Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹1.9 L+₹65,831 (53.8%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3₹1.9 L+₹67,284 (55.0%)Accepted-Finance | L3 | Accepted-Finance L3 | |
| 4 | L4₹2.0 L+₹78,038 (63.8%)Accepted-Finance | L4 | Accepted-Finance L4 | |
| 5 | L5₹2.1 L+₹86,863 (71.0%)Accepted-Finance | L5 | Accepted-Finance L5 |
Tender Value
₹2 L
EMD Value
₹4,000
Closing Date
9 Oct 2023, 2:00 pmClosed
Executive Engineer
Office of the Executive Engineer Electric Division Vijaypur JPDCL Jammu
Shifting of 100 KVA Sub Station at Marhoon within the jurisdiction of Executive Engineer Electric Division JPDCL Jammu
2023_PDD_229079_1
EDV / 33 of 2023-2024 Dated 08.09.2023
Open Tender
Electrical Works
Turn-key
30 days
SAMBA
Please refer Tender documents.
8 documents required · 8 mandatory
₹200
Executive Engineer Electric Div Vijaypur JPDCL
₹4,000
17 Nov 2023
8 Sept 2023
10 Oct 2023
9 Sept 2023
9 Oct 2023
9 Sept 2023
9 Sept 2023 - 9 Oct 2023
Amount
Scope of works : Dismantlling of existing 100 KVA Distribution Sub Station (1 No.)
Dismantling of 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer .
Dismantling of 9 Mtr Long PCC Pole including back filling of soil & consolidating by ramming, watering etc.
Dismantling of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc including all necessary Nut & Bolts & Washers etc.
Dismantling of 11 KV Link set
Dismantling of 11 KV Horn Gap Fuse Set, 3 Phase 200A
Dismantling of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Dismantling of 185 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type (Damaged One)
Dismantling of Earthing of substation
Dismantling of 11kV Polymeric composite Pin Insulator
Dismantling of 11kV Polymeric composite Disc Insulator
Dismantling of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mmdiameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Re-erection, Testing & Commissioning of Dismanteled 100KVA Distribution transformer sub station
Installation, testing & commissioning of Dismantelled 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer (old Transformer to be re-erected )
Supply,Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.(old one to be used)
Transportation & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminum paint coated including all necessary Nut & Bolts & Washers etc.(old one to be used)
Installation, Testing & Commissioning of 11 KV link Set (old one to be used)
Installation, Testing & Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200 A (old one to be used).
Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type(old one to be used)
Providing & Fixing of 185 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
Providing & Fixing of Distribution Box for 100 kVA DTR with MCCB for incomer & SFU's for Outgoing Circuits(200 A)
Providing of Earthing of substation --Excavation of earth pit of dia. 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GIStrip for neutral earthing of size 25 mm x 3 mm for connection of transformer body ,G.O Set &lightening arrestor as per IS 2629/85, GI nuts &bolts ,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Stone Pad 300mmx300mmx75mm
Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm(old one to be used)
Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm(old one to be used)
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of Danger Plates with Clamps
Fixing of Galvanized Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia. GI stranded wire complete(old one to be used)
LAYING OF LT LINE ON 8 MTR PCC POLES USING ACSR WEASEL CONDUCTOR ( 3 Phase ,4 wire)-0.100 Km
Supply, Transportation, Erection of 8 Mtr Long PCC Pole (WL-200 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Providing & Fixing of GI U-Clamp with Shackle Insulator (Polymer/Porcelain) alongwith GI Nut & Bolt of sorts
Supply, Laying & Stringing of ACSR WeaselConductor through insulators including proper binding & twisting with soft Aluminium Wire(three Phase four wire)
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of LT Line Spacers
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing and fixing of Aluminium sleeves
The Trikuta Engineer
SAFFRON ENGINEERS
M/S APR CONSTRUCTIONS
M/S TRANS TECH ENGINEERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .