SPL REPAIR TO CENTRAL AC PLANT AGAINST BER AT CERTAIN UNIT UNDER GE BANAR
2026_MES_766098_1
CWE (A) JODH/BNR- OF 2026-27(82627/16/E8)
Open Tender
Electrical and Maintenance Works
270 days
BANAR
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
GE BANAR
₹2.1 L
Yes
18 May 2026
18 May 2026
18 Jun 2026
18 May 2026
16 Jun 2026
9 Jun 2026
18 May 2026 - 8 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Installing, testing and commissioning of WATER COOLED CHILLER complete 30 TR OR above nearest actual capacity with twin screw /Scroll compressor with twin circuit, motor(s) starter(s), WATER cooled condenser, insulated chiller, flow switch at chiller, vibration insolators, integral refrigerant piping and wiring, accessories as required and called for automatic and safety controls mounted in central console on a steel frame complete as per specifications. Motor shall be suitable for 415+(-) 10%, 50 cycles, 3 phase AC supply. Refrigerant used shall be R- 407C / R-134a.Chiller should be provided with micro- procesor based control panel for safe and efficient operatoin of chillers. Same should be capable for communicating over Bacnet/ Modbus protocol. Chiller compressor should have displacement power factor of 95% at all load conditions. Deration due to higher ambient shall also be considered in actual capacity calculation. Chiller should not trip at air inlet temperature of 52.0 Deg. C to condenser. complete all as specified and directed b y Engr-in-charges. | 3 | Each | 31,00,000 | ₹93,00,000 |
Chiller | - | - | 31,00,000 | - | |
Chiller Water IN 10 Deg C | - | - | 31,00,000 | - | |
Chilled water OUT 5 Deg C | - | - | 31,00,000 | - | |
Fouling Factor 0.00025 M2/KW | - | - | 31,00,000 | - | |
Condenser | - | - | 31,00,000 | - | |
Condenser Air IN 32 Deg C | - | - | 31,00,000 | - | |
Condenser Air IN 36 Deg C | - | - | 31,00,000 | - | |
Fouling Factor 0.0002 FPS | - | - | 31,00,000 | - | |
Screw Chiller Capacity Range should be - 100% to 15 % or better at constant design temperature. | - | - | 31,00,000 | - |