Superintending Engineer (EWCL)
Type-IV/3, Transmission Staff Colony Dewa Road, Chinhat Lucknow
Increasing Capacity of 33/11 KV Sub Station Gola Tehsil, Lakhimpur existing from 1x5 MVA to 1x10 MVA
2023_MVVNL_803136_1
06/EWCL/2023-24
Open Tender
Electrical Works
Fixed-rate
90 days
33/11 KV Sub Station Gola Tehsil, Lakhimpur
As per tender documents
2 documents required · 2 mandatory
₹1,180
A/c No. 0758002100009592, IFSC PUNB0586800
₹5,680
30 May 2023
19 May 2023
29 May 2023
19 May 2023
29 May 2023
19 May 2023
Amount
Safe loading, carriage and unloading & proper stacking of following store materials from any Electy. Store of Lucknow Zone to 33/11 KV S/S Gola Tehsil, Lakhimpur site (work site).
33 KV Lightening Arrester
33 KV Single T/F Control Pannel
11 KV 3x300 SQ MM XLPE
MS Angles 75x75x6mm
ACSR Panther Conductor
MS Channel 100x50 mm
11 KV 3x300 SQ MM XLPE Cable Outdoor jointing Kit
11 KV 3x300 SQ MM XLPE Cable Indoor jointing Kit
Dismentaling of old existing 10 MVA transformer from 33 KV T/F Bus bar at switchyard and other related work at 33/11 KV S/S Malkegaon RBL.
Carriage of 10 MVA TF from installed Substation to required site.( carriage from 33/11 KV S/S Malkegaon RBL to 33/11 KV S/S Gola Tehsil Lakhimpur.)
Repairing, Overhauling & centifusing of TF oil of 10 MVA T/F
Erection and installation of 33/11KV 10 MVA T/F in a levelled position of the plinth. The work includes shifting of T/F to the site & installation within the S/S premises, assembling, fixing and fitting of all accessories with required packing and filling of T/F oil upto desired level. Ensuring that there is no leakage and all jumpering & connection & testing are included in the scope of work & at the time of T/F installation,damage plinth of T/F should be maintained by contractor.
Dismantling & safe shifting of existing & working 33/11 KV 05 MVA T/F from plinth to suitable storage place after opening jumper and cable connections as per instruction of Site Engineer.
Earthing for power T/F by way of boring and lowering of 40mm dia, 2.9 mm thick GI Pipe B class from ground upto the water level (minimum 60 feet deep) as per standard practice as per RESPO/REC Drg with making of earth pit of 300x300 mm & 1 feet deep with Cover. (All materials to be provided by Contractor).
Fabrication and grouting (1:4:8) of MS Channel 100x50mm in L Shape & in proper size and alignment to provide support through GI earthing strips (50x6)mm size for power transformer neutral including supply & fixing of flexible copper bonds for neutral earthing as per RESPO Drg. (All decentralised materials to be provided by Contractor).
Fabrication and erection of cable support made of two pieces of MS channel 100x50mm, 3.0 mtr. long joined to each other by means of 5 no. MS Flat 50x6mm pieces of size 150mm long each by welding at equal intervals as per drawing and grouting in block of size 300x300x700mm (1:4:8) complete. This includes providing of required MS Clamp made of MS Flat holding the cable including nuts & bolts and fixing of XLPE cable .(All decentralised materials to be provided by Contractor).
Installation of Lightening Arrestors : Assembling, installation & mounting of 3 No.(1set) L.A. on the L.A Structure/complete with making earth connections (separate) with GI Strip 50x6mm. The work includes fabrication for fixing if required. (All decentralised materials to be provided by Contractor).
Shifting carefully and installation of 33KV Single Transformer Control Panel in Control Room including fixing, bolting & grouting of above as per required and testing, commisioning complete work as per required.
Earthing of 11 KV, 33 KV Switchgears & Equipment: Earthing of 11 KV, 33 KV Switchgears equpiment by lowaring and boring of Chemical Earthing outside of switchyard and connecting through G.I. Strip 50x6mm with indoor/outdoor equipments with making of earth pit of 300x300 mm & 1 feet deep with Cover. (All the material provided by the contractor)
Painting of all structures and equipments with good quality ISI Mark one coat of red oxide primer & two coats of Aluminium Paint. (All materials to be provided by Contractor).
Laying & dressing of 11KV 3x300 Sq.mm XLPE cable from 10 MVA T/F to 11KV incoming Switchgear by excavation of trench in the ground of size 450mm wide, 900mm deep providing 150mm fine sand cushion below the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All decentralised materials to be provided by Contractor).
Hoisting of 11KV XLPE Cable for 11 KV switchgears & 33/11KV T/F of requried size.
Supply and laying of following size Copper Control Cable through underground/cable trench/trenching SGR interlinking through proper connections to T/F Control panel/protection board/Battery and Battery Charger/Bunch joints, Relay 33/11KV T/F junction Box/33KV VCB, CTs etc. as per site conditions:
2x2.5 Sq.mm
4x2.5 Sq.mm
Supply and fixing of Control Cable Trey
Providing & Fixing of Single Core PVC Cable, 1x400/630 sq.mm. & fixing between Transformer incoming 3x300 Sq.mm XLPE Cable and Transformer 11 KV/LV Side Bushing connector for reducing of tension at LV Side Bushing.
M/s Shubham Traders
RAJ ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .