Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹8.0 LAdmitted-Finance H 123 GYAN MANDIR ROAD GALI NO 3 JAITPUR EXTENSION BADARPUR NEW DELHI 110044 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110044 | -22.89% | ₹8.0 L | L1 | Admitted-Finance |
| 2 | L2₹8.2 L+₹14,347.35 (1.79%)Admitted-Finance NOT SPECIFIED | -21.51% | ₹8.2 L+₹14,347.35 (1.79%) | L2 | Admitted-Finance |
| 3 | L3₹9.4 L+₹1.3 L (16.7%)Admitted-Finance 158 RAKSA SHIVPURI ROAD JHANSI RAKSA JHANSI JHANSI JHANSI UTTAR PRADESH 284419 | JHANSI | UTTAR PRADESH | 284419 | -10.00% | ₹9.4 L+₹1.3 L (16.7%) | L3 | Admitted-Finance |
| 4 | L4₹11.4 L+₹3.4 L (42.5%)Admitted-Finance 15 119 DAKHINPURI NEW DELHI 110062 | SOUTH | DELHI | 110062 | +9.90% | ₹11.4 L+₹3.4 L (42.5%) | L4 | Admitted-Finance |
Tender Value
₹10.4 L
EMD Value
₹20,793
Closing Date
3 Sept 2026, 3:00 pmClosed
Executive Engineer (E)
O/o The Executive Engineer (E) South Elect. Div., PWD, Sukhdev Vihar, Mathura Road, Near Okhla Flyover, New Delhi
Repair and Replacement of existing Wornout Feeder Pillar at Existing Pump houses on Located SSN Marg and Bandh Road under M-South Electrical Division
2026_PWD_297578_1
61/EE(E)/EMD South Elect. Divn./PWD/2026-27
Open Tender
Electrical Works
Works
30 days
New Delhi
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹20,793
Yes
15 Sept 2026
25 Aug 2026
3 Sept 2026
25 Aug 2026
3 Sept 2026
25 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Fabrication, Installation, Testing and Commissioning of floor mounting double door minimum 400 mm depth with locking arrangement front and rear openable, totally enclosed, compartmentalized, dust, vermin proof and outdoor type Feeder Pillar (IP54) fabricated out of 2mm thick cold rolled carbon annealed sheet steel, (approx) surface area 2.50 Sq.Mtr, with 500 Amp TPN AL. bus bar, cable alley on both sides, powder coated paint of approved shade after 7 tank cleaning process and 1 no 25x5mm GI strips throughout the width of feeder pillar consisting two earth studs on each strip complete with provision for incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including providing 50mm X 50mm X 6 mm thick (NS) 90 cm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 etc complete as reqd.
(Drawing shall be got approved from Engineer-incharge before fabrication)
Incomer:-
a) 400A FP 36KA MCCB - TMR O/L, S/C Ics=100%Icu : 01 No.
b) 200A Onload Changeover Switch: 1 No.
Metering:-
a) DIGITAL AMMETER WITH SELECTOR SWITCH : 01 No.
b) DIGITAL AMVOLT METER WITH SELECTOR SWITCH : 1 No.
c) INDICATING LED LAMP RYB : 03 Nos.
d) 6A SP MCB : 03 Nos.
e) 400/5A CT CLASS-1 : 03 Nos.
Out Going :-
50HP STAR DELTA STARTER : 03 Seta) 125A TP MCCB - TMR Ics=100%Icu b) 70A TP CONTACTOR 220Vc) ADD ON BLOCK - 2NO+2NCd) OVER LOAD RELAY (30-50A)e) SINGLE PHASE PREVENTERf) START /STOP PUSH BUTTONg) DIGITAL AMP. METER(0-100A) WITH SELECTOR SWITCHh) ON/OFF TRIP INDICATING LIGHTI) 150/5A CT CLASS-1J) AUTO MANUAL SELECTOR SWITCHk) STAR DELTA STARTER | 2 | Each | 3,04,678 | ₹6,09,356 |
| 2 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required: 01 Set | 2 | Each | 315 | ₹630 |
| 3 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. | 4 | P/set | 7,658 | ₹30,632 |
| 4 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required | 40 | Mtr. | 287 | ₹11,480 |
| 5 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) | 10 | cum | 7,878.5 | ₹78,785 |
| 6 | Providing and fixing of wornout/rusted feeder pillar front/back door made out of 2 mm thick CRCA sheet duly powder coated & complete with heavy duty hinge joint & locking arrangements i/c spray painting etc complete as reqd. | 15 | p/sq.mtr | 3,972 | ₹59,580 |
| 7 | Supply & fixing of Onload Manual Changeover Switch 400 Amp with SS enclosure, 4 Pole, 415V AC i/c drilling holes, making connections i/c dismantling of burnt out Changeover switch etc complete as reqd. | 2 | Each | 32,909 | ₹65,818 |
| 8Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. | |||||
| 8.01 | 400 A,50KA,FPMCCB | 2 | Each | 44,663 | ₹89,326 |
| 9Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : | |||||
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.59 MB
BOQ_396468.xls
BOQ • 0.30 MB
NIT.pdf
Tender Documents • 2.58 MB
MakeCorrigendum.pdf
PDF • 0.68 MB
Make.pdf
PDF • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .