Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.0 LAccepted-AOC 894 NEAR 132 KV POWER HOUSE SINDHARI ROAD BALDEV NAGAR BARMER RAJ 344001 | BARMER | RAJASTHAN | 344001 | L1 | Accepted-AOC AOC | |
| 2 | L2₹14.8 L+₹29,560 (2.04%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L2 | Rejected-Finance NOT LOWEST BIDDER | |
| 3 | L3₹15.5 L+₹1.1 L (7.35%)Rejected-Finance 33 MAHAVEER NAGAR NANDRI ROAD PO SARAN NAGAR JODHPUR 342015 | JODHPUR | JODHPUR | RAJASTHAN | 342015 | L3 | Rejected-Finance NOT LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Shri Electrical Enterprises L2 | DIWAKAR CONSTRUCTION CO. L3 | GITANSH ENGINEERS AND COMPANY L1 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches in soft/ loose soil n.exc 1.5mtr wide and not exc 1.5mtr in depth and getting out complete all as specified. | 150 | Cum | 200 ₹30,000 | 150 ₹22,500 | 140 ₹21,000 Lowest |
| 2.00 | All item as per Ser No 1.00 above but exc 1.5 mtr or part there of in depth beyond the first 1.5 mtr depth complete all as specified. | 0.5 | Cum | 300 ₹150 | 150 ₹75 Lowest | 200 ₹100 |
| 3.00 | M&L for tibba sand locally available sand filling in trenches dry and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified. | 38 | Cum | 400 ₹15,200 | 150 ₹5,700 Lowest | 200 ₹7,600 |
| 4.00 | M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified. | 180 | Sqm | 270 ₹48,600 | 200 ₹36,000 Lowest | 210 ₹37,800 |
| 5.00 | Laying only old retrieved stone slab cover on the cable abutting each other for the cable protection gap between two adjacent patties n.exc 10mm complete all as specified. | 30 | Sqm | 40 ₹1,200 Lowest | 250 ₹7,500 | 50 ₹1,500 |
| 6.00 | Returning, filling, in including spreading, leveling , watering and well ramming in layers n.exc 25 cm in soil complete all as specified. | 110 | Cum | 50 ₹5,500 | 50 ₹5,500 | 25 ₹2,750 Lowest |
| 7.00 | Removing excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtrs above the starting point complete all as specified. | 40 | Cum | 70 ₹2,800 | 30 ₹1,200 | 26 ₹1,040 Lowest |
| 8.00 | Supply, laying, testing & commissioing of 25 Sqmm 4 core size XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 Part I marked, suitable for LT 1100 Volt system,laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe including jointing & testing and taking down old U/S cable complete all as specified.
Note :- Excavation, earth work ,cable protection , sand fillings shall be measured and paid separately under respective items of schedule. | 100 | RM | 225 ₹22,500 | 220 ₹22,000 Lowest | 255 ₹25,500 |
| 9.00 | All as per Ser No 8.00 above but size 16 sqmm 4 core | 800 | RM | 190 ₹1,52,000 | 130 ₹1,04,000 Lowest | 225 ₹1,80,000 |
| 10.00 | All as per Ser No 8.00 above but size 10 sqmm 4 core | 300 | RM | 155 ₹46,500 | 130 ₹39,000 Lowest | 210 ₹63,000 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
5 Jul 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer, Banar
Garrison Engineer Banar, Jodhpur-342027
REPAIR MAINT OF STREET AND GARDEN LIGHTS AND ITS CONNECTED ITEMS AT RALAWAS UNDER GE BANAR
2025_MES_713108_1
8825/31/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BANAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer Banar
₹40,000
Yes
17 Sept 2025
7 Jun 2025
12 Jul 2025
7 Jun 2025
5 Jul 2025
21 Jun 2025
Amount
Excavation in trenches in soft/ loose soil n.exc 1.5mtr wide and not exc 1.5mtr in depth and getting out complete all as specified.
All item as per Ser No 1.00 above but exc 1.5 mtr or part there of in depth beyond the first 1.5 mtr depth complete all as specified.
M&L for tibba sand locally available sand filling in trenches dry and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified.
M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified.
Laying only old retrieved stone slab cover on the cable abutting each other for the cable protection gap between two adjacent patties n.exc 10mm complete all as specified.
Returning, filling, in including spreading, leveling , watering and well ramming in layers n.exc 25 cm in soil complete all as specified.
Removing excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtrs above the starting point complete all as specified.
Supply, laying, testing & commissioing of 25 Sqmm 4 core size XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 Part I marked, suitable for LT 1100 Volt system,laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe including jointing & testing and taking down old U/S cable complete all as specified. Note :- Excavation, earth work ,cable protection , sand fillings shall be measured and paid separately under respective items of schedule.
All as per Ser No 8.00 above but size 16 sqmm 4 core
All as per Ser No 8.00 above but size 10 sqmm 4 core
Taking out faulty underground LT 1100 volts grade heavy duty, armoured with steel strip of wire, with stranded aluminium conductor of sizes up to 50 Sqm 4 core by excavation and relaying at same location or any other location, rectification of fault removing of surplus soil and using new stone for cable cover as required complete all as speicified. Note: Excavation, stone for cable cover, tibba Sand and earth work will be measured and paid for seperately under respective items of schedule.
M&L for Cutting the road / hard standings and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete and matching with the surroundings complete all as speicified.
Supply and fixing in replacement GI Pipe light grade 50 mm dia with necessary accessories/ fittings bracing with pole/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah and all as specified and directed sizes:-
All as per ser item No 13.00 above but of size 40 mm dia
All as per ser item No 13.00 above but of size 25 mm dia
Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade 10 to 25 Sqmm 4 core and including taking out cable from faulty portion in any situation/position complete all as specified.
Supply, fixing and testing LT Outdoor End termination joint out door type heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade 16 to 25 Sqmm 4 core and including taking out cable from faulty portion in any situation/position complete all as speicified.
Strip opening and taking down carefully defective/non functional street light/flood/ gate/garden/post top lantern light fittings of LED's from its existing position and capacity & refixing the same after checking of serviceability (the power supply can not be meet to driver/ flexible cable burnt from junction box to driver/ control MCB not working in junction box) of the fitting complete all as specified. Note :- (a) Any other items i.e MCB, flexible cable,driver to be measured and paid separately. (b) Contractor provide Extendable wheel laddar or hydra without any extra cost.
S&F in replacement of LED street light fitting 60 Watt made out of pressure die cast aluminium powder coated housing high impact resistant 4mm thick toughened glass cover and matrix of power LEDs inbuilt electronic driver up to 10 KV surge protection fitted with adjustable pole adapter to enable on site tilt angle setting depending on road geometry CCT 5700-6000 CRI greater than 70, IP 66, PF >0.95,THD < 5%,input power 60 W system with 100 lumens per watt output operating voltage 160-260V complete all as specified.
All as per item No 19.00 above but of 90 watt light fitting.
Supply and fixing in replacement of LED flood light fitting 100 watts (with total lumen output not less than 100 lumens/Watt) with ingress protection IP 66 and external SPD of capacity 10 KV in addition to inbuilt SPD of electronic driver, having Pressure die cast housing with high efficient output emitter LED for better distribution, protection with heat resistant toughened glass with individual LED lenses complete including MS clamps of suitable size for fixing on Steel/PCC/Pole complete all as specified.
S&F Post top lantern LED type 20 watts 230V AC outdoor type with decorative post top for 360 degree indirect light IP-65 protection with impact and corrosion resistant complete with driver and lamp complete ll accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size and all acessories complete all as speicified.
Supply only electronic driver for LED light fitting, LED out put power 45/60 watt, input voltage range : 160 - 260 volt AC , out put voltage DC as per make/ model range: 24 volt to 110 volt, make as per site requirement complete all as speicified.
All as per item No 23.00 above capacity 90/100 watt
All as per item No 23.00 above capacity 120/150 watt
M & L for earthing in replacement complete with galvanised steel earth plate electrode 600 x 600x 6mm burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edged of the plate not less than 1.5 mtr below normal ground level, connected to galavanised iron earth lead by means of bolt, nut, check nut and washer of galavanised iron wire 4mm as earthing lead as shown in Electrical Plate No 3 of SSR Part I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in hard/dence soil, earth pit in PCC 1:3:6 type C1 using 20mm stone aggreate, funnel, 20mm dia GI medium grade water pipe, 15mm dia GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs, wire mesh, charcoal or coke and common salt in alterative layer all around the earth electrode compacted thickness 15 cm including excavation and earth work pit cover including disposal of surplus soil to a distance not excessding 50m, complete testing on completion all complete as shown in electrical plate No 3 of SSR Part I 2009 complete all as speicified.
S&F in replacement of 32 mm dia GI pipe bracket (Light grade) bent to shape of length not less than 1.2 mtr including fixing on wall/pole using flat iron clamps of suitable size ,nuts,bolts,washers etc includig paint of two coats of alluminium paint over one coat of red oxide primer suitable for street light fittings complete all as speicified.
Supply & fixing in replacement of PVC insulated, sheathed weather proof, copper conductor of size 1.5 sqmm, 3 core complete all as speicified.
M&L in replacement of PVC conduit 20 mm, heavy duty rigid non metallic including of all tee, bends, elbows etc complete all as specified.
M&L in repair for Danger notice plate of 1.6mmthick mils steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal redcolour and fixed wih M.S clamps bolts and nuts of approved size for LT20x15cm size complete all as speicified.
Supply and Fixing in replacement of pole mounted junction box of inside dimension 240x130x110 made out of FRP body (hot mulded type) with IP-66 protection and locking with screws alongwith 5/6 Amp rating MCB SP-01 No, up to 100 Amp rated 3 pole connector suitable to insert the cable size up to 25 Sqmm-01 No,with neutral link and din rail suitable for mounting the MCB/Connector etc complete in side box and duly fixed on steel tubular pole/PCC/RCC pole including cable glands, aluminum lugs/thimbles for incoming and out going cales complete all as speicified.
Supply and fix MCB SP 6-32 Amps 230V 10KA 'C' curve and taking down existing unserviceable from its own position and taken as schedule of credit complete all as speicified.
M&L painting of LT steel tubular pole /pcc pole any type of size externaly above foundation and junction box including all MS work with one coat of aluminium paint after scraping /cleaning well the existing surface complete all as speicified. Note :- The item included in the painting 5 Nos 30 cm wide bands black & Yellow synthetic enamel paint in alternate layer upto 1.0 mtr high above foundation and writing the pole No in 5 cm wide on base of yellow colour as per direction of Engr-in-Charge.
Supply and fix MCCB 4 Pole 100A Amps 415V 16KA and taking down existing unserviceable from its own position and taken as schedule of credit complete all as speicified.
Supply and fixing in replacement of power contactor of 415 volts 50Hz, 40 Amp capacity with 230 volts operated coil on existing panel/Timer complete all as speicified.
Restretching aluminium conductor or GI wire on existing over head lines without removing including unbinding from insulator and rebinding to insulator using aluminium binding wire, connections of incoming and outgoing cables, binding with spacers where required, complete all as specified Note :- (i) Length of span shall be 40 to 50 m. (ii) Due care shall be given while resagging of overhead conductor that there shall be no damage to pin/post/disc insulator and pole. In case, due to any negligence, damage is caused, it shall be made good by the contractor and nothing extra shall be admissible.(iii) Proper shut down will be taken from department and T&P will be provided by contractor
S&F PVC seperators/spacers clamp mounted on ACSR conductor suitable for 2/4 run
Trimming and cutting of tree branches coming across LT over head line, clearing alround 3m the LT line and disposal of branches/bushes to a distance upto 40/50m and cleaning the site complete all as speicified. Note :- (i) Length of span shall be 40 to 45m. (ii) Due care shall be given while trimming/cutting the tree branches that there shall be no damage to over head line conductor/pole. In case, due to any negligence, damage is caused, it shall be made good by the contractor and nothing extra shall be admissible.(iii) Proper shut down will be taken from department and T&P will be provoded by conractor.
S&F in replacement of steel structure, as in cross arms, bracing supports ,clamps, back plates of any type, section incl. nuts, bolts, washers, welding ,bending cold or hot in any size and shape all as directed Including two coats of aluminium paints over & including M&L single coat of red oxide primer incl preparation of surface complete all as speicified.
Supply and errecting in replacement of Prestressed concrete pole, 9.0 meter long,102mm x 152mm at top and 102mm x 289mm at bottom, class 10 including painting alternative black & white strips of 30 cm width upto 1.5 mtr above ground level and including dismantling and taking out the damaged/old PCC pole and setting aside within 50 mtr distance and opening the street light bracket/crossarms with connected items and street light fitting from old pole and refixing the same on new pole for street light fitting and all as required complete all as speicified.
S&F in replacement of GI stay assembly set comprising of 14mm dia 400mm iron stay bow and16mm dia, 2150mm long stay rod stay plate 230x230x6mm thick, GI stay wire 7/8 SWG of required length complete with all accessories as shown in electric plate No 1 of SSR Part 1 2009 complete with excavation earth work including PCC 1:3:6 of required quantity with loop insulator, clamps nut bolts etc complete all as required complete all as speicified.
M&L for dismantling PCC for coping/base foundation of PCC/steel tubular pole complete all as speicified.
Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole as a foundation or in any situation complete all as speicified.
Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole by demolition of existing /broken coping with taking out the LT cables and GI pipe Etc and refixing in new coping or in any situation complete all as speicified.
Shri Electrical Enterprises (BID ID -3339849)
DIWAKAR CONSTRUCTION CO. (BID ID -3340150)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .