Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 LAccepted-AOC ETTA BHATTA MAINROAD SURAJPUR BHATGAON SURAJPUR CHHATTISGARH | DURG | CHHATTISGARH | 490001 | L1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical MINERS BASTI MINERS COLONY WARD NO 04 BIHARI HOTEL R N SINGH COMPLEX BIJURI ANUPPUR MADHYA PRADESH 484440 | ANUPPUR | MADHYA PRADESH | 484440 | - | Rejected-Technical L2 | |
| 3 | Rejected-Technical MISSION HOSPITAL CHOWK KEDARPUR AMBIKAPUR DIST SURGUJA CG 497001 | SURGUJA | CHHATTISGARH | 497001 | - | Rejected-Technical L3 |
Tender Value
₹8.6 L
EMD Value
₹10,800
Closing Date
9 Apr 2024, 5:00 pmClosed
Staff Officer ENM
Office of the General Manager SECL Baikunthpur Area
1.Conversion of 3.3KV overhead line of CHP Feeder to 33KV from Churcha West Substation to D1 Belt Discharge Point Churcha Mine (RO) 2. Providing and Fixing of 3.3KV, 600Amp gang operated Air Breaker Switch at different location of Churcha Mine (RO)
2024_SECL_306049_1
SECL/GM/BKP/ENM/eTender/23-24/ 35
Open Tender
Civil Works - Others
Item Rate
60 days
Churcha
As per NIT
8 documents required · 8 mandatory
₹10,800
25 May 2024
29 Mar 2024
10 Apr 2024
30 Mar 2024
9 Apr 2024
30 Mar 2024
30 Mar 2024 - 2 Apr 2024
Amount
Item Description/ Heading : 1. Work of conversion of 3.3KV overhead line of CHP Feeder to 33KV from Churcha West Substation to D1 Belt Discharge Point for installation of 33KV/3.3KV transformer to resolve voltage drop problem for the belt line in transporting coal from Pit Bunker to CHP under Churcha Mine (RO) of Baikunthpur Area. 2. Providing & Fixing of 3.3KV, 600Amp gang operated Air Breaker Switch at different location of Churcha Mine (RO).
1. Work of conversion of 3.3KV overhead line of CHP Feeder to 33KV from Churcha West Substation to D1 Belt Discharge Point for installation of 33KV/3.3KV transformer to resolve voltage drop problem for the belt line in transporting coal from Pit Bunker to CHP under Churcha Mine (RO) of Baikunthpur Area. - (i) Erection of Steel Pole upto 13 m in C.C. : Erection of Steel Pole of length exceeding 10 meters but not exceeding 13 meters in cement concrete 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggrregate 40 mm nominal size) foundation including excavation and refilling etc as required. (6 Poles for conductor erection and 4 pole for back support to the existing line to dismante the stay sets)
(ii) Supplying and erection of galvanised stay set for 11/ 33 KV OH line complete with 19/20 mm dia X 1.8 meter long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, Thimble, Stay clamp, bow tightner, 7/4.00 mm dia GI stay wire and 33 KV strain Insulator etc in cement concrete (1 Cement : 3 coarse sand : 6 graded stone agrregate 40 mm nominal size) foundation including excavation and refilling etc as required.
(iii) Erection of Pole Top/ V shape two wire angle Iron/ Channel cross arm in steel tubular/ Rail/ PCC Pole for 11 KV/ 33 KV as required
(iv) Erection of double pole three wire cross arm with bracing support for 11/ 33 KV OH line as required (2 DPs converting to TP & 1 New TP)
(v) Clamps, Nut & Bolts
(vi) Erection of a set of crossing bracing frame work for 11/ 33 KV overhead line double pole structure
(vii) Supplying and erection of 33 KV Pin Insulator complete with large steel head GI Pin, Nuts, Washers etc. as required
(viii) Supplying and erection of 11 KV Disc Insulator for 11/33 KV overhead lines with galvanised Insulator fitting, ball & socket type and complete with galvalised strain clamps, bolts, nuts washers etc as required
(ix) Erection of AA conductor of 7/1.96 mm to 7/3.10 mm dia 290 Kg/Km (13 Span X 180 m X 290 Kg/ Km)
(x) Supplying and erection of single piece non liner resistor type lightning arrestor suitable for 3 wire 33 KV overhead lines with rated voltage 30 KV (rms) with a nominal discharge current rating 10 KA (Station class) and complete with galvanised clamping arrangements, GI Bolts, nuts, washers etc as required
(xi) Earthing with GI earth plate 600 mm X 600 mm X 6 mm thick including accessories and providing masonry enclosure with cover plate havoing locking arrangement and watering pipe of 2.7 m long etc. with charcoal/ coke and salt as required.
(xii) Providing and fixing of 33 KV Grade 600 Amps Isolator without earth switch with erection of strcuture by providing clamps, nut-bolts etc. (required accessories) for the isolator on Triple pole
(xiii) Drilling holes on the top of poles with gas cutting for replacing 11 KV Pin Insulator to 33 KV Pin Insulators
(xiv) Dismantalling of Iron Sytructure, Insulator, Conductor etc.
2. Providing & Fixing of 3.3KV,600Amp gang operated Air Breaker Switch at different location of Churcha Mine (RO). - (i) 3.3 KV 600 Amps (11 KV 600 Amps) Gang Operated Air Breaker Switch
Total impact of GST for the purpose of CTC
M/s. SWETA ELECTRICALS
MS R.P. JAISWAL
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_317134.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .