Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.3 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹2.6 L+₹24,920 (10.8%)Rejected-AOC ASWATHY NIVAS MAMPAZHAKARA PERUMPAZHUTHOOR NEYYATTINKARA P O THIRUVANANTHAPURAM 695126 | THIRUVANANTHAPURAM | KERALA | 695126 | L2 | Rejected-AOC L2 | |
| 3 | L3₹2.6 L+₹33,395 (14.4%)Rejected-AOC TC 14 1479 1 MYTL BUILDING PARI S ROAD BAKERY JUNCTION TRIVANDRUM 695014 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695014 | L3 | Rejected-AOC L3 |
Tender Value
₹2.4 L
EMD Value
₹6,000
Closing Date
11 Nov 2024, 3:00 pmClosed
Assistant Executive Engineer
Office of the Assistant Executive Engineer, PWD Electronics Rural Subdivision, PMG, Thiruvananthapuram
DEPOSIT-SITCO of 10 KVA UPS and VRLA Batteries in Kerala State Veterinary Council.
2024_PWD_701396_1
PWD/BLDG/EST/18910/2023_7_2_2
Open Tender
Electrical Works
Item Rate
180 days
Kerala State Veterinary Council
as per SBD
15 documents required · 15 mandatory
₹555
₹6,000
10 Jan 2025
1 Nov 2024
13 Nov 2024
1 Nov 2024
11 Nov 2024
1 Nov 2024
1 Nov 2024 - 11 Nov 2024
Amount
SITCO of 10 KVA UPS and VRLA Batteries in Kerala State Veterinary Council.
OD163572/2024-2025:Supply, Installation, Testing, Commissioning and Optimizing of three phase input, single phase output ≥10KVA Double Conversion very small footprint Pure Sine Wave output UPS with Three Years onsite comprehensive warranty having maintenance bypass switch, automatic static bypass, capability for cold starting etc. and having following technical specifications. 1. Output Power: Active & Reactive Power ≥10KVA, Active Power ≥10KW. 2. Topology: On-Line Double conversion, Voltage and Frequency Independent (VFI) Sinusoidal (SS) with best output dynamic performance (111). 3. Input: Voltage range 380V ±3% – 415 ±3%VAC, Frequency 50Hz. ±10%, Power factor ≥0.99 or better with IGBT based PF controlled rectifier with battery status monitoring system. 4. Output: 230V 50Hz. AC with better than ±1% static and ±3% dynamic regulation with DSP based PWM technology and IGBT output stage. 5. Total Harmonic Distortion (THD) in Voltage & Current (i & u) in output and input is ≤3% 6. Should have TCP/IP communication interface for SNMP & BMS with software. 7. Ingress Protection IP20 or better. 8. Standards for safety, EMC and design: IEC 62 040 – 1 to 3. 9. Markings: ISI / CE 10. Current Crest Ratio is 3:1 or better. 11. Supplied with Sealed Maintanance Free Battery Bank for Thirty minutes backup time @ 100 % Load: (1400VAh per KVA per hour ), (Min. 7680 VAH) suitable Uninyvin cables for inter-connecting batteries & UPS to battery bank, proper copper lugs, Suitable rack for battery etc. 12. Including the buyback value of old 7.5 KVA/144 V UPS with 40 Ah Tubular Batteries. 13. Approved Make: UPS: APC, Emerson, GE, Legrand, Socomec. Battery: Amaron, Exide, Panasonic, Tata Green
FI-TEC POWER SOLUTIONS PVT LTD (BID ID -1969181)
MEDICAL AND VISUAL TECHNOLOGIES Pvt.Ltd (BID ID -1971917)
Bidder Name
MEDICAL AND VISUAL TECHNOLOGIES Pvt.Ltd
FI-TEC POWER SOLUTIONS PVT LTD
F1 Solutions
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1096204.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .