Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.2 LAccepted-AOC | L1 | Accepted-AOC lowest | |
| 2 | L2₹40.3 L+₹1.1 L (2.81%)Rejected-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | L2 | Rejected-AOC second lowest | |
| 3 | L3₹40.3 L+₹1.1 L (2.91%)Rejected-AOC | L3 | Rejected-AOC third lowest |
| Sl No | Description | Qty | Unit | GK INDUSTRIES L1 | Kittu Electricals private limited L3 | ELCON ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00SITC of 125 KVA DG set . | ||||||
| 1.00 | OD150706/2024-2025:Supply & Installation Testing and Commissioning of 125 KVA Diesel Generator set including required contactors/ control devices and acoustic enclosure as per CPCB norms IV+ and as per technical details given below on suitable size CC foundation. 1. Engine. a).Type of Engine - Prime Power Diesel Engine. b). No. of Cylinders - As per manufactures standards. c). Method of cooling - Liquid cooled with radiator. d). Aspiration - Turbo charged after cooled e). Design - Suitable for generating set operation. f). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2. Standard accessories with Diesel Engine a. Fly wheel to suit flexible coupling b. Close Coupling. c. Air cleaner. d. Radiator with fan provided with fan guard e. Fuel Pump. f. Mechanical governor. g. Fuel filter. h. Lubricating oil filter. i. Exhaust silencer. j. Exhaust Muffler k. Battery Charger/Generator 3. Engine Instrument Panel with the following items. a. Starting switch with key or button b. Lubricating oil pressure gauge. c. Water temperature gauge. d. RPM Indicator with hour meter. e. Battery charging ammeter. 4. Safety Controls for Engine and Alternator a. Trip for low lubricating oil pressure. b. Trip for high water temperature. c. Trip for Over Voltage, Under Voltage, Over frequency and under Frequency etc 6. Brush less Alternator a. Make - Stamford or equivalent b. Type - Self exited and self regulated. c. Capacity -125 KVA/100 kW @ 0.8 PF d. System of Voltage - 3 Phase, 415 V, 4 wire system e. Speed - 1500 rpm. f. Voltage regulation band - +/- 0.5% of rated voltage g. Frequency : 50 Hz h. Insulation - Class H The alternator should confirm to IS 4722 and warranted for 2 years.Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel Fuel connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10 Acoustic enclosure The DG set shall be supplied along with specially designed, company fabricated (to be fabricated by the same company from where the DG is delivered) acoustic enclosure to meet the stringent MOEF/CPCB norms of 75dBA @ 1m at 75 % load under free field conditions. Acoustic enclosure: As per CPCB norms and erected on suitable concrete foundation. The DG set shall be installed as directed at site. 11.Standard control panel including all necessary accessories and meters 12 Documents to be supplied Engine manual Spare parts book Warranty certificate Alternator manual and test certificate 1 set of control wiring diagram 1 set tool kit The DG set should have single point service for supply , Testing include Engine, Alternator and Control panel. The DG set should have warranty of 3 years from the date of installation. Exhaust Piping Exhaust Piping shall be vent to the top of the nearest tallest building. If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of synthetic enamel paint over a coat of zinc chromate primer shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) Supply and providing following size B class MS pipe complete with suitable size 12 mm thick flanges coupling with minimum 4/5 mtr length using suitable packing , MS bolt , nut, and washers and raising the same using chain pullers , necessary scaffolding, supporting with main building using necessary channel/ angle iron bracketing suitable size. including painting with two coat of high temperature resistance aluminium paint after zinc rich primer etc.. for extending exhaust pipe of DG set after standard length. The Contractor should carry out all the Periodical services as per manufactures instructions during the defect liability period, including the supply of materials required. such as oil, filters etc. | 1 | each | 14,30,000 ₹14,30,000 | 14,80,000 ₹14,80,000 | 14,00,000 ₹14,00,000 Lowest |
| 1.00 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | 3 | set | 7,500 ₹22,500 Lowest | 8,000 ₹24,000 | 8,200 ₹24,600 |
| 1.00 | 5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) | 35 | metre | 1,050 ₹36,750 | 1,050 ₹36,750 | 800 ₹28,000 Lowest |
| 1.00 | 90.12.10.6:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size | 40 | metre | 410 ₹16,400 | 420 ₹16,800 | 400 ₹16,000 Lowest |
| 1.00 | 90.16.2.3:Supply and laying of the following sizes of
B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class) | 15 | metre | 400 ₹6,000 Lowest | 500 ₹7,500 | 500 ₹7,500 |
| 1.01 | 90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip | 100 | metre | 460 ₹46,000 Lowest | 490 ₹49,000 | 750 ₹75,000 |
| 1.01 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.
Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) | 4 | sqm | 2,400 ₹9,600 Lowest | 2,600 ₹10,400 | 2,500 ₹10,000 |
| 1.01 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. | 0.3 | sqm | 3,500 ₹1,050 | 3,000 ₹900 Lowest | 3,000 ₹900 Lowest |
| 1.01 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board | 50 | kg | 17 ₹850 Lowest | 150 ₹7,500 | 150 ₹7,500 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
21 Jul 2025, 6:00 pmClosed
Executive Engineer
O/o Executive Engineer PWD Electrical Division Thrissur
LAC ADS THQ Kothamangalam SITC of DG for new block SITC of DG set AC units and UPS in new casualty dialysis block under THQ Hospital at Kothamangalam General Electrical Work
2025_PWD_776573_1
PWD/BLDG/5518/2025-2026
Open Tender
Electrical Works
Item Rate
180 days
Ernakulam
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,760
₹50,000
25 Aug 2025
14 Jul 2025
24 Jul 2025
14 Jul 2025
21 Jul 2025
14 Jul 2025
Amount
SITC of 125 KVA DG set .
OD150706/2024-2025:Supply & Installation Testing and Commissioning of 125 KVA Diesel Generator set including required contactors/ control devices and acoustic enclosure as per CPCB norms IV+ and as per technical details given below on suitable size CC foundation. 1. Engine. a).Type of Engine - Prime Power Diesel Engine. b). No. of Cylinders - As per manufactures standards. c). Method of cooling - Liquid cooled with radiator. d). Aspiration - Turbo charged after cooled e). Design - Suitable for generating set operation. f). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2. Standard accessories with Diesel Engine a. Fly wheel to suit flexible coupling b. Close Coupling. c. Air cleaner. d. Radiator with fan provided with fan guard e. Fuel Pump. f. Mechanical governor. g. Fuel filter. h. Lubricating oil filter. i. Exhaust silencer. j. Exhaust Muffler k. Battery Charger/Generator 3. Engine Instrument Panel with the following items. a. Starting switch with key or button b. Lubricating oil pressure gauge. c. Water temperature gauge. d. RPM Indicator with hour meter. e. Battery charging ammeter. 4. Safety Controls for Engine and Alternator a. Trip for low lubricating oil pressure. b. Trip for high water temperature. c. Trip for Over Voltage, Under Voltage, Over frequency and under Frequency etc 6. Brush less Alternator a. Make - Stamford or equivalent b. Type - Self exited and self regulated. c. Capacity -125 KVA/100 kW @ 0.8 PF d. System of Voltage - 3 Phase, 415 V, 4 wire system e. Speed - 1500 rpm. f. Voltage regulation band - +/- 0.5% of rated voltage g. Frequency : 50 Hz h. Insulation - Class H The alternator should confirm to IS 4722 and warranted for 2 years.Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel Fuel connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10 Acoustic enclosure The DG set shall be supplied along with specially designed, company fabricated (to be fabricated by the same company from where the DG is delivered) acoustic enclosure to meet the stringent MOEF/CPCB norms of 75dBA @ 1m at 75 % load under free field conditions. Acoustic enclosure: As per CPCB norms and erected on suitable concrete foundation. The DG set shall be installed as directed at site. 11.Standard control panel including all necessary accessories and meters 12 Documents to be supplied Engine manual Spare parts book Warranty certificate Alternator manual and test certificate 1 set of control wiring diagram 1 set tool kit The DG set should have single point service for supply , Testing include Engine, Alternator and Control panel. The DG set should have warranty of 3 years from the date of installation. Exhaust Piping Exhaust Piping shall be vent to the top of the nearest tallest building. If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of synthetic enamel paint over a coat of zinc chromate primer shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) Supply and providing following size B class MS pipe complete with suitable size 12 mm thick flanges coupling with minimum 4/5 mtr length using suitable packing , MS bolt , nut, and washers and raising the same using chain pullers , necessary scaffolding, supporting with main building using necessary channel/ angle iron bracketing suitable size. including painting with two coat of high temperature resistance aluminium paint after zinc rich primer etc.. for extending exhaust pipe of DG set after standard length. The Contractor should carry out all the Periodical services as per manufactures instructions during the defect liability period, including the supply of materials required. such as oil, filters etc.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
90.12.10.6:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.11.6:MCCB AccessoriesSupply and fixing 250 - 400A earth fault module of MCCB with builtin CBCT.
OD76723/2025-2026:Supply, conveyance and filling high grade Diesel
OD76720/2025-2026:Supply and providing the 25x6 mm sizes of bolt and nut with washers on the existing MS box /earth bus etc. as required including drilling necessary holes as required
OD76719/2025-2026:Supply and providing the 25 x 3mm sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
OD76718/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD213884/2022-2023:Supply and providing 5/6 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD92106/2025-2026:Supply and providing 2.5mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength including fixing with suitable synthetic adhesive,
OD213886/2022-2023:Aluminium anodised semi oval type legend plate with inscription of ON/ OFF/ FORWARD/ REVERSE/ START/ STOP/ UP/ DOWN/ R PHASE/ Y PHASE/ B PHASE/ TRIP/ OPEN/ CLOSE/ LEFT/ RIGHT/ MOTOR ON/ MOTOR OFF/ ACCEPT/ RETRACT/ RESET/ EMERGENCY/ EMERGENCY ON/ EMERGENCY OFF/ PUMP RUNNING/ PUMP OFF/ EMERGENCY STOP/ SLOW/ FAST or other inscriptions directed.
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD19352/2025-2026:Supply and fixing thermal insulation with 50 mm thick glass wool around the MS pipe. including providing cladding with 0.63 mm Aluminium sheet neatly.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
OD93098/2025-2026: Supply, fabrication, and fixing 100 x 150 mm size or nearest size 0.3 Mtr / nearest length MS pipe reducer with C class pipes facing the cutting edges painting with two coats 600°C Heat Resistant Aluminium Paint etc complete.as per the direction of the departmental officers at site
OD93099/2025-2026: Supply and fabrication 100 mm dia C class 0.5 mtr/required long MS pipe bend by using Tata/Jindal/equivalent make pipe facing the cutting edges painting with two coats of 600°C Heat Resistant Aluminium Paint etc complete.as per the direction of the departmental officers at site
OD93100/2025-2026: Supply and fabrication 150 mm dia C class 0.5 mtr/ nearest lonth MS pipe bend by using Tata/Jindal/equivalent make pipe facing the cutting edges painting with two coats of 600°C Heat Resistant Aluminium Paint etc complete.as per the direction of the departmental officers at site
OD93101/2025-2026: Supply and conveying 150 mm dia ISI marked Tata/ Jintal /equivelent make seem less C- Class MS pipe and cutting in to required length, facing the cutting edges , including conveyance charges to High court compound, and installation / clamping of the same on wall/parapet / cross beams/ ceiling including labour charges for loading, unloading, scrapping, cleaning, removing oil particles if any, painting the pipe with 2 coats of 600°C Heat Resistant Aluminium Paint etc. including lifting charges to height using lifting machines as per the direction of the departmental officers at site.
OD93102/2025-2026: Supply and conveying 100 mm dia ISI marked Tata/ Jintal /equivelent make seem less C- Class MS pipe and cutting in to required length, facing the cutting edges , including conveyance charges to High court compound, and installation / clamping of the same on wall/parapet / cross beams/ ceiling including labour charges for loading, unloading, scrapping, cleaning, removing oil particles if any, painting the pipe with 2 coats of 600°C Heat Resistant Aluminium Paint etc. as per the direction of the departmental officers at site.
OD93123/2025-2026: Supply, and providing MS flanged joint for 100 /150 mm MS pipe, with 12 mm thick MS flanges, including welding the flanges to MS pipes, providing suitable size 5 mm thick / nearest asbestos packing between flanges, and necessary MS bolt and nuts with washers, painting with two coats 600°C Heat Resistant Aluminium Paint etc complete.as per the direction of the departmental officers at site
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD92176/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run
OD214052/2022-2023:Charges for scheme preparation for submitting to Electrical inspectorate, after collecting the existing and proposed details
OD214056/2022-2023:Supply and fitting LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
90.12.5.33:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 150 sq mm
90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.15:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 150 sq. mm (50mm)
OD214367/2022-2023:Supply , installation , testing and commissioning of 5 KVA UPS, with Isolation transformer, Output Volts 230V, Charging a) 1 ph to 1 ph b) Input pf : 0.99 @ full load c) Output pf : unity d) Input voltage range : 140V -280V with cut off e) THD : ≤ 10% f) Overall Efficiency : 87% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave. j) Battery over charge & under charge cut off. k) 3 year warranty. l) Bypass arrangement. m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : exide / panasonic or equivalent current Up to 15A, MS battery rack ,battery inter connection with copper wire Brand approved Socomech / Techser / NUMERIC-LEGRAND/APC/ GE suitable for Dialysis unit ) 12v 150 ah x 10 Nos tubular batteries C10 rated, Exide/Amron make. For 2 hours backup total VAH 12480. 3 years warranty )
OD214368/2022-2023:SITC of Inverter type wall mounting split air conditioner unit of the following ratings conforming to relevant IS suitable for operating on 230V, 50Hz single phase AC supply, filled with R-410 A refrigerant gas, high energy efficient, RoHS complaint, capable of performing functions like cooling,dehumidifying, air circulating, filtering etc of following capacity including refrigerant copper piping 3m with insulation,control cable up to 5m, 3 m drain pipe, condenser stand, microprocessor control with cordless remote control, base frame etc. . PCB should have minimum 5 year warranty and 10 year warranty on compressor(warranty card are to be provided). It should be ensured that the air conditioner is in perfect working during the entire guarantee period. 2/2.2TR (3 Star& above) Inverter A.C unit, (Blue star/LG/ Daikin / carrier/Panasonic/Hitachi) Including stand and Installation charges & the periodical service during the Defect liability period. 1.8 / 2 Tr single phase 5 Star rated high wall inverter type Split Ac unit( Thosiba, Daikin, Carrier)
OD214369/2022-2023:Supply, Conveyance & Installation of Voltage stabilizer suitable for split type 2 TR AC unit, capacity 15A with voltage range of 175-275V and out put range of 210 - 240V (V Guard VG500) or its equivalent.
OD214753/2022-2023:Supply and providing 3/8 inch ( 9.52 mm ) and 5/8 inch ( 15.8 mm ) 22 SWG soft drawn copper refrigerant pipe with all accessories such as elbow, support clamp etc. for interconnecting indoor unit and condensing unit, bracing, leak testing including thermal insulation with 10 m m nitrile rubber etc.
OD92515/2025-2026:SITC of insulated condensate drain piping out of PVC-6kg/cm2 pipes complete with hangers/ supports/ clamps/clips and all fittings etc and insulated with 13 mm thoick nitrile rubber sleeves and joints sealed with 50 mm black PVC tapes-25 mm dia
1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
OD214937/2022-2023:Supplying and clamping 20 mm sizes of corrugated PVC flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI / painted MS saddles spacing not exceeding 60 cms on surface including making good the damages, colour washing etc. as required
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.23:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External tee
OD24201/2025-2026:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD92391/2025-2026:Supply and fixing LED indicator (6 V AC/DC, 12V AC/DC, 24 V AC/DC, 48V AC/DC, 63.5V AC/DC, 110 V AC/DC, 220V DC, 240 V AC), 22.5 mm cut out dia (Red, Green, Black, Yellow, Orange colours )
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
OD98194/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required. 4 sqmm-16 sqmm with 12 mm wide x 1 mm thick clip
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD24833/2025-2026:Supply and fixing V,A,F, 3 Phase meter (multi function meter) with accuracy class 1 in the existing panel assembly and giving connection etc as required.
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
OD27207/2025-2026:Providing and fixing 250A 4P ATS with AST controller
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD27235/2025-2026: Supply, conveyance, installation , testing and commissioning of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan
OD27251/2025-2026:Dismantling and refitting charges of Fan,Tube , Switch box etc in to another places and fixing ,making wire connection etc in good working conditions as per direction from dptl. officials .
OD27263/2025-2026:Dismantling charges of Fan,Tube , Switch box etc
90.3.5:Conveyance, installation, testing and commissioning of pre-wired light fitting of all types complete with all accessories and fluorescent lamps etc. suspended from ceiling using 2 nos steel chain (16 SWG or nearest available size) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.
OD27254/2025-2026:Supply,installation,testing and commissioning of 1800 lumen round/ square surface mount down light fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea directly on ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
OD27255/2025-2026:Supply,conveyance,installation,testing and commissioning of 3600 lumen square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea pre-wired fluorescent fitting complete with all accessories and fluorescent lamps etc. suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. (for fitting in false ceiling)
OD27279/2025-2026:Charges for rearranging the position of MSB panel board after disconnecting the existing cables without any damages
OD27376/2025-2026:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit with modular switch, modular plate etc as required
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD28725/2025-2026: Supply, conveyance installation testing and commissioning the light fittings made of CRCA sheet with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. including providing 1200 mm 20 W T8 LED tube , having total efficiency of 100 Lumen /watt with 4 feet Aluminium extrusion in the tube for better heat dissipation,, THD < 20% PF> 0.95 ( LM 79 & LM 80 Certificate from NABL should be submitted )
ELCON ELECTRICALS (BID ID -2257696)
Kittu Electricals private limited (BID ID -2257298)
Bidder Name
Kittu Electricals private limited
ELCON ELECTRICALS
GK INDUSTRIES
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .