(A) Electrical General work in connection with Engg. work "At HWR Station:- Provision of Station Approach Road through L/Xing Gate No. SK/325 to Station". (B) Electrical General work in connection with S&T work "Interlocking of Four Numbers Engineering Manned Level Crossing Gates with TVU >50,000 at Katihar Division".
40_2026
40_2026
Open
6 Months
Katihar, Bihar
₹0
₹1.6 L
1 Jul 2026
1 Jul 2026
10 Jul 2026
>50,000 at Katihar Division (KJ-33, SK-226, SK-214, SK-274))
Item- 1 Please see item Breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, wiring, testing & commissioning of Numbers 60.00 797.00 47820.00
concealed point wiring by FR PVC insulated and
unsheathed 1.5 sq mm, single core multi strand
copper wire with earth continuity wire by PVC
insulated and unsheathed 1 sq mm , single core
multi strand copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia heavy duty including all types
of joints and bends as required, complete with 6
amps flush type controlling modular switch to be
mounted on modular GI inner plate and modular
mounting frame of suitable module as per
requirement complete to be concealed in wall as
per instruction of Engineer Incharge at site.
Existing wall should be cut and re-mended to
original finish by contractor's own material. (a)
FL Point/LED Tube Point/Wall Mounted Bracket
Fan Point with c/rose
3 3 (c) Fan point with c/rose and 5 step fan Numbers 20.00 1450.00 29000.00
5 5 (e) Plug point 6 amps on board complete Numbers 24.00 361.00 8664.00
KATIHAR DIVISION-ELECTRICAL/N F RLY
6 6 Supply, wiring, testing & commissioning of Numbers 24.00 737.00 17688.00
c o n c e a l e d plug point on separate board
complete with 2 x 6 Amp modular socket and
6/10 amps modular switch to be mounted on
modular GI inner plate 6M and 6M modular
mounting frame with GI box to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
7 7 Supply, wiring, testing & commissioning of Numbers 32.00 855.00 27360.00
concealed 6/16 amps power plug point on
separate board complete with modular 16 amps
switch (with indicator) and 6/16 amps 3 pin
combined shuttered socket to be mounted on
modular GI inner plate 4M or suitable size with
modular mounting frame to be concealed in wall
as per instruction of Engineer Incharge at Site.
8 8 Supply, fixing, connection & testing of 40 Watt Numbers 60.00 1890.00 113400.00
LED Tubelight, Surface/ Pendent mounting LED
Battens in Extruded aluminium housing as per
instruction of Engineer Incharge at Site.
9 9 Supply and testing of wall mounted bracket fan Numbers 16.00 1998.00 31968.00
400 mm sweep complete with all accessories to
be fixed on wall by suitable fixing arrangement
including connection by 2 core, 1.5 sqmm PVC
insulated and FR PVC Round Sheathed, Copper
Conductor (flexible) industrial cable as per
instruction of Engineer Incharge at Site.
10 10 Supply, fixing & testing of LED retrofit lamp 9 Numbers 32.00 146.00 4672.00
watt, B-22 cap as per instruction of Engineer
incharge at site.
11 11 Fixing, testing & commissioning of ceiling fan Numbers 20.00 46.00 920.00
with supply & fixing of MS clamp with hook, nut,
bolt, washer etc. as per instruction of Engineer
incharge at site. (Fan will be supplied by
12 12 Supply, installation, testing & commissioning of Numbers 16.00 2824.00 45184.00
300 mm sweep (metallic) heavy duty exhaust
fan, 1400 RPM complete with fixing on wall by
suitable size bolts & nuts grouted on wall as per
instruction of Engineer incharge at site.
13 13 Supply, wiring & testing of main wire by 2.5 sq Metre 4000.00 75.00 300000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
14 14 Supply, wiring & testing of main wire by 4 sq Metre 3600.00 87.00 313200.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
15 15 Supply, wiring & testing of main wire by 6 sq Metre 1200.00 100.00 120000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
through PVC rigid conduit pipe/polythene pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
16 16 Supply, installation, testing & commissioning of Numbers 8.00 1193.00 9544.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25
Amp Socket and 25 Amp plug to be mounted on
6 module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm, Single
Core FR-LSH PVC Insulated Industrial Grade
Copper Conductor (Unsheathed) Flexible Cables,
1100 Volts with earth coninuity wire by 1 sq mm
copper cable Conforming to IS: 694 to be drawn
through Rigid PVC conduit pipe not less than 20
mm dia as per instruction of Engineer incharge
17 17 Supply, installation, testing & commissioning of Numbers 8.00 54091.00 432728.00
Inverter Split Air Conditioners 1.5 Ton, (BEE star
raying-5 star, Coil material-Copper, Echo-friendly
refrigerant, Nominal cooling capacity in Ton /
(kcal/hr)-1.5 Ton / 4500 kcal/hr) with all
accessories as per OEM suitable for operation on
230V AC ,single phase, 50 Hz as per instruction
of Engineer incharge at site. Re-mending work
should be done after installation of RAC. (with 1
pair outdoor wall stand) (Industrial
AC/Heavyduty AC)
18 18 Supply, installation, testing & commissioning of Numbers 8.00 4926.00 39408.00
Wall mounting voltage stablizer single phase, 15
Amp capacity with voltage working range 130 V-
290 V AC & having time delay system, high &
low voltage trip, digital display etc. as per
instruction of Engineer Incharge at Site.
19 19 Supply, fixing & testing of Wall Mounted Numbers 4.00 2161.00 8644.00
Microcontroller Based Programmable Digital Air
Conditioning Changeover Timer as per
instruction of Engineer incharge at site.
20 20 Supply & testing of GI octagonal pole 6 mt long Numbers 16.00 14193.00 227088.00
with foundation bolt, loop box of bakelite sheet
with one 6A SP MCB and 16 sq mm stud type
connector etc. The octagonal pole shall be hot
dip galvanized in single dip. Technical
specification of pole as following:- Height - 6 mt
Top dia (A/F) - 70 mm Bottom dia (A/F) - 130 mm
Sheet thickness - 3 mm Base plate (L x B x T) -
(200 x 200 x 12) mm Foundation Bolt size (no.x
dia) - 4 x 20 dia mm Pitch Circle Dia (PCD) - 200
mm Bolt length - 600 mm Projected Bolt Length -
21 21 Erection of Rail/Tubular/Octagonal pole to 1/5 th Numbers 16.00 1712.00 27392.00
of its height with CC foundation from base block
(30 cm x 30 cm x 15 cm) including digging &
refilling of earth to a height of 30 cm above
ground level as per drawing
no.CEE/OH@47'40@FGA) in ratio 1:3:6 by
cement sand & Chips 19 mm & down including
excavation of earth.
22 22 Supply, installation, testing & commissioning of Set 16.00 63804.00 1020864.00
45 W FLAIR PRO is All-in-One Solar Streetlight
having compact and fully integrated design with
intelligent features includes a built-in Solar
Panel, Lithium Ferro Phosphate (LiFePO4)
Battery, Charge Controller and Motion Sensor as
per instruction of Engineer Incharge at Site.
23 23 Supply, installation, testing & commissioning of Numbers 20.00 11728.00 234560.00
90 Watt LED street light with pressure die-cast
housing and toughened glass and individual
LEDs with secondary lens optics for City Road
application withIP66 ingress protection. 4kV
inbuilt and 10kV external surge protecton with
Top opening driver cover for easy maintenance
as per instruction of Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
24 24 Supply, installation, testing & commissioning of Set 8.00 37439.00 299512.00
Sine wave Inverter 1400 VA or 1450 VA suitable
for operation on 230 volt AC, with supply of 02
nos. 12 volt @ 150 Ah SMF battery including
inverter battery trolley as per instruction of
Engineer incharge at site.
25 25 Supply, installation, testing & commissioning of Numbers 4.00 66074.00 264296.00
10 KVA, 11KV/244V Step Down Transformer,
confirming to IS:2026, single phase, 50 C/s, oil-
immeresed, naturally cooled (ONAN), core type
with Aluminium wound, having no taps, 50/55 C
temp. rise in & winding respectively, HV&LV side
connected in single phase, outdoor type, having
porcelain bushings on HV & LV side, complete
with first filling of oil complying with IS:335 and
other details including fittings as per IS:2026 as
26 26 Horizontal machine boring of 300 mm dia hole Metre 120.00 2538.00 304560.00
across track/Road/High drain etc. at a depth of
1.0 mtr below of ground level with suitable
boring instruments & neessary arrangement and
as per technical procedure.
27 27 Supply, laying, commissioning & testing of CI Metre 280.00 1388.00 388640.00
Pipe 150 mm dia Class LA type (IS 1536-2001) to
be laid partly along the pole and partly through
ground under railway track/road in cable trench
for protection of cable with suitable fixing
arrangement by MS clamp, nut, bolt, washer
etc. as per instruction of Engineer incharge at
28 28 Supply, laying, commissioning & testing of HDPE Metre 280.00 278.00 77840.00
Pipe 75 mm dia PN-6 grade to be laid partly
along the pole /underground with suitable fixing
arrangement by MS clamp made of MS flat of
size 50x6 mm and suitable size nut, bolt, washer
and required bend, joints as per instruction of
Engineer incharge at site.
29 29 Supply & erection of Earthing electrode Numbers 20.00 4349.00 86980.00
complete by 50 mm dia GI Pipe, medium gauge
3 mt long including construction of earth pit and
RCC pit cover, earth continuity wire by 6 SWG GI
earth wire with salt, charcoal, soldered end
terminal, GI nut & bolt etc including connection
to Platform Electric metal pole as per Drg. No.-
PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as
per instruction of Engineer Incharge at site.
30 30 (a) Supply, installation, testing & commissioning Set 12.00 2005.00 24060.00
of 12 way SPN Distribution Board, Flush/Surface
mounting, IP 43 grade protection with copper
bus bar, fully shrouded neutral bar, earth bar,
cable ties, metal double door as per IS 8623 - III
with supply and fixing of following RCBO/MCB's
as per instruction of Engineer Incharge at Site.
module Conforms to IEC 61009-1
Conforms to IS/IEC 60898 - 1:2002
KATIHAR DIVISION-ELECTRICAL/N F RLY
33 33 (a) Supply, fabrication, erection, testing, Set 4.00 32916.00 131664.00
commissioning & painting of floor mounted
powder coated cubicle panel board (Modular
look) of suitable size (neither big nor small) ),
outdoor type with double door made of suitable
size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x
6 mm, 14 SWG MS sheet/Powder coated CRCA
sheet with provision of weather proof,rust
proof,dust proof,water proof having internal
rubber gasket with supply and fixing of following
ACB/MCCB/Bus bar/Meter etc. (Connections to
be made by copper strips, glands should be
provided at cable entry and exit, components
should be compartmentalized, Each
compartment will be provided with the door and
pad locking arrangement. The compartment
illumination lamp with door operated switch
shall be provided for each compartment. Panel
board drawing approval must be obtained with
clear indication of make of items of
electrolytic grade copper consisting of 4 bars ( 3
Ph and Neutral ) ( Bus bar should have
insulation cover)
ammeter (0-500) amps with s/switch and CTs
39 39 Laying, commissioning & testing of HT/LT Metre 2600.00 55.00 143000.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by