| Sl No | Description | Qty | Unit | M M Engineers L2 | M/s AADRIKA ASSOCIATES L1 |
|---|---|---|---|---|---|
| 1.01 | Disconnecting of HT supply from main panel after switching off 11 KV VCB discharging the supply. Complete drain out of transformer oil from transformer into empty oil drum by oil machine, dismantling of conservator tank and all protection relays, cable end boxes, vent pipes and other items as required. | 2 | Jobs | 59,800 ₹70,564 | 59,000 ₹69,620 Lowest |
| 1.02 | Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and reinsulating of weak point with the help of HT insulation material and proper taping etc. | 2 | Jobs | 3,92,000 ₹4,62,560 Lowest | 3,92,000 ₹4,62,560 Lowest |
| 1.03 | Replacement of Top covers gasket vertical vent gasket & kissing hardware to stop the oil leakage. | 2 | Jobs | 1,05,000 ₹1,23,900 | 99,000 ₹1,16,820 Lowest |
| 1.04 | Replacement of HV bushing with the help of skilled and trained labor with all tools and tackles etc as per site requirement. | 3 | Set | 1,86,000 ₹2,19,480 | 1,77,000 ₹2,08,860 Lowest |
| 1.05 | Replacement of silica gel. | 2 | Jobs | 15,600 ₹18,408 Lowest | 15,600 ₹18,408 Lowest |
| 1.06 | Checking & matching of control wiring of all protection relays and calibration of bucchalz relay and protection relays testing the same. | 2 | Jobs | 60,000 ₹70,800 Lowest | 60,000 ₹70,800 Lowest |
| 1.07 | Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides HI pot machine. | 2 | Jobs | 1,31,000 ₹1,54,580 Lowest | 1,31,000 ₹1,54,580 Lowest |
| 1.08 | Filling of transformer oil to up to top up level as required.( actual oil level is 950 Ltr). Make - Trans power | 420 | Ltrs | 56,700 ₹66,906 Lowest | 56,700 ₹66,906 Lowest |
| 1.09 | Repair of cooling fins for stopping the leakage. | 8 | Jobs | 60,800 ₹71,744 Lowest | 60,800 ₹71,744 Lowest |
| 1.10 | Dehydration & filtration of complete transformer oil and checking the die electric strength up to 50 KV at site. | 2 | Jobs | 61,000 ₹71,980 | 60,000 ₹70,800 Lowest |
Tender Value
Refer Docs
EMD Value
₹28,500
Closing Date
25 Sept 2025, 3:00 pmClosed
Sh. Yogesh Lohchab
Wazirabad Water Works
Renovation-servicing of 750 KVA VOLTAMP make Transformers installed at intake raw water pump house at Wazirabad water works. Make- VOLTAMP
2025_DJB_278419_6
NIT No. 09 (2025-26)
Open Tender
Miscellaneous Works
Item Rate
45 days
Wazirabad Water Works
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJBEMD A/c No-50448339804
₹28,500
9 Oct 2025
19 Sept 2025
25 Sept 2025
19 Sept 2025
25 Sept 2025
19 Sept 2025
19 Sept 2025 - 25 Sept 2025
Disconnecting of HT supply from main panel after switching off 11 KV VCB discharging the supply. Complete drain out of transformer oil from transformer into empty oil drum by oil machine, dismantling of conservator tank and all protection relays, cable end boxes, vent pipes and other items as required.
Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and reinsulating of weak point with the help of HT insulation material and proper taping etc.
Replacement of Top covers gasket vertical vent gasket & kissing hardware to stop the oil leakage.
Replacement of HV bushing with the help of skilled and trained labor with all tools and tackles etc as per site requirement.
Replacement of silica gel.
Checking & matching of control wiring of all protection relays and calibration of bucchalz relay and protection relays testing the same.
Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both sides HI pot machine.
Filling of transformer oil to up to top up level as required.( actual oil level is 950 Ltr). Make - Trans power
Repair of cooling fins for stopping the leakage.
Dehydration & filtration of complete transformer oil and checking the die electric strength up to 50 KV at site.
Complete cleaning and chemically washing of oily and muddy transformer body and painting of transformer with enamel paint. The work also includes the transportation of man & material at site of work.
M M Engineers (BID ID -1623970)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .