EE/DED
Opposite of PWD Inspection Bungalow Kachari Road, Siliguri 734001, District Darjeeling
Electrical repairing works of first and second floor of Excise office building, Siliguri, Darjeeling.
2024_WBPWD_715261_1
WBPWD/EE/DED/e-NIT- 05 of 2024-25 (2nd Call)
Open Tender
ELECTRICAL WORKS M/R
Item Rate
120 days
SILIGURI
Please refer Tender documents.
4 documents required · 4 mandatory
₹1.3 L
4 Sept 2024
16 Jul 2024
5 Aug 2024
16 Jul 2024
2 Aug 2024
16 Jul 2024
Amount
Sub-Head 1--Distribution Wiring Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed]
Average run 9 Mtr
Average run 7 Mtr
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish
On Board
SUB-HEAD 2-- PLUGS & SOCKETS Supply & Fixing 240 V, 3 nos. 6 A, 3 pin Modular type plug socket with 1 no. 16A Modular type socket along with switchs (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 2 nos 6A, 5 pin Modular type plug socket with 2nos 6A modular type switch (Brand approved by EIC), without plug top, on 6 module GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc
Supply & Fixing 240 V, 25 A, Modular type AC starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections..
SUB-HEAD 3--BDB,PDB,VTPN ETC Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS.
2+12 Way [Siemens Enclosure(8GB32102RC14) or equivalent model of Legrand/L&T/ABB] as approved by EIC. ( for switch board and 2x5A Plug Board)
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand/ Schneider/ Crabtree/L&T/SIEMENS/ABB) as per direction of EIC. )
6 Way [Make - Legrand, Enclosure-607716/ Schneider, Enclosure-A9HTND06 /Crabtree, Enclosure- (DCDKTHODCW06 or equivalent cat of LT/Siemens as approved E.I.C] (for light load circuit)
4 Way [Make - Legrand, Enclosure-607715/ Schneider, Enclosure-A9HTND04 /Crabtree, Enclosure- (DCDKTHODCW04 or equivalent cat of LT/Siemens/ABB as approved E.I.C] (for normal & Emergency AC Circuit )
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall as per GS as per direction of EIC.
6 Way ( Up to 160 A ) Make -Siemens-Enclosure-8GB31572RC)/L&T,Enclosure- (LTVD06MGN) or equivalent cat of ABB as approved by E.I.C]
4 Way ( Up to 160 A ) Make - Legrand, Enclosure 607913/Siemens-Enclosure-8GB31572RC)/Schneider-Enclosure-A9HVD04M/L&T,Enclosure- (LTVD04MGN) or equivalent cat of Crabtree/ABB as approved by E.I.C]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T) as per direction of EIC. ]
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs including necessary connection as per GS [ Make - Legrand / Schneider/L&T/Siemens/ABB) as per direction of EIC]
125A (for Power DB)
100 A (for Light DB)
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make-Legrand/ Schneider/Siemens/Crabtree/L&T) as per direction of EIC. ]
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical / SPNDB enclosure with IP-42/43 as per GS
4/6/8/12 Way (Vertical)
6 Way (Horizontal)
SUB-HEAD 4-- Polythene pipe and wires Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex/Polycab/RR/KEI) of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS.
3x(1.5 sqmm) (for 2x6A Board)
2x(2.5 sqmm)+1x(1.5 sqmm) ( for computer & power board)
2x(4 sqmm)+1x (2.5 sqmm) (forAC power board)
2x(6 sqmm)+1 x (4 sqmm) ( for SPN DB)
4x(10sqmm)+2x(6 sqmm) ( for HTPN DB)
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works
20 mm size
25 mm size
Cutting Channel of required size on masonry wall by Electric operated cutting machine incl. supplying & fixing of heavy gauge Polythene pipe of following diameter as per GS.
19 mm dia 3 mm thick
25mm dia 3 mm thick
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works
150 mm x 100 mm x 65 mm
200 mm x 150 mm x 65 mm
175 mm x 100 mm x 65 mm
Supply & Fixing bakelite / perspex top cover on existing switch board by Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required
150 mm x 100 mm x 65 mm
200 mm x 150 mm x 65 mm
175 mm x 150 mm x 65 mm
S & F solderless Copper socket by crimping of Copper wires.
a)1.5 sq mm
b) 2.5 sq mm
c) 4 sq mm
d) 6 sq mm
e) 10 sq mm
SUB-HEAD 5--Supplying & Laying of Cable Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make Polycab / RR /KEI/ Havells as approved by E.I.C]
3.5 CORE 150 SQMM (from meter to normal LT Panel )
4CORE 70 SQMM (from emergency LT sub-panel to emergency VTPN for power)
4CORE 50 SQMM (from emergency LT sub-panel to emergency VTPN for light)
3CORE 10 SQMM (for compound light )
Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting
Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting
Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings as per GS
50mm dia
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
3.5CORE 150 SQMM
4CORE 70 SQMM
4CORE 50 SQMM
3CORE 10 SQMM
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
3.5CORE 150 SQMM
4CORE 70 SQMM
4CORE 50 SQMM
3CORE 10 SQMM
SUB-HEAD 6---SUPPLY OF LIGHT FITTINGS Supply and delivery of twin Industrial box type LED luminaries incl. Supply of 2nos. 18W LED Tube with Al heatsink [Make- Philips/CG / Bajaj / Wipro/Havells/Magik as approved by E.I.C]
Supply and delivery of single Industrial box type LED luminaries incl. Supply of 1nos. 18W LED Tube with Al heatsink [Make- Philips/CG / Bajaj / Wipro/Havells/Magik as approved by E.I.C]
Supply of 30 W Recessed mounted 2'x2' LED light fittings having 120 lm/Watt and CCT-6500K with glare free uniform illumination Incl. necessary connections as per direction of EIC. (make- Phillips/Havells/CG / Bajaj / Wipro as approved by E.I.C )
Supply of 10 W Recessed mounted 1'x1' LED light fittings having 100 lm/Watt and CCT-6500K with glare free uniform illumination Incl. necessary connections as per direction of EIC. (make- Phillips/Havells/CG / Bajaj / Wipro as approved by E.I.C )
Supply of 14W LED bulb (Bajaj/CG/Philips/ wipro) on existing batten holder
SUB-HEAD 7-- FIXING OF LIGHT FITTINGS Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitable size MS fastener, Ceiling plate, nipples etc. as required
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling.
Fixing only lamp
Fixing of square or circular recessed mounted LED fittings after cutting of false ceiling and finising of same
SUB-HEAD 08 -- SUPPLY OF FANS Supply of ac ceiling fans of 1200mm sweep with burst-proof P2/S3 Capacitor complete with all accessories without regulator. ( Make - Usha-Striker or equivalent model of Havells/CG/Orient as approved by E.I.C)
Supply of 450mm sweep wall bracket fan(high speed) with metal body & blades(Orient - Wall-II Tornado or equivalent cat of CG/EPC/Cinni) with necessary wooden board on wall with nuts, bolts, washer etc.
Supply of heavy duty Exhaust fan(Make-EPC] of followinng sizes after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust incl. s&f louver shutter as per G.S. )
12"( 300mm ) Speed 920 RPM
9"( 230mm ) Speed 1370 RPM
SUB-HEAD 9-- FIXING OF FANS Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Supply & Fixing 240V, Modular Socket (2 Module) type fanregulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS
Engraving the deptt. number with 10 mm lettering on the body as per GS.
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall as per GS
Sub head-10 compound light Supply of 240V, 70 W LED Street light luminarie complete with all accessories and equipped with IP66 Protection (Crompton Cat no.TRP-409-70-57-SL-GL-NSG or equivalent model of Philips/Bajaj/ Magik /wipro /other equivalent make as approved by E.I.C) on existing GI pipe bracket as per direction of E.I.C
Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to
S/F Stainless Steel water proof looping cable box of size 200x150x100mm having hinged top Cover with rubber gasket lining, railway type mechanical locking anangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same after cuuting wall and mending damages.
Supply & Drawing 1.1 KV grade 3Core 22/0.3 (1.5 sqmm) XLPE insulated Un-armoured Cu Cable (Brand approved by EIC) for connection from loop box to fittings through the Pole including making connections as necessary.
Supply & fixing compound light timer Control Unit(Indoor type) for Faculty building, Hostel Building compound and decorative light of Academic building, assembled with following accessories and wiring with 4sq.mm Cu wire(For MCB to Contractor/terminal block),1.5 sq.mm Cu wire(For control wiring). Suitable size 16 SWG CRCA sheet metal box having min depth 3.5" and should have adequate strength and space to accommodate the following accessories. i)32 A TP MCB(Make:L&T/Legrand/ABB)-1no as incommer ii)Digital 24 hour time switch(Make-GIC)-1no. iii)30A 3-Pole Power Contractor(L&T:Cat No-CS94101)-1no. iv)25 A TP MCB "C" curve(Make:L&T/Legrand/ABB) -1no as out going v) Toggle Switch(ON-OFF-ON)-1No vi) Out going terminal stud with nut--4sets. vii)Indication lamp (R,Y,B)- 1 Set. viii)EI Danger Board (6”X4”) – 1No. Metal Box should have gasket arrangement inside the door and entry and exit points of IN-OUT power, which protect the dust insertion and two locking arrangement with allen key. The panel box should be painted by powder coated paint & the layout diagram of the panel board should be approved by the E.I.C before manufacturing
SUB-HEAD 11 --LED SIGN BOARD S&F outdoor type LED sign board ( BILINGUAL) 1nos.16'X5'X6" fabricated from 3mm thick ACP sheet on all six sides finished with approved metalluic colour & suitable sixe hollow Al. rectangular bar as frame inside the box. Sillicob adhesive to be used in such a way so that ingress of water can be restricted inside the box &m aintainence or replacement of LED modules can be done inside the box should be of non ferrous metal /stainless steel. Appropiate size of MS angle, nuts/ bolts and clamps to be used ouside for fixing the box.
SUB-HEAD 12 --MISCELLANEOUS Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board
Supplying and fixing 415V, 200A TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc(Make – L & TT/Havells/HPL)
Supplying and fixing 415V, 100A TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.[ make-Siemens/L&T/Havells]
Normal LT Panel Board Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 16 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel. (Normal Panel)
Construction Details : All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
Incomming Switch :
(a) 415V 315 Amps TPN SFU units with HRC fuses (Make:- L&T/SIEMENS/ABB) in open exexution---- 1 No.
Bus Bar :
500V,500 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set.
The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
Outgoing Switches :
a) 415V 160 Amps TPN SFU units with HRC fuses (Make:- L&T /SIEMENS/ABB) in open exexution ----- 3Nos. (AMF & Bypass Switch &Spare)
(b) 415V 100 Amps TPN SFU units with HRC fuses (Make:- L&T : Cat No.- SK95568 or equivalent cat of SIEMENS/ABB) in open exexution ----- 3Nos (2 nos. for normal AC TPNDB & 1 no. spare)
(c) 415V 63 Amps TPN SFU units with HRC fuses (Make:- L&T : Cat No.- SK95421 or equivalent cat of SIEMENS/ABB) in open exexution ----- 2Nos(PumpLight & Spare)
Metering Panel
a) Multipurpose Meter Digital Type Load Monitor ( Make L&T, Model -QUASAR) - 1 No.,
b) LCD single function Meter ( Make L& T, Model- CAT NO.WL111020OOOO or equivalent)- for ammeter --- 1 no.
c) LCD single function Meter ( Make L& T, Model no..WL112020OOOO or equivalent) for voltmeter-- 1 no..
d) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent) - 1 Set.
e) 300/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos.
f) Supplying & Fixing 6 Amp SP MCB---- 6 nos.
g) EI danger Board-2 nos
Interconnection :-
All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pve insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
Earthing :-
A separate continuous aluminum earth busbar of size 50mm x 6mm shall run across the full length of the panel board and brought outside the panel. All electrical equipment are to be properly earthed with suitable size G.I. wire.
The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
Installation :-
The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C.
All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC.
Emergency LT Panel Board Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 16 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel. ( Emergency Panel)
Construction Details :
All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side.
Incomming Switch :
(a) 415V 200 Amps TPN SFU units with HRC fuses (Make:- L&T : Cat No.- SK95642 or equivalent cat of SIEMENS/ABB) in open exexution---- 1 No.
Bus Bar :
500V, 315 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set.
The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
Outgoing Switches :
a) 415V 125 Amps TPN SFU units with HRC fuses (Make:- L&T / SIEMENS/ABB) in open exexution ----- 1No.
b) 415V 100 Amps TPN SFU units with HRC fuses (Make:- L&T/ SIEMENS/ABB) in open exexution ----- 3Nos.
(c) 415V 63 Amps TPN SFU units with HRC fuses (Make:- L&T / SIEMENS/ABB) in open exexution.----2 Nos.
Metering Panel
a) Multipurpose Meter Digital Type Load Monitor ( Make L&T, Model -QUASAR) - 1 No.,
b) LCD single function Meter ( Make L& T, Model- CAT NO.WL111020OOOO or equivalent)- for ammeter --- 1 no.
c) LCD single function Meter ( Make L& T, Model no..WL112020OOOO or equivalent) for voltmeter-- 1 no..
d) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent) - 1 Set.
e) 200/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos.
f) Supplying & Fixing 6 Amp SP MCB---- 6 nos.
g) EI danger Board-2 nos
Interconnection :-
All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pve insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
Earthing :-
A separate continuous aluminum earth busbar of size 50mm x 6mm shall run across the full length of the panel board and brought outside the panel. All electrical equipment are to be properly earthed with suitable size G.I. wire.
The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
Installation :-
The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C.
All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC.
SUB-HEAD 14 -- SITC of Air-Conditioning Machines and Television SITC of Single phase , 230V, 50Hz, 1.5 ton capacity (standard BEE- Rating) split type Air-conditioner machine fitted with Rotary compressors suitable for refrigerant R32 incl as per Direction of EIC. (Make- Mitsubishi Electric/Zamil/ O General ) as per choice of EIC
SITC of Single phase , 230V, 50Hz, 1 ton capacity (Standard BEE Rating) split type Air-conditioner machine fitted with Rotary compressors suitable for refrigerant R32 incl as per Direction of EIC. (Make- Mitsubishi Electric/Zamil/O General ) as per choice of EIC
SITC of hard / soft copper refrigeration pipeline with 9mm nitral rubber insulation and Al foil tape compl with fittings , elbow , bends , supporting arrangement on walls (Make- Ryoku /Rajco / Nippon )
a) Liquid line (3/8" OD with 0.6mm thick)
b) Suction line (5/8" OD with 0.7mm thick)
Supply & laying Flexible Drain Water piping work out of PVC / HDPE hard pipes of 25 mm dia. incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors.
S & L, 4 core x 2.5 sq.mm. copper cable (Make - Havells / KEI/Polycab)
SITC of 32" smart HD TV with picture quality index-900, 20W or more Dolby Digital Plus sound and having features like Mobile to TV - Mirroring, bluetooth support, Wi-Fi direct, Minimum 2nos HDMI and 1 no USB port, (Make- Samsung T4410/Sony KD-32W8220K/LG 32LQ360PSA as approved by E.I.C)
SUB-HEAD 14 -- SITC of DG Set Supply ,delivery, Installation at site on foundation , commissioning of 82.5 KVA, 415V, at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 HZ, 3 phase system & for 0.85 Load factor, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-IV+ approved Engine & Acoustic Enclosure having following specifications :- Engine:- conforming to IS/IES 600 34-1,ISO 1460,ISO 8528,ISO 3046,ISO 9001,ISO 13020, capable of taking 10% over loading for one hour included in 12 hours of continuous operation. Make : CUMMINS / Caterpiller /Greaves /KOEL/Ashok Leyland
A) ENGINE
a) Make - CUMMINS / Caterpiller /Greaves /Kirlosker / Ashok Leyland
b) Output (Prime) - 132BHP/as per Co.'s specified
c) Aspiration - Turbocharged Charged air cooled.
d) No of Stroke & Cylinder- 4 stroke, 4 in line cylinders.
f) Battery - 1 x 12V, 95 AH Dry type/Mfg standard.
g) Type of cooling - Liquid cooled
h) Air intake system - Air intake manifold with air filter system.
i) Exhaust system - Provided with turbo charger & residential exhaust Silencer with flexible bellow and companion flanges inside the acoustic enclosure.
j) Coupling & fly wheel - Be fitting coupling, fly wheel
and flywheel housing.
k) Lubricating system - Provided with oil pan, engine mounted lube oil pump and lube oil filter along with first fill of lube oil.
l) Fuel system - Comprising of MICO fuel pump with Electronic Governor, 12 V solenoid coil and replaceable fuel Filter
m) Starting system - 12 V D.C. electric starter and 12 V Battery charging Alternator
n) Safety control - Comprising of protection against Low lube oil Pressure trip, High water temperature trip and Emergency stop switch.
o) Power Start Control - Provided with Microprocessor based generator set monitoring & control system mounted in the Genset control Panel Engine will run in Auto/Manual mode both.
B) ALTERNATOR
Make - Stamford/Leroy Somer
Rating - 82.5 KVA, 0.8pf(Lag)
Voltage regulator - +/_ 0.5 % (max) in static conditions.
Type of alternator -Permanent Lubricating Single Bearing, Brushless, self excited and self regulated through an AVR
Protection - IP: 23 protections with class H insulation.
Overload - Permissible over load of 10 % for one hour in 12 hours of operation
D) Base Frame - Engine and alternator are mounted, coupled and aligned on a common channel iron fabricated base frame with pre-drilled holes through AVM pads.
E) Fuel Tank - Capacity 215 ltrs. Made of 14 SWG sheet metal built inside base frame complete with drain valve, air vent inlet and outlet connection, fuel gauge.
F) Acoustic Enclosure - Sound proof, weather proof environmental friendly CPCB-II approved, made of powder coated sheet steel to maintain noise level below 75dB(A) at a distance of 1 metre from acoustic enclosure under free field condition and provided with hinged gasketted doors with suitable locking arrangement.
INSTALLATION OF DG set and other EI works
Supply of HSD Oil.
Supply of Mobil Oil.
S & F exhaust pipe of 100 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set to nearest building (Horizontal Run) with suitable high temperature painting.
S & F exhaust pipe of 125 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set to nearest building (Vertical Run) with suitable high temperature painting.
Making insulation by 2" glass wool including netting arrangement and covered with aluminium clading as per direction of the EIC.
a) 100 mm. dia exhaust pipe.
b) 150 mm dia exhaust pipe
S&F special type MS angle iron bracket support made of 40x40x6 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 200 mm. dia (Vertical Run)
S&F rain protection canopy.
Hiring charges for scaffolding arrangement for exhaust pipe installation, per storey of building per vertical run.
Earthing with 65 mm. dia GI pipe (ISI Medium) x 3.0 mtr. Long 1 no. 50 x 6 mm. galvanized (Hot dip) sheet strip (4 mtrs. Long) 12 mm. dia x 125 mm. long GI nuts, bolts & washers etc. for neutral earth.
Earthing with 50 mm. (2") dia GI pipe(ISI Medium) x 3.64 mm. thick x 3.04 mtrs. long with nuts, bolts & washers etc. as to GS. (2 nos. for DG, 2 nos. for AMF panel).
Extra for treatment of soil by using salt & charcoal or coke for pipe electrode for neutral earth.
Supply & fixing black PVC heat shrink sleeve for covering the 50 x 6 mm. GI flat.
Extra connecting the neutral of DG to earth electrode including S&F 50mmx6mm Galvanized(Hot Dip) steel strip on wall/floor with GI saddles & insulating the same by one layer of PVC strip over one layer of ampere tape.
Supply & laying of 1.1 KV grade 12 core 2.5 sq.mm. PVC copper conductor control cable partly recessed and partly by shaddle on wall to interconnect DG set with AMF panel.
Supply & laying 1 x 50 sq. mm. single core flexible copper wire in suitable size PVC pipe (reinforced) on wall / floor from neutral earth bus to DG set neutral point including both side socketing.
S & F 415V EI danger board. (size : 20 cm. x 30 cm.)
Commissioning & testing of the Diesel Generator Set along with AMF panel with agency's own tools & tackles in presence of EIC.
Cutting RCC floor by special tools & tackles very carefully without any damaging and removing the shifted rubbish & levelling up and restoring the surface for 8 nos. earth-pit as per direction of EIC.
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
DG Foundation: Dismantling artificial stone flooring upto 50 mm. thick by carefully chiselling without damaging the base and removing rubbish as directed within a lead of 75 m.
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] (ii) With 1:4 cement mortar
Artificial stone in floor, dado, staircase etc with cement concrete (1:2:4) with stone chips, laid in panels as directed with topping made with ordinary or white cement (as necessary) and marble dust in proportion (1:2) including smooth finishing and rounding off corners including raking out joints or roughening of concrete surface and application of cement slurry before flooring works using cement @ 1.75 kg/sq.m all complete including all materials and labour. In ground floor. 3 mm. thick topping (High polishing grinding on this item is not permitted with ordinary cement). Using grey cement (i) 25 mm. thick
Demolish of existing internal wall & finishing
M.S. or W.I. grill of approved design joints continuously welded with M.S., W.I. flats and bars for windows ,railing etc. fitted and fixed with necessary screws and lugs in ground floor. (Add extra @1% for each addl. floor up to 4th floor and @1.25% for each addl. floor above 4th floor). (ii) Grill weighing above 16 kg./sq.m.and above .
Cable & Cable Laying Supply & delivery of XLPE/A Al cable of following size throughunderground (Make- Havells/Polycab/KEI) 4 Core 70 Sqmm
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.
Supplying & fixing of 65 mm dia medium gauge GI Pipe ( ISI Medium) Protection with necessary fittings and jointing metarials as required
Laying of above Cable through existing GI Pipe
Laying of cable above 3½ core 70 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
4 Core 70 Sqmm.
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
4 Core 70 Sqmm.
Changeover Switch, Busbar Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc (Make- L & T, siemens, Havells)
Supplying & fixing 4 bar 415 V, 160A, Al, sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991)
Subhead-15: SITC of Fire Detection System Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 54 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST )
Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST )
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector IP 54 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST)
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/System Sensor/Agni Suraksha )
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab/KEI ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall.
Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice.
Dismentaling existing fittings and electrical equipments, wirings of the building.
RAJESH ENTERPRISE
M/S DAWN ELECTRICAL INDUSTRIES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .