Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.2 LAccepted-AOC | L1 | Accepted-AOC lowest bidder |
| Sl No | Description | Qty | Unit | All Star Electricals L1 |
|---|---|---|---|---|
| 1.00Providing e- office system in the taluk office fort kochi | ||||
| 1.00 | OD278486/2024-2025:Supply installation testing and commissioning of 10KVA UPS with 65AH 20 nos SMF battery 60minite backup a) 3 ph to 3 ph b) Input pf : 0.99 @ full load c) Output pf : 1 d) Input voltage range : 305V -485V with cut off e) THD : ≤ 3% f) Overall Efficiency : ≥94% g) Ambient Temperature : 0-40°C h) Generator Compatibility) Pure sine wave j) Battery over charge & under charge cut off. k) 3 year warranty. l) Bypass arrangement. m) Indications : Digital indications of Input V & A, output V & A, Battery charge, Temperature m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : Exide / equivalent ,UPS : Supra/Hykon/GE/legrand /equivalent | 1 | each | 5,00,000 ₹5,00,000 Lowest |
| 1.00 | 90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) | 1 | each | 7,000 ₹7,000 Lowest |
| 1.00 | OD278487/2024-2025:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required.FP enclosure for independent mounting of MCB/ RCCB/ RCBO | 1 | each | 600 ₹600 Lowest |
| 1.00 | 90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43) | 3 | each | 4,500 ₹13,500 Lowest |
| 1.00 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 5 | each | 1,000 ₹5,000 Lowest |
| 1.01 | 2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole | 4 | each | 1,000 ₹4,000 Lowest |
| 1.01 | OD278504/2024-2025:
Supply and installation of the 40 A and 63 A, 10 kA, TP MCB (C curve) suitable for 50 Hz , AC supply conforming to IS 8828-1995/ IEC 60898 of the following current ratings in the existing enclosure and giving connections as required | 1 | each | 1,500 ₹1,500 Lowest |
| 1.01 | 2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole | 22 | each | 250 ₹5,500 Lowest |
| 1.01 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. | 22 | each | 5 ₹110 Lowest |
Tender Value
₹7.3 L
EMD Value
₹18,371
Closing Date
3 Jun 2025, 11:30 amClosed
Assistant Executive Engineer
PWD Electrical Subdivision Ernakulam
General Electrical work
2025_PWD_758122_2
ESDE(ET)-02/AEE/2025-26
Open Tender
Electrical Works
Item Rate
180 days
Ernakulam
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,620
₹18,371
18 Aug 2025
28 May 2025
5 Jun 2025
28 May 2025
3 Jun 2025
28 May 2025
Amount
Providing e- office system in the taluk office fort kochi
OD278486/2024-2025:Supply installation testing and commissioning of 10KVA UPS with 65AH 20 nos SMF battery 60minite backup a) 3 ph to 3 ph b) Input pf : 0.99 @ full load c) Output pf : 1 d) Input voltage range : 305V -485V with cut off e) THD : ≤ 3% f) Overall Efficiency : ≥94% g) Ambient Temperature : 0-40°C h) Generator Compatibility) Pure sine wave j) Battery over charge & under charge cut off. k) 3 year warranty. l) Bypass arrangement. m) Indications : Digital indications of Input V & A, output V & A, Battery charge, Temperature m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : Exide / equivalent ,UPS : Supra/Hykon/GE/legrand /equivalent
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
OD278487/2024-2025:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required.FP enclosure for independent mounting of MCB/ RCCB/ RCBO
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD278504/2024-2025: Supply and installation of the 40 A and 63 A, 10 kA, TP MCB (C curve) suitable for 50 Hz , AC supply conforming to IS 8828-1995/ IEC 60898 of the following current ratings in the existing enclosure and giving connections as required
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.14:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.8 module mounting box
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.6.4.54:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD278481/2024-2025:Supply and providing earth lead from the test joint to the earth electrode using the 3.15 mm bare copper conductor (10 SWG) conductors including cutting, and fixing firmly with plate test joint etc as required.
OD278482/2024-2025:Supply and fixing 2 x 25mm X 3 mm copper strip test joint for the earthing system.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD278506/2024-2025:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required 12 x 3 mm, 25 x 3 mm brass bolt & nut
Bidder Name
All Star Electricals
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1249765.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .