Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.0 LAccepted-AOC | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹38.9 L+₹57,955 (1.51%)Rejected-AOC FLAT NO S 4 DOOR NO 10 4 107 17 SRINIVASA TOWERS SRI RAMNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L2 | Rejected-AOC Not being L1 | |
| 3 | L3₹49.9 L+₹11.6 L (30.3%)Rejected-AOC 38 41 28 104 AREA INDUSTRIAL ESTATE VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | L3 | Rejected-AOC Not being L1 |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
28 Nov 2023, 6:00 pmClosed
Garrison Engineer Naval Depot
Garrison Engineer Naval Depot Industrial Estate Post 104 Area Visakhapatnam 530007
REPAIRS MAINTENANCE OF INTERNAL WIRING DBs SUBMAIN WIRING FITTINGS AND FIXTURES AT INS DEGA DEGA VIHAR AND INS EKSILA UNDER AGE E M OF GE ND VISAKHAPATNAM
2023_MES_624089_1
8303GEND
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
VISAKHAPATNAM
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE ND VISAKHAPATNAM
₹96,000
6 May 2024
19 Oct 2023
4 Dec 2023
19 Oct 2023
28 Nov 2023
9 Nov 2023
Amount
The rates quoted by the tenderer shall deemed to be inclusive for the following provisions in addition to the other conditions specified in the tender documents. No claim whatsoever shall be entertained at a later date on this account:- [i] The repairs shall be done by skilled workmen in the relevant field to the entire satisfaction of Engineer-in-Charge. The contractor shall engage sufficient manpower for the entire period so that progress of work shall not be hampered due to non availability of labour at any time. [ii] The contractor on getting information through Site order / Works diary regarding the nature of repair to be carried out, he shall immediately respond to the same and make all out efforts to carry out the same on priority within 48 hours. In case of any delay in responding / attending the repairs within 48 hours, the GE may at his absolute discretion impose penalty on the contractor at Rs. 100/- per day per each work ordered upto 05(Five) days and Rs. 200/- per day thereafter till completion of the work in case of delay without valid reasons as decided by GE. [iii] Further, the above penalty is applicable even for the multiple locations of work at the same period. It is the responsibility of contractor to make suitable arrangements for attending the repairs simultaneously at all the places. [iv] The decision of the GE as to whether a particular repair has been attended or not on a particular day will be final and binding. The above penalty shall be in addition to the provisions made in clause 50 of IAFW-2249 i.e (Compensation for delay in completion of work). (v)
M & L for Point wiring with PVC insulated unsheathed multistranded copper conductor cable FRLS grade of size 1.5 Sqmm (nominal area) 1100V grade drawn through and including PVC conduit of size 20mm dia medium grade (surface/ concealed) including accessories fixed on wall/floor/roof, etc including provision of 2.0mm thick prefabricated galvanised boxes white modular cover plate and frame of suitable size for fixing modular switches, sockets, regulator, etc including provision of PVC insulated, unsheathed multistranded copper conductor FRLS grade of size 1.5 Sqmm as earth continuity conductor and connecting to common earth dolly suitable for One light / fan point / Bell point controlled by one switch including taking down old point wiring with fittings & fixtures complete all as specified and directed. [Note: Quoted rate is deemed to be inclusive for necessary cutting chases in walls / floors / ceiling of any description, pinning in making good to disturbed surfaces where required and pointing in cement mortar 1:3 and finished to match with existing finishes complete]
All as per item No. 2 above but suitable for one 5 Amps socket point on independent board complete all as specified and directed.
All as per item No. 2 above but suitable for one 5 Amps socket point on same board complete all as specified and directed
All as per item No. 2 above but point wiring with 4.0 Sqmm (nominal area) suitable for one power socket point on independent board complete all as specified and directed.
M & L for Point wiring with FRLS grade PVC insulated unsheathed multistranded copper conductor cable 1.5 Sqmm (nominal area) 1100V grade drawn through and including stove enamelled steel conduit of size not less than 25mm dia including accessories fixed on wall/floor/roof, etc with MS terminal boxes made out of 2.0mm thick mild steel sheet including provision of FRLS grade insulated, unsheathed multistranded copper conductor of size 1.5 Sqmm as earth continuity conductor and connecting to common earth dolly suitable for flame proof switches/sockets of any type for One light / fan point / Bell / 5A socket point controlled by one, one way switch including taking down old point wiring with fittings & fixtures and making good to the disturbed surfaces of wall / ceiling to match with existing finishes complete all as specified and directed.
All as per item No. 6 above but point wiring with 4.0 Sqmm (nominal area) suitable for one flame prrof 15/16 Amps switch socket point on independent board complete all as specified and directed.
M & L for Point wiring with PVC insulated unsheathed multistranded copper conductor cable FRLS grade of size 1.5 Sqmm (nominal area) 1100V grade drawn through EXISTING PVC conduit of size 20mm dia medium grade (surface/ concealed) including accessories fixed on wall/floor/roof, etc including provision of 2.0mm thick prefabricated galvanised boxes white modular cover plate and frame of suitable size for fixing modular switches, sockets, regulator, etc including provision of PVC insulated, unsheathed multistranded copper conductor FRLS grade of size 1.5 Sqmm as earth continuity conductor and connecting to common earth dolly suitable for One light / fan point / Bell point controlled by one switch including taking down old point wiring with fittings & fixtures complete all as specified and directed. [Note: Quoted rate is deemed to be inclusive for necessary cutting chases in walls / floors / ceiling of any description, pinning in making good to disturbed surfaces where required and pointing in cement mortar 1:3 and finished to match with existing finishes complete]
All as per item No. 8 above but point wiring with 4.0 Sqmm (nominal area) suitable for one power socket point on independent board complete all as specified and directed.
S & F modular switch 1 way, 6 Amps, 1 module, single pole complete all as specified and directed.
S & F modular switch 1 way, 16 Amps, 1 module single pole complete all as specified and directed.
S & F modular socket outlet, 6 Amps, 2/3 pin combined 2 module 230 volts multipurpose complete all as specified and directed.
S & F modular socket outlet, 6/16 Amps, 2/3 pin combined 2 module, 230 volts multipurpose complete all as specified and directed.
S & F modular fan regulator, 120W, 2 module/ 1 module, step type, complete all as specified and directed.
S & F ceiling rose, surface bakelite, 65X30 mm with 3 terminals, complete all as specified and directed
S & F in repairs Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth complete all as specified and directed
S & F in repairs Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and directed
S & F in repairs switch piano flush type , 5 Amp, 240 Volts single pole one way complete all as specified and as directed.
S & F in repairs switch Socket combination 2in 1, 5 Amp flush type , complete all as specified and as directed.
S & F in repairs Switch piano, 15 Amp 240 volt,single pole 1 way, flush type , complete all as specified and as directed.
S & F in repairs switch Socket combination 5 in 1, 5/15 Amp flush type , complete all as specified and as directed.
S & F in repairs Fan regulator electronic type, rotary step, 240 volts , complete all as specified and as directed.
S & F in repairs Switch piano, flush type, single pole, two way 5 Amp, complete all as specified and as directed.
S & F in repairs Bell push , flush type , 5 Amp, complete all as specified and as directed.
S & F in repairs Buzzer ding dong, AC 230 Volts, Single polep, complete all as specified and as directed.
S & F LED tube light fittings, retro bar professional WH 5700K to 6200K and minimum 1800 to 2000 lumens of warm/cool white comprising of batten with all accessories internally prewired and connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F LED tube light fittings, 2 feet long of 900 to 1000 lumens of cool white wall mounted batten with all accessories internally prewired and connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F Square recessed mounted LED light (1'x1') of minimum 1500 Lumens with warm/cool white with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F Square recessed mounted LED light (2'x2') of minimum 3600 Lumens with warm/cool white with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F in repairs Square recessed mounted LED light of round type for Ceiling cutout: Ø 160 mm, height 16 mm, minimum 1200 Lumens (12 Watt) warm/cool day light with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size complete all as specified and as directed .
S & F in repairs Square recessed mounted LED light of round type for Ceiling cutout: Ø 210 mm, height 16 mm, minimum 1800 Lumens (18 Watt) warm/cool day light with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size complete all as specified and as directed .
S & F in repairs Square recessed mounted LED light of round type for Ceiling cutout: Ø 210 mm, height 16 mm, minimum 600/900 Lumens (6/9 Watt) warm/cool day light with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size complete all as specified and as directed .
S & F flood light 9000 to 10000 lumens (100 W) new generation LED LED warm/cool daylight with high luminous efficacy, Pressure die cast aluminium housing IP 66 protection, front toughened glass, energy saving with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F highbay light 12000 lumens (120 W) new generation LED warm/cool daylight with high luminous efficacy, Pressure die cast aluminium housing IP 66 protection, front toughened glass, energy saving with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F highbay light 15000 (150 W) lumens new generation LEDLED warm/cool daylight with high luminous efficacy, Pressure die cast aluminium housing IP 66 protection, front toughened glass, energy saving with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F Building Security light LED type of minimum 3000 Lumens (35W) Pressure die cast aluminium housing IP 66 protection with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including bracket made of 40mm dia GI light grade pipe of 1.2m long bent to shape fixed with suitable MS clamps, bolts, nuts and washers duly painted including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge.
S & F in repairs LED bulb 7 watts non dimmable pin type with modular angular holder complete all as directed
S & F CMRI certified flame proof Weather proof LED tube light fittings of not less than 4000 lumens output, 5700K, PF>0.95 with pressure die cast aluminium housing IP-65 protection heat resistance toughened glass cover, electronic driver with all accessories internally prewired connecting with flexible copper conductor of size 1.5 Sqmm including taking down existing light fittings complete all as directed.
S & F CMRI certified flame proof Weather proof LED bulk head fittings of not less than 4000 lumens output, 5700K, PF>0.95 with pressure die cast aluminium housing IP-65 protection heat resistance toughened glass cover, electronic driver with all accessories internally prewired connecting with flexible copper conductor of size 1.5 Sqmm including taking down existing light fittings complete all as directed.
Taking down existing ceiling fan of any type and sweep from any position and refixing the same in original / new location after necessary servicing, cleaning for dust, grease including replacement of minor spares such as bushes, bearings, canopy, capacitors 2.5 mfd, fan clamps etc as required at site and applying two coats of synthetic enamel paint (spray painting) including filling the cavities with filler and writing MES Nos on the fans complete all as specified and directed by the Engineer-in-Charge. [Note: Quoted rate is deemed to be inclusive for writing MES Nos on the fans]
M & L for removing defective / burnt out winding of ceiling fans of any capacity and rewinding with super enamelled copper winding wire of suitable size including replacement of insulating materials such as laminated lethroid paper, sleeves and varnishing complete all as specified and directed .
Taking down existing Exhaust fan/Air circulator/Pedestal Fan of any type and sweep from any position and refixing the same in new / old position after necessary over hauling / servicing and cleaning for dust, grease including replacement of minor spares such as bushes, bearings, capacitors 4.0 mfd, etc as required at site and applying two coats of synthetic enamel paint (spray painting) including filling the cavities with filler and writing MES Nos on the fans complete all as specified and directed by the Engineer-in-Charge. [Note: Quoted rate is deemed to be inclusive for writing MES Nos on the fans]
M & L for removing defective / burnt out winding of Exhaust fan/Air circulator/Pedestal Fan upto 380mm sweep and rewinding with super enamelled copper winding wire of suitable size including replacement of insulating materials such as laminated lethroid paper, sleeves and varnishing complete all as specified and directed by the Engineer-in-Charge.
M & L for removing defective / burnt out winding of Exhaust fan/Air circulator/Pedestal Fan 450mm & 600mm sweep and rewinding with super enamelled copper winding wire of suitable size including replacement of insulating materials such as laminated lethroid paper, sleeves and varnishing complete all as specified and directed by the Engineer-in-Charge.
S F in repairs MCCB, 4 Pole, 63 Amps, 415 Volts, 50Hz of breaking capacity 16 KA with all necessary aluminium lugs and glands, etc complete all as directed
S F in repairs MCCB, 4 Pole, 100 Amps, 415 Volts, 50Hz of breaking capacity 16 KA with all necessary aluminium lugs and glands, etc complete all as directed
S F in repairs MCCB, 4 Pole, 125 Amps, 415 Volts, 50Hz of breaking capacity 16 KA with adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as directed
S F in repairs MCCB, 4 Pole, 160 Amps, 415 Volts, 50Hz of breaking capacity 36 KA with adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as directed
S F in repairs MCCB, 4 Pole, 200/250 Amps, 415 Volts, 50Hz of breaking capacity 36 KA with adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as directed
S F in repairs MCCB, 4 Pole, 400 Amps, 415 Volts, 50Hz of breaking capacity 36 KA with adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as directed
S & F in repairs factory made sheet metal enclosure double door VTPN DBs (fixed flush to the wall) with provision for MCCB, 160 Amps as incomer and outgoing as TPN, 8 way, 415 Volts, IP-43 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed. [Note: MCCB shall be measured and paid seperately]
S & F in repairs factory made sheet metal enclosure double door VTPN DBs (fixed flush to the wall) with provision for MCCB, 125 Amps as incomer and outgoing as TPN, 4 way, 415 Volts, IP-43 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed. [Note: MCCB shall be measured and paid seperately]
S & F in repairs factory made sheet metal enclosure double door TPN MCB DBs (fixed flush to the wall), 4 way, 415 Volts, IP-42 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed.
S & F in repairs factory made sheet metal enclosure double door SPN MCB DBs (fixed flush to the wall), 8 way, 240 Volts, IP-42 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed.
S & F in repairs factory made sheet metal enclosure double door SPN MCB DBs (fixed flush to the wall), 8 way, 240 Volts, IP-42 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed.
S & F in repairs factory made sheet metal enclosure double door SPN MCB DBs (fixed flush to the wall), 12 way, 240 Volts, IP-42 protection with 200 Amps rated bus bar with suitable size copper PVC sheathed cable for earth continuity and making good disturbed surfaces in PCC / Brick work including plastering and finishes to match with adjoining wall surfaces complete all as specified and directed.
S & F in repairs MCB, SP, 6 to 32 Amps, 240 Volt, rupturing capacity 10 KA, 50 Hz, 'C' series complete all as directed
S & F in repairs MCB, SPN, 6 to 32 Amps, 240 Volt, rupturing capacity 10 KA, 50 Hz, 'C' series complete all as directed
S & F in repairs MCB, TP, 63 Amps, 415 Volt, rupturing capacity 16 KA, 50 Hz, 'C' series complete all as directed
S & F in repairs MCB, TPN, 63 Amps, 415 Volt, rupturing capacity 16 KA, 50 Hz, 'C' series complete all as directed
M & L for sub main wiring with 4 runs of single core 1100 volts grade, 10.0 Sqmm, PVC insulated, unsheathed, FRLS copper conductor cable drawn through and including 40mm dia surface/concealed PVC conduit and conduit accessories including provision of 1 run of 10.0 Sqmm PVC insulated, unsheathed, FRLS copper conductor cable as earth continuity conductor including taking down old sub main wiring and making good disturbed surfaces complete all as specified and directed. [NOTE: 5 runs of 10.0 Sqmm cable and 1 run of PVC conduit shall be measured as one unit length.]
M & L for sub main wiring with 2 runs of single core 1100 volts grade, 6.0 Sqmm, PVC insulated, unsheathed, FRLS copper conductor cable drawn through and including 25mm dia surface/concealed PVC conduit and conduit accessories including provision of 1 run of 6.0 Sqmm PVC insulated, unsheathed, FRLS copper conductor cable as earth continuity conductor including taking down old sub main wiring and making good disturbed surfaces complete all as specified and directed. [NOTE: 3 runs of 6.0 Sqmm cable and 1 run of PVC conduit shall be measured as one unit length.]
M & L for sub main wiring with 2 runs of single core 1100 volts grade, 4.0 Sqmm, PVC insulated, unsheathed, FRLS copper conductor cable drawn through and including 25mm dia surface/concealed PVC conduit and conduit accessories including provision of 1 run of 4.0 Sqmm PVC insulated, unsheathed, FRLS copper conductor cable as earth continuity conductor including taking down old sub main wiring and making good disturbed surfaces complete all as specified and directed. [NOTE: 3 runs of 4.0 Sqmm cable and 1 run of PVC conduit shall be measured as one unit length.]
M & L for sub main wiring with 2 runs of single core 1100 volts grade, 2.5 Sqmm, PVC insulated, unsheathed, FRLS copper conductor cable drawn through and including 20mm dia surface/concealed PVC conduit and conduit accessories including provision of 1 run of 2.5 Sqmm PVC insulated, unsheathed, FRLS copper conductor cable as earth continuity conductor including taking down old sub main wiring and making good disturbed surfaces complete all as specified and directed. [NOTE: 3 runs of 2.5 Sqmm cable and 1 run of PVC conduit shall be measured as one unit length.]
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 4 core 25 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 4 core 16 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 3.5 core 95 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 3.5 core 70 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 3.5 core 50 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 3.5 core 35 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 2 core 10 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing LT XLPE insulated, PVC sheathed, bedded, armoured, heavy duty, electric power cables of size 4 core 4 Sqmm, 1100 volts grade, with aluminium conductor laid in trenches / passing through pipe / duct complete all as specified and directed by the Engineer-in-Charge.
Excavation in trenches not exc 1.5m wide and depth for foundations, laying of cables, pipe etc n.exc 10 Sqm on plan and getting out in hard / dense soil complete all as specified and directed.
Returning filling in, including spreading, levelling,watering and well ramming in layers not exc 25cm thickness as in soil complete all as specified and directed.
Removing excavated material /soil to a distance not exceeding 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed
M&L for Sand filling in trenches using dry river sand as cushioning 23 cm thick punned to 18 cm thickness, to under ground cable including spreading, levelling and consolidation complete all as specified and directed. [Note: Punned thickness of sand shall only be measured.]
Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1 flat of size 250mm x 150mm x 40mm for cable protection laid across alignment of cable in trenches complete all as specified and directed.
S & F GI tubing 40mm bore, light grade for cable protection laid in trenches / walls complete all as specified and directed.
M & L for cutting of road / hard standing for laying of cables / cable protection pipe and making good the disturbed portion in PCC 1:3:6, type C-1 using 20mm graded stone aggregate including removal of debris to a distance not exc 50m complete all as specified and directed.
S & F Starter for shutter 3 Phase DOL type suitable for rolling shuuter / hanger door motor two way revolving type (clockwise and anticlockwise both type) including taking down defective starter complete all as directed by Engineer-in-Charge.
S & F Starter for shutter 3 Phase DOL type suitable for pump of capacity 7.5HP including taking down defective starter complete all as directed by Engineer-in-Charge.
S & F limit switch 10A-125, 250 or 480 Volts, AC suitable for rolling shutter / hanger door for three phase supply including taking down defective limit switch complete all as directed by Engineer-in-Charge.
S & F in repairs Air termination, single pointed aluminium rod 12mm dia and 300mm long complete all as specified.
S & F in repairs Aluminium strip 25x3.15mm as roof conductors and down conductors buried in ground / fixed on wall with means of hylam sheet with epoxy based insulator and screws, bolts, nuts and lead washers complete all as specified and directed.
S & F in repairs Test point terminal box of size 200x100x100mm made of 2mm thick hot dip galvanised sheet drilled and screwed including 6 Nos 15mm long hexagonal head screws complete with test point terminal block made of gun metal or Phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws and secured to wall complete all as specified and directed.
M & L for Servicing of rolling shutter / hanger door motor of 7.5 HP capacity by opening, cleaning, and rewinding the motor with appropriate gauge super enameled copper wire, varnishing with golden colour varinish, drying, greasing, replacement of insulating materials, sleeves, worn out shaft bush, condenser, bearings, chain link and sprocket, nuts & bolts, split pins and refixing the motor in original position, painting (two coats of existing colour) including testing and commissioning complete all as specified directed by the Engineer-in-Charge
S & F in repairs Wall mounted alternating current plug and socket distribution box (Industrial socket) including plug connector 16 Amps, 2 pole and earth, IP 40 protection of metal body single phase 240 Volts, 50 Hz with provision for one 16 Amps MCB 2P including necessary fixing arrangements complete all as directed by the Engineer-in-Charge.
S & F in repairs Wall mounted alternating current plug and socket distribution box (Industrial socket) including plug connector 32 Amps, 3 pole, neutral and earth, IP 40 protection of metal body single phase 415 Volts, 50 Hz with provision for one 32 Amps MCB TPN including necessary fixing arrangements complete all as directed by the Engineer-in-Charge.
S & F in repairs Modular sheet metal enclosure with single pole and neutral enclosure with a two pin and earth plug and socket complete with one MCB, SP, 20 Amps, 240 volts, 10 KA complete all as specified and directed.
S & F Aviation Obstruction light of LED type integral light comprising of aluminium housing with polycarbonate enclosure, 302 Nos LED along with other fixing accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including taking down existing light fittings of any type complete all as specified and as directed by the Engineer-in-Charge.
Supplying and laying synthetic Rubber insulated mats 2 mm thick suitable for electrical shock safety of sizes 2m x 1m for indoor LT panel complete all as directed
Supply and replacement of LED driver suitable for 36/50/75 Watt LED panel light (2'x2') of and type complete all as specified and directed
Supply and replacement of LED driver suitable for 25/30 Watt LED building security light of and type complete all as specified and directed
Supply and replacement of LED driver suitable for 20 Watt LED light of any type complete all as specified and directed
S & F in repairs switch socket combination modular type upto 8 module 2 pin & 3 pin, 5 Amps, 230 volts multipurpose complete all as specified and directed.
S & F in repairs switch socket combination modular type upto 8 module 2 in 1 type, 3 pin, 16/15 Amps, 230 volts multipurpose complete all as specified and directed.
S & F in repairs GI powder coated louvers suitable for exhaust fans upto 300mm sweep complete all as directed. [Note: Quoted rate is deemed to be inclusive for necessary scaffolding as required for work at any height]
S & F in repairs GI powder coated louvers suitable for exhaust fans above 300mm sweep and upto 600mm sweep complete all as directed. [Note: Quoted rate is deemed to be inclusive for necessary scaffolding as required for work at any height]
S & F 2mm thick GI hot dip galvanised / powder coated perforated type cable trays with cover of size 100mm width, 50mm depth fixed with and including necessary MS clamps, nuts, bolts fixed to walls / ceiling including taking down old tray complete all as directed by the Engineer-in-Charge.
S & F PVC cable tray of size 100mm width, 50mm depth fixed with and including necessary MS clamps, nuts, bolts and cover fixed to walls / ceiling including taking down old cable tray complete all as directed by the Engineer-in-Charge.
S & F PVC cable tray of size 50mm width, 50mm depth fixed with and including necessary MS clamps, nuts, bolts and cover fixed to walls / ceiling including taking down old cable tray complete all as directed by the Engineer-in-Charge.
S & F uPVC panel trunking system 75mm width, 75mm depth elongated flexible bottom mounting fixed with and including necessary end joints, T bends, and other accessories, MS clamps, nuts, bolts and cover fixed to walls / ceiling including taking down old trunking complete all as directed by the Engineer-in-Charge.
M & L for Chemical earthing by drilling of hole upto 250mm dia to a depth not less than 3.5m and fixed sealed maintenance free chemical filled earthing electrode 17.2mm dia and 3.048m long with copper coating thickness 254 microns including supply and installation of CAPE or equivalent make as approved by GE, earth enhancing mineral compound tested for leaching and TCLP with NABL accredited Lab as per IEC 62561-7-25Kg buried directly and vertically in the hole with top edge not less than 1.25m below normal ground level connected with copper earth strip 30x6mm by means of bolts, nuts, check nuts and washers of copper connected to earthing test point all as specified or indicated including testing on ompletion and as directed. [Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, refilling the earthing hole including earthing lead upto 7.5m complete all as specified in SSR Part-I and all as per manufacturers instructions.]
Earthing complete with Copper plate electrode of size 600x600x3mm thick buried directly in ground with earth pit not less than 2.25m deep below the normal ground level with top edge of plate not less than 1.5m below normal GL connected to Copper earth strip 20x3mm by means of bolts, nuts, check nuts and washers all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on ompletion and as directed. [Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS angle iron frame 40x40x6mm, cast iron cover, MS handle 12mm dia, CI funnel and wire mesh, GI watering pipe 20mm dia medium grade for watering, GI protection pipe light grade 32mm dia, earthing lead upto 7.5m complete all as specified in preambles of SSR Part-II and as shown in plate No. 3 of SSR Part-I.]
Earthing complete with Galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25m deep below the normal ground level with top edge of plate not less than 1.5m below normal GL connected to GI earth strip 25x4mm by means of bolts, nuts, check nuts and washers of Galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on ompletion and as directed. [Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS angle iron frame 40x40x6mm, cast iron cover, MS handle 12mm dia, CI funnel and wire mesh, GI watering pipe 20mm dia medium grade for watering, GI protection pipe light grade 40mm dia, earthing lead upto 7.5m complete all as specified in preambles of SSR Part-II and as shown in plate No. 3 of SSR Part-I.]
Earthing complete with Galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25m deep below the normal ground level with top edge of plate not less than 1.5m below normal GL connected to GI earth lead 4mm dia by means of bolts, nuts, check nuts and washers of Galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on ompletion and as directed. [Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, Precast RCC 1:2:4, Type B-1 cover 40mm thick reinforced with 8mm dia CTD bars @ 75mm c/c both ways, MS handle 12mm dia, CI funnel and wire mesh, GI watering pipe 20mm dia medium grade for watering, GI protection pipe light grade 15mm dia, earthing lead upto 7.5m complete all as specified in preambles of SSR Part-II and as shown in plate No. 3 of SSR Part-I.]
S & F Earth continuity conductor or main earthing lead of 25x4mm GI strip fixed to wall on batten or recess or cases or buried in ground or drawn in conduit / pipe or fixed to poles complete all as specified.
S & F Earth continuity conductor or main earthing lead of 20x3mm copper strip fixed to wall on batten or recess or cases or buried in ground or drawn in conduit / pipe or fixed to poles complete all as specified.
M & L for servicing of solar water heater with solar panel complete including necessary cleaning, brazing / welding & jointing of inlet outlet pipes, tanks,solar panels etc as per the site requirement and testing & checking of solar water heater and making in working condition using all necessary minor spares complete all as specified and directed Note:- The service shall be carried out through authorized technician of the OEM.
Repair / Servicing of UPS modules up to 30 kva comprising of IGBT, Based rectifire, Static IGBT based inverter with in built Galvanic Isolation transformer , Bi-directional Static and manual By-Pass Switches , input and out put filters for limiting THD within limits including loading and unloading and transportaion to civil service center and back complete all as specified and directed. Note:- The Repair/Service shall be carried out through authorized service centre of OEM and contractor will have to submit all necessary documents in regard.
Repair / Servicing of UPS modules 30 KVA to 60 KVA comprising of IGBT, Based rectifire, Static IGBT based inverter with in built Galvanic Isolation transformer , Bi-directional Static and manual By-Pass Switches , input and out put filters for limiting THD within limits including loading and unloading and transportaion to civil service center and back complete all as specified and directed. Note:- The Repair/Service shall be carried out through authorized service centre of OEM and contractor will have to submit all necessary documents in regard.
Repair / Servicing of UPS modules 400 KVA comprising of IGBT, Based rectifire, Static IGBT based inverter with in built Galvanic Isolation transformer , Bi-directional Static and manual By-Pass Switches , input and out put filters for limiting THD within limits including loading and unloading and transportaion to civil service center and back complete all as specified and directed. Note:- The Repair/Service shall be carried out through authorized service centre of OEM and contractor will have to submit all necessary documents in regard.
Supply and fixing in repair of SNMP communication system, (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) , with software and cards wit 12 workstations and service for 30 to 400 KVA UPS complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
Supply and fixing of DC card ser No DC-DC-03-0814 (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) for 30-400 KVA UPS complete all as specified and directed. Note:- Make has to be Approved by GE before Procurement of the material.
Supply and fixing of Firing Card ser No 8400-CH24-0606 (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) for 30-400 KVA UPS complete all as specified and directed. Note:- Make has to be Approved by GE before Procurement of the material.
Supply and fixing of AC Fans as per existing shape and size (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) for 30-400 KVA UPS complete all as specified and directed. Note:- Make has to be Approved by GE before Procurement of the material.
Supply and fixing battery lead of 10 Sqmm cross section copper conductor minimum length of 1 mtr including battery terminal and nut bolt complete all as specified and directed.
Supply and fixing in repair maintence free battery 12 Volt upto 65 AH complete all as specified and directed.
Supply and fixing in repair maintence free battery 12 Volt from 65 AH up to 120 AH complete all as specified and directed.
Supply and fixing in repair maintence free battery from 12 Volt 120 AH to 200 AH complete all as specified and directed.
S&F in repairs Rectifier Control card/Inverter Control card for 30-60 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE)complete all as specified and directed Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairs Input sensing Transformer for 30-60 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairs IGBT Driver card for 30-60 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairs Output feedback transformer for 30-60 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairs Capacitors for 30-400 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairsPower cables and control cables for 30-400 KVA online UPS System (Make shall be of original equipment manufacturer or of any leading manufacturer to be approved by GE) complete all as specified and directed . Note:- Make has to be Approved by GE before Procurement of the material.
S&F in repairs LED Tube Light Batten Frame wall mounted with all accessories internally prewired and connecting up with twin core twisted copper conductor cable suitable for 18/20 W LED Tube Rod including taking down old fittings complete all as specified and directed .
M&L painting of complete LT panels of any size and make with existing colour with 2 coats of synthetic enamel spray painting after cleaning of surfaces by scrubbing all dust particles/grease/oil etc complete all as specified and directed .
S&F modular cover plate and frame 1 module to 4 module suitable for modular switch/socket complete all as specified and directed .
S&F modular cover plate and frame 6 module to 8 module suitable for modular switch/socket complete all as specified and directed .
Taking down old metal flush box of any type and S&F of modular metal flush box 1 module to 4 module suitable for modular switch/socket complete all as specified and directed . [Note: Quoted rate is deemed to be inclusive for necessary cutting chases in walls / floors / ceiling of any description, pinning in making good to disturbed surfaces where required and pointing in cement mortar 1:3 and finished to match with existing finishes complete]
Taking down old metal flush box of any type and S&F of modular metal flush box 6 module to 8 module suitable for modular switch/socket complete all as specified and directed . [Note: Quoted rate is deemed to be inclusive for necessary cutting chases in walls / floors / ceiling of any description, pinning in making good to disturbed surfaces where required and pointing in cement mortar 1:3 and finished to match with existing finishes complete]
Labour for Taking Down Existing Lightining conductor/Aluminium Strip/Terminal Rod/Test Point box etc and refixing by use of minor accessories such as screws, insulators etc at existing buildings and testing complete all as specified and directed .
Labour Only for checking servicability /working/ functional state of UPS modules up to 10-400 Kva and frequency converter , checking of all components and make it functional with minor repair, cleaning etc and submit the test report complete all as specified and directed . Note :- checking of serviceablility , functional state shall be carried out through authorized service centre of OEM and Test report is to be submitted duly signed by contractor, User representative, JE and Engineer-in -charge
S&F in repairs Air ventilator (PVC body exhaust Fan) 200 mm sweep complete all as specified and directed .
S&F in repairs Air ventilator (Metal body exhaust Fan) 250 mm sweep complete all as specified and directed .
S&F in repairs Wall mounted Air circulator Fan having copper winding motor, AC, single phase 230/240 Volt of size 450 mm sweep, metallic type complete all as specified and directed . Note :- contractor will have to give 5 years replacement warranty for all the fans supplied
S&F in repairs Bell push modular one way, 6 Amp, 1 module 230 V complete all as specified and directed .
M.V.K.ENTERPRISES
M/S Jayalakshmi Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .