| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹8.7 LAdmitted-Finance NOT SPECIFIED | L1 | Admitted-Finance | ||
| 2 | L2₹8.8 L+₹7,932.06 (0.91%)Admitted-Finance 15 119 DAKHINPURI NEW DELHI 110062 | SOUTH | DELHI | 110062 | L2 | Admitted-Finance | ||
| 3 | L3₹9.8 L+₹1.1 L (12.1%)Admitted-Finance | L3 | Admitted-Finance | ||
| 4 | L4₹10.1 L+₹1.4 L (15.8%)Admitted-Finance B 26 DSIDC SHOPPING COMPLEX CENTER KALYANPURI DELHI 110091 | EAST | DELHI | 110091 | L4 | Admitted-Finance | ||
| 5 | L5₹10.2 L+₹1.5 L (17.5%)Admitted-Finance | L5 | Admitted-Finance |
Tender Value
₹14.4 L
EMD Value
₹28,844
Closing Date
20 Aug 2026, 3:00 pmClosed
Executive Engineer (E)
O/o The Executive Engineer (E) South Elect. Div., PWD, Sukhdev Vihar, Mathura Road, Near Okhla Flyover, New Delhi
SITC of Street Light Fittings and miscellaneous Electrical Works at Devli Road Under M-South Division.
2026_PWD_297063_1
56/EE(E)/EMD South Elect. Divn./PWD/2026-27
Open Tender
Electrical Works
Works
30 days
New Delhi
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹28,844
Yes
2 Sept 2026
14 Aug 2026
20 Aug 2026
14 Aug 2026
20 Aug 2026
14 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Fabrication, Installation, Testing and Commissioning of floor mounting double door minimum 300 mm depth with locking arrangement front and rear openable, totally enclosed, compartmentalized, dust, vermin proof and outdoor type Feeder Pillar (IP54) fabricated out of 2mm thick cold rolled carbon annealed sheet steel, (minimum) surface area 1.50 Sq.Mtr, with 300 Amp 4 strip AL. bus bar, cable alley on both sides, powder coated paint of approved shade after 7 tank cleaning process and 1 no 20x3mm GI strips throughout the width of feeder pillar consisting two earth studs on each strip complete with provision for incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including providing 50mm X 50mm X 6 mm thick (NS) 90 cm long legs out of which 45 cm duly grouted in existing cement concrete 1:2:4 etc complete as reqd. (Drawing shall be got approved from Engineer-incharge before fabrication) | |||||
| 1.01 | Incomer:- | - | - | - | - |
| 1.02 | 200A TP 25KA MCCB WITH SPREADER LINK (Ics=100%Icu) : 01 No. | - | - | - | - |
| 1.03 | Metering:- | - | - | - | - |
| 1.04 | DIGITAL AMMETER (0-200) WITH SELECTOR SWITCH: 01 No. | - | - | - | - |
| 1.05 | DIGITAL VOLT METER (0-500) WITH SELECTOR SWITCH : 01 No. | - | - | - | - |
| 1.06 | INDICATION LED LAMP RYB : 03 No. | - | - | - | - |
| 1.07 | 2A SP MCB : 03 No. | - | - | - | - |
| 1.08 | 200/5A CT CLASS-1: 03 No. | - | - | - | - |
| 1.09 | Out going :- | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.59 MB
BOQ_395670.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .