Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹40,000
Closing Date
10 Aug 2026, 6:00 pm
SURAT IND DIVISION
Emergency work of locate 22kv / 11kv UG cable fault locating & attending the fault by providing joining kit etc. [suitable Straight through joining kit & Outdoor end termination kit to be supplied by contractor and 22kv / 11kv XLPE cable will be supplied by DGVCL] under All Sub Sub divisions area under Pandesara Division
325948
T-29/DGVCLSDPND/0028/07/2026 Approved Date: 20-07-2026
Open
Electrical
Works
Surat
6 documents required · 6 mandatory
₹1,180
SURAT IND DIVISION
₹40,000
20 Jul 2026
20 Jul 2026
20 Jul 2026
10 Aug 2026
20 Jul 2026
Labour charge for excavation of 2100mm long
x 1200mm wide x 1200 mm deep joint pits for
installation of 11kV / 22kV Straight through
joints as per instruction of engineer-in-charge &
1. covering the cable with 150 mm dia (Outer), No
thickness 25 mm, 1.0 meter long RCC half
round muffs & refilling same as per
instruction of EIC .
Supply & fixing of heat shrinkable straight
through joint type for upto 22kV 3C x 185 mm2
2. size XLPE cable as per DGVCL technical No
specification(Using Approved make cable kit as
per DGVCL technical specification)
Supply & fixing of heat shrinkable straight
through joint for upto 11kV 3C x 185 mm2 size
3. XLPE cableas per DGVCL technical specification.
(Using Approved make cable kit as per DGVCL
technical specification)
Supply & fixing of heat & shrinkable end
4 terminations (Indoor/outdoor) for upto 22 kV 3C
x 185 mm2 size XLPE cable as per DGVCL
technical specification(Using Approved make
cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end
terminations (Indoor/outdoor) for upto 11kV 3C No
x 185 mm2 size XLPE cable as per DGVCL
5 technical specification(Using Approved make
cable kit as per DGVCL technical specification)
Work of fault finding 11/22 cable under ground Nos
6 XLPE cable fault locating exact place of fault.
Consecutive more than one Fault Finding on Nos
7 same cable till the cable charged fully.
8 Labour charge for excavation of cable trench of Meter
400mm width x 1200mm depth, in any type of
soil for laying of cable of size up to 240 mm2
(For additional cable 200 mm additional width
shall be considered i.e. half trench length is to
be considered)
9 Labour charge for laying of 11kV / 22 kV XLPE Meter
Cable of size up to 240 mm2 & preparation of
sand layer 100mm thick, in the cable trench &
covering the cable with 150 mm dia (Inner),
thickness 25 mm, 1.0 meter long RCC half
round muffs and providing and fixing of 4inch
width yellow colour polyethylene tape with
printing "CAUTION ELECTRIC CABLE BELOW" at
0.75 m depth from ground surface after laying
cable in trench. This will provide indication that
electric cable is passing underground so as to
protect cable from mechnical injuries, refilling
the same, as per Instruction of Engineer in
Charge (EIC).
10 Labour work for RCC concreting on disputed CMT
location and repairing of damage portion of
road crossing for the work carried out for roads
crossing as well as concreting & muffing of
ploes including all materials (1:2:4)
11 Providing & fixing concrete stone route marker NO
of 300 mm width x 150 mm thick x 650 mm
height embedded in earth at least 300 mm
below & 350 mm above ground level
respectively at distance approx 50 meters along
the length of cable. The RCC concreting (1:2:4)
(all necessary maeterials will be in bidder's
scope) of route marker is to be carried out
mm width x 150 mm thick x 300 mm below
ground level as per instruction of EIC. The
route marker should be with name of company
with approved yellow colour-DGVCL. The
distance from marker to cable and cable depth
with feeder name etc., marked with arrow sign
is to be painted on it.The route marker is to be
fixed at location near to any fixed permanent
location (not necessary to fix exact on top of
cable) as per instruction of EIC.
12 Providing and fixing of pipe type earthing from No
80 mm dia class-B GI pipe with pit to be filled
per DGVCL Drg. No. dg /100 for DP and cable.
The earthing pit should be joined with cable by
G.I. strip of size 1” width & 2 mm thick. All
material GI pipe, Coke, Salt etc will be supplied
by bidder.
13 Labour charge for erecting of 11kV / 22 kV XLPE
cable of size up to 240 mm2 on DP Structure
with fixing of 02 Nos polymer cleats on top and Per Job
middle part. Polymer cleats, nut bolts etc.
fixing material to be provided by contractor.
14 Providing & fixing of 6.11kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984 and BIS certification
on the erected DP structure for the mechanical
protection of cable by inserting the cable inside
HDPE pipe. The HDPE pipe shall be erected in
Per Job
such a way that 300mm shall be below the
ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No
Polymer cleat.All materials including polymer
cleat and Nut bolt to be provided by contractor.
15 Testing of cable at various points and
commissioning the feeder as per instruction of
engineer-in-charge.Test result shall be
submitted by contractor with bill.
16 Supply & fixing of heat shrink type end
terminations (outdoor) for 11kV 3C x 240 mm2 Nos
size XLPE cable as per DGVCL technical
specification(Using Approved make cable kit as
per DGVCL technical specification)
17 Supply & fixing of heat & shrinkable end
terminations (outdoor) for 22 kV 3C x 240 mm2
size XLPE cable as per DGVCL technical Nos
specification) (Using Approved make cable kit as
per DGVCL technical specification)
18 Supply & fixing of heat shrink type end
terminations (indoor) for 11kV 3C x 240 mm2
size XLPE cable as per DGVCL technical Nos
specification) (Using Approved make cable kit as
per DGVCL technical specification)
19 Supply & fixing of heat shrinkable straight
through joint for 11kV 3C x 240 mm2 size XLPE
cableas per DGVCL technical specification. Nos
(Using Approved make cable kit as per DGVCL
technical specification)
20 Supply & fixing of heat shrinkable straight
through joint type for 22kV 3C x 240 mm2 size
XLPE cable as per DGVCL technical Nos
specification(Using Approved make cable kit as
per DGVCL technical specification)
RS THIRTY ONLY. Total
Grand Total
Grand Total
In Words:- Fifteen Lacs only.
Note: (1) Above rates are inclusive of all taxes, levies, duties & PF etc. Exclusive of GST
(2) 22KV XLPE cable will be supplied by DGVCL.
(3) Agency have to supply and provide end termination and St.Jointing kit of 11/22KV rating of Raychem/ 3M/
dension/tyco brand for the work as per G.T.P. attached with tender.
(4) Pit for straight joint have to Excavate for 2100mm wide & 1200 mm depth & if more size pit excavate
Proportionate rate should be given & agency is fully responsible for excavate pit either by JCB or
(5) In emergency, when Dept. fault finding VAN not available, than only item at Sr. No 6 & 7 In Sch-B may
be applicable and justification must be attached.
SIGN OF CONTRACTOR
Executive Engineer (O & M)
DGVCL, Pandesara Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Tender Notice.pdf
T-29 Tender Drfat.pdf
T-29 Schedule B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].