Supply Installation Testing and Commissioning of LT Panel for Upgradation of Jaguar Substation at HAL Korwa.
22315
HAL/KWD/PM/25/SPR/89
IMM
Accessories Complex - Avionics Divn - Korwa
₹0
₹2.5 L
30 Sept 2025
30 Aug 2025
30 Aug 2025
30 Sept 2025
Hindustan Aeronautics Limited Avionics Division, Korwa Post Office : HAL The : Amethi Dist : Amethi (UP) - 227412
Name of work: “Supply, Installation, Testing and Commissioning of LT Panel for Upgradation of Jaguar Substation at HAL, Korwa."
Tender No. - HAL/KWD/PM/25/SPR/89
Part-B PRICE BID
NAME OF AGENCY (To be filled in highlighted box ) :
GST No. (To be filled in highlighted box ) :
HSN/SAC Code (To be filled in highlighted box ) :
BILL OF QUANTITIES WITH SPECIFICATIONS
The tenderers are requested to read the following before quoting:
1 The payment terms shall be governed as per the terms indicated in General conditions of contract.
2 Basic Rate to be quoted for each item.Subject work is called on works contract basis and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
3 Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
4 Amount towards GST will be paid along with RAR payment against invoice.
5 The tenderers are requested to abide by the rules of prevailing GST act.
6 This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid future claims/dispute.
Design, fabrication, supply, installation, testing and commissioning of cubicle type Indoor LT Panel as per IS 8623, CPRI approved with front lockable door arrangement, suitable for mounted on the M.S channel frame work(size 74x40x5mm approx.), with cable entry from top/bottom as per site requirement with removable gland plates with required knock-outs, panel fabricated out of CRCA 2.0 mm sheet steel folded and braced as necessary to provide a rigid support for all components, totally enclosed, dust and vermin proof, multi-tier cubicle type formation with front hinged doors lockable doors for the individual feeders / compartments, preparation of surface and treatment by nine tank process, powder coated with approved colour for not less than 70 microns, with front lockable door(double leaf wherever required), and all doors and covers shall be fully gasketed using good quality EPDM gasket and/or rubber strips and ensure good lockable, durable door opening & closing mechanism, suitable meshed ventilator louvers with suitable cover, Aluminium bus bars for three phase and neutral, bus bar insulators, heat shrinkable PVC sleeves etc. with necessary interconnections as specified in Technical specifications for electrical works, comprising of following switchgear and accessories complete by making suitable foundation as required for fixing of panel in all respects and as directed by Engineer-in-charge. Note: (i) Electrical/Mechanical interlocking for incomers and bus-couplers in such a way that no two incoming supply should come on a single busbar section. (ii) Minimum depth of panel : 1200mm. (iii) Horizontal Busbar shall be placed at upper side of LT Panel. (iv) Panel should be fabricated on MS C-channel size 75X40X5 mm approx. throughout the length and width where supply of MS channel is in vendor's scope. (v) Provision for temporary electrical connection for supply during installation of new panel is in vendor scope. (vi) Overall height of the panel shall not exceed 2.4 meters. Operating levers, handles etc. of highest unit shall not be higher than 1.7 meters. (vii) See chapter no.-6 of Tender document, Technical bid -Part-A (Page No. 95 to 100) for detail scope of work.
Sl. No Specification of item Quantity Unit Rate in Figs excluding GST Rate excluding GST in words Amount Excluding GST in Figs (E=C*A)
1 Generator INCOMER (Red Colour) a). 01 No 1250 Amp. ACB, 50KA, Ics=100%Icu, 4Pole, EDO Type Microprocessor Based Trip for Overload, Short circuit and Earth Fault Protection, Make-Legrand (DMX3), Schneider(NW(6.0)), Lauritz Knudsen(U-POWER OMEGA(MTX3.5G)), ABB( Emax(PR122)) or equivalent latest model of given make with spreaders, Under Voltage release, TNC switch, Neutral link etc. as required complete in all respect . b). 03 No 6A 1P 10kA C-Curve MCB Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. c).02 Nos Red LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. d).01 No Yellow LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. e). 01 No Blue LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. f). 01 No Green LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. g). 01 No Amber LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. h). 03 Nos 1200/5A Acc.Cl:1, 5-15 VA Resin Cast Circular Current Transformer, Make - AE, KAPPA, POWERMAT, TRINITY. i). 01 No 3/4 Row Advanced Class -1.0 Accuracy Multifunction Energy Meter with RS485, Parameters: Volts, Amps, PF, THD, F, W, Wh, VA, VAh, Var, Varh, Runhrs, Onhrs, Interupts, Preloaded Demand & Import /Export. Make -Lauritz Knudsen, Schneider, ABB, ELMEASURE. j). 01 No Spring return TNC switch with lever type handle and under voltage release k). 1 Set Electrical/Mechanical interlocking for incomers and bus-couplers in such a way that no two incoming supply should come on a single busbar section. l). 1 Set Busbar made up of electrolytic grade high conductivity aluminium in rectangular cross section and suitable for 415V, 4P, 50 Hz, 2500 A, 50 kA for 1 sec of required length and cross sectional area , with current density of 1A/sqmm for connecting all above Incomer ACB with cable and adjacent panel etc. complete in all respect. 3 Set 0.00
2 Transformer INCOMER (Blue Colour) a). 01 No 2000 Amp. ACB, 50KA ,Ics=100%Icu, 4Pole, EDO Type Microprocessor Based Trip for Overload, Short circuit and Earth Fault Protection, Make-Legrand (DMX3), Schneider(NW(6.0)), Lauritz Knudsen(U-POWER OMEGA(MTX3.5G)), ABB( Emax(PR122)) or equivalent latest model of given make with spreaders, Under Voltage release, TNC switch, Neutral link etc. as required complete in all respect. b). 03 No 6A 1P 10kA C-Curve MCB Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. c). 02 Nos Red LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. d).01 No Yellow LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. e). 01 No Blue LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. f). 01 No Green LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. g). 01 No Amber LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider, ABB. h). 03 Nos 1200/5A Acc.Cl:1, 5-15 VA Resin Cast Circular Current Transformer, Make - AE, KAPPA, POWERMAT, TRINITY. i). 01 No 3/4 Row Advanced Class -1.0 Accuracy Multifunction Energy Meter with RS485, Parameters: Volts, Amps, PF, THD, F, W, Wh, VA, VAh, Var, Varh, Runhrs, Onhrs, Interupts, Preloaded Demand & Import /Export. Make -Lauritz Knudsen, Schneider, ABB , ELMEASURE. j). 01 No Spring return TNC switch with lever type handle and under voltage release k). 1 Set Electrical/Mechanical interlocking for incomers and bus-couplers in such a way that no two incoming supply should come on a single busbar section. l).1 Set Busbar made up of electrolytic grade high conductivity aluminium in rectangular cross section and suitable for 415V, 4P, 50 Hz, 2500 A, 50 kA for 1 sec of required length and cross sectional area , with current density of 1A/sqmm for connecting all above Incomer ACB including MS supporting structure with insulators as requi 6 Set 0.00
3 OUTGOING (Gray Colour) a). 9 Nos 630Amp, 4Pole , 36KA, MCCB with On, Off, Trip indication and Overload, Short circuit, & INBUILT Earth Fault protection with Microrprocessor Based Release (Make - LEGRAND, Lauritz Knudsen, Schneider, ABB) with spreaders, suitable rating bus bar for connecting MCCB with main bus bar, standard extended rotatery handle, Auxiliary contacts, Neutral link etc. as required complete in all respect. b). 9 Nos Red LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. c). 9 Nos Amber LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. d). 9 Nos Green LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. e). 27 Nos 600/5A Acc.Cl: 1 5-15VA Resin Cast Rectangular Current Transformer Make - AE, KAPPA, POWERMAT, TRINITY. f). 9 Nos Digital flush type class -1.0 accuracy AMMETER with RS-485 communication port for measurement of 3 Phase Currents seperately with inbuilt selector switch. Make: Legrand, Lauritz Knudsen, Schneider,ABB. g). 1 Set Main Busbar made up of electrolytic grade high conductivity aluminium in rectangular cross section and suitable for 415V, 4P, 50 Hz, 2500 A, 50 kA for 1 sec of required length and cross sectional area , with current density of 1A/sqmm for connecting all above Incomer Panel, out going MCCBs , cable and adjacent panel etc. complete in all respect. 6 Set 0.00
4 BUS-Coupler (Orange Colour) a). 1 No 2000 Amp. ACB, 50KA ,Ics=100%Icu, 4Pole, EDO Type Microprocessor Based Trip for Overload, Short circuit and Earth Fault Protection, Make-Legrand (DMX3), Schneider(NW(6.0)), Lauritz Knudsen(U-POWER OMEGA(MTX3.5G)), ABB( Emax(PR122)) or equivalent latest model of given make with spreaders, Under Voltage release, TNC switch, Neutral link etc. as required complete in all respect. b). 03 No 6A 1P 10kA C-Curve MCB Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. c). 1 No Red LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. d). 1 No Green LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. e). 1 No Amber LED Indicator 22.5 mm, Voltage: 240V AC, Make -LEGRAND, Lauritz Knudsen, Schneider,ABB. f). 1 No Spring return TNC switch with lever type handle and under voltage release g). 1 Set Electrical/Mechanical interlocking for incomers and bus-couplers in such a way that no two incoming supply should come on a single busbar section. h). 1 Set Busbar made up of electrolytic grade high conductivity aluminium in rectangular cross section and suitable for 415V, 4P, 50 Hz, 2500 A, 50 kA for 1 sec of required length and cross sectional area , with current density of 1A/sqmm for connecting all above panels ACB, adjacent Panels etc. complete in all respect. 5 Set 0.00
5 Removal of Old LT Panel: Removal of existing 16.80 meter approx. length, English Electric-make, indoor LT panels having 05 nos. Transformer incommer (Size 2000mmX 540mm X 2330mm), 02 nos. DG set incommer (Size 2000mmX 540mm X 2330mm), 05 nos. Bus coupler (Size 2000mmX 540mm X 2330mm) and 18 nos. (18X3=54 outgoing) outgoing SFU panels (Size 1230 mmX 570mm X 2330mm) and end connections/termination etc. & shifting/handing over it to HAL scrape yard. 1 Set 0.00
6 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 400 sqmm size with S&F of Lugs & brass compression Glands (as required) as per direction of EIC. 5 Nos. 0.00
7 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 300 sqmm size with S&F of Lugs & brass compression Glands(as required) as per direction of EIC. 4 Nos. 0.00
8 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 240 sqmm size with S&F of Lugs & brass compression Glands(as required) as per direction of EIC. 48 Nos. 0.00
9 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 185 sqmm size with S&F of Lugs & brass compression Glands(as required) as per direction of EIC. 5 Nos. 0.00
10 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 150 sqmm size with S&F of Lugs & brass compression Glands(as required) as per direction of EIC. 1 Nos. 0.00
11 Indoor End Termination of 1100 V grade, XLPE insulated, PVC sheathed armoured/unarmored Aluminium conductor cable of 3.5C x 120 sqmm size with S&F of Lugs & brass compression Glands(as required) as per direction of EIC. 2 Nos. 0.00
12 Supply, making & testing of Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masnory enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required as per direction of EIC. 18 Nos. 0.00
13 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer soaced at 50mm) as per direction of EIC. 200 Meter 0.00
14 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required as per direction of EIC. 100 Meter 0.00
Sub Total (Rs.) 0.00
Add GST @18% 0.00
Total amount including GST (Rs.) ₹ 0.00
Total Amount in words
Note: (i): It is a Item rate tender. Hence tenderers should quote the unit rates for all the items against the enclosed bill of quantities for making the payment as per actual work done at site. (ii): The quoted rates in the bill of quantities are inclusive of all types of taxes, duties levies, fees and charges etc., imposed by Central/ State Govt. and local bodies Compensation Cess. Labour Cess, Custom Duty, royalties and other levies. It shall also included all other costs including loading, un-loading insurance. transportation, testing and Certification expenses except GST. GST at the prevailing percentage is added in the BOQ at the end. (iii). Vendor may visit the site on any working day before submission of bid.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
CHECKLIST.pdf
TENDER_DOCUMENT • 0.01 MB
NIT.pdf
TENDER_DOCUMENT • 0.31 MB
PQFreeView.pdf
TENDER_DOCUMENT • 0.03 MB
TechnicalBid.pdf
TENDER_DOCUMENT • 4.43 MB
PriceBid.xlsm
TENDER_DOCUMENT • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .