REPAIR MAINTENANCE OF HT LT VCB ACB, APFC PANELS AND CERTAIN MISCELLANEOUS WORKS AT NPOL, KOCHI
2022_MES_539045_1
8132E8AGERDK
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KAKKANAD
As per tender doucments
6 documents required · 6 mandatory
₹500
Yes
AGE I R AND D KOCHI
₹19,800
Yes
26 Sept 2022
18 Jul 2022
17 Aug 2022
18 Jul 2022
15 Aug 2022
1 Aug 2022
Amount
M&L for Maintenance of HT/LT VCB/ACB of rating from 400 Amp to 3600 Amp 415 Volt 50 HZ of any make installed at substation/MRS at NPOL complete by taking the shut down with prior intimation and cleaning the HT/LT VCB/ACB by using air blower tightening of connection of control circuit and complete checking of all fuses, checking relay and control circuit for smooth functioning by employing one skilled tradesman as and when required and also to carry out following works . Note: Unit rate include for preventive maintenance / attending break down as and when required.
Check and clean incoming and outgoing terminals / compartment
Checking the serviceability of close and trip coil condition and taking out for replacement.
Checking the serviceability of control circuit , relays ,fuses and Electrical /Mechanical interlocks,
Replacing the spares such as Shunt release, UV release, tripping/ Closing coil shall be measured and paid separately under respective item.
Note : (a) Rate Quoted deemed to be including cost of replacing small piece of control circuit wires up to 1.00m, LT fuses and Push buttons for ON/Off if required .
Supply and fix in replacement shunt release for LT ACB 415/240 Volt AC up to 3600 Amp as per existing. Make: L&T / GE/Havells/English Electric
Supply and fix in replacement under voltage release 415/230 Volt suitable for LT ACB of rating up to 630 Amp as per existing. Make: L & T / GE/Havells/ English Electric
Supply and fix in replacement Volt meter 0-500 Volt digital type, Three phase of size 96 X 96 mm flush mounted case in existing panel including wiring from bus bar to volt meter terminals so as to match with the existing control wiring complete all as specified and as directed. [Make: Neptune/ AEI/ Meco/L& T/Elmeasure ]
Supply and fix in replacement digital Ammeter of size 96 X 96mm flush mounted of range from 50 Amp to 3500 Amp, three phase connected from CT ratio -/ 5 in existing panel with necessary wiring from CT to Ammeter and so as to match with existing control wiring complete all as specified and as directed by the engineer - in-charge. [Make: Neptune/ AEI/ Meco/ L& T/Elmeasure.]
Supply and fix in replacement current Transformer of following rating ,Indoor type, insulated ring type in existing panel including taking down old unserviceable CT's of any make /rating complete all as specified and as directed. [Make :AE / Kappa/PGR]
CT ratio 200 /5 Amps .
CT ratio 500 /5 Amps .
CT ratio 1000 /5 Amps .
CT ratio 1500 /5 Amps .
CT ratio 2500 /5 Amps.
CT ratio 3000 /5 Amps
M&L Earthing complete with galvanized steel earth plate electrode 600x600x6.0mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanized iron strip 25 X 4 .00 mm as earthing by means of bolts nuts and washers of galvanized iron including excavation and earth work and disposal of surplus soil including 40 mm GI tubing light grade and necessary fittings for protection of GI strip including laying of charcoal , dust and common salt, PCC 1:2: 4 type B 1 using 20 mm graded aggregate with earth pit with 40 X 40 X 6.0 mm MS angle iron frame RCC cover 40 mm thick (1:2: 4) Type C0 (using 12.50 mm graded stone aggregate) reinforced with 8 mm dia round bar @ 75 mm C/C both way with plastering 15 mm thick CM ( 1: 6) internally and up to 150 mm below ground level externally. PGI funnel with wire mesh, 20 mm dia medium grade GI pipe for watering complete all as shown on electrical plate No : 03 of SSR part - I 2009 and connected to earth test point including testing completed all specified and directed.
Supply, install, test and commissioning in replacement of Automatic power factor improvement panel of 50 KVAR capacity including APFC relay, capacitor of type heavy duty cylindrical, contactors and control wiring with copper wire in indoor type panel board made out of 2 mm thick CRCA sheet, CPRI approved , including cooling fan, copper bus bar of 250 Amp capacity, (independent cabin including locking arrangement for each, bus bar chamber etc with all necessary protection etc and 125 Amp capacity MCCB TPN rup capacity 16 KA as incomer complete all as specified and as directed . The panel shall be fixed with angle iron frame made of angles of size 50 X 50 X 6mm, bolted in ground /floor mounted and comprising the following:
i) 125 amp MCCB TPN Rup capacity 16 KA-01 No, Make: L&T /Legrand/ C&S/ Siemens ii) Digital V-A -F meter - 1 No. [Make: Neptune/ AEI/ Meco] iii) CT's for ratio as required -3 Nos [Make :AE / Kappa/PGR] iv) R -Y -B phase Indicator lamps LED type - 1 set [Make : Neptune / L&T / Vaisnavo/C &S] v) MCB 6 Amp SP 10 KA - 8 Nos, Make: L&T /Legrand/C & S vi) MCB 32 Amp TP 10 KA - 16 Nos Make: L&T /Legrand/C & S vii) 8 - stage APFC relay with built in P.F Meter - 1 Set [Make :C & S Cat NO. RG-8T/ Equivalent in L & T/C & S ]
M& L for surface dressing to E/M installations /1.5m from outside of fencing, E/M store yards of following area not exceeding 15 cm deep getting out soft / loose soil removing shrubs, small trees height up to 1.0m, removing the grass from route and cleaning the fencing by removing small trees /Vegetation on fencing complete all as specified and as directed. Note : (i) Rate includes removing all waste material and grass not exceeding 50m distance from installation ,depositing where directed at a level not exceeding 1.5m above the starting point and cleaning of yard , Complete all as specified and directed by Engineer-in Charge
Main Receiving substation of area 450 Sqm inside the Technical area
Substation no 02 ( MATS) of area 50 Sq m inside the Technical area
Substation no 03 (Near Post office) of area 180 Sqm
Substation no 04 ( At Site A ) of area of area 180 Sqm
Substation no 05 (Site A near type IV/V Accn) of area 180 Sqm
Substation no 06 (At Site ' B Near DREMI) of area 120 Sq m
Substation no 07 ( At Site ' B Near Type III Accn Area) of area 120 Sq m
Substation no 08/ T complex S/S ( At Site ' B ) of area 800 Sq m
Supply and fix fire retardant insulated synthetic mat for 1100 Volt of 2.0 mm thick +/- 10% conforming to IS 15652:2006, tested for breakdown strength, ageing properties, insulation resistance, effect of acid, Alkaline, Diesel & transformer oil ,leakage current test, fire test etc having the width of 1000mm +/-20mm complete as required suitable and using adhesive and allied chemical and scaling of all part s of all joints and border ends and fixing tape making good as paste near HT switch gear and transformer. Make: SUNTEX Insulatica PVt. Ltd / Equivalent Complete all as specified and directed by EIC.
Supply and fix in replacement Capacitor duty contactors with auxiliary contacts of following capacity including dismantling the existing duty contactors of any rating/make and making connection to fuse links /MCB and capacitor bank complete all as specified and as directed. Make: C & S/ L & T /Epcos
Capacitor duty contactor suitable for 50 KVAR
Capacitor duty contactor suitable for 25 KVAR
Capacitor duty contactor suitable for 20 KVAR
Capacitor duty contactor suitable for 15 KVAR
Capacitor duty contactor suitable for 12.5 KVAR
Capacitor duty contactor suitable for 5/8.5 KVAR
Supply and fix in replacement 8 - tag APFC relay with built in P.F Meter after dismantling the existing meter from APFC unit and programme the newly installed relay unit as per OEM instructions or in presence of OEM representative to match with existing arrangement of capacitor banks complete all as specified and as directed by engineer in charge. [Make :C & S / Equivalent in L & T ]
Supply and fix in replacement Capacitor banks, Cylindrical type Heavy duty of rating as required at site as specified and directed by EIC.(Make : EPCOS/ C & S/ L & T/)
Supply and ix in replacement LED type piolet lamp suitable for working voltage range up to 240 Volt AC . Make : Neptune / L&T / Vaisnavo/ C &S
M & L for cutting the tree branches at a distance not exceeding 2.0 Mtrs way from LT distribution lines, of tree branch of trunk size up to 50mm dia as directed and removing branches at a distance not exceeding 50 Mtrs from Road /Path. Note: Each pole locations / Distance between Two poles of Distance maximum up to 30 Mtrs is considered as One job irrespective of number of tree branches for cutting tree branches for over head lines .
M & L for cutting the tree branches at a distance not exceeding 2.0 Mtrs way from Street light poles /fitting, roof top of E/M Installation of G+0 Building of tree branch of trunk size up to 50 mm dia as directed and removing branches at a distance not exceeding 100 Mtrs from Road /Path. Note: Branch cutting around 2.0 Mtrs area to a 3 Nos street light pole is considered as one Job.
S& F in replacement on load change over switch of 630 Amp , 4 pole in existing panel with necessary modification in bus bar arrangement if required all as complete as directed by EIC .Make: L &T/ Havells / Siemens
M&L for wiring from CT's inserted in Incoming Switch gear/Bus Bar for sensing the instantaneous power factor to APFC relay with two run 2.5 Sq mm PVC insulated FR conductor passing through PVC conduit not less than 20 mm dia surface type fixed on wall/Panel with necessary saddles and fixing arrangements complete all as specified and as directed. Note: (i) Rate includes contractor has to check the APFC relay/panel after completion of work with different load condition, after disconnecting the existing supply connections to Relay panels complete. (ii) Quoted rate inclusive of conduit and fixing arrangements
Supply, install, test and commissioning of Indoor type LT Feeder piller box made out of 2.0 mm thick CRCA sheet outdoor type, CPRI Approved ,totally enclosed weather dust and vermin proof as per IS with front and rear 300 Amp capacity for RYB and half for neutral and insulated with insulators, including connecting incoming and outgoing cables necessary made out of 50 X 50 X 6 mm angle iron grouted at Floor above 30 cm from ground level Comprising the following including taking down old unserviceable feeder piller box, all as specified and as directed. Note: Cost includes necessary internal wiring for meters, CTs, indication lamps, etc and Rigid bus bar connections from bus bar to MCCB terminals connection Bus to MCCB/MCB connections
Incoming
i) MCCB 400 Amp 4 pole 16 KA - 01 Nos as incomming ii) Digital Volt Meter 0- 500 Volt -01 Nos Make: L & T iii) LED type Indicating lamps -03 Nos [Make : C& S/ Neptune / L&T / Vaisnavo] iv) MCCB 125 Amp 4 pole - 01 Nos (As out going)
Out going
i) Industrial Plug and socket TPN 125 Amp, 4 pole , 16 KA - 01 ( As Out going ) ii) MCB TPN 63 Amp 10 KA - 01 ( As Out going ) iii) Digital Ammeter 0 - 200 Amp -01 Nos [Make: Neptune/ AEI/ Meco] iv) CT's 200 /5 Amp - Set of three [Make :AE / Kappa]
AMRITH ENGINEERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .