Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.9 LAccepted-AOC VIKRAM COACHING GALI SUDAMA NAGARI MADI NATH BAREILLY 243001 | BAREILLY | UTTAR PRADESH | 243001 | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹29.3 L+₹43,584 (1.51%)Rejected-Finance 24 C VAIBHAV SUNCITY VISTAR BAREILLY UP 243001 | BAREILLY | UTTAR PRADESH | 243001 | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹31.9 L+₹3.0 L (10.5%)Rejected-Finance | L3 | Rejected-Finance Not lowest |
Tender Value
₹34 L
EMD Value
₹68,000
Closing Date
13 Aug 2022, 6:00 pmClosed
Maj Surya Shreedhar GE (AF) Bareilly
Garrison Engineer (AF) Military Engineer Services Bareilly - 243002
CONSTRUCTION OF NEW EARTHING PITS AT VARIOUS LOCATIONS AND SPECIAL REPAIR REPLACEMENT OF VARIOUS CABLES WITH MISCELLANEOUS ITEMS OF ROAD SIDE STREET LIGHTS AT AF STATION BAREILLY
2022_MES_539006_1
8672/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BAREILLY
CLASS D CATEGORY b(i)
7 documents required · 7 mandatory
₹500
Yes
GE (AF) Bareilly
₹68,000
Yes
30 Aug 2022
18 Jul 2022
15 Aug 2022
18 Jul 2022
13 Aug 2022
1 Aug 2022
Amount
M&L for earthing comprising of copper earth plate electrode 600 mm X 600 mm X 3mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to copper earth strip of size 20 X 3mm by means of nut-bolts, check nuts and washers of copper all as shown on electrical plate No. 3 of MES schedule 2009, Part–I (Specifications) and connected to main switch board/ main DB’s/ earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust and common salt all around the earth plate in alternate layers of minimum 150mm (compacted thickness) in all directions with and including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63mm thick GI sheet, wire gauge, 50mm thick RCC cover of size 450mm X 450mm in cement concrete 1:2:4, type B-1, duly reinforced with 8mm dia mild steel TMT bars @ 100mm both ways center to center with suitable lifting handle made of 10mm dia mild steel round bar to lift the cover, earth pit of PCC 1:3:6 type C-1, GI protection pipe light grade 40mm bore including testing on completion of job complete all as specified and directed.
S&F GI tubes 50mm bore medium grade laid in trenches/ surface/ duct/ under the floor for protection of cables/ earth strip complete all as specified and as directed.
S&F Test point terminal block made of gun metal or phosphorus bronze of size (75x75x25)mm drilled and screwed including 3 Nos. 8mm dia 25mm long hex head screws for holding the bronze plate including fastening/ bolting the roof down conductor and earth electrode over the bronze plate with copper bolts & nuts of suitable size, providing 10mm thick fibre sheet of size 15x15cm below the test point to avoid direct contact with wall including enclosing the test point with 1.6mm thick MS sheet front openable box duly painted complete all as directed by Engineer -in-Charge.
S&F of (20x3)mm size copper strip as in earth continuity conductor or main earthing lead buried in ground, fixed to wall or in any other situation for loop earthing and the like up to test point mounted on necessary insulators and fastening screws, rawl plugs complete all as specified and as directed.
Taking up old unserviceable LT UG cable of various sizes complete all as specified and as directed.
Supply and laying XLPE insulated armoured heavy duty electric cable of size 4 core 10sq.mm with aluminium conductor 1100 Volts grade, ISI marked as per IS 7098-I, laid in trenches/ ducts or fixing or passing through GI pipe across the road/ path/ drains/ along wall/ floor/ equipment etc. complete all as specified.
Supply and laying XLPE insulated armoured heavy duty electric cable of size 4 core 16sq.mm with aluminium conductor 1100 Volts grade, ISI marked as per IS 7098-I, laid in trenches/ ducts or fixing or passing through GI pipe across the road/ path/ drains/ along wall/ floor/ equipment etc. complete all as specified.
Supply and laying XLPE insulated armoured heavy duty electric cable of size 4 core 25sq.mm with aluminium conductor 1100 Volts grade, ISI marked as per IS 7098-I, laid in trenches/ ducts or fixing or passing through GI pipe across the road/ path/ drains/ along wall/ floor/ equipment etc. complete all as specified.
Relaying of old serviceable LT XLPE UG cable 1100V grade of size 2/4 core, 10 to 25sq.mm after fault rectification complete all as directed by Engineer-in-Charge [Note for srl tem No. 6.00 to 9.00:- Excavation & earth work shall be measured and paid separately].
Excavating manually in trenches n. exc. 1.5m wide and n. exc. 1.5m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes etc. n. exc. 10sq.m. on plan and n. exc. 1.5m in depth and getting out in soft/ loose soil.
Supply and spread dry sand as in cushioning for UG cable all as specified in clause 19.75 of SSR Part I. [Note: Punned down thickness shall be considered for payment]
Supply and laying dry burnt bricks, sub class ‘B’ old size in cable trenches for cable protection complete all as specified and as directed by the Engineer-in-Charge.
All as per Item No. 12 herein before but except bricks. [Note: Serviceable bricks retrieved from taking out cable item shall be reused].
Returning, filling in including spreading leveling watering and well ramming in layers not exc. 25cm in any type of soil.
Removing excavated materials to a distance not exc. 50m and depositing where directed at a level n.exc 1.50m above the starting point.
M&L for LT cable straight through jointing kit heat shrinkable type suitable for XLPE/ PVC insulated cable of size 4C x 10 - 25sq.mm complete including testing the cable joint for healthiness, cutting & removing unserviceable joint, preparation of both ends of cable to be joined with necessary stretching, aligning, making joint all as specified and as required at site.
Horizontal Boring under hard standing/ pavements or roads manually using suitable auger for insertion of GI pipes up to 50mm bore and making good the disturbed surface complete all as specified and as directed. [Note: GI pipe will be measured and paid separately]
S&F GI tubes 40mm bore light grade laid in trenches/ drawn through horizontal boring for protection of cables
S&F shock proof, rust proof, fire retardant non transparent Kiosk pole box of size 310 X 210 X 120 mm made of Engineering plastic one piece moulding, for out door duty, with four Nos. of insulated aluminium bus bar of 60 Ampere capacity mounted on unbreakable insulators, 10 Ampere MCB SP with aluminium lugs of suitable size up to 50 Sq.mm including 02 Nos. 40X3 mm flat iron clamps duly painted both side with two coats of synthetic enamel paint over a coat of red oxide primer, necessary suitable size nut-bolts, washers etc. complete all as specified and as directed including disconnecting & taking down existing unserviceable box.
M&L for Preparation of surfaces of steel electric poles/ masts of height up to 7.5m (exposed) by scraping with emery paper and making free from rust, dust and any foreign material and applying one coat of aluminium paint including lettering on poles such as Pole No and source point of electric supply with white enamel paint on black back ground, zebra painting up to 1.2 m height from ground level with two coats of synthetic enamel paint in 30cm height of alternate bands all as specified and as directed.
Dismantling of electric pole up to 9 metre long and taking out from the trench with and including necessary excavation, earth work, breaking of pole foundation and making good the disturbed surface complete all as specified and as directed.
Fixing only electric pole of height up to 9m in re-location complete all as specified and directed. [Note: Necessary excavation, earth work, foundation & coping will be measured and paid separately]
Supply and replacement of Traffic Signal Light LED based, solid state, low power consumption, powder coated CRCA/ Poly carbonate body with toughened front glass with rubber gasket, ultra bright AlGaAs LED in red and green colour 1x20 watt LED, working voltage: 150-300 V AC complete all as specified and as directed. (Model No. TLL of make: Keltron/ Innovation Technologies or equivalent)
Supply and install LED post top lantern with spun aluminium housing with opal acrylic diffuser, 25W, IP 65 protection complete including necessary cable connection all as specified and as directed including taking down existing unserviceable fitting. [Cat No. CORALPT25WLED757PSYMTOPC of Make: Havells or Cat No. BGCTN 25W LED WW of Make: Bajaj or Techno-commercially equivalent in Philips/ Wipro].
S&F of LED street light fitting 70W, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP-66 with high power LEDs and unique peanut lens to ensure uniform light distribution complete with all accessories pre-wired including taking down existing unserviceable fitting complete all as specified and directed. [Cat. Part No. BRP408 LED HP/CW 240V PSU GR 70W of Philips or ENDURACITYLINERNEOSL70WLED757PASYBOTGODS (ENDURA CITYLINER NEO) of Havells or LR02-781-XXX-57-G2 (Skyline) of Wipro]
S&F of LED street light fitting 90W, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP-66 with high power LEDs and unique peanut lens to ensure uniform light distribution complete with all accessories pre-wired including taking down existing unserviceable fitting complete all as specified and directed. [Cat. Part No. LSTP-90-CDL-M of CG or ENDURAPEARLPLUSSL90WLED757PASYTOPCASTCC of Havells or LR02-102-XXX-57-G2 (Skyline) of Wipro]
S&F LED flood light luminaire, with high power LEDs 70 watt with pressure die cast aluminium housing & heat resistant toughed glass (IP 66 protection) with system lumen efficacy ≥ 110 Lum / Watt, with operating voltage range 140 - 270 V AC, 50Hz ± 3Hz, Surge protection >3KV including driver and connecting up with three core PVC insulated, sheathed flexible copper conductor cable of size 1.0 Sq.mm from MCB to flood light for controlling the flood light complete all as specified and directed by Engineer in-Charge. [Cat No. LFL-80-CDL/60-M of make: CG/ Cat No. JETAALBAFLOODLIGHT70W of make: Havells/ Cat No. BVP120 LED 70 CW FG S1 PSU GR of make: Philips]
S&F LED flood light luminaire, with high power LEDs not less than 110 watt with pressure die cast aluminium housing & heat resistant toughed glass (IP 66 protection) with system lumen efficacy ≥ 110 Lum / Watt, with operating voltage range 140 - 270 V AC, 50Hz ± 3Hz, Surge protection >3KV including driver and connecting up with three core PVC insulated, sheathed flexible copper conductor cable of size 1.0 Sq.mm from MCB to flood light for controlling the flood light complete all as specified and directed by Engineer in-Charge. [Cat No. LFLN-120-CDL/60-M of make: CG/ Cat No. JETAIRISFL120WLED757ARNBLTG of make: Havells/ Cat No. BVP192 LED110 CW HO NB FG GR PSU of make: Philips]
S&F LED flood light luminaire, with high power LEDs not less than 200 watt with pressure die cast aluminium housing & heat resistant toughed glass (IP 66 protection) with system lumen efficacy ≥ 110 Lum / Watt, with operating voltage range 140 - 270 V AC, 50Hz ± 3Hz, Surge protection >3KV including driver and connecting up with three core PVC insulated, sheathed flexible copper conductor cable of size 1.0 Sq.mm from MCB to flood light for controlling the flood light complete all as specified and directed by Engineer in-Charge. [Cat No. LFLN-200-CDL/60-M of make: CG/ Cat No. JETAIRISMAXFL200WLED757PWBLTG of make: Havells/ Cat No. BVP483 LED210 CW AMB PSU GR of make: Philips]
M&L for pole mount street light bracket made of GI pipe light grade 40mm dia, appx 0.65 m long welded at an angle of 120º to MS cap made of MS sheet of suitable thickness and of length 6” and dia suitable for fixing at the top of steel tubular poles, fixed with nuts and bolts complete including painting with two coats of aluminium paint over a coat of zinc chrome primer all as specified and as directed
M&L for street light bracket made of GI pipe medium grade 40mm dia, appx 1.20 m long bent to shape suitable for fixing street light fixed to pole with 2 Nos of MS FI brackets with nuts and bolts complete including painting with two coats of aluminium paint over a coat of zinc chrome primer all as specified and as directed
S&F in repair three core PVC insulated flexible cable cord 1.5 sq.mm multi stranded copper conductor flexible cables 1100 Volt grade complete for making connection from pole box to street light all as specified and as directed. [Make: Finolex/ Polycab/ Havells/ Plaza].
All as per Item No. 32 herein before but of size 2.5 sq.mm
S&F MCB SP, 240 volts, 6 to 32 Amps, 'C' curve, 10 KA all as specified and as directed.
Supply and install nature switch & analog timer (using infrared sensor technology) based automatic street light control panel enclosed in SMC enclosure, 1 Ph, 5kW, 230 Volts AC, IP-54 protection with necessary sensor alongwith suitable power contactor, incoming/ outgoing MCB enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof, internal wiring with FRLS copper conductor cables complete all as specified and as directed. [Make:- 02EC-5kW1P-DUAL of make Swadeep or equivalent in Indo Asian/ Havells]
Supply and install nature switch & analog timer (using infrared sensor technology) based automatic street light control panel enclosed in SMC enclosure, 1 Ph, 12kW, 230 Volts AC, IP-54 protection with necessary sensor alongwith suitable power contactor, incoming/ outgoing MCB enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof, internal wiring with FRLS copper conductor cables complete all as specified and as directed. [Make:- 02EC-12kW1P-DUAL of make Swadeep or equivalent in Indo Asian/ Havells]
Supply and install nature switch & analog timer (using infrared sensor technology) based automatic street light control panel enclosed in SMC enclosure, 3 Ph, 5kW, 230 Volts AC, IP-54 protection with necessary sensor alongwith suitable power contactor, incoming/ outgoing MCB enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof, internal wiring with FRLS copper conductor cables complete all as specified and as directed. [Make:- 02EC-5kW3P-DUAL of make Swadeep or equivalent in Indo Asian/ Havells]
Supply and install nature switch & analog timer (using infrared sensor technology) based automatic street light control panel enclosed in SMC enclosure, 3 Ph, 8kW, 230 Volts AC, IP-54 protection with necessary sensor alongwith suitable power contactor, incoming/ outgoing MCB enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof, internal wiring with FRLS copper conductor cables complete all as specified and as directed. [Make:- 02EC-8kW3P-DUAL of make Swadeep or equivalent in Indo Asian/ Havells]
Supply & erecting in true vertical position, steel tubular swaged pole 410-SP-22, 8.5 meter long complete with mild steel base plate, pole cap, finial taper plug, bolts, nuts, washers etc. including painting the exposed outer surfaces with two coats of aluminium paint over a coat of red oxide primer including applying one coat of black bituminous paint on portion embedded in concrete foundation complete all as specified and directed. [Note: Earth work and excavation, PCC foundation & coping shall be measured and paid separately]
M&L for plain cement concrete (1:4:8) type D2 (using 40mm graded stone aggregate) as in foundations, filling and mass concrete, sub base for flooring etc. all as specified and as directed.
M&L for plain cement concrete (1:2:4) type B1 (using 20mm graded stone aggregate) as in foundations, filling and mass concrete, sub base for flooring etc. all as specified and as directed.
M&L for providing cement concrete (1:3:6) type C1, (using 20mm graded stone aggregate) as in lintels up to 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, copings, bed plates etc complete with and including necessary use and waste of formwork complete all as specified and as directed.
S&F outdoor type stand mounted high mast control panel made of 3mm thick CRCA sheet duly powder coated, comprising of MCB TPN 63 A as incomer, single dial timer switch, 3P contactor 45 Amps for automatic switching of luminaires, 3P contactor 9 Amps - 02 Nos for power tool control, push buttons, terminals for incoming 16 Sq.mm and outgoing 12x2.5 Sq.mm cables including necessary PCC pedestal, disconnecting and taking down existing unserviceable panel complete all as specified and as directed by the Engineer-in-charge.
M&L for cutting of bituminous/ PCC/ paver block road or hard standing to a width of n.exc. 20cm and depth n.exc. 0.90m for laying electric cable/ GI tube, returning, filling in the trench including making good the payment/ hard standing with existing layers complete all as directed.
SHRI SIDHI VINAYAK INFRASTRUCTURE DEVELOPERS
M/s Agarwal Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .