Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-AOC | L1 | Accepted-AOC bIDEERE FOUDN TECHNICALLY AND FINANCIALLY QUALIFIED FOR AWARD OF WORK | |
| 2 | L2₹10.3 L+₹29,190 (2.92%)Rejected-Finance ASWATHY NIVAS MAMPAZHAKARA PERUMPAZUTHOOR NEYATTINKARA TRIVANDRUM KERALA 695126 | THIRUVANANTHAPURAM | KERALA | 695126 | L2 | Rejected-Finance Financially not lowest | |
| 3 | L3₹10.3 L+₹35,530 (3.56%)Rejected-Finance 3 333 F M P ARCS VENGACHUVADU VAZHAKKULAM P O CHAITHANYA BUILDING SA ROAD KADAVATHRA MUVATTUPUZHA ERNAKULAM 686670 | MUVATTUPUZHA | ERNAKULAM | KERALA | 686670 | L3 | Rejected-Finance Financially not lowest |
Tender Value
₹10.6 L
EMD Value
₹21,180
Closing Date
10 Aug 2022, 4:00 pmClosed
Project Engineer cum Estate Officer(I/C)
IISER, Maruthamala.p.o, vithura,Thiruvananthapuram
Electrical works for Helium Plant near Physical Science Block at IISER, Thiruvananthapuram
2022_IISRT_704752_1
IISERTVM/EO/EM/203/12/2022-23
Open Tender
Electrical Works
Item Rate
60 days
IISER
Please refer Tender documents.
3 documents required · 3 mandatory
₹560
IISER, Thiruvananthapuram
₹21,180
19 Sept 2022
3 Aug 2022
11 Aug 2022
4 Aug 2022
10 Aug 2022
4 Aug 2022
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (MCCB will be supplied by dept on free of cost)
160A TPN MCCB, 50kA
Fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (DBs will be issued by dept at free of cost)
12 way (4 + 36), Double door
4 way (4 + 12), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required
Single pole
Triple pole
Triple pole and neutral(for AC)
Supplying and fixing 160A rating with 25kA breaking capacity 4 pole MCCB with thermomagnetic release and terminal spreaders in suitable size enclosure with rotary handle operation, indication lamps for RYB, trip, ON and OFF including drilling holes in the enclosure,suitable spreader links making connections, etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following size sheet steel enclosure on surface/ recess on wall as required.
Two way enclosure
Four way enclosure
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V "C" curve TP MCB complete with connections, testing and commissioning etc. as required) (for split AC)
Supply, Installation, testing and commissioning of following LED light fittings, complete with all fixing accessories etc. directly on ceiling upto 6mtr height/ wall, including necessary connections earthing etc. as required. (Make:Crompton/Philips/Wipro/Osram/Havells/Polycab/Bajaj)
36/40W 2 x 2 recessed type light
65/70W High bay light
Supply of one number XLPE/PVC power FRLS insulated cable of 1.1 kV grade of following size as required.
4C x 16 sqmm XLPE Aluminium armoured cable(for AC)
4C x 120sqmm XLPE Aluminium armoured cable(For Helium plant UPS)
4C x 70sqmm PVC insulated Copper unramoured cable
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
Upto 35 sq. mm (clamped with 1mm thick saddle)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4C X 16 sq. mm (28mm)
4C X 120 sq. mm
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required
Supply,Installation, testing and commissioning of Inverter type Hi-Wall Split Air Conditioning units of following capacities (with copper condensor & evaporator coil) filled with eco friendly refrigerant gas and powder coated Outdoor unit mounting stand, cabling, drain piping, refrigerant topup (if required) all complete as required and as directed by the Engineer In Charge. Make: Bluestar/Voltas/Hitachi/Carrier/Panasonic)
3.0TR Hi-Wall type split AC (BEE - 5 Star rated)
FI-TEC POWER SOLUTIONS PVT. LTD
Linsta Services
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .