Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.1 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹19.8 L+₹75,388.20 (3.95%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹20.3 L+₹1.3 L (6.57%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹20.3 L
EMD Value
₹40,580
Closing Date
10 Feb 2023, 6:00 pmClosed
CWE PITHORAGARH
HQ CWE (HILLS) PITHORAGARH, Post Bharkatia Pithoragarh ( UK)PIN-262520
CA NO.CWE/HILLS/EWS/56 OF 2022-2023 PROVN OF EXTERNAL ELECTRIC SUPPLY SERVICES AND OXYGEN PIPE LINE FOR 450 LPM OXYGEN PLANT UNDER GE 871 EWS
2023_MES_574615_1
CA NO.CWE/HILLS/EWS/56 OF 2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JOSHIMATH
CLASS E
9 documents required · 9 mandatory
₹500
GE 871 EWS
₹40,580
Yes
16 Mar 2023
12 Jan 2023
17 Feb 2023
12 Jan 2023
10 Feb 2023
28 Jan 2023
12 Jan 2023 - 25 Jan 2023
Amount
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out in hard dense soil complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and exc 1.5 m but n exc 3.0 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out in hard dense soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m complete all as specified and directed.
M&L dry sand, filling in trenches around under ground cable complete all as specified and directed. Note :- For the purpose of payment only punned thickness will be measured.
M&L for providing of new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable complete all as specified and directed.
M&L for PCC 1:4:8 type D-2, using 40 mm graded crushed stone aggregate below foundation of poles including necessary form work complete all as specified and directed.
M&L for PCC 1:3:6 type C-2, using 40mm graded crushed stone aggregates as in foundation filling and mass concrete including necessary form work for fair finished surfaces of concrete complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate for coping of poles including necessary form work for fair finished surfaces of concrete complete all as specified and directed.
Supplying, design, loading, unloading, installing, testing and commissioning outdoor type floor mounted step down transformer 11000/433 volts (at no load) capacity 100 KVA, AC 3 phase 50 HZ double copper wound oil immerged naturally cooled with external cooling tube core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol DYn-11 (Vector group) with neutral brought out on secondary side (LV side) and having tapping at 2.5% interval from -7.5% to + 7.5% on HV side having facility to be changed voltage by means of hand operated off load tap changing gear. The maximum temperature rise should not exceed 50 degree celsius in oil and 55 degree celsius in HV/LV winding from ambient temp when measured by resistance method after continuous full load run in ambient temp of 40 degree celcius. The transformer shall be confirm IS : 1180 Part I 2014 Level I and latest relevant IS and ECBC marked and shall comprise of the following :- (a) One cable box on HV side (primary side) with 3 Nos porcelain bushing with arcing horn suitable for 11 KV complete with bushing copper rods, nuts and washers. (b) One cable box on LT side (secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers with two nos cables glands, suitable for incoming/outgoing of 3 1/2 core 120 Sqmm LT 1100 volt grade XLPE insulated & PVC Sheathed armoured heavy duty cable including glands, joint and jointing materials complete.
(c) Oil conservator with filter type drain valve and oil level indicator gauge. (d) De-hydrating breather (TRANSPARENT TYPE) with first fill dehydrating agent (silica gel) (e) Explosive vent. (f) Thermometer pocket with temperature indicator on tank cover. (g) Two earthing terminals on tank cover to facilitate fixing of 32x6mm galvanised iron earth strip for earthing of neutral & body. (h) Rating plate and terminal marking plate. (i) Oil drain filter valve. (j) Lifting lugs. (k) Oil filling hole with cap/plug with connecting plate complete. (l) Air release valve. (m) Four plain solid cost steel detachable rollers. (n) Extra bushing for neutral, outside the LT cable box for providing independent earthing for neutral. (o) First filling of new and unused transformer oil IS-335/93 (fourth revision) marked filtered and tested for not less than 50 KV dielectric strength at 2.5 mm air gap between testing electrodes. (p) Brick work foundation suitable for 100 KVA Step down transformer, having 100 mm PCC on top type C1 (1:3:6) at top and PCC B2 (1:4:8) at bottom complete all as directed at site. Note: - (i) Certificate of dielectric strength will be provided by contractor after initial filling of oil.
Supply, installation commissioning and testing of servo motor controlled voltage stabilizer for automatic operation on unbalanced load, three phase naturally oil cooled indoor type (IP-55, CPRI approval required) Copper wound including first filling of oil of dielectric strength not less than 40 KV with MCCB and bypass system & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 1% and speed of correction 8 Volts per second and of capacity 75 KVA including suitable size of PCC 1:2:4 platfrom as per recommendation of manufacturer complete all as specified and directed. Note:- Voltage stablizer will be placed on PCC Plinth at height not less than 45 Cm from the ground level.
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
Supply, laying or fixing, jointing and testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 Sqmm, 3 core complete all as specified all specified.
Supply, laying & testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq mm, 3.5 core complete all as specified all specified.
Supply, laying & testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq mm, 3.5 core complete all as specified all specified.
Supply, laying & testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq mm, 3.5 core complete all as specified all specified.
Supply, laying & testing of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq mm, 2 core complete all as specified all specified.
Supply, installation and erect in true vertical position Steel tubular swaged poles, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.00 metres long), complete with cast iron/ MS base plate 6mm thick and of size 300x300mm, pole cap, pole made out of ERW M.S. tubing including of holes of required Nos and size for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting three signal red colour bends at lower portion of exposed pole starting from plinth block, each band of 300mm height at 300mm spacing, painting pole No the black paint by stencilled letters/ figures of 8cm height complete all as specified and directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
S&F anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered (clamps measured separately) and applying two coats of aluminium paint over a coat of primer after preparation of steel surfaces complete all as specified and directed.
M&L for lightning arresters expulsion type suitable for 11000 Volts complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed.
M&L for outdoor type gang operated device tripple pole, mechanically operated, mounted on insulator 11000 Volt and steel frame, with Operating mechanism twelve insulator type worked from ground level, for current rating up to 200 Amps complete all as specified and directed.
M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20 cm size complete all as specified and directed.
M&L for disc type insulators, porcelain vitreous white brown or green, 145mm high and 255mm dia ball and socket type, single disc assembly for tension with tension clamps for conductor having working pressure 11000 Volts complete all as specified and directed.
M&L for stay assembly complete with accessories i.e. stay plate 300mm x 300mm x 6mm, galvanised thimbles, GI stay wire 7/4 SWG, loop type insulators, vitreous porcelain, white brown or green of large size with overall dimensions 90mm x 140mm, clearance of hole 25.5mm, etc and all other accessories as shown in electrical plate No 1 on Ser Page No 495 of MES Schedule Part-I (2009) complete including dismantling stay assembly complete all as specified and directed.
M&L for 80 mm bore of GI tubing light grade galvanized with all fitting and fixed complete to walls and ceilings or laid in floors for protection HT /LT cable complete all as specified and directed.
M&L for 50 mm bore of GI tubing light grade galvanized with all fitting and fixed complete to walls and ceilings or laid in floors for protection HT /LT cable complete all as specified and directed.
M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6.30 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone agg) duly reinforced with mild steel round bars 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handles with and including necessary excavation & earth work including laying the GI pipe concealed in floor /wall all as per plate No. 3 of SSR Part I complete all as specified and directed and testing on completion. (Note:- 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost to department)
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized steel earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion complete all as specified and as directed. NOTE :- GI earth wire and protection pipe beyond 7.5 mtr will be measured and paid separately. (Note:- 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost paid by department)
Supplying and laying synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
S&F hand rails, half round or other steel section or core for wooden hand rail straight portion drilled and countersunk for balusters running bars, for doors balusters, nosing to steps including embeding in concrete and screwing etc wind ties for roof including secruing bolts, post and struts in fencing including cuttings tops to shape as directed, dirlling hoels notching for wire etc, flat iron fillets (for screwing wire mesh etc) including all necessary drilling, bolting or riveting etc and simmilar work conforming to Fe-290-0 Gde-E-165 complete all as specified and directed.
S&F 4 mm dia GI wire chain link fencing and size of mess 100 x 100 mm fixed to any type of post with straining bolts etc including provn of binding wire complete all as specified and directed.
S&F mild steel round bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
M&L for formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter rough finished surfaces of concrete complete all as specified and directed.
S&F framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and directed.
M&L for ACSR conductor straightening properly on insulators and binding with aluminum taps/ binding wire/ conductor jumper etc complete of size 6/1x2.59mm (weasel) complete all as specified and directed.
M&L for laying of 20 mm graded coarse aggregate with making equal layer of surface on power sub station complete all as specified and directed.
S&F 22 mm dia copper pipeline of thickness 0.9mm, installing with complete accessories and laid on GI tray & supported with ms angle iron all as specified and directed.
S&F sleaves foam type insulation upto 22mm dia oxygen gas pipe line including complete packing with insulation tape and ms clamps, nut, bolt and washer of a distance 1 m apart from each other all as specified and directed.
S&F gas valve with valve box including complete accessories all as specified and directed.
M&L for perforated powder coated cable tray of size 25x75x25 mm, thickness 2mm for holding of oxygen gas pipe line complete all as specified and directed.
M&L for earthing complete with using copper earth plate (electrode) 600 mmx 600 mmx 3.15mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 20x3 mm copper earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, copper earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone agg)duly reinforced with mild steel round bars 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handles with and including necessary excavation & earth work including laying the GI pipe concealed in floor /wall all as per plate No. 3 of SSR Part I complete all as specified and directed and testing on completion..NOTE :- GI earth wire and protection pipe beyond 7.5 mtr will be measured and paid separately. (Note : 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost paid by department)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .