| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹13.8 LAccepted-AOC 10 532G ST MARY S BUILDING KANAKKARI KANAKKARI KOTTAYAM KERALA 686632 | KOTTAYAM | KERALA | 686632 | 1 | Accepted-AOC L1 |
Tender Value
₹16.5 L
EMD Value
₹41,236
Closing Date
15 Feb 2024, 11:30 amClosed
Chief Engineer, KIIDC
Parvathy, tc 36/1, nh 66 bypass service road, eanchakkal jn, chackai p.o., thiruvananthapuram- 695024.
Installation of Solar power plant
2023_KIIDC_632662_2
IRR/KIIDC/TR/4942/2023_6_1_1/2
Open Tender
Electrical Works
Item Rate
60 days
Kanjirapally
Please refer Tender Document
4 documents required · 4 mandatory
₹2,760
₹41,236
19 Mar 2024
6 Feb 2024
17 Feb 2024
6 Feb 2024
15 Feb 2024
6 Feb 2024
Amount
20KW ROOFTOP SOLAR PV POWER PLANT FOR NEW BLOCK
OD27306/2023-2024:Supply, Installation, Testing and Commissioning of 20 kW On-grid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono Per half cut Solar PV panel solar cells, net metering facility, necessary protections, earthing, mounted on GI structure of suitable strength with following components complete as required:- 1) Solar Photovoltaic Module of capacity 545Wp Wp or above, manufactured in India, conforming to IS14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photo Voltaic Module conversion efficiency shall not be less than 18.3%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. 2) Solar grid tie inverter of 20kW capacity of 0-600 V DC Input voltage range, output voltage of three-phase, 415V, 4 wire, 50Hz, AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and ideal for ambient temperature from 0 to 60degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency and shall be capable of operating in parallel with the grid utility service as per IEC 61727 and shall be capable of interrupting line-to-line fault currents and line-to-ground fault currents. Inverter shall be direct current isolation provided at the output . The PCU-generated harmonics, flicker, DC injection limits, Voltage Range, Frequency Range and Anti-Islanding measures at the point of connection to the utility services should follow the latest CEA (Technical Standards for Connectivity Distribution Generation Resources) Guidelines. Communication Modbus protocol with LAN/WAN/GSM options along with remote access facility and SCADA package with latest remote monitoring systems. Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. 3) Lightning and surge voltage protection. Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing necessary channel/conduit lugs and other accessories etc. as required. The Grid interfacing, including all equipment required for the same such as breakers, isolators, lightning arrestors, panels, protection equipment, cables, conductors and SPV Panel yard etc. as per statutory requirements and comply with the CERC Grid code. Each of the equipment/ components utilised shall be compliant and be subjected to all routine and acceptance tests prescribed in the relevant Indian Standard Specification/IEC. 4) Comprehensive AMC of the entire solar power plant for 5 years from the date of handing over. The cost includes all spares, cleaning charges, data and recurring charges for communication equipment, etc. as required
5KW ROOFTOP SOLAR PV POWER PLANT FOR TOILET BLOCK
OD29942/2023-2024:Supply, Installation, Testing and Commissioning of 5 kW On-grid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Solar PV panel, net metering facility, necessary protections, earthing, lightning protection and PV panels mounted on GI structure of suitable strength with following components complete as required:- 1) Solar Photovoltaic Module - Mono Per half cut of capacity 545Wp Wp or above, manufactured in India, conforming to IS14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photo Voltaic Module conversion efficiency shall not be less than 18.3%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. 2) Solar grid tie inverter of 5kW capacity of 0-600V DC Input voltage range, output voltage of three-phase, 415V, 4 wire, 50Hz, AC Power with efficiency not less than 98%, total harmonic distortion less than 3% and ideal for ambient temperature from 0 to 60 degree C in a IP65 enclosure. The inverter shall adjust the voltage and frequency level to suit the Grid Voltage Frequency and shall be capable of operating in parallel with the grid utility service as per IEC 61727 and shall be capable of interrupting line-to-line fault currents and line-to-ground fault currents. Inverter shall be direct current isolation provided at the output . The inverter-generated harmonics, flicker, DC injection limits, Voltage Range, Frequency Range and Anti-Islanding measures at the point of connection to the utility services should follow the latest CEA (Technical Standards for Connectivity Distribution Generation Resources) Guidelines. Communication Modbus protocol with LAN/WAN/GSM options along with remote access facility and SCADA package with latest remote monitoring systems. Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. MNRE & IEC compliance GTI complies with all the National & International standards for safety and efficiency and reliability, such as IEC - 61683, IEC - 60068, IEC - 61000, IEC - 61727, IEC - 62116 3) Lightning and surge voltage protection. Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing necessary channel/conduit lugs and other accessories etc. as required. The Grid interfacing, including all equipment required for the same such as breakers, isolators, lightning arrestors, panels, protection equipment, cables, conductors and SPV Panel yard etc. as per statutory requirements and comply with the CERC Grid code. Each of the equipment/ components utilised shall be compliant and be subjected to all routine and acceptance tests prescribed in the relevant Indian Standard Specification/IEC. 4) Comprehensive AMC of the entire solar power plant for 5 years from the date of handing over. The cost includes all spares, cleaning charges, data and recurring charges for communication equipment, etc. as required.
LT cabling and connection
OD12427/2023-2024:Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4Cx16sq.mm Al Cable
7.8.1:Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
Civil work
2.10.1.1:Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m: All kinds of soilPipes, cables etc, not exceeding 80 mm dia
Bidder Name
Roze solar solutions Pvt Ltd
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .