| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.2 LAccepted-AOC DOOR NO 15 1 141 BHAVANA ENCLAVE 1 NEAR HOTEL GRAND BAY MAHARANIPETA NOWAROJI ROAD VISAKHAPATNAM 530002 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530002 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹38.7 L+₹3.5 L (9.97%)Rejected-Finance | L2 | Rejected-Finance Being not L1 | |
| 3 | L3₹40.2 L+₹5.0 L (14.2%)Rejected-Finance DOOR NO 14 6 21 5 OPP MARVAL SCHOOL BC ROAD NEW GAJUWAKA VISAKHAPATNAM 530026 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530026 | L3 | Rejected-Finance Being not L1 | |
| 4 | L4₹45.6 L+₹10.5 L (29.7%)Rejected-Finance D NO 65 6 500 2 MULAGADA COLONY HIMACHALNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L4 | Rejected-Finance Being not L1 |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
28 Oct 2020, 6:00 pmClosed
Garrison Engineer Utility-I Visakhapatnam
Garrison Engineer Utility-I Near Samudrika Naval Base Post Visakhapatnam -530 014
REPAIR / MAINT OF CENTRAL AC PLANTS PACKAGE AC UNITS AT MWC, TPW, NOIC UNDER AGE EM - I OF GE ( UTILITY - I ) VISAKHAPATNAM
2020_MES_383209_1
8265/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Garrison Engineer Utility-I Visakhapatnam
CLASS D
9 documents required · 9 mandatory
₹500
Garrison Engineer Utility-I
₹99,000
Yes
7 Dec 2020
3 Oct 2020
30 Oct 2020
3 Oct 2020
28 Oct 2020
16 Oct 2020
Amount
M & L for de-scaling the shells and tube condenser by circulating the diluted hydrochloric acid at the appropriate ratio depend upon the scale deposits till removal of all the scale inside the copper tubes and removal of the both end covers, brushing with nylon brush, removal of all scale and degreasing with caustic soda, flushing out thoroughly, re-fixing the end covers with new gasket packing, nut and bolts and connecting the inlet and out let water connection checking of water leaks, all specified and directed.
M&L for servicing the Air handling units 35324 CFM capacity (central AC), with and including dismantling units, sheet metal parts, blowing out the dust, chemical cleaning by spraying the organic based scale removing agent Vaniklin at the appropriate ratio till removal of complete dust & scale deposits in the fin area of evaporator coil, flushing through for proper air flow across the coil, greasing of blower motor, checking of electrical connection, cleaning of air filters, greasing of blower motor, replacement of un serviceable bearings, water drain lines, renewal of rusted sheet metal screws, applying synthetic enamel paint over a coat of primer on the rusted portion and testing & commissioning the unit all as specified and as directed by Engineer-in-Charge.
All as per Item No.2 herein before but Air handling units 34400 CFM capacity
M&L for complete leak testing the compressor , complete refrigerant pipe with Nitrogen gas, locating the leaks, rectify the leak by brazing/ welding and pressure testing the complete system for 100 to 140 TR capacity of air cooled package AC system all as specified and as directed by Engineer-in-Charge:
Supply and fix in repair " V "belts for Air handling units 34400 CFM Make : Fenner or equivalent
All as per Item No.5 herein before but Air handling units 35324 CFM capacity
All as per Item No.5 herein before but Air handling units 35142 CFM capacity
All as per Item No.5 herein before but Air handling units 17050 CFM capacity
Supply and charge refrigerant gas F-22 all as directed by Engineer-in-Charge. Make: Mafron/ Freon/ Floron
Supply and charge refrigerant gas R-407C all as directed by Engineer-in-Charge. Make: Mafron/ Freon/ Floron
Supply and charge refrigerant gas R-134 all as directed by Engineer-in-Charge. Make: Mafron/ Freon/ Floron
M&L for taking down the defective unserviceable solenoid valve coil and supply & fixing of new solenoid valve coil suitable for 7/8” size valve, 220/230V 50 Hz all as directed by Engineer-in-Charge. Make: Danfoss/ Indfoss.
S&F in replacement, box type filter of size 600x600mm (99% down to 10 microns) to match existing filters. Make: Spectrum/ Carry air or equivalent.
S&F in replacement, box type filter of size 600x300mm (99% down to 5 microns) to match existing filters. Make: Spectrum/ Carry air or equivalent.
S&F in replacement, HEPA filter of size 600x600x150mm (99% down to 3 microns) to match existing filters of capacity 3x33 TR. chiller Make: Spectrum/ Carry air or equivalent.
S&F in replacement, HEPA filter of size 600x600x150mm (99% down to 3 microns) to match existing filters of capacity 3x46 TR. chiller Make: Spectrum/ Carry air or equivalent.
M&L for dismantling defective induction motor of any make 415 V of any duty or any class of insulation from the bed duly coupled with pump, transporting to work shop, removing burnt out winding from stator, rotor and rewinding with suitable gauge super enameled copper wire of approved make and replacing driven end and non driven end bearings, insulation materials, varnishing, heating reassembling, testing and commissioning for the following capacities. Notes :- Motor removed for rewinding shall be overhauled completely and the quoted rate shall be deemed to be inclusive for the same.
a) 6 to 10 HP
b) 21 to 25 HP
M&L for replacement of unserviceable/ damaged power contactors in various AC plant panels and supply and fix the following power contactors complete including necessary control wiring all as directed. Make: L&T/ BCH/ C &S
(a) MNX 12 contactor 3 pole
(b) ML-2 Contactor 3 pole
(c) ML-3 Contactor 3 pole
(d) MNX 25 contactor 3 pole
S&F butterfly value 150mm dia with necessary rubber gasket, bolts, nuts and washer including taking out existing valve all as directed Make : Zoloto / Kirloskar
S&F butterfly value 100mm dia with necessary rubber gasket, bolts, nuts and washer including taking out existing valve all as directed Make : Zoloto / Kirloskar
Supply only compressor oil Seathel No.68 / Servofreeze69
Supply only compressor oil SW 220 or equivalent for carrier/Voltas compressor
Complete servicing of FRP cooling tower, removal of complete scales, dirt etc. by using chemicals, cleaning the sump louvers, PVC fills, fan assembly, renewal of spray nozzles, renewal of nuts and bolts, and complete painting of the cooling tower as per the standard practice for 3 x 100 TR capacity cooling tower all as specified and directed.
Complete servicing of FRP cooling tower, removal of complete scales, dirt etc. by using chemicals, cleaning the sump louvers, PVC fills, fan assembly, renewal of spray nozzles, renewal of nuts and bolts, and complete painting of the cooling tower as per the standard practice for 3 x140 TR capacity cooling tower all as specified and directed.
Supply and fix shaft seal assembly suitable for 40/25 TR Compressor.
Supply & Fixing in repair DOL Starter with relay range13-20 Amps suitable for 10/15 HP Motor with SPP feature . Make : L&T/ C&S
Supply only condenser fan motor, 1 HP capacity, 240V, 50Hz, 900 RPM.
M&L for winding,overhauling of condeser water pump complete and replacement of bearing and machining of main bearing shaft and galnand packing and studsnuts bolt etc fgor monoblock 5 HP to 12.5 HP complete all as specified and directed.
S&F of mother board for 48 TR Make as per OEM all as specified and as directed by Engr-in Charge.
S&F temparature censor cable suitable 140 TR chiller plant suitable for model Carrier 30 HXCat MWC
S&F HP switch 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F LP transucer 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F HP transucer 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F SCPM board 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F mother board 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F internal oil filters 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S&F 3TF47 siemens contactor 110 V AC 140 TR chilller plant suitable for model Carrier 30 HXCat MWC
S& F of Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) of capacity 500 Ltrs hoisted and fixed in position complete including taking down existing all as specified. Make : Sintex/Polycon
S& F of Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) of capacity 1000 Ltrs hoisted and fixed in position complete including taking down existing all as specified. Make : Sintex/Polycon
Overhauling of split casing type pump up to 40 HP dismantling the pump carryout overhauling including replacing the complete damaed spare parts . Repair /replacing the wornout shaft ,replacig the bushes roller/ball bearings,wearing gland packages,renewal all corruded studs, gaskets, damaged impellars etc. Assembly watch good of alignemnt including testing and commissioning the pump all as directed and specified by Engr-in-Charge.
M&L for replacing the chocked drier core assembly inclduing removing the defective ,cleaning the core washing with CTC/dettol and fixing new core of activated aluminatype corefixing the new gasket testing leak and testing for screw type chiller plant upto 140TR
M&L for taking down central control unit 3x16 HP capacity of VRF AC unit including dismantling the units carefully, chemical cleaning of cooling coils and refrigerant pipe lines with appropriate cleaning agents, flushing through for proper air flow across the coils to improve the cooling efficiency, reassembling & re-installing the units in their original position complete all as directed.
Supply and fixing and testing of the following Spare Parts as required during repair of 3x16 HP VRF AC plant of Bluestar complete all as directed
Power board (CDCO-D182-00) 01 6480
Power board (CDCO-D182-00) 01 6480
VRF ODU FAN CONTROLLER (CDCO-D345-00) 01 7680
10HP Capacitor boards (CDCO-D338- 00) 1 18600
ODU fan motors (MOBLDC-008280-4- 00) 2 19800
VRF ODU FAN CONTROLLER (CDCO-D345-00) 1 7680
VRF ODU FAN CONTROLLER (CDCO-D345-00) 1 7680
Power board (CDCO-D182-00) 1 6480
10HP Capacitor boards (CDCO-D338- 00) 1 18600
ODU fan motors (MOBLDC-008280-4- 00) 2 19800
Supply and fixing and testing of the following Spare Parts as required during repair of 3x100 TR Chiller AC plant of Voltas at 551&552 TPW complete all as directed
Oil level censor
Expansion valve controller
Pressure transudcer
Catchkll-4
M&L for replacing the old lubrication oil for the variable speed Screw type liquid chiller compressor isolating or shut down by serviceables, oil equilizing valves,side inspection covers by the compressor,openimng the oil filter assembly,oil sump and connection oil line, cleaning filter element etc with CTC/Petrol and refixingthe filter unit,boxing up the side inspection cover with new gas ket and charging the compressor oil as required quantity as per the standard qty as per model of the 3X300 TR carrier make compressor of synthetic oil (18.9 Ltr /Unit) Part code No.2000998 and leak testing the joints and opening the closed valves and testing &comissioning the compressor for the following capacity&Model of compressor All as directed by Engineer-in-Charge NOTE:- Compressor oil shall be meaasured and paid separately under relavent schedule item.
a) Synthetic Oil for 3X300 TR variable speed Scew type liquid chiller.
M&L for repair/replacement of the folllowing spares of 3X300 TR variable speed screw type liquid chiller of capacity 300 TR of Make: Carrier Model : 23XRV3132NRVAA9 for repair/ replacement under relevant schedule item
Line sync,Board 179646 Cat Part No. 2017313 - 02- for Chiller No.1&2
Strainer,Oil sump Cat Part No. 2011229
O'-Ring Strainer Cat Part No.2021964
Oil filter after oil pump Cat part no.2021339
COOL CONTROL
REAL ENGINEERING WORKS
ANAND ENTERPRISES AND ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .