The E.E.(O&M), Sachin Division
Tenderization for ARC Work of Laying testing & commissioning of 11/22 KV UG XLPE CABLE with 11/22 KV Cable End Termination & ST joint Kits (to be Supplies by Agency) along with Dismantle of HT,LT & TC works under Kharvasa sub division and if required any other Sdn under jurisdiction of Sachin Division under ND and if Required Any other Scheme.
328208
SD/O&M/EXP/26/697 Date:27.07.2026
Open
Electrical Works
Works
Surat
6 documents required · 6 mandatory
₹1,180
Online Payment in DGVCL Sachin Division Account
₹40,000
28 Jul 2026
28 Jul 2026
28 Jul 2026
13 Aug 2026
28 Jul 2026
ITEM CODE Details of Works Qty Unit Amount
Labour charge for excavation of cable trench of 400mm width x
1200mm depth, in any type of soil for laying of cable of size up to
240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x
1200mm depth, in any type of soil for laying of cable of size up to
240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 400mm width x
1500mm depth, in any type of soil for laying of cable of size up to
240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to
240 mm2 & preparation of sand layer 100mm thick, in the cable
trench & covering the cable with 150 mm dia (Inner), thickness
mm, 1.0 meter long RCC half round muffs and providing and
fixing of 4inch width yellow colour polyethylene tape with printing
"CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from
ground surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as to
protect cable from mechnical injuries, refilling the same, as per
Instruction of Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger machine without
damage to surface road at max 2.0 mtrs depth & putting of
kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to
240 mm2 in HDPE pipe, as per Site Condition (excluding cost of
pipe). The detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment for HDD is
must required to be submitted. HDD to be carried out at depth
mtrs to 2.0 mtrs as per site conditions and as per instruction of
Labour charge for horizontal drilling manually without damage to
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2
class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984-1987(3rd revision) and BIS certification
and laying of 11KV/22KV XLPE cable of size up to 240 mm2 size,
as per Site Condition (excluding cost of pipe). The detail map and
excell sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment of cable
to be submitted. Drilling to be carried out at depth Minimum
mtrs to 2.0 mtrs as per site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. ,
mm thickness H.D.P.E. pipe confirms to IS 4984 and BIS
certification for laying of underground 11KV / 22KV XLPE cable
up to 240 mm2 size.
Labour work for RCC concreting on disputed location and
repairing of damage portion of road crossing for the work carried
out for roads crossing as well as concreting & muffing of ploes
including all materials (1:2:4)
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Providing & fixing concrete stone route marker of 300 mm width x
150 mm thick x 650 mm height embedded in earth at least
mm below & 350 mm above ground level respectively at distance
approx 50 meters along the length of cable. The RCC concreting
(1:2:4)(all necessary maeterials will be in bidder's scope) of route
marker is to be carried out 300 mm width x 150 mm thick x
9 9925000009 mm below ground level as per instruction of EIC. The route No. 446
marker should be with name of company with approved yellow
colour-DGVCL. The distance from marker to cable and cable
depth with feeder name etc., marked with arrow sign is to be
painted on it.The route marker is to be fixed at location near to
any fixed permanent location (not necessary to fix exact on top of
cable) as per instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole
with cable connection arrangement along with fitting of necessary
10 9925000010 fabrication for 11KV cable including excavation of pit & refilling of No. 2026
earth as per instruction of EIC. (Exclusive of concreting & muffing
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with
cable connection arrangement along with fitting ofnecessary
11 9925000011 fabrication for 11KV/22 KV cable including excavation of pit & No. 1047
refilling of earth as per instruction of EIC. (Exclusive of concreting
& muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole
with cable connection arrangement along with fitting of necessary
12 9925000012 fabrication for 11KV cable including excavation of pit & refilling of No. 1416
earth as per instruction of EIC. (Exclusive of concreting & muffing
Erection of Single pole structure using 8.0 Mtr PSC pole with
cable connection arrangement along with fitting ofnecessary
13 9925000013 fabrication for 11KV/22 KV cable including excavation of pit & No. 613
refilling of earth as per instruction of EIC. (Exclusive of concreting
& muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up
to 240 mm2 on DP Structure with fixing of 02 Nos polymer cleats per
on top and middle part.Polymer cleats, nut bolts etc. fixing Job
material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984 and
BIS certification on the erected DP structure for the mechanical
protection of cable by inserting the cable inside HDPE pipe. The Per
HDPE pipe shall be erected in such a way that 300mm shall be Job
below the ground level and the rest 2700 mm shall be supported
on the DP Structure with 01 No Polymer cleat.All materials
including polymer cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B
GI pipe with pit to be filled with salt & coke and construction of
chamber as per DGVCL Drg. No. dg /100 for DP and cable. The
earthing pit should be joined with cable by G.I. strip of size 1”
width & 2 mm thick. All material GI pipe, Coke, Salt etc will be
supplied by bidder.
Supply & fixing of heat shrink type end terminations
(outdoor) for upto 11kV 3C x 185 mm2 size XLPE cable as per
DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for
18 9925000018 upto 22 kV 3C x 185 mm2 size XLPE cable as per DGVCL No. 6231
technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for
19 9925000019 upto 11kV 3C x 185 mm2 size XLPE cable as per DGVCL No. 3635
technical specification)
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Supply & fixing of heat & shrinkable end terminations (indoor) for
20 9925000020 upto 22 kV 3C x 185 mm2 size XLPE cable as per DGVCL No. 6231
technical specification
Supply & fixing of heat shrinkable straight through joint for upto
21 9925000021 11kV 3C x 185 mm2 size XLPE cableas per DGVCL technical No. 6774
Supply & fixing of heat shrinkable straight through joint type for
22 9925000022 upto 22kV 3C x 185 mm2 size XLPE cable as per DGVCL No. 11590
technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x
1200 mm deep joint pits for installation of 11kV / 22kV Straight
through joints as per instruction of engineer-in-charge & covering
the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter
long RCC half round muffs & refilling same as per instruction of
Providing and fixing of insulating bus bar, made from 11KV/22KV
XLPE cable after removal of semi conducting layer and applying
of PVC heat shrinkable anti-tracking core insulating tubing
(1.1KV), on both end terminal using Aluminium long barrel heavy
24 9925000024 duty up to 240 sq mm lugs, Aluminium bus connector. Taping with No. 1661
PG- clamp for bus conductor as per drawing and as per
instruction of EIC. The Alluminium lugs and PG clamp shall be
covered with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE
cable will be in scope of DGVCL while all other materials will be in
bidder's scope)
Testing of cable at various points and commissioning the
25 9925000025 feeder as per instruction of engineer-in-charge.Test result No. 2125
shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout
drawings with GIS mapping as per actual cable routing showing
road crossing, HDPE pipe sleeving, jointing locations, markers
Providing and fixing of Sign Board at junction point Made out of
mm aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as
per design, pre treated with phosphate process and acid etching
coated with one coat of epoxy primer and two coats of best
quality paints, refloctrorised with Hi-Intensity retro – reflective
sheeting as per the latest and frame fabricated from suitable size
iron angle. The Sign Board is to be fixed on the base prepared
from channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x 800 mm
height (500 mm to be grouted in ground). The details to be
displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on Distribution
Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as
per design, pre treated with phosphate process and acid etching
coated with one coat of epoxy primer and two coats of best
28 9925000028 quality paints, refloctrorised with Hi-Intensity retro-reflective No. 2805
sheeting as per the latest and frame fabricated from suitable size
iron angle. The Sign Board (Danger Board is to be fixed at the
location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm
(W) from 3 mm aluminium sheet along with 1.0 mm dia aluminium
binding wire for fixing of aluminium tag near end termination joint
29 9925000029 at DP structure for identifyng the cable. The details of feeder i.e. No. 83
11 / 22 KV with feeder name shound be punched on the tag by
letter punch of size 16 mm as per instruction of In-charge
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Supply & fixing of heat shrink type end terminations (outdoor) for
30 9925000030 11kV 3C x 240 mm2 size XLPE cable as per DGVCL technical No. 4427
Supply & fixing of heat & shrinkable end terminations (outdoor) for
31 9925000031 22 kV 3C x 240 mm2 size XLPE cable as per DGVCL technical No. 6231
Supply & fixing of heat shrink type end terminations (indoor) for
32 9925000032 11kV 3C x 240 mm2 size XLPE cable as per DGVCL technical No. 4338
Supply & fixing of heat & shrinkable end terminations (indoor) for
33 9925000033 22 kV 3C x 240 mm2 size XLPE cable as per DGVCL technical No. 6231
Supply & fixing of heat shrinkable straight through joint for 11kV
34 9925000034 3C x 240 mm2 size XLPE cableas per DGVCL technical No. 6829
Supply & fixing of heat shrinkable straight through joint type for
35 9925000035 22kV 3C x 240 mm2 size XLPE cable as per DGVCL technical No. 11590
Installation, Testing and commissioning of 11 KV,630 A SCADA
Compatible, RRL type- 3 Way RMU including Two numbers of
earthings as per Drawing (material is in bidder's scope) and as
per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A SCADA
Compatible, RRLL type- 4 Way RMU including Two numbers of
earthings as per Drawing (material is in bidder's scope) and as
per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA
Compatible, RRL type-3 Way, RMU including Two numbers of
earthings as per Drawing (material is in bidder's scope) and as
per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA
Compatible, RRLL type-4 Way, RMU including Two numbers of
earthings as per Drawing (material is in bidder's scope) and as
per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way (i.e Two
numbers of Isolator & One number of Breaker) Ring Main Unit as
per DGVCL's technical specification mentioned in drawing no:
Drg. 11kv-01. All required material will be supplied by contractor.
Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main Unit as
per DGVCL's technical specification mentioned in drawing no:Drg.
11kv-02.All required material will be supplied by contractor.
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two
numbers of Isolator & One number of Breaker) Ring Main Unit as
per DGVCL's technical specification mentioned in drawing no:
Drg. 22kv-01. All required material will be supplied by contractor.
Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two
numbers of Isolator & Two number of Breaker)Ring Main Unit as
per DGVCL's technical specification mentioned in drawing no:Drg.
22kv-02.All required material will be supplied by contractor.
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Modifications e.g.Providing and fixing of Terminal protectors i.e.
Re-use able boot (HT Side 11/22KV, LT Side 1.1KV) including
11/22 KV insulating taps and L.T.(1.1 KV) insulating taps ,Busbar,
Tapping from Bus Bar (11/22 KV XLPE cable) through P.G.
Clamp for H.T. Jumper to D.O. Fuse to bushings of Transformer
Center, providing & Fixing of jumper and providing & fixing of Heat
Shrinkable Anti Tracking Core Insulating Tubing (Insulation Level
44 9925000046 11/22 KV) in H.T. jumper , Clamping arrangement of cable No. 10152
support frame on both side of existing Over Head type Distribution
Transformer to utilize in Under Ground cable network as per
drawing & as per instruction of Engineer incharge. All live parts
i.e. PG-Clamp, connections of D.O.fuses, HT bushings etc . shall
be covered with fixinng of 11/22 KV HT insulating tapes. ( 11/22
KV XLPE cable will be in scope of DGVCL while all other
materials will be in bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade cable
trench or in open space
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM 70320
Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long
RCC half round pipe
Laying (Including Installation , Testing and Commissioning) of
various size of 11 KV XLPE Insulated alluminium armoured cable
in ground 1200 mm Deep , 300 mm Wide Trench, Providing sand
cushioning below (75 mm thick layer of sand ) and above (75 mm
thick layer of sand ) of the cable and covering it with RCC Half
round hume pipe (150 mm inner dia with thickness of 30 mm,1
meter length) before refilling pre-bonding / warning tap should
provide below 700 mm from the ground level and back filling the
same to make ground level as per original. As per Specification
and drawing og UGVCL. ( RCC Half Round pipe should be
provide thorughout on cable wihtout gap, only cable will be
supplied by DGVCL)
Laying (Including Installation , Testing and Commissioning) of
various size of Double Circuit 11 KV XLPE Insulated alluminium
armoured cable in ground 1200 mm Deep , 500 mm Wide Trench,
Providing sand cushioning below (75 mm thick layer of sand ) and
above (75 mm thick layer of sand ) of the cable and covering it
with RCC Half round hume pipe (150 mm inner dia with thickness
of 30 mm,1 meter length) before refilling pre-bonding / warning tap
should provide below 700 mm from the ground level and back
filling the same to make ground level as per original. As per
Specification and drawing og UGVCL. ( RCC Half Round pipe
should be provide thorughout on cable wihtout gap, only cable will
be supplied by DGVCL)
Layingt of HDPE Pipe Confirming to IS 4984:1955 (Ammendment
No 2) having diameter 160 mm and minimum thickness 5 mm at a
minimum depth of 1200 mm below the road surface by push
thorugh method by drilling the road with HDD machine/manually
without breaking the road surface and laying of any size of HT/LT
XLPE insulated alluminium armoured cable through the duct as
per the instruction of EIC and specifications. (Without cost of
HDPE Pipe , Cable will be supplied by DGVCL)
Supply of HDPE Pipe having 160 mm diameter , minimum
4 thickness 7.3 mm as per IS (ammendment no 2 - IS 4984:1995) Meter 640
of PE- 100 , 6 kg/cm2 , for laying of 11 KV XLPE Cable
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Proving and Fixing HT push on/heat shrink type End Indoor
termination kit Preferably 3m(m-seal) or Raychem make at
switchgear end boxes, transformer (PAD/Pole mounted) for 3 core
11 kV XLPE Aluminium Conductor Armoured cable as specified
with connection of leads including cutting, stripping of cable,
insulations, providing compression type terminal ,crimping of lugs
with suitable crimping tool, indoor application.
For 300 mm2 HT XLPE Cable
Proving and Fixing HT push on/heat shrink type End Outdoor
termination kit Preferably 3m(m-seal) or Raychem make at
switchgear end boxes, transformer (PAD/Pole mounted) for 3 core
11 kV XLPE Aluminium Conductor Armoured cable as specified
with connection of leads including cutting, stripping of cable,
insulations, providing compression type terminal ,crimping of lugs
with suitable crimping tool, outdoor application.
For 300 mm2 HT XLPE Cable
Proving and Fixing HT push on/heat shrink type Straight Joint
Preferably 3m(m-seal) or Raychem make for 3 core 11 kV XLPE
Aluminium Conductor Armoured cable as specified with
7 connection of leads including cutting, stripping of cable, No. 8040
insulations, providing compression type terminal ,crimping of lugs
with suitable crimping tool.
For 300 mm2 HT XLPE Cable
DISMENTALLING Schedule B-3
DISMENTALLING OF 8 MTR PSC POLE WITH CREDITING OF
1 9926000033 FABRICATION AT STORE & STACKING OF POLE SAFELY ON No. 678
ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF 10 MTR PSC POLE WITH CREDITING OF
2 9926000034 FABRICATION AT STORE & STACKING OF POLE SAFELY ON No. 1350
ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC
POLE) (WITH TRANSFORMER) WITH CREDITING OF
3 9926000035 FABRICATION & TRANSFORMER AT STORE & STACKING OF No. 3975
POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC
POLE) (WITHOUT TRANSFORMER) WITH CREDITING OF
FABRICATION AT STORE & STACKING OF POLE SAFELY ON
ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALING OF RSJ (9/11 METER) POLE AND
CREDITING THE OLD MATERIAL TO STORE
DISMENTALING OF TRANSFORMER CENTER ON
10MTR,270KG PSC POLE(WITHOUT TRANSFORMER) WITH
6 9926000043 CREDITING OF FABRICATION AT STORE AND STACKING OF No. 2828
POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTALING OF TRANSFORMER CENTER ON
10MTR,270KG PSC POLE(WITH TRANSFORMER) WITH
7 9926000044 CREDITING OF FABRICATION AT STORE AND STACKING OF No. 5332
POLE SAFELY ON ROAD SIDE OR CREDITING TO
DEPARTMENTAL STORE
DISMENTLING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM
8 9926000045 AND CREDITING FITTING OF ALL ACESSARIES AND KM 20515
FABRICATION TO DEPARTMENTAL STORE
DISMENTLING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM
9 9926000046 AND CREDITING FITTING OF ALL ACESSARIES AND KM 25643
FABRICATION TO DEPARTMENTAL STORE
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
DISMENTALING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM
AND CREDITING FITTING OF ALL ACESSARIES TO
DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 3*50 SQ MM +1*25 SQ
MM+1*35 SQ MM AND CREDITING FITTING OF ALL
ACESSARIES TO DEPARTMENTAL STORE.
DISMENTALING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+
SQ MM AND CREDITING FITTING OF ALL ACESSARIES TO
DEPARTMENTAL STORE.
Supply and Installation of 11/22 kV Distribution Transformers HT
13 9926000086 Terminal protector (UV Resistance) with using 95/120/150 sq.mm 1700
long barrel aluminum lug. (1Set = 3 Nos i.e. on R, Y, B)
Supply & Installation of HT EPR Tap on 11/22 kV Distribution
Transformer with replacement of bare conductor by HT ABC
14 9926000087 conductor (DO bottom side to transformer) after removal of semi 1800
conductor by HT ABC (6 inch both side). HT ABC to be supplied
by DGVCL. (1Set = 3 Nos i.e. on R, Y, B)
Supply, Installation, Testing and Commissioning of Maintenance
Free, Ready Capsule, Pipe-In-Cage (Pic) Type, Earth Electrodes
15 9926000088 for HT Feeder Pole Having 2000 mm Electrode Length as per the No 4150
Tender Specifications and Drawing. (All Materials Will Be
Supplied By Agency)
Supply, Installation, Testing and Commissioning of Maintenance
Free, Ready Capsule, Pipe-In-Cage (Pic) Type, Earth Electrodes
16 9926000089 for HT Feeder Pole Having 3000 mm Electrode Length as per the No 5450
Tender Specifications And Drawing. (All Materials Will Be
Supplied By Agency)
Supply and Installation of 25 X 3 mm GI Strip having hot dip-
galvanized-zinc coating of 80-100 microns without any joints or
welding. Both the end of the GI strip should be connected with GI
nut bolts and required fabrication work for giving separate earthing
connections to(1) Neutral of the transformer(2) MS structures of
the transformer center (Approximately 25 meter GI strip per
transformer centre- as per requirement and instruction of
Engineer in- charge) (All Materials will be supplied by Agency)
Supply and Installation of uPVC standard make Pipe of 1.25"
diameter for covering GI strip with UV protected Cable Ties of
18 9926000092 X 7.6 mm size to bind with pole face(Approximately 25 meter Meter 85
uPVC pipe for GI strip covering per transformer centre -as per
requirement and instruction of Engineer in-charge.
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to
Drop out Fuse and Drop
19 9926000093 out fuse to Transformer H.T. including Busbar (12 mm sleeve) as 5600
specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to
Drop out Fuse and Drop
20 9926000100 out fuse to Transformer H.T. without Busbar (12 mm sleeve) as 2800
specification. (All Materials will be supplied by Agency)
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to
Drop out Fuse and Drop
21 9926000094 out fuse to Transformer H.T. including Busbar(15 mm sleeve) as 6050
specification. (All Materials will be supplied by Agency)
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
Supply & fixing of upto 33 kV Conductor sleeve for Busbar to
Drop out Fuse and Drop
22 9926000101 out fuse to Transformer H.T. without Busbar(15 mm sleeve) as 3090
specification. (All Materials will be supplied by Agency)
Supply & fixing of Disc type Red Color FRP(Non-flammable)
material with Weather
23 9926000095 resistant, Non-conductive bird guard OD=300 MM, ID=33 MM, No 80
Width =1.25 MM, one
side cut from ID to OD. (All Materials will be supplied by Agency)
Providing and fixing of LT Terminal protectors i.e. Re-useable
24 9926000096 boot (LT Side 1.1 kV) including LT (1.1 kV) insulating taps. All live No 900
part at LT side shall be covered with fixing of LT insulating taps.
25 Nylon Net around Transformer Center
25.2 9926000098 Nylon Dori
Labour charge for fitting Nylon Net (All fabricated material for Per
fitting nylon net shall be provided by DGVCL) TC
Dismentalling of existing Dist.X'mer center(RSJ /STP POLE)
26 9924000055 25/63/100/200 KVA with all fabrication & creditig the old material No. 5528
27 9924000056 Disconnection from LT pole 1 phase No. 46
28 9924000058 Disconnection from LT pole 3 phase No. 66
Dismentaling & removing of service line from pole & crediting to
Dismentaling & removing of service line from pole & crediting to
Total of Schedule B1 + B2 + B3 is Rs. TOTAL
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
1.DGVCL will provide key material like M.S. materials,ABC/Bare
conductors,PSC/RSJ Poles,Insulators,Fabricated materials etc. to
the contractor.
2.All fabricated items shall be fabricated as per DGVCL approved
drawing and by welding rods confirming to the relevent ISI
specification and as directed by Engineer in charge.
3.Necessary electricity connection for fabrication items shall be
provided by DGVCL on payment of required charge for
connection & electricity bill of the same shall be paid by the
4.All the rates are inclusive of PF & Exclusive of GST applicable
5.All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying the
paints on to the RSJ poles & steel fabricated materials of
RSJ/PSC poles is must required.
(b) Two coats of approved ISI mark red oxide (primer) is to be
properly painted for the RSJ poles & steel fabricated materials of
(c) Two coats of approved ISI mark silver paint (i.e. triple
mangoes or equivalent quality silver paint) is to be properly
painted on to the RSJ poles & steel fabricated materials of
1. Excavation, Drilling and Cable laying should be done with all
road safety measures such as hard barricading, displaying
“DANGER” sign and “DGVCL - Work in Progress” on it with light
reflective strips or paint. Proof of all barricading and safety
equipment need to submit.
2. Cable laying should be done through roller (not through
tractor or pulling by any other vehicles).
3. Ownership document regarding roller/pulling machine and
HDD machine need to submit or agreement with agency of above
narrated machine regarding work for this tender required to
4. Trail pit excavation and De-excavation should be done
simultaneously so that any chance of road accident can be
5. Three no of Polymer cleat should be provided on rising cable
for proper fitting and if it is not feasible to provide third polymer
cleat at the bottom than two nos of polymer cleat on upper side
and strap strip on bottom end required to install for proper fitting
of rising cable.
Deputy Engineer (Tech)
Technical 6. 100% videography of cable laying along with landmark
Terms location of cable laying required to be done and submit Pen drive
Sachin Division
to the concern engineer for their verification.
7. Aluminum strip required to use to connect end of cable at
cable rising location as per instruction of Engineer in charge. Also
no joints will be allowed in GI strip for cable Earthing and strip will
be connected through GI bolts only.
8. Issues regarding ROW on field should be resolved by
contractor itself.
9. Testing & measuring equipment: - 5 KV Digital insulation
testers, Digital Earth clamp meter for measurement of Earthing
and leakage current, Digital Rodometer with NABL accredited
agency valid test certification.
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Letter No: DGVCLSDUR/0201/07/2026 Approved Date: 27-07-2026 05:32
10.Earthing value & Insulation Resistance (IR) value of all
location along with Geo tagged (longitude & latitude) wise testing
and measured value photograph need to submit with Bill.
11.Depth chart should be provided at every 100 meter with
mentioning landmark.
12. Partial Discharge test to be carried out on sample part of
cable before charging as decided by in charge engineer.
13. Qualified cable jointer with Minimum five years of experience
required with necessary certification regarding qualification and
specific experience.
14. Performance Bank Guaranty required to submit 5% of tender
value for two years against cable joint failure. Moreover, cable
joint failure or end termination failure will have to repair within
Hrs for 2 years of guaranty period.
15. Fixing of mechanical protection HDPE pipe at rising should be
properly buried as per specification.
16. Fixing of Route marker strictly as per specification.
17. Minimum annual Turnover should be at least tender estimated
value and in addition to CVC guideline narrated in tender for UG
cable laying work.
18. Marking of feeder name, direction and location on cable is
compulsory during final scrutiny to declare work completion.
19. End termination and straight joint kit should be of premium
quality as specified in Annexure-2. Technical specifications for the
same to be submitted along with bid.
20. Cable straight joint should be done with mid span joint instead
of long barrel Lug.
21. Agreement with vendor of cable joint kit and End termination
kit to supply for this tender for concern bidder should be submit at
the time of bidding.
File No: DGVCLSDUR/MSC/e-file/4523/2026/1064/Billing
Approved By: Executive Engineer,Technical,DGVCLDOS
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. Schedule A ok.pdf
2. Bid Document ok.pdf
3. Detail Technical Specification ok.pdf
Schedule B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].