Loading…
Loading…
Tender ID
Tender Value
₹20.3 L
EMD Value
₹20,273
Closing Date
5 Feb 2026, 6:00 pmClosed
Executive Engineer (Electrical)
SR to Providing & Erecting Street light & Related at SRP Gr-12 & Chetak Cammando force, Magodi Dist:- Gandhinagar. ( Civil SR Grant 2025 -26)
265698
NIT-02 (2025-26) Electrical Sr.No.1
Open
Electrical
Works
Gandhinagar
12 documents required · 11 mandatory · 1 optional
₹900
Yes
GUJARAT STATE POLICE HOUSING CORPORATION LTD, Payable at Gandhinagar
₹20,273
Yes
16 Jan 2026
16 Jan 2026
16 Jan 2026
5 Feb 2026
16 Jan 2026
Name of work:- SR to Providing & Erecting Street light & Related at SRP Gr-12 & Chetak Cammando force, Magodi Dist:- Gandhinagar.
( Civil SR Grant 2025 -26)
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
1A Providing & erecting bracket consisting of ISI mark "B" class G.I. Pipe 4.2 cm outside 15.00 Each 487.00 RS: Four
diameter complete with suitable G.I. Sleeve tubing of 2 mm. thick and required size Hundred Eighty
and length suitable for 76.5 / 80 mm. required size of pole top or pipe in pipe surface Seven only
for terrace as per instruction of EIC or wall bracket as per instruction of EIC having
nuts and bolts for fixing the brackets and having spread of Upto 0.70 mtr. length with
suitable rise as per site condition and suitable welded stiffner reducer and nipple with
check nut complete painted with one coat of yellow zinc and two coats of alluminium
paint for Single arm bracket suitable for pole or terrace as per design given by EIC
(a) For single arm bracket. (Jindal / Asian / Tata / Surya Prakash make Only)
(Fabricators:- Bajaj, Valmont, Transrail, Ambica,RR Ispat, Impression Only) (Test
certificate to be submitted)
1B For Double arm bracket. (Jindal / Asian / Tata / Surya Prakash make Only) 5.00 Each 616.00 RS: Six
(Fabricators:- Bajaj, Valmont, Transrail, Ambica,RR Ispat, Impression Only) (Test Hundred Sixteen
certificate to be submitted) only
2 Supplying and making Coil type earthing, coil made from 8 SWG galvanised iron 10.00 Each 369.00 RS: Three
wire with 50 mm OD and 50 turns (length of turns approx. 200 mm) and having Hundred Sixty
additional continuous streight length of 3.00 mtr at open end and should be Nine only
connected to earthing bolt and burried in 1.5 mtr deep specially prepared earth pit
complete with salt and charcoal/coke as required for coil type earthing.(Approx
weight of coil 1.0 to 1.1 Kgs)
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
3 Providing 1:2:4 cement concrete foundation & 70 % PCC from bottom including 10.00 Each 801.00 RS: Eight
excavation for the pole of size 45 x 45 x 100 cm. Deep by farma in below ground Hundred One
level with plinth of 45 cm x 45 cm (or 45 cm dia x 45 cm) high upper ground level only
(20 cms.)with necessary curing, finishing & Colour in approved manner.
( for 4 & 6 mtr pole)
4 Supplying and erecting Galvanized iron pipe post ISI mark 'B' class 88.9 2.00 Each 4397.00 RS: Four
mm. O.D. 6 mtrs. Long duly painted with two coats of alluminium paint and Thousand Three
metallic base plate of 300 x 300 x 4 mm. thick to be erected as a compound Hundred Ninty
light pole with wire entry nipple and earthing bolt. Approximate weight of pole Seven only
47 Kg. within permissible limits as per IS effective length of sections Bottom:
5.5 mtr. having outside dia. 88.9 mm. Top: 0.5 mtrs. having outside dia.
mm. ( ISI test certificate from pipe manufacture &
Class/make/length/O.D/wall thickness/GI/ MS/ Weight test certificate from
pole manufacture shall be submitted) (Jindal / Asian / Tata / Surya Prakash
make only For G.I Pipe)(Fabricators:- Bajaj, Valmont, Transrail, Ambica,RR
Ispat, Impression Only) (Test certificate to be submitted)
5 Supplying & erecting Steel tubular pole (Swaged) confirming to IS - 2713 1.00 Each 8380.00 RS: Eight
(Part-II) 1980. Manufacturing process of steel tubular pole should be as per Thousand Three
IS specification. Basic steel tube should be ISI Marked. Pole should be Hundred Eighty
painted by one coat of Zinc comet Primer and two coat of Aluminium only
/approved paint. Erected on / in existing Foundation. The length of poles are
as below. [a] 9.0 mtr. Long Swaged Steel tubular pole (i) Pole as per IS
code 410-SP-4 with 300 X 300 X 4 mm base plate. (Approximate Pole weight
78 Kg.) For burial erection. (Jindal / Asian / Tata / Surya Prakash make Only)
(Fabricators:- Bajaj, Valmont, Transrail, Ambica,RR Ispat, Impression Only)
(Test certificate to be submitted) (ISI test certificate from pipe manufacture &
Class / make / length / O.D. / wall thickness / GI / MS / Weight test certificate
from pole manufacture shall be submitted)
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
6 Supplying & erecting approved make SMC press moulded composite FRP. loop- 10.00 Each 890.00 RS: Eight
in, loop-out approx. 2mm thick box complete with Bakelite connector strip Hundred Ninty
5way(3P+N+E), DIN rail for mounting mob & hinged doors as per requirement only
having locking arrangements with mounting clamp with nuts, bolts & washers
suitable for erection on pole with cable clamps& earth bolt of following size of box.
7 Providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to 250.00 Each 111.00 RS: One
operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in Hundred Eleven
existing box. confirming to IS 8828/1996 with ISI Mark only
8 Supplying and Erecting of Fabricating terminal box for street light pole 115.00 Each 702.00 RS: Seven
made from 16 G. (1.5 mm.) thick M.S. sheet having following size complete Hundred Two
with fixing arrangement for terminal board, with necessary hole for 4 core 4 only
sq.mm. armoured copper cable entry and exit with 10 mm nipple from the
box. The box shall be provided with cover having up-down movement with
suitable mechanism and hinges on Top and bolting lock at bottom end. The
box shall be fixed by 2 nos.clamps fabricated from 25 x 6 mm flat. The box
shall be powder coated paint or good oil paint inside & outside of the box.
The size of box should be 330 x 260 x 140 mm. (depth). Also Providing and
fixing Terminal board of size 5.0 x 127 x 152.4 mm.bakelite sheet with
suitable brass studs with nuts, washers and clamps of size 25 mm x 3 mm
suitable for pole painted with one coat of red lead paint. (Asian colour must
9 Supplying and erecting "A" class Galvanised iron pipe for following size 50.00 Mtr. 171.00 RS: One
dia. meter having smooth finished bore of the pipe on both ends erected on Hundred Seventy
the face of the wall with clamps, nuts and bolts for laying of cable along the One only
pole / wall shaping the pipe as per site requirement to release cable entry.
10 Providing & Erecting Flexible PVC insulated multistrand multicore 1.1 kv grade ISI 610.00 Mtr. 46.00 RS: Forty
marked copper wires of following size to be erected as directed. 3 core 1.5 sq.mm. Six only
PVC insulated round copper wire ISI mark.
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
11 Providing & Erecting Flexible PVC insulated multistrand multicore 1.1 kv grade ISI 440.00 Mtr. 77.00 RS:
marked copper wires of following size to be erected as directed. 3 core 2.5 sq.mm. Seventy Seven
PVC insulated round copper wire ISI mark. only
12 Providing & fixing 20 mm. dia. PVC insulated G.I. Corrugated Flexible 100.00 Mtr. 31.00 RS: Thirty
pipe with necessary socket, PVC bushes, saddle, Check-nuts etc. complete One only
of following sizes.
13 SITC of Outdoor aesthetically designed LED Street Light Luminaire with total 85.00 Each 3512.00 RS: Three
consumption of Max. 45 W with single piece die cast aluminium housing, high power Thousand Five
LED shall be mounted on high quality metal core PCB with extremely precison Hundred Twelve
designed heat sink complete with IP66 protection Class with polycarbonate / only
thoughened glass cover the fixture should be suitable for pole/bracket mounting. The
fixture to comply both LM79 and LM 80 guidelines with LED module min.
lumen/watt with toughen Glass L70 at 50,000 hrs, provided with high quality
polycarbonate lenses for better light distribution. The watt capacity of Each LED
must be >=4 Watt in street light fitting.The Fixture Should be able to be Pole
Mounted and also bracket mounted, provided with high quality driver for protection
against high and low Voltage cut Off, opertional for high amibient and high humid
envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also the
Fixture should meet the following technical criterias Oprating range Voltage 160 to
270 V, system efficiency >= 110 lm/w, and total lumens not less then 4950, CCT >
5000K, CRI > 65, beam angle 120 deg, surge immunity level at least 4 KV integral
and 10 KV non integral
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
The Separate Potted driver should have over current, over voltage protection,
short circuit protection so that the fixture recovers once the fault is removed.
In addition to the above product should be operational in the temperature
range of 0 deg to 50 deg and humidity range of 10% to 90% RH.(Stricly
sample approved by EIC subject to tender specification) (Note:- The
manufacturer/authorized Channel partner of the manufacturer has to submit 5 yrs
free replcement Guarantee for complete Fixture)(Cool White Color/warm
white/natural white (approved by engineer incharge)
14 SITC of Outdoor aesthetically designed LED Street Light Luminaire with total 25.00 Each 6117.00 RS: Six
consumption of Max. 90 W with single piece die cast aluminium housing, high power Thousand One
LED shall be mounted on high quality metal core PCB with extremely precison Hundred
designed heat sink complete with IP66 protection Class with polycarbonate / Seventeen
thoughened glass cover the fixture should be suitable for pole/bracket mounting. The only
fixture to comply both LM79 and LM 80 guidelines with LED module min.
lumen/watt with toughen Glass L70 at 50,000 hrs, provided with high quality
polycarbonate lenses for better light distribution. The watt capacity of Each LED
must be >=4 Watt in street light fitting.The Fixture Should be able to be Pole
Mounted and also bracket mounted, provided with high quality driver for protection
against high and low Voltage cut Off, opertional for high amibient and high humid
envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also the
Fixture should meet the following technical criterias Oprating range Voltage 160 to
270 V, system efficiency >= 110 lm/w, and total lumens not less then 9900, CCT >
5000K, CRI > 65, beam angle 120 deg, surge immunity level at least 4 KV integral
and 10 KV non integral
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
The Separate Potted driver should have over current, over voltage protection,
short circuit protection so that the fixture recovers once the fault is removed.
In addition to the above product should be operational in the temperature
range of 0 deg to 50 deg and humidity range of 10% to 90% RH.(Stricly
sample approved by EIC subject to tender specification) (Note:- The
manufacturer/authorized Channel partner of the manufacturer has to submit 5 yrs
free replcement Guarantee for complete Fixture)(Cool White Color/warm
white/natural white (approved by engineer incharge)
15 SITC of Outdoor aesthetically designed LED Flood Light Luminaire with 20.00 Each 6228.00 RS: Six
total consumption of Max. 90 W with broad single piece die cast aluminium Thousand Two
housing of broad size for better thermal managment (Appr.by EIC) , LED's Hundred Twenty
mounted on high quality metal core PCB with extremely precison designed Eight only
heat sink complete with IP66 protection Class with polycarbonate / Toughned
glass cover. the fixture should be suitable for pole/bracket mounting. The
fixture to comply both LM79 and LM 80 guidelines with high power LED
module min. 130lumen/watt with toughen Glass L70 at 50,000 hrs, provided
with individual high quality polycarbonate lenses for better light distribution.
The Fixture Should be able to be Pole Mounted and also bracket mounted,
provided with high quality driver for protection against mis Wiring,over voltage
high and low Voltage cut Off, opertional for high amibient and high humid
envirnoments, THD of driver should be less than 10% and P.F > 0.95. Also
the Fixture should meet the following technical criterias Oprating range
Voltage 160 to 270 V, system efficiency > 110 lm/w,Operation current 700ma,
and Lumen Output of mini. 9900 Lumes, CCT > 5000K, CRI > 65, seperate
high quality lense,beam angle 120 deg, surge immunity level at least 10 KV
non integral & 4 KV intrgral
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
The Sperate Potted driver should have over current, short circuit protection
so that the fixture recovers once the fault is removed, over voltage protection.
In addition to the above product should be operational in the temperature
range of 0 deg to 50 deg and humidity range of 10% to 90% RH. [Note:-The
manufacturer / authorised Channel partner of the manufacturer has to submit
5 yr free replcement Guarantee for complete Fixture] Model approved by
Engineer in Charge subject to above Specification.[Approval will be given
strictly subject to item specification]
16 SITC of Heavy duty High mast Outdoor aesthetically designed LED 16.00 Each 10911.00 RS: Ten
Flood Light Luminaire with total consumption of Max. 240 W with broad Thousand Nine
single piece die cast aluminium housing of broad size for better thermal Hundred Eleven
managment (Appr.by EIC) , LED's mounted on high quality metal core PCB only
with extremely precison designed heat sink complete with IP66 protection
Class with polycarbonate / Toughned glass cover. the fixture should be
suitable for pole/bracket mounting. The fixture to comply both LM79 and LM
80 guidelines with high power LED module min. 130lumen/watt with toughen
Glass L70 at 50,000 hrs, provided with individual high quality polycarbonate
lenses for better light distribution. The Fixture Should be able to be Pole
Mounted and also bracket mounted, provided with high quality driver for
protection against mis Wiring,over voltage high and low Voltage cut Off,
opertional for high amibient and high humid envirnoments, THD of driver
should be less than 10% and P.F > 0.95. Also the Fixture should meet the
following technical criterias Oprating range Voltage 160 to 270 V, system
efficiency > 110 lm/w,Operation current 700ma, and Lumen Output of mini.
26400 Lumes, CCT > 5000K, CRI > 65, seperate high quality lense,beam
angle 120 deg, surge immunity level at least 10 KV non integral & 4 KV
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
The Sperate Potted driver should have over current, short circuit protection
so that the fixture recovers once the fault is removed, over voltage protection.
In addition to the above product should be operational in the temperature
range of 0 deg to 50 deg and humidity range of 10% to 90% RH. [Note:-The
manufacturer / authorised Channel partner of the manufacturer has to submit
5 yr free replcement Guarantee for complete Fixture] Model approved by
Engineer in Charge subject to above Specification.[Approval will be given
strictly subject to item specification]
17A Painting of street light pole with bracket complete with one coat of zinc 150.00 Each 263.00 RS: Two
coat & two coats of Aluminium paint for following size of pole.[a] up to 6 mtr. Hundred Sixty
17B up to 9 mtr 50.00 Each 332.00 RS: Three
18A Providing & fixing double compressed heavy duty flange type brass cable 250.00 Each 43.00 RS: Forty
gland with rubber ring for P V C insulated armoured cable complete with Three only
outgoing tails, insulating tape etc. For following size cables. For 2 to 4 core x
2.5/4.0 Sq. mm (Sigma, MCI, Comet Make Only)
18B 2 to 4 core 10 Sq. mm 10.00 Each 48.00 RS: Forty
18C 2 to 4 core x 25.0 mm2 8.00 Each 61.00 RS: Sixty
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
19A Providing & erecting XLPE (IS : 7098) (I)-88 ISI marked armoured Copper 100.00 Mtr. 269.00 RS: Two
cable for 1100 volt to be laid 90 cms. Under ground or to be laid 90 cms. Hundred Sixty
Under ground or to be laid on wall with suitable G.I. heavy guage 1.0 mm Nine only
thick cable clamp or in existing DWC pipe underground or road crossing or
floor of following size of cables. (a) For 4 core x 2.5 mm2
19B For 4 core x 4.0 mm2 750.00 Mtr. 361.00 RS: Three
19C For 3core x 10.0 mm2 100.00 Mtr. 495.00 RS: Four
20 Providing & erecting approved make XLPE (IS:7098) (I)-88 ISI mark 380.00 Mtr. 189.00 RS: One
armoured multistrand Aluminium Cable 1100 volt to be laid 90 cms. Hundred Eighty
Under ground or to be laid on wall with 1.0 mm thick G.I. heavy guage cable Nine only
clamp or in existing DWC pipe underground or road crossing or floor of
following size of cables.(a) For 4 core x 25.0 mm2
21A Providing & fixing Solderless crimping type Copper lugs conforming to IS suitable 1150.00 Each 8.00 RS: Eight
for cable of following size evenly crimped with high pressure tool & connected to only
switchgear terminals with brass/cadmium plated nut bolts in an approved manner. (
Dowells,HMI, Comet Make Only ) [a] 1.5/2.5 to 6 Sq.mm
21B For 10.00Sq.mm 40.00 Each 10.00 RS: Ten
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
22 Providing & fixing Solderless crimping type Aluminium lugs conforming to 32.00 Each 15.00 RS: Fifteen
IS suitable for cable of following size evenly crimped with high pressure tool & only
connected to switchgear terminals with brass/cadmium plated nut bolts in an
approved manner. ( Dowells,HMI, Comet Make Only ) 25 Sq.mm.
23 Providing & laying HDPE Double walled corrugated pipes (DWC) (conforming to 1050.00 Mtr. 117.00 RS: One
IS: 16205 (part 24) 2018)) with minimum load required of 450N capacity with anti Hundred
rodent and ultra violet material properties with necessary connecting accessories of Seventeen
same material at required depth to be laid 90 cms. under ground for laying of cable only
below ground / road surface for enclosing cable and back filling the same to make
ground as per original. (A) For Outer dia. 50 mm and Inner dia. 38 mm. ) (Test
Certificate to be Submitted)
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
24 Providing, erecting, testing and commissioning insu intelligent street light 2.00 Each 20255.00 RS: Twenty
controller specially designed for energy saving in conventional street light Thousand Two
system (Cat. No. SLC-03-1 ph-15 KVA-20 Amp. per phase) having technical Hundred Fifty Five
specification, 1 phase, 2 wire, 230 V AC/ph, +/- 25% R Y B N 2 wire supply only
system, 50 Hz (+/- 10%) 2 W (Stand BY) to 4 W (at street light operation)
consumption, Advance 8 bit micro controller, switching on longitude and
latitude base, accuracy of +/- 1 minute per month, with in built battery, with
battery life of more than 8 years, with special device which hold the
parameter for more than 10 year without any power and password protected.
16 characters and two line LCD display with backlight, 4 keys user friendly
keyboard system, 7500/15000 VA feeder pillar capacity, 63/100 Amps
isolator, 3 output with termination, 40/63 Amps 2/3 pole contactor, 3 X
Amp., with FR cable provision to by pass by way of relay operation through
auto/manual switch, 2 to 55 centigrade and humidity 90 % non condensing,
Out door type installation on pole with clamps (Provided with clamps and nut
bolt) or wall or floor, Three locking system flush type internal panel lock,
external pad lock and internal U clamp locking systems for against theft of
Panel, having 25 Kg weight, 16 Gauge MS weather proof box with industrial
exterior powder coated with 7 tank process RAL 7035.Electrical wiring and
control panel for high mast systems motor with up and down facility with
upper and lower limit input. (High and low limit switch and motorized systems
is to be provided with high mast and cable terminated to terminal strip.)
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
25 Supplying and erecting Servo Controlled Voltage Stabilizer (SCVS) as per 3.00 Each 64803.00 RS: Sixty Four
following requirement: (1) Input Voltage Range - Three Phase 340 To 480 Thousand Eight
Volt AC. (2) Out put Volatge-Three Phase 415 Volt AC (Line - Line) with Hundred Three
Voltage Regulation of +/-1%. (3) Frequency range -47 Hz To 63 Hz. (4) only
Efficiency - More or equal to 98%. (5) Type of Stabilizer-Suitable for Balance
& Unbalance Load and Voltage including SPD (6) Controlled Type - Digital
Micro Controller Based Disply. (7) Rate Of Correction - Upto 100 Volt/Sec
(Line - Line) (8) Servo Motor Drive - AC Syncronous Stepper Motor - As per
KVA Capacity, Out put volatge and Voltage regulation requirement. (9) Nil
Wave form Distortion and Effect of Load Power. (10) Responce Time -
milli second. (11) Protection requirements - Input low Cut off protection/Input
High Cut Off Protection /Output Low Cut Off protection/lOutput High
(12) Fault Annuciation Panel LED shows Input present, Input high Input low,
Output Normal, Output High, Outpur low, Overload. (13) Output On time
delay-10 seconds (14) Ambient Tempeature capacity-0-45 RH upto 90%. (15)
Enclosure Type - IP 20 (16) Type of Cooling - Air (17) cabinet/Enclosure :
Cabinet must be made from 1.8mm thick CRCA sheet, Output: Bypass
switch with changeover switch and Provied SPD & 5 year free replacement
guarantee on Stamp paper. Loading and unloading of above item shall be
done by hydra and skill work force under supervision of electrical engineer
and guidelines given by manufacturer to avoid damage to the item. Picture of
it to be submitted in running bill / final bill.Size of door and Ele. room/Pump
room shall be checked by agency's engineer before giving order. giving
order.If found any problem in size discuss with GSPHCL engineer for
rectification before.
(Make - Servomax,Fuji,Krykard,ProtkG)(A) For 15 KVA
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
26 Supplying & erecting IP 55 grade following size section pillar fabricated from 1.00 Each 4531.00 RS: Four
joint less M.S. Sheet with angle iron legs made from jointless M.S. Angle with Thousand Five
cable clamps to be buried in ground to have appropriate erection to work Hundred Thirty
uniform until erected with cement concrete foundation and 45 cm high bricks One only
work finishing with plaster etc. hinged double door internally supported on
both side, with internal and outside looking arrangement with look and keys in
duplicate 35 x 35 x 5 mm M.S. Angle of Two Nos. one is welded and other
with nut and bolt for erecting Bakelite sheet. Painting the Section Pillar inside
and out side with seven tank powder coated paint. section pillar roof should
be without joint with water leakage proof & tested as per IP 55 test & followed
by IS 2147 of 1962 with 4 nos. 100 Amp Copper Busbar (A) 75 X 60 X
cm section pillar fabricated from 16 Gauge MS Sheet with angle iron legs
45 cm long made from 35 X 35 X 5 mm thick MS angle.
27 Providing & erecting approved make ATS panel suitable for following size of 1.00 Each 39831.00 RS: Thirty Nine
3 phase, 415 V., 50 cycles, A.C. diesel generating set complete of scope as Thousand Eight
detailed below: Hundred Thirty
1) Power module: Motorised Changeover switch with ATS controller, One only
Auxiliary contactor with NO & NC contacts with Automatic Battery Charger,
indicating lamps for Generator ON, Mains ON, Load and suitable control
terminals and power terminals with neutral earthing studs.(A) ATS Panel for
15/20 / 25 KVA 3 phase DG Set(make: HPL,socomac, Schnider,Elmeasure)
28 Providing & erecting 240 V MCB double pole switch for motor & inductive 10.00 Each 327.00 RS: Three
load (C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in Hundred Twenty
existing box having following capacity (A) 40 Amp. Seven only
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
29 Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C 4.00 Each 590.00 RS: Five
Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box Hundred Ninty
having following capacity (a) 6 to 32 Amp. only
30A Supplying & fixing box for housing RCCB + MCB combination made of 18 4.00 Each 272.00 RS: Two
SWG sheet steel duly powder coated with gasket, dust & vermin proof Hundred Seventy
bakelite shield two earthing terminals for following type of RCCB, RCCB + Two only
MCB(a) [a] For 2 pole
30B For 4 Pole 4.00 Each 442.00 RS: Four
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
31 Providing ad erecting approved make single phase Double Door metal clad 1.00 Each 1478.00 RS: One
D.B. as per relevant indian standards ammended upto date. Supplying and Thousand Four
fixing following way single phase MCB distrubution board of company Hundred Seventy
fabricated with sheet box with powder coated inside and outside after apply Eight only
seven tank chemical process of MCBDB Door, Back side & Body must be
made of 1.2 mm thick CRCA sheet cover complete with suitable integral
single piece construction tinned copper busbar and link with all necessary
interconnection and with necessary size MS frame for mounting MCBDB.
Manufacturer must be provided (1) IP 43 and as per IS:8623-1 & 3, IEC
61439-1 & 3 having D type PU gasket. (2) Seven tank Powder coating
Certificate (3) Tinned Copper/Brass make neutral & Earthing link with
isolation & Protecting Cover for 240 Volts on surface / recess complete with
loose wire box, terminal connectors for all incoming and outgoing circuits,
with suitable size FRLS PVC insulated copper conductor up to terminal blocks
and internal connection, tinned coppper bus bar, 1 no. tinned copper neutral
link, tinned copper earth bar, din bar, detachable gland plate,
interconnections, powder painted including earthing etc.Single phase
incoming and horizontal single phase outgoing. For 12 Way MCBDB
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
32 Providing & Erecting 2.0 mtr long Earthing system by making minimum 3.00 Each 7025.00 RS: Seven
bore of 225 mm dia in soft soil. Suitable for doing pipe-in-pipe technology Thousand
earthing.Earthing electric rod must be made from Corrosion free Hot dip Twenty Five
galvanizing pipes having following specification. only
(A) Earthing Electrode: outerpipe:- 88 mm minimum O.D., ISI 'B ' Class ISI
mark of Reputed Brand, Inner pipe:- 42 mm minimum O.D., Pipe B Class ISI
mark reputed Brand Terminal Size: 70mm X 100mm length, Terminal Should
be made from inner pipe for that pipe must be pressed and gave rectangular
shape so its work as a terminal.The hot deep galvanising must be done after
above process.Galvanised thickness must be minimum 75 micron any where.
SS Nut bolt:- 2 no.with washer suitable for 14mm dia. hole must be provided
at terminal. total minimum Weight(approx.) of earth electrodewith inside
conductive material minimum should be 26 kg.
(B) Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm/meter testing as
per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar
(C) Back fill Compound:- Earthing compound should be capable to retain
moisture for long time Back Filling Compound weight is 25 Kg.
(D) Chamber and cover:- Earthing chamber should be size of 400 mm X
mm X 400 mm depth and Cover should be heavy duty cast iron with required
size of 300 mm X 300 mm X 4 mm thick.
Necessary test report must be submitted.
1. Short circuit test by ERDA/ CPRI for 25KA
2. Resistivity test of conducting material from NABL accredited lab.
3. Hot dip galvanised / zinc coating micro test from reputed laboratory.
4. General test report from OEM regarding specification of earthing.
[Make and model approved by EIC Strictly subject to item specification only]
[OEM has to submit all detail & sample for approved before supplying]
[Water must be poured in bore before starting earthing. Earthing value must
be measured with earth tester. Agency has to bring the earth resistance to at
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
33A Providing & erecting Mains with ISI marked, 1.1 KV grade electrolyte multi 50.00 Mtr. 27.00 RS: Twenty
stranded, annealed copper conductor with heat resistant PVC insulated Seven only
conforms to IS:694, IEC - 227 erected in existing pipe of following size
(Specifically for control panel, relays, power switchgears, motor starters &
control wiring) with required size of copper lugs, S/S nuts and bolts . (a) One
wire 2.50 sq. mm
33B One wire 4.00 sq. mm 250.00 Mtr. 37.00 RS: Thirty
33C One wire 6.00 sq. mm 25.00 Mtr. 56.00 RS: Fifty Six
33D One wire 16.00 sq. mm 50.00 Mtr. 141.00 RS: One
34 Providing, erecting, fabricating the M.S. structure as per requirement of 150.00 Kg 75.12 RS:
site as per structure design Including proper size approved by EIC of M.S. Seventy Five and
angles, flats, bars, square pipe, channels, sections (Tata, Jindal, Asian, JSI Paise Twelve
Make) complete with cutting, welding, grinding and finishing duly painted with only
Asian/Nerolac make premium quality oil paint and true care red oxide metal
primer,asian paint make with erection on site as per direction of engineer in
charge with necessary grouting cementing, plastering and finishing complete.
All hole opening of square pipe end must be closed with M.S plate welding.
Payment will be done on KG as per Actual weight.
Item Description Rate Amount
No. Quantity Unit
In Figure In Words
35 Supplying & erecting 12 mm thick Hylum sheet on existing 25 x 25 x 3 mm 2.00 Sq. 2289.00 RS: Two
red oxide painted angle iron frame suitable for fixing ICDP / ICTP / DPMCB / Mtr. Thousand Two
FPMCB SWITCH and energy meter (contractor shall make approved drawing Hundred Eighty
of Hylum sheet to arrange required No. of Energy meter & ICDP / ICTP / Nine only
DPMCB / FPMCB switch-busbar etc. as per Actual space available in
electrical room at site)
36 Drilling the road without breaking the road surface (Asphalt) for laying of 80.00 Mtr. 488.00 RS: Four
cable for feeding power supply by making up to following size of holes at both Hundred Eighty
ends complete. (A) Up to 100 mm bore dia Eight only
37 Locating Underground Cable Fault of Underground Cable including 5.00 Job. 6780.00 RS: Six
digging,pin pointing with cable route tracker bu using cable fault location Thousand Seven
equipment like cable fault Van/Vehicle with supportive meters and Hundred Eighty
accessories & doing high pressure testing of cable for checking healthiness only
of cable with suitable equipment after jointing of the faulty cable (excluding
jointing kit) with report of showing distance from main source approx.(a) LT
Cable 35 sq.mm and above
38 Disconnecting the cable connection and Providing straight joint with PVC 8.00 Each 1073.00 RS: One
mould using heat shrink /cast resin type epoxy compound Insulating material Thousand
and making the joint complete using necessary in line connectors, hardener, Seventy Three
earth continuity connection, spacers etc. and reconnecting the same & only
ensure the joint resistance within the limits as per IS.(A) up to 25 Sq mm
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Document
Schedule- B Magodi.pdf
ELE3 specifications Booklet.pdf
16.01.2026 N.I.T. ele 2025-26 no-2.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .