Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
1 Sept 2026, 6:00 pm4d left
CWE Ezhimala
CWE Ezhimala Indian Naval Academy PO 670310
As per BOQ and tender documents
2026_MES_783792_1
80532
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CWE Ezhimala Indian Naval Academy PO 670310
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (M) Ezhimala
₹60,000
11 Aug 2026
11 Aug 2026
7 Sept 2026
12 Aug 2026
1 Sept 2026
26 Aug 2026
12 Aug 2026 - 18 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for repairing/maintenance/servicing of HT 11kv VCB along with CTs/PTs of capacity upto 630A of any make and type by drawing out breaker from main panel and carry out the following works complete all as specified and directed. Timing test, CRM test, insulation resistance test, calibration test, relay setting of VCB on main panels according to KSEB. Complete servicing and testing overload relay, digital voltmeter, digital ammeter, indication lamp and all the protective equipment inside the VCB and main panels to be serviced and working properly incl followings:-
(a) Tripping off the breaker and racking out the breaker trolley complete from the panel for servicing/inspection/overhauling.
(b) Servicing/Inspecting/checking of automatic safety shutter operation for serviceability and adjusting for proper operation.
(c) Servicing/Inspecting/checking of circuit spouts and circuit spout connections for RYB phases.
(d) Checking of cross bar assembly, fixed contacts and current carrying parts of the breaker complete.
(e) Cleaning/decarbonizing of all fixed and moving contacts, levers, springs, etc. with soft emery paper, CRC solution and soft dry cloth to remove all carbon deposits and tightening all screws, nuts, bolts, spring etc. and incl applying superior quality petroleum jelly on all contacts.
(f) Checking of safety/tripping relays and AC/DC power supply circuits for proper functioning.
(g) Checking, setting and adjustment of rack in/rack out, spring charging system and operation of the breaker trolley.
(h) Lubrication and greasing of breaker operating mechanism, all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear etc.
(j) Checking of all end terminals, tightening of all earth connections, tightening all hardware, rack-in the breaker, put in position, engage the VCB with the supply system and testing for smooth functioning.
Notes:
(i) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, indication lamp etc. and Timing test, CRM test, insulation resistance test, calibration test, relay setting of VCBs, commissioning all as specified and as directed by the Engineer-in-Charge.
(ii) Servicing/maintenance of VCBs shall be carried out by authorised service centre/agency/representative of any KSEB approved by GE.
(iii) The test reports shall be submitted by the contractor. | 26 | Each job | - | - |
| 2 | S&F in repairs auxiliary Switch as per existing size/type and suitable for 11 KV VCB of any make and type complete all as specified and directed. | 6 | Each | - | - |
| 3 | S&F in repairs tripping coil assembly 24 volts DC suitable for 11 KV HT VCB of any make and type as per existing size/type complete all as specified and directed. | 4 | Each | - | - |
| 4 | S&F in repairs closing coil assembly 24 volts DC suitable for 11 KV HT VCB of any make and as type per existing size/type complete all as specified and directed. | 4 | Each | - | - |
| 5 | S&F in repairs space heater 240 volts, single phase as per existing size/type and suitable for 11 KV VCB of any make complete all as specified and directed. | 12 | Each | - | - |
| 6 | S&F in repairs thermostat for space heater, single phase range 0 to 90 degree celcius all as per existing size/type and suitable for 11 KV VCB of any make complete all as specified and directed. | 12 | Each | - | - |
| 7 | Supply only Rack in Rack Out Handle as per existing size, type and suitable for 11 KV VCB of any make/type complete all as specified and directed. | 5 | Each | - | - |
| 8 | Supply only Spring Charging Handle as per existing size, type and suitable for 11 KV VCB of any make/type complete all as specified and directed. | 4 | Each | - | - |
| 9 | S&F in replacement voltage transformer ratio 11 KV/110 volts confirming to IS-3156 1992, 50 Hz, class B insulation with primary voltage 11 KV/RT3 and secondary voltage 110 V/RT3, 50 VA, class 1.0 3P, type phase to earth complete incl making all connections complete all as specified and directed. | 4 | Each | - | - |
| 10 | S&F in replacement HT current transformer suitable for 11 KV HT VCB of any make, having ratio 300/150-5 amps or 200/100-5 amps accuracy class 1.0 5P10, 10 VA, 50 Hz incl making all connections complete all as specified and directed. Make: Jyoti electricals/AE/Gemini/Ereva. | 3 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
TD80532.pdf
Tender Documents • 0.47 MB
80532PS.pdf
Tender Documents • 0.35 MB
BOQ_878197.xls
BOQ • 0.69 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].