6392 (latest with upto date ammendments) welded at both ends as per BIS:816 (latest with upto date ammendments) with electrodes confirming to BIS 814 (latest with upto date ammendments) & provided with nuts and bolts BIS: 1369 (latest with upto date ammendments) of required sizes 4 mm thick champion make compressed asbestos fiber gasket or synthetic rubber gasket confirming to BIS:2712 (latest with upto date ammendments) & approved specifications as per site conditions including flushing, cleaning & hydraulic testing complete to the best satisfaction of Engineer-in-charge..(Note:- The rates of providing of flange and butt welding will be paid separately)
Providing welding & fixing of MS flanges cinfirming to IS:6392-1971 (Latest with upto date amendments) and welding of MS Flanges with G.I. Pipes/ MSERW pipes in two layers on both faces to make the joint leak proof (The cost of providing and laying of G.I.Pipes/MSERW Pipes to be measured and paid for separately). The welding of flanges should conform to IS 816-1969 with electrode as per IS : 814-1991 and required number of nuts & bolts conforming to IS: 1364. The thickness of gasket not less than 3.00mm conforming to IS : 2712-1998. The work shall be done as per entire satisfaction of Engineer-in-Charge within all leads and lifts. ( MS Flanges to be welded after 66 metre interval of pipe)
0 to 50 100 mm. Table-5
0 to 970 100 mm. Table-28
970 to 1600 100 mm. Table-17
1600 to 2380 100 mm. Table-5
Providing circumferential butt welding joints GI pipe ( Medium Class) 100,mm dia two layer on each end of welding using 3 mm and 4 mm dia electrodes after levering the pipes ends according to relevant ISI specification and entire satissfaction of the Engineer -in-Charge including all leads and lifts.
0 to 50 100 mm. Table-5
0 to 970 100 mm. Table-28
970 to 1600 100 mm. Table-17
1600 to 2380 100 mm. Table-5
Sanjay Gaur
Sarabjit Singh Katoch
A.K. Traders
SANJAY SAINI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .