Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹6.0 Cr
EMD Value
₹6.0 L
Closing Date
25 Nov 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Municipal Commissioner, Ahmedabad
Providing and Laying Offtake line, Construction of New Water Distribution Station, Construction of 5 L.L capacity of ESR and Water Distribution Network along with Electro-Mechanical Work, including 5 year of O and M, at New Water Distribution Station at Kamod Gam Lambha Ward in South Zone of AMC in South Zone of AMC under Water Project
364487
E-Tender Notice/2026-27 T.No.1
Open
Miscellaneous Works
Works
Ahmedabad
3 documents required · 3 mandatory
₹12,000
municipal commissioner, ahmedabad
₹6.0 L
7 Nov 2026
7 Nov 2026
7 Nov 2026
25 Nov 2026
7 Nov 2026
120 days
Providing and Laying Offtake line, Construction of New Water Distribution
Station, Construction of 5 L.L capacity of ESR & Water Distribution Network
along with Electro-Mechanical Work, including 5 year of O & M, at
New Water Distribution Station at Kamod Gam Lambha Ward in South Zone
Volume II: - Financial Bid
Section F: Schedule of Quantities & Rates
(1) Date of download Tender Documents : From website on www.tender.nprocure.com
(2) Last date of online Tender Submission : Dt. 25/11/2026 Upto 18.00 hours
(3) Last date of submission of Tender Fees, : Dt. 26/11/2026 up to 17.00 hours
EMD & Bidder’s letter (Hard copy)
(4) Date of e-Tender (Technical Bid) Opening : Dt. 27/11/2026 at 11.00 hours
Municipal Commissioner Multi Media Consultants Pvt. Ltd.
Ahmedabad Municipal Corporation 401, Shivalik Shilp,
Sardar Patel Bhavan Iskcon Cross Roads, S. G. Highway,
Ahmedabad – 380 001 Ahmedabad - 380
Gujarat (INDIA) Phone : (079)- 40399079 /
e-mail : [email protected],
website : mmcpl.co.in
Providing and Laying Offtake line, Construction of New Water Distribution Station,
Construction of 5 L.L capacity of ESR & Water Distribution Network along with
Electro-Mechanical Work, including 5 year of O & M, at
New Water Distribution Station at Kamod Gam Lambha Ward in South Zone of AMC.
PRICE QUOTATION SHEET
Earnest Money Paid Rs. : Rs. 5,97,890/-
Date of Opening of Tender :
Quoted Price in Rs.
I / We am / are willing to carry out work at _____________________ % above / below* percent (should be written in figures and
words) of the estimated cost, as mentioned above. Amount of my / our tender works out for Rs. ________________ (in figures)
Estimated amount put to tender Rs. Estimated amount put to tender Rs.
Add ________ % above Rs. __________ Deduct ________ % below Rs. ___________
Total Rs. __________ Net Rs. ___________
Signature of Contractor Additonal City Engineer(Water Project)
Name : Ahmedabad Municipal Corporation
Company's Seal :
AHMEDABAD MUNICIPAL CORPORATION
Water Project Department
PROVIDING AND LAYING OFFTAKE LINE, CONSTRUCTION OF NEW WATER
DISTRIBUTION STATION, CONSTRUCTION OF 5 L.L CAPACITY OF ESR , WATER
DISTRIBUTION NETWORK ALONG WITH ELECTRO-MECHANICAL WORK
INCLUDING 5 YEAR OF O & M, AT NEW WATER DISTRIBUTION STATION AT
KAMOD GAM LAMBHA WARD IN SOUTH ZONE OF AMС.
SUMMARY OF COST FOR ESTIMATE
SR NO NAME OF WORK AMOUNT IN RS.
A FOR CIVIL WORKS
1 Offtake Line Labour Work
2 Construction of 1.0 (M.L) U.G. Sump & Panel cum pump
room, Construction of Compound Wall & Miscellaneous
3 Additional Works for ESR not Covered in EPC Works
4 Distribution Network Labour Works
Amount of Civil & Network Works (A)
B ELE. / MECHANICAL WORK
1 Mechanical Work
2 Electrical Work
3 Instrumentation Work
4 Tools, Test Equipments & Office Furniture
5 5 Years O & M Works
Amount of Ele./Mech Works (B) Rs.
Estimated Amount (A)+(B) Rs.
Add (+/-) Above or Below Percentage %
Total Amount After ( above or below Rs. )
Total Amount After ( above or below Rs. )
C EPC Works for ESR
1 Construction of 5.0 (Lakh. Litre) Capacity ESR at 18mt To be quoted
Staging Height (EPC work) online
Total Amount (A+B)
Total Amount (A+B)
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULES OF QUANTITIES AND RATES FOR
LABOUR WORKS FOR LAYING 250 MM DIA DI K-9 OFFTAKE PIPE FROM EXISTING 1400 MM DIA
WATERMAIN TO NEW WATER DISTRIBUTION STATION AT KAMOD GAM LAMBHA WARD IN
SOUTH ZONE OF AMС.
Sr. Items Qty Rate in Rs. Unit Amount
No. Dist. in Rs.
1 Excavation for foundation with shoring and strutting if required as
per required gradient and line including safety provisions using site
rails and stacking excavated stuff including up to all required lead
cleaning the site etc. complete for all lifts and strata as specified.
2 Transporting from A.M.C. store and laying spigot & socket
C.I./D.I. pipe line including jointing material with tyton joint. Rate
include excavation as per requirement in any soil, refilling after
laying pipe line, watering and temptation & carting surplus earth
up to any lead & clearing the site. All joint shall be made water
tight and leak free etc. comp.
a 250 mm dia 530 113.39 Rmt.
3 D.I. Specials
D.I. Specials - Manufacture, Supply, Delivery of Ductile
Iron flanged Socket Spigot Bends, tees, reducers or any other
specials as per BS-EN-545/1995 Class-A series K12 suitable
for use with D.I Pipes manufactured as per IS:8329/1994 delivery
of specials to site of works any where in Gujarat including
fixing, all taxes, loading, unloading, carting, stacking,insurance,
inspection charges, octroi etc. complete.
4 Labour charges for collecting sluice valves /Scour Valve including
loading, transporting From AMC's store lowering in location to
required with excavation refilling alignment by crane/tripod and
chain block including cost of total nos.of nut, bolts, Necessary
gaskets and excluding fixing Tail Piece with lead & jute etc.
completed as directed by engineer in charge comp.
5 Providing and supplying CI Temper proof Air valves with SS
Float gun metal nozzle of approved make & quality of following
class and diameter including all taxes, transportation, freight
charges, octroi, inspection charges, loading, unloading, conveyance
to the departmental stores, stacking etc. complete.
With Isolating Sluice Valve PN
Sr. Items Qty Rate in Rs. Unit Amount
No. Dist. in Rs.
6 Lowering, laying & jointing in position following air Valves
including cost of all labour, jointing material, including nut bolts &
giving satisfactory hydraulic testing, etc. complete. With Isolating
Sluice Valve PN
7 Filling with available excavated earth (excluding rock) in trenches, 190.00 129.10 3
plinth, sides of foundation in layers not exceeding 20 cm in depth
consolidating each deposited layer by ramming and watering.
8 Providing & laying cement concrete 1:2:4 (1 cement :2 coarse sand 20.00 4732.00 m3
: 4 graded stone aggregates 20 mm nominal size) and curing
complete ,excluding cost of form work including(Thrust block &
9 Providing and casting in situ C.C. in grade M-20 (proportions as 10.00 5520.00 m3
per mix design or as per table9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to
mm for RCC work, including scaffolding centering, formwork,
needle vibrated consolidation, curing complete up to 6 meter depth
or height (excluding cost of reinforcement and neat finishing) with
centering and shuttering/deshuttering etc. complete for structure
other than water retaining (Below G.L) .(With formwork)
10 Supplying cutting, bending, binding and placing in position steel as 1.00 77504.00 MT
per plan and design and as per ISS 2502 including cost of steel and
binding wire for reservoirs/structures only including lift up to
meter height or depth below G.L. for all diameters
Do - deformed (TMT) bars confirming to relevant IS Fe -
grade for all diameters.
11 Construction of chambers in brick masonary, locally available in
C.M. 1 : 6, foundation concrete 150 mm thick in C.C. 1:4:8 of trap
metal size 25 mm to 40 mm thick, inside cement plaster in C.M.
1:3 and cement pointing outside in C. M. 1 :3 & top cover of
precast RCC slab 100 mm thick upto 1 mt. depth from G.L. but
excl. cost of excavation and refilling. With cast in situ RCC slab in
two piece with fixing FRC frame and cover etc.
complete(excluding cost of frame & cover ) with 23 mm thick
brick masonary wall in C.M.1:6
For Sluice Valve, Air Valve
a) 0.9 x 0.9 x and 1.0 mt. deep chamber 2.00 7738.00 No.
b) For Extra depth 2.00 4479.00 Rmt.
c) 1.3 m x 0.9 m x 1 m deep chamber 2.00 9389.00 No.
d) For Extra depth 2.00 5282.00 Rmt.
e) 1.3 x 1.3 x and 1.0 mt. deep chamber 2.00 11351.00 No.
f) For Extra depth 4.00 6084.00 Rmt.
Sr. Items Qty Rate in Rs. Unit Amount
No. Dist. in Rs.
12 FRC Manhole 6.00 2125.00 No
Providing & Fixing F.R.C. Extra Heavy Duty (EHD-35)
Manhole Covers & Frames Cover : 728mm ø & 100 mm thick
circular cover, 35.00 MT load design, 100x2mm MS flat allround,
16mm ø plain round bar for lifting the cover & should be fitted
with plastic cups. Frame : 560 mm ø clear opening, outer size-
888x888x175 mm. On the upper periphery of frame 25 x 3 mm
wide MS flat should be well embed in concrete to protect the
edges of frame. FRC E.H.D.-35 manhole cover & frame described
as above incl Carting
Heavy Duty Frame & cover of MH
13 Extra rate over item of excavation of earth for excavation of asphalt
pavement/RCC of following thickness including demolishing the
asphalt carpet, metal, soiling/cutting Reinforcement etc. comp.
with stacking the material as directed.
a up to 0.20 meter thickness (By Manual) 113.85 71.43 m2
b up to 0.30mt (by any type of Breaker Machine or R.C.C Cutter 56.93 178.57 m2
machine including cost of operator, fuel & transportation etc
c 0.30mt & above (by any type of Breaker Machine or R.C.C Cutter 56.93 312.50 m2
machine including cost of operater, fuel & transportation etc
14 Reinstatement of asphalt road/pavement using same material for 170.78 231.47 m2
soling and new metalling grouting with tack coat etc complete as
15 Providing and operation dewatering pump including fuel charges & 50.00 535.71 Shift
operatore charges etc as directed etc comp(shift for eight hour) for
each pump set,no payment should be allowed for non working
condition of machinery.
16 Conveyance charge of earth, lime, murrum, building rubbish, 150.00 415.76 3
manual garbage, sludge, excavated rock, fly ash, aggregate of any
kind etc.(for valve chamber)
17 Demolition and disposal of unserviceable materials with all lead 10 603.23 m3
and lift.(i) Unrenforcement cement concrete
18 Demolition including stacking of serviceable materials and 10 1047.38 m3
disposal of unserviceable maerials with all lead and lifts (b) R.C.C
19 Demolation of Brick work and stone masonary including stacking 10 544.95 m3
of serviceable materials and disposal of unserviceable materials
with all lead and lift.(i) In cement mortar.
20 Providing & Supplying group wise MS bare pipe per kg are as
a) upto 914mm OD & upto 10mm Thickness of Plate/Pipe 2710 70.67 Kg
b) Above 914mm OD & Above 10mm Thickness of Plate/Pipe 150 71.17 Kg
Sr. Items Qty Rate in Rs. Unit Amount
No. Dist. in Rs.
21 Welding in all positions with required number of runs, for M.S.
pipes internally and / or externally including gauzing wherever
necessary, fixing appurtenances and other accessories in
connection with pipe laying work as per specification. Butt joints
with convex fillet welds Lag Lengths.
a) Above 7 mm thickness plate 50 729.00 Rmt
b) 4 to 7 mm thickness 25 681.00 Rmt
22 Gas cutting ( Either square cut or V cut) pipes, plates etc. complete
for following thickness plate
a) Above 10 mm thickness plate 50 72.00 Rmt
b) 5 to 10 mm thickness 50 56.00 Rmt
23 Drilling of 600mm dia Horizontal borehole for watermain pipeline 80.00 11604.16 Rmt
crossing under the road incl in all strata with required length incl
fixing of 500mm dia M.S./RCC casing pipe with pushing etc
complete various size of pipe for 273.1 to 355.6mm dia watermain.-
without water main & with MS casing pipe 500, thick 8 .
24 Making connection upto 250 mm dia DI/MS/HDPE Pipe with 1.00 90000.00 No
Existing trunk main including cutting the pipe to required annular
shape dia. by Electro Welding and jointing upto 600 mm dia
DI/MS pipe, including dewatering, excavation, refilling etc. with
all required materials such as welding rods and other necessary
required materials including giving a satisfactory leakage proof
25 Supplying Electric breakar machine for RCC slab or Asphalt 10.00 1071.43 Shift
demolishing work on site by using operator, fuel, power supply etc.
complete as directed.(no payment should be allowed for non
working condition of machinary and for pipeline excavation and
M.H. work.allowed only for break down work)(based on
previously approved rate by CE Sir)
26 Providing, laying, spreading and compacting graded stone
aggregate to wet mix macadam specification including premixing
the Material with water at OMC in mechanical mix plant carriage
of mixed Material by tipper to site, laying in uniform layers in
subbase / base course on well prepared surface and compacting
with vibratory roller to achieve the desired density as per MoRTH
(a) Production & Supply of WMM 50.00 1495.54 3
(b) Laying of WMM 50.00 31.25 3
Sr. Items Qty Rate in Rs. Unit Amount
No. Dist. in Rs.
27 Providing laying and jointing in true line and level following Dia
U.P.V.C. Pipe (SCH-40) for cold water including fittings as
approved by Engineer In Charge. Pipe shall be fixed on the wall
with the help of clamp at every two metre C/C or shall be
concealed as directed including necessary fittings etc. including
testing of pipe and joints and fixing the same with adhesive
solvent, including cost of all materials.
a) 15 mm Dia uPVC Pipe 25.00 71.93 Rmt.
b) 25 mm Dia uPVC Pipe 25.00 90.93 Rmt.
c) 40 mm Dia uPVC Pipe 15.00 146.65 Rmt.
d) 50 mm Dia uPVC Pipe 15.00 193.73 Rmt.
28 Making holes on existing C.I./ D.I./MS water pipe line including
necessary GI fittings item also includes necessary excavation,
dewatering and refilling as per instruction engg. In charge etc.
Total of Labour in Rs.
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
CONSTRUCTION OF NEW WATER DISTRIBUTION STATION AT KAMOD GAM LAMBHA WARD IN
SOUTH ZONE OF AMС.
Sr. Items Qty. Rate in Rs. Unit Amount
1 Excavation for foundation with shoring and strutting if required as
per required gradient and line including safety provisions using site
rails and stacking excavated stuff including up to all required lead
cleaning the site etc. complete for all lifts and strata as specified.
2 Filling with available excavated earth (excluding rock) in trenches, 1668.00 129.10 m3
plinth, sides of foundation in layers not exceeding 20 cm in depth
consolidating each deposited layer by ramming and watering.
3 Filling in plinth with sand under floors including watering ramming, 10.00 455.63 m3
consolidating and dressing complete
4 Extra over item no. 1 above for lead from 50 m to 5 Kms. as 360.00 415.76 m3
5 Extra over item no. 1 above for lead from 5 Kms. to 10 Kms. as 1160.00 462.71 m3
6 Providing and casting in situ C.C. in grade M-15 (approx. corresp. 170.00 4,732.00 m3
to prop. 1:2:4) (proportions as per mix design or as per Table 9 of
IS456 2000 in masses by weigh batching ) using granite, quartzite
trap metal of size 6 mm to 20 mm for RCC work, including
scaffolding centering, form work, needle vibrated consolidation,
curing comp. (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. comp. for structure
for other than water retaining. Footing (without form work)
7 Providing and casting in situ C.C. in grade M-15 (approx. corresp. 71.00 4,906.00 m3
to prop. 1:2:4) (proportions as per mix design or as per Table 9 of
IS456 2000 in masses by weigh batching ) using granite, quartzite
trap metal of size 6 mm to 20 mm for RCC work, including
scaffolding centering, form work, needle vibrated consolidation,
curing comp. (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. comp. for structure
for other than water retaining. Footing (with form work)
Sr. Items Qty. Rate in Rs. Unit Amount
8 Providing and laying one layer of bitumen kraft paper conforming 372.00 17.00 m2
to IS : 1398 of approved make and quality.
9 Providing and cast in situ C.C. in grade M-30 proportions of
ingredients as per mix design by weigh batching using granite,
quartzite trap metal of size 12 mm to 20 mm and or 6 mm to 12 or
mm to 12 mm mm including scaffolding centering formwork,
needle vibrated consolidation, curing and hydrulic testing etc.
complete (excluding cost of reinforcement) with centering &
shuttering/ deshuttering etc. for all water retaining structures.
a) R.C.C. Raft and footings 140.00 8,213.00 m3
c) R.C.C. Columns 30.00 9,317.00 m3
d) R.C.C. Beams 30.00 8,486.00 m3
e) R.C.C. Slab & Staircase 50.00 8,213.00 m3
10 Providing and cast in situ C.C. in grade M-25 proportions of
ingredients as per mix design by weigh batching using granite,
quartzite trap metal of size 12 mm to 20 mm and or 6 mm to 12 mm
including scaffolding centering formwork, needle vibrated
consolidation, curing and hydrulic testing etc. complete (excluding
cost of reinforcement) with centering & shuttering/ deshuttering etc.
for all water retaining structures.
a) R.C.C. footings & Raft 55.00 8,077.00 m3
b) R.C.C. Columns 60.00 9,195.00 m3
c) R.C.C. Vertical Walls 5.00 7,936.00 m3
d) R.C.C. beams, lintels and bracket for gantry or chain pully blocks, 120.00 8,347.00 m3
plinth beams, tie beams, weather shed etc.
e) R.C.C. Slabs, Stair & platform 21.00 8,077.00 m3
11 Providing and cast in situ C.C. in grade M-20( proportions as per
mix design or as per table of IS456 2000 in masses by weigh
batching) using granite, quartzite trap metal of size 6 mm to 20 mm
for RCC Work including scaffolding centering formwork, needle
vibrated consolidation, curing complete up to 6 meter depth or
height (excluding cost of reinforcement and neat finishing) with
centering and shuttering/ deshuttering etc. complete for structure
other than water retaining.
a) R.C.C. footings & Raft with formwork 19.00 5,520.00 m3
b) RCC Coping 2.00 6,722.00 m3
Sr. Items Qty. Rate in Rs. Unit Amount
12 Extra Over Item no 7,9,10,11a for Ready Mixed concrete using 594.00 1,000.00 m3
cement content as per approved Mix Design in fully automatic
batching plant and transported to site of work in transit mixer for
any lead having continuous agitated mixer, manufactured as per mix
design of specified grade for cement concrete work including
pumping of R.M.C. from transit mixer to site of laying if required,
The rate is excluding the cost of centering shuttering finishing and
reinforcement but including cost of admixtures in recommended
proportions as per IS: 9103 to accelerate/ retard setting of concrete,
improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. The Concrete must be
without Fly Ash (Min cement level as should be as specified in
13 Supplying cutting, bending, binding and placing in position steel as 103.00 77,504.00 MT
per plan and design and as per ISS 2502 including cost of steel and
binding wire for reservoirs/structures only including lift up to
meter height or depth below G.L. for all diameters Do - deformed
(TMT) bars confirming to relevant IS Fe - 500 grade for all
14 Extra Over Rate Item No 12 for TMT FE500 replaced over CRS 10.00 1,073.00 MT
TMT FE 500 in UG Sump Slab and Beam
15 Grouting with 1:3 cement, sand mortar for anchor bolt pockets, 5.00 4,536.00 m3
machine bases, pipe sleeves, pockets holes, etc. including
roughening and cleaning of concrete surfaces, curing, etc. complete.
16 Supplying, fabricating and embedding M.S. anchor bolts, channels, 1650.00 82.50 Kg.
angles, chequered plates all other type of Structural Steel in
concrete members during concreting as per drawings and
instructions in all positions and at any level including keeping them
in correct position and alignment, including adjustment of
reinforcement and shuttering, etc complete and including two coats
of approved oil paint over red oxide primer of exposed surfaces for
above mentioned inserts after embedment, etc. all as specified.
Sr. Items Qty. Rate in Rs. Unit Amount
17 Providing and casting in situ C.C. in grade M-20 (proportions as per 1.00 6,504.00 m3
mix design or as per table9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to
mm for RCC work, including scaffolding centering, formwork,
needle vibrated consolidation, curing complete up to 6 meter depth
or height (excluding cost of reinforcement and neat finishing) with
centering and shuttering/deshuttering etc. complete for structure
other than water retaining(Below G.L) for top flat slab /slab of
various thickness
18 Interior plain faced 15 mm thick cement plaster (1:3) with floating 360.00 295.90 m2
coat of neat cement slurry on Underneath of top of UG tank where
specified on drawings at all levels including scaffolding, curing, etc.
complete. This rate shall include moulding where specified. The
rate shall include 2% approved quality water proofing compound
(by weight) of cement.
19 Providing and applying 20 mm thick inside cement plaster with 760.00 202.00 m2
water proofing agent on inside of sump consisting of 12 mm thick
backing coat of CM 1:3 (1 cement : 3 sand) and 8 mm thick
finishing coat of CM 1:1 (1 cement : 1 sand) etc. complete including
necessary curing, scaffolding required if any etc. complete.
20 Providing and applying 15 mm thick cement plaster in single coat
on brick work with floating coat of net cement slurry for interior
plastering of pumphouse and outside plastering of sump upto
finished even and smooth in Cement motar 1 : 3 (1 cement :
sand) including racking out joint curing, scaffolding required if
any, with necessary cement finishing etc. complete as directed.
(ii) Ceiling 230.00 247.13 m2
21 20 mm thick sand faced cement plaster on walls upto height 10 1435.00 297.68 m2
metres above ground level consisting of 12mm thick backing coat of
C.M. 1:3 (1-cement : 3-sand) and 8 mm thick finishing coat of C.M.
1:1 (1-cement : 1 sand) etc. complete.
22 Providing and laying cement concrete flooring 1:2:4 (1 cement :
coarse sand : 4 graded stone aggregate 20 mm nominal size)
including water proofing compound finishing with a floating of neat
cement slurry etc. complete laid in one layer finished including
necessary curing at bottom of sump.
Average 50 mm thick 300.00 356.94 m2
Sr. Items Qty. Rate in Rs. Unit Amount
23 Providing and laying Trimix with dewatering machine and floater 460.00 48.21 m2
machine on constructed RCC work including cost of machine and
labour etc. compact directed .
24 Making 15 mm groove in RCC work on road and finished it good 380.00 26.79 Rmt
incl. all labour charges etc comp as directed.
25 Providing and laying polished Kota stone slab flooring over 20 mm
(average) thick base of cement mortar 1:6 (1 cement : 6 coarse
sand) laid over and jointed with grey cement slurry including
rubbing and polishing etc. complete.
Avg 20 to 25mm thick 70.00 1,085.48 m2
26 Providing and laying polished Kota stone slab 25 mm thick in riser 10.00 1,176.03 m2
of steps,skirting dedo and pillars laid on 10 mm thick cement
mortar 1:3 (1 cement : 3 coarse sand) and jointed with grey cement
slurry including rubbing and polishing etc. complete
27 Providing and fixing in position 150 mm diameter and 610 mm 5.00 2,576.00 No.
heigh CI air ventilators including fixing of jali grating and cover and
painting the same. (wt. 40 Kg.)
28 Providing F.R.C. MH seat cover incl. carting to the work site etc. 5.00 2,125.00 No.
comp. Directed. (Based on rate of central store) F.R.C. Extra Heavy
Duty (EHD-35) Manhole Covers & Frames Cover : 728mm ø &
100 mm thick circular cover, 35.00 MT load design, 100x2mm MS
flat allround, 16mm ø plain round bar for lifting the cover & should
be fitted with plastic cups. Frame : 560 mm ø clear opening, outer
size- 888x888x175 mm. On the upper periphery of frame 25 x
mm wide MS flat should be well embed in concrete to protect the
edges of frame. FRC E.H.D.-35 manhole cover & frame described
29 Providing & Fixing F.R.C. MH seat cover incl. carting to the work 5.00 1,633.93 No.
site etc. comp. Directed. (Based on rate of central store) FRC
medium duty Chamber seat cover (FRC) cover 706 x 556 x 50 mm
rectangular cover frame size 600 x 450 mm clear opening outer size
816 x 666 x 100 mm (MD-10) cover
30 Providing 100 mm x 100 mm size vata in cement mortar (1:1) 200.00 23.45 Rmt
including smooth finish, curing, etc. complete.
31 Providing 100 mm x 100 mm size vata in cement concrete (1:2:4) 135.00 44.00 Rmt
including water proofing compounds, smooth finish, curing, etc.
complete for the internal side of the sump, pump house
Sr. Items Qty. Rate in Rs. Unit Amount
32 Brick masonry in cement mortar (1:5) using common burnt clay 81.00 4,283.91 m3
building bricks having crushing strength not less than 35kg/cm2
including scaffolding,curing, etc. complete for walls, parapets, etc.
33 Brick work using common burnt clay building bricks having 266.00 4,253.46 m3
crushing strength not less than 35 kg / Sq. Cm. in foundation
and plinth in cement mortar 1:6 (1 cement : 6 fine sand) etc.
complete for walls, parapets etc. at all levels
34 Brick work using common burnt clay building bricks having 27.00 4,011.66 m3
crushing strength not less than 35kg / Sq. C. M. in ramp, steps and
Foundation & Plinth in cement morter1:5 (1 cement : 5 coarse sand)
35 Providing Half brick masonry in common burnt clay building bricks 10.00 593.90 m2
having crushing strength not less than 35 Kg/cm2 in C. M. 1:4 for
partition work including raking out joints, curing, scaffolding etc.
complete as directed for any height.
36 Finishing wall with weather proof exterior emulsion paint on wall 1510.00 113.40 m2
surface (two coats) to give an required shape even shade after
thoroughly brushing the surface to removal dirt, and remains of
loose powdered materials.etc complete
37 Distempering (two coats) with oil bound distemper of approved 1220.00 76.08 m2
brand and manufacture and or required shade on undecorated wall
surface to give an even shade, over and including a priming coat
with distemper primer of approved brand and manufacturer after
thoroughly brushing the surface free from mortar dropping and
other foreign matter also including preparing the surface even and
sand papered smooth.
38 Applying two coats of Birla(white cement based) or Asian 1176.00 40.19 m2
(acryliclapy putty) or equivalent & two coats of primer of approved
brand and manufacture on new wall surface to give an even shade
including thoroughly brushing the surface free from mortar
dropping and other foreign matte rand sand papered smooth.
Sr. Items Qty. Rate in Rs. Unit Amount
39 Providing and fixing window having extruded aluminum Colour 22.00 1,568.27 m2
anodized section frame main outer size 95mm x 24mm x 1.17 mm
(of Jindal Section no : 2459 @ wt. of 0.738 Kg/mt), horizontal
Three track member size 92mm x 31.75 mm x 1.30 mm (of Jindal
Section no. 8688, @ Wt. 1.07 Kg/mt), vertical member of size
92mm x 31.75mm x 1.50 mm (of Jindal Section no. 8933, @ Wt.
1.06 Kg/mt.) with sliding shutters of horizontal member size 40mm
x 18mm x .29 mm (of Jindal section no. 8947 @ wt. 0.456 Kg/mt.)
vertical member of size 40mm x 18mm x 1.29mm (of Jindal Section
no. 8949 @ wt. of 0.456 Kg/mt with 5 mm thick transparent bronze
colour tinted float glass with powder coated aluminum fittings and
fixtures and transparent silicon sealant glass fixing to frame as per
40 Providing and fixing standared extruded of alluminium section of 10.00 1,163.92 m2
size 63mm x 38.10mm x 1.2mm @ Wt. 0.643 Kg/mt with colour
anodized alluminium frame for ventilation with 5 mm thick frosted
glass as details etc complete for Ventilation
41 Providing precast cement concrete jali or louvers 40 mm thick 1:2:4 1.00 640.20 m2
mix (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm
nominal size) reinforced with 1.6 mm dia. Mild steel wire including
roughening, cleaning, fixing and finishing in CM 1:3 and curing,
painting complete
42 Supplying, fixing Push and Pull, 20 gauge rolling shutter of 12.00 4,277.00 m2
approved make for the sizes indicated on drawings including hood
cover, channel sliding assembly, helical coil springs, brackets,
interlocking latches, locking arrangements, painting with 2 coats of
enamel paint over one coat of approved primer paint etc. complete.
Shutters having width below 3.5M (gear Operated)
43 Kota stone in Jams and Sills of the window and ventilation and 50.00 1,107.00 m2
Door with one molding as directed by Engineer-in-charge.
44 Paint on soffit of tank roof slab with 2 coats of bituminous paint 400.00 143.00 m2
including cleaning the surface by scrapping and air blowers as
directed by engineer in-charge.
45 Providing and fixing 50 mm dia and 300 mm long PVC pipe/spout 40.00 40.00 No.
in RCC beams of U.G. Tank roof slab and RCC peripheral wall on
slab top. Rate shall include carting/cutting in required size and
shape etc. complete as directed.
Sr. Items Qty. Rate in Rs. Unit Amount
46 Providing and fixing PVC pipe of 6 Kg./cm2 of 160 mm dia for 5.00 1,235.00 No
rain water pipe with shoe.
47 Providing and fixing 40mm dia. GI pipe medium weight quality as 15.00 1,397.00 Rmt
openable type with angle iron support at 1.5 m c/c using 75 x 75 x
10 mm angles, 1 m long with three rows of pipes as railing
including necessary painting with two coats of approved quality oil
paint over one coat of approved primer including necessary
welding, bolting required, if any.
48 Painting two coats including priming coat on new steel & other 50.00 121.28 m2
metal surfaces with enamel paint, brushing, interior to give an
even shade including cleaning the surface of all dirt, dust, other
foreign matter.
49 Providing and fixing in position 60 cm wide MS ladder with angle 5.00 5,619.00 Rmt
of 75 x 75 x 6 mm as support and 50 x 50 x 5 mm angle as step at
200 mm c/c including (both side) GI side railing with ISA
support including fixing in cement concrete for any height including
making holes in RCC walls if any and making good the RCC wall /
masonry wall after fixing work of staircase etc. complete as directed
including two coats of approved quality oil paint directed including
two coats of approved quality oil paint over one coat of approved
quality primer.
50 Manufacture,Supply & Delivery of Ductile Iron Flange socket
spigot bends,tees,reducers,or any other specials ass per BS-EN-
545/1995 Class-Aseries K12 Suitable for use with DI pipes
manufactured as per IS:8392/1994 delivery of specials is to be made
to Store or site of works anywhere in gujarat including all taxes
loading, unloading, carting, stacking, insurance , inspection
charges,octroi etc. complete.Bends (Both side Flange ended)
a) Bends (Both side Flange ended)
b)/I Puddle pipe with flanges at both ends
b)/II Puddle pipe with one End flanges
c) Ring flanges
ii) Above 300 mm dia. 50.00 158.00 Kg.
d) Blank Flanges
ii) Above 300 mm dia. 50.00 158.00 Kg.
Sr. Items Qty. Rate in Rs. Unit Amount
51 Providing and laying chequered precast cement concrete tiles 22mm 40.00 522.78 m2
thick with aggegate of sizes upto 6mm in floors, treads of steps and
landings on 20mm thick bed of C.M. 1:6 (1-cement : 6-sand) or
L.M. 1:1.5(1-Lime putty : 1.5 coarse sand) joint with neat cement
slurry with pigments to match the shade of the tiles.
52 Providing, Fabricating & fixing WDS name board of Size 1.00 15,640.00 No.
3.00mX0.60 made from ISA 50X50X5 mm M.S angle with 3 Nos
supports at back side vertical member of angle size 1.1m ht incl
m hold fast inserted in compound wall with necessary dismantling
and fixing with cement concrete. The rate shall also incl 16 g M.S
sheet of size 3.00X0.60 mt incl ACP Sheet with Printing letter with
AMC logo as directed by EIC. rate shall incl painting board with
coat of enamal paint over one coat of anti-corrosive primer.
53 Providing, Fabricating & fixing caution board of size 1.50m x 1.00 7,900.00 No.
0.60m made from ISA 40 x 40 x 5 mm MS angle with 2 nos.
supports at back side vertical member of of angle size 1.10m height
(inclu. 0.30m hold fast inserted in compound wall with necessary
dis-mantling and fixing with cement concrete. The rate shall also
include 14g MS sheet of size 1.50mt x 0.60mt including writing
notice letters as directed by engineer in charge the rate shall incude
painting board with two coats of enamel paint over one coat of anti-
corrosive primer.
54 Providing and fixing Radium sign board of size 3.00mt x 0.60 mt 1.00 7,400.00 No.
made from ACP sheet with writing coloured reflected letter of WDS
name board with necessary clamp for hanging board at pump house
etc. comp as directed by Eningeer in charge
55 Providing and fixing 1.20 Metre high fencing with 2.0 Metre long 30.00 385.40 Rmt
M.S. Angle posts 40mm x 40 mm x6 mm and oil painting 3 coats
fixed at 2.5 Mt,C/c. with five Horizontan lines and two diagonals of
galvanised steel barbed wire weighting 9.38 Kg. per 100 Metre,
strained and fixed to posts with G.I,staples including fixing the
postsin ground with 0.5 M x 0.5.M x 0.5 M. block in C.C1:5:10 etc
56 Providing & Supplying JCB Machine on rental basis in case of 10.00 535.71 Hr
emergency situation and break down type work & also during
unavoidable condition as per instruction of engg.incharge , rate
includes all nece. shifting, fuel and operating charges and stacking
of useful & non-useful materials separately up to store. (No
payment should be allowed for non working condition of machinery
and for pipe line excavation and laying work)
Sr. Items Qty. Rate in Rs. Unit Amount
57 Providing the site grading to the site by excavation / earth fill as per 1500.00 2.50 Mtr
lines and levels and grading the finished ground level with surplus
imported earthfill in dry condition, as directed by the engineer-
incharge etc complete.
58 Making hole of following dia pipe in RCC. Rate includes electrical
hand operated braker set, Gas cutting set with all required
equipment & removing debris etc. complete
59 Providing & laying rubble below raft foundation including carting 30.00 1,335.00 Cmt
to the work site , ramming consolidating & dressing etc, Complate
including supplying and spredsing of stone dust filling the gap in
rubble and leveling complete .as instruction given by Engineer in-
60 Providing in line level plumb, fabricating and fixing three row 240.00 449.00 Rmt
horizontal barbed wire fencing and punched tape concertina
coil of 9 turns per meter of 610 mm diameter fixied with clips
on top of the angle iron posts. The punched tape concertina
coil having sharp barbs at every 25 mm spacing shall be
mm thick and 19 mm width and weighting 13 Kg./100 mtr.
(Average) as per manufacture's specification. The rate shall
also include providing and fixed 1.20 mt. total long MS angle
40 x 40 x 6 mm @ 3.00 mt. c/c spacing embedded in RCC
column, angle posts shall be painted with one coats of red
oxide and two coats of enamel paint of approved quality at top
of compound wall.
61 Labour charges for writing of capital letter "AMC" in green 80.00 381.00 No.
plaster of 30 cm height, 25 mm thick and 12 mm embossed as
per given detail in outside of compound wall as instructed by
Engineer in charge.
62 Manufacturing, supplying, laying and jointing 150 mm dia 80.00 367.00 Rmt.
RCC P2 Pipe of 0.3 m long as per IS-458 'specification for
compound wall and fixing as per directed by Engineer-in-
63 Fabricating and fixing in position MS structural section such 2850.00 82.50 Kg.
as flat, pipes, plates, hold fast, anchoring bolts / bars of
required size including fixing, welding and two coats of
approved anti corrosive paint over prime coat of red-oxide
including RCC gate column as per drawing etc. complete as
directed by Engineer-in-charge.
Sr. Items Qty. Rate in Rs. Unit Amount
64 Providing and Laying of Rubber Moulded Paver Block 150.00 383.04 m2
Grey/Coloured 60 mm thick, M-35 Grade of any size ; shape
(Usually Uni-Paver Blocks) using black trap good quality
aggregate of 20 mm nominal size for footpath, parking areas,
service lanes and other areas as mentioned in the drawing /
instruction of engineer in charge. Cost includes formworks
using rubber mould, Rate providing and laying paver blocks
as per required grading and specification. The paver block
shall be mechanically compacted. The work of paving blocks
shall be executed in line and level by skill mason of flooring
work only. It should be laid in such a way that the no cutting
of the paver block to be necessary. If cutting of paver block
necessary then it should be cut by machine only and carting.
The finished surface of the paver block shall have reasonably
good, plain finished. Paver blocks shall be compacted and
shall be relaid if necessary. Gravel or such type of materials
shall not be allowed for production. Laying on 5 cms thick
65 Supplying and fixing of 300 mm-L x 150 mm-B x 380 mm-H Kerb
block for Footpath in M-20 grade using 20 mm nominal size black
trap aggregate of Sevaliya/Timba or equivalent quality for pre-cast
blocks, reasonably exposed finish/ formwork , mould with well
equipped with vibratory system for kerb stones of approved design
including curing, etc. complete, including the cost of formwork etc.
complete. The rate shall also include necessary cutting of asphalt,
fixing the Kerb stones in line and level on 5 cm thick sand bedding
with necessary equipments and materials. The rate shall also include
the flush pointing in CM (1:3) for all joints of the kerbstones.
Filling of zari alone the sides of the kerb stone fixed with
Bituminous concrete Bituminous concrete / C.C. mixed in proper
position to flush with the road surface as directed by Engineer in
change to form a portable mixture.
(a) Laying on 5 Cms thick sand Bedding 100.00 350.89 Rmt
66 White washing with lime on wall surfaces (two coats) to give an 50.00 10.97 m2
even shade including thoroughly brooming the surface to remove all
dirt, dust, mortar drops and other foreign matter etc. complete.
67 Extra over above item for every subseqent coat of white washing 50.00 5.06 m2
with lime on wall surfaces
68 Demolition and disposal of unserviceable materials with all 5.00 603.23 m3
lead and lift.(i) Unrenforcement cement concrete
Sr. Items Qty. Rate in Rs. Unit Amount
69 Demolition including stacking of serviceable materials and 5.00 1,047.38 m3
disposal of unserviceable maerials with all lead and lifts (b)
70 Demolation of Brick work and stone masonary including 5.00 544.95 m3
stacking of serviceable materials and disposal of unserviceable
materials with all lead and lift.(i) In cement mortar.
71 Dismentaling steel work including distempering and stacking 5.00 3.63 Kg.
the material with all lead and lift.
72 Manufacturing, supplying, loading, unloading to work site,
lowering trenches, laying and jointing RCC pipes following
class with Socket and spigot joints as per IS 458-2003
including EPDM Rubber ring as per IS 5382-1985 etc.
Comp.As Directed by Engineer in charge RCC NP3 Pipe
a 300 mm dia. 20.00 616.07 Rmt
73 Constructing Bombay Pattern Type Catch Pit of size 0.60 x 6.00 3,500.00 Nos
0.60 depth up to 1 mt including excavation, B.B.C.C. (1:5:10),
23 cms thick brick maso. wall in the prop. of CM (1:6) with
40 mm thick IPS flooring in the prop M15 at bottom and
mm thick cement plaster inside the catch pit in the proportion
of CM (1:3) with out jali etc. comp. as directed.
74 CatchPit Jali Fixing P/F FRC catch pit jali with frame 600mm 6.00 1,383.93 Nos
x 600mm clear opening etc. comp.. As directed by engineer in
75 Boring holes 3.5 m deep in ordinary soil (for cast in situ piles) 11.00 1,509.00 Nos
and getting out the soil and disposal of the surplus excavated
soil as directed within a lead of 50 Meter for following
diameter of pipes.(iii) 300 mm
76 Boring holes additional depth in ordinary soil (for cast in situ 72.00 431.14 Rmt
piles) and getting out the soil and disposal of the surplus
excavated soil as directed within a lead of 50 Meter for
following diameter of pipes.(iii) 300 mm
Sr. Items Qty. Rate in Rs. Unit Amount
77 Providing and placing with tremie reinforced cement concrete 10.00 4,577.33 Cum
M25 grade in bored hole using 6 mm to 20 mm machine
crushed well graded stone aggregate, natural or crushed sand
of approved quality, Portland slag cement mixing in batch
mix plant, transport, curing, casting of pile of any dia cut off
level & chipping of pile up to cut off level, disposal of
chipped material with all leads & lifts, etc. complete as per
execution drawing & specification & as directed by engineer
In charge. Including mobilization, demobilization,
remobilization, transportation of required plant and
machineries if required. as directed by engineer in charge.
1) Excluding reinforcement, test and M.S. Liners.
78 Providing and casting in situ ordinary Cement concrete M-200 120.00 4,560.15 Cum
for R.C.C. RCC Road Slab including centering, scaffolding
curing and finishing complete.
Toilet block work related Items
79 Providing and laying white glazed tiles 6 mm thick in flooring, 5.00 908.17 m2
treads of steps and landing laid on a bed of 12 mm thick
cement mortar 1:3 (1 cement : 3 coarse sand) finishing with
flush pointing in white cement
80 Providing and laying white glazed tiles 6 mm thick in skerting 18.00 1,044.23 m2
risers of steps and dedo on 10 mm thick cement plaster 1:3 (1
cement : 3 coarse sand) and jointed with white cement slurry
81 Providing and fixing water closet squatting pan (Indian type 1.00 1,510.98 No.
W.C. pan) size 580 mm x 450 mm white colour vitreous china
long pattern type conforming to IS : 2556 (Part III) together
with 100 mm size vitreous China 'S' trap as per IS : 2556 (Part
XIII) both of an approved make including jointing the trap
with the pan and soil pipe in C. M. 1:1 (1 cement : 1 sand)
with 32 dia. C. P. brass half turn flush cock complete
including earthwork, bed concrete of 1:4:8.
82 Providing and fixing flat back white colour vitreous china 1.00 1,976.88 No.
wash basin 550 mm x 400 mm size with CI brackets painted
white. Wash basin shall have 15 mm dia GI supply pipe,
overflow chase, 15 mm dia pillar cock and stop cock with
PVC bottle trap and PVC pipe piece upto wall plus 32 mm dia
PVC waste pipe upto floor level connected to 32 mm dia CI
pipe below floor and connected to nearby floor trap complete
with unions and plumber's white soldered joints with
necessary cleaning eye, complete. All chases cut in wall for
fixing pipes shall be made good in CM (1:4).
Sr. Items Qty. Rate in Rs. Unit Amount
83 Providing, laying and jointing in true line and level U.P.V.C.
Pipe (SCH-40) for including fittings make PRINCE /
SUPREME / ASTRAL / FINOLEX or equivalent as approved
by Engineer In Charge. Pipe shall be fixed on the wall with
the help of clamp at every two metre C/C or shall be concelled
as directed including necessary fittings etc. including testing
of pipe and joints and fixing the same with adhesive solvent,
including cost of all materials.
a) 15 mm dia. 100.00 71.93 Rmt
b) 25 mm dia. 25.00 90.93 Rmt
84 Providing & fixing gun metal check or non return full way
85 Providing and fixing brass screw down stop tap.
86 Providing and fixing screw down bib taps of following 2.00 157.29 No.
size.(C)Gun metal screw down bib tap. i) 15mm dia.
87 Providing and fixing 150 mm x 100 mm intercepting sewer 1.00 976.00 No.
trap embedded in concrete complete including excavation and
88 Constructing machinehole with R.C.C. top slab in 1:2:4 mix 1.00 12,887.06 No.
(1-cement: 2-coarses and :4- graded stone aggregate 20 mm
nominal size) foundation concrete 1:3:6 mix (1-cement : 3-
coarse sand : 6-Brick bats 40+50 mm size) inside plastering
15 mm thick with Cement Mortar 1:5 (1-Cement : 5-coarse
sand)finished with a floating coat of neat cement and making
channels in cement concrete 1:2:4 mix (1-Cement: 2-Coarses
and : 4-stone aggregate 20 mm nominal size) finished smooth
complete including curing and festing (i) Inside size 900mm x
1200 mm and 2.0 M. deep including C.I. cover with frame
size 560mm diameter total weight of cover and frame to be
not less than 128kgs. (Wt. of cover 64Kg. and Wt. of frame
64Kg.) (A) With 230 mm thick walls of brick msonry using
brick having crushing strength not less than 35Kg./Sq.cm. in
Cement Mortar 1:5 (1-Cement : 5-Coarse sand) (1) A type
depth 0.90 Metre for 150 mm diameter sewer.
Sr. Items Qty. Rate in Rs. Unit Amount
89 Constructing brick masonry chamber for under ground C.I. 1.00 3,624.51 No.
Inspection chamber and bends with bricks having crushing
strength not less than 35Kg.Cm 2in C.M. 1:5 C.I. cover with
frame (Light duty) 455mm x 610mm internal dimensions total
weight of cover with frame to be not less than 38Kg. (Wt. of
cover 23Kg.) and Wt. of frame 15Kg.) (R.C.C. top slab e with
1:2:4 mix (1-cement :2- coarse sand :4-graded stone aggregate
20mm size) foundation concrete 1:5:10 inside plaster 15mm
thick with cement mortar 1:3 finished smooth with a floating
coat of neat cement on walls and bed concrete etc. complete.
(ii) Inside dimensions 500mmx700mm and 450mm deep for
pipe line with one or two inlets.
90 Providing and fixing in position PVC vent pipes of 160 mm 1.00 1,235.00 No.
dia 3 m length.
91 Providing and fixing cast iron (Spun) Nahni trap of the 1.00 600.08 No.
following nominal diameter of self cleaning design with C.I.
screaed down or hinged grating including cost of cutting and
making good the walls and floor 100mm inlet and 50mm
outlet. (C) 100mm dia.
92 Providing and fixing S.W. gully trap with C.I. grating brick 2.00 1,234.57 No.
masonry chamber and water tight C. I. cover with frame of
300 mm x 300 mm size (inside) with standard weight. (i)
Square mouth traps.(B) 150mm x 100mm size P or R type
93 Providing and fixing100mm size P or Strap for water closet 1.00 311.85 No.
squatting pan including jointing the trap with the pan and soil
pipe in cement Mortar1:1 (1-Cement : 1-Fine sand) (A)
Vitreous China.
94 Providing and laying (to level or slopes) and jointing with stiff 25.00 288.23 Rmt
mixture of Cement Mortar in proportion 1:1 Selt glazed stone
ware pipes including testing of pipes and joints
complete.(B)150mm dia.
95 Providing erecting and fixing double coated syntex PVC (ISI) 5000.00 3.91 litre
water tank of required capacity each with all necessary fittings
and connection etc. complete on terrace.
Sr. Items Qty. Rate in Rs. Unit Amount
96 Demolition and disposal of stacking of serviceable materials and 60.00 1,047.38 Cmt
disposal of unserviceable materials with all lead and lift (i) R.C.C
Total of WDS in Rs.
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULES OF QUANTITIES AND RATES
CONSTRUCTION OF 5.0 LAKH LITER , 18 MT STAGING HEIGHT ESR (EPC BASIS) ON OPEN FOUNDATION FOR
NEW WATER DISTRIBUTION STATION AT KAMOD GAM LAMBHA WARD IN SOUTH ZONE OF AMС.
Sr. No. Item Description Qty. Rate without Unit Amount
Additional items for ESR
1 Manufacture, Supply & Delivery of Electric Resistance Welded ( Up to 400mm) Submerged Arc 19,300 70.67 Kg
Welded(Above 400mm) M.S.Pipe having beveled ends plates or coil conforming to IS-3589-2001 or
its latest revision/ammendment for following thickness outside diameter at GWSSB Store or site
anywhere in Gujarat State including all taxes, insurance, transportation, freight charges, octroi,
inspection charges,loading ,unloading conveyeance to Departmental store,stacking etc.all complete.
(Rate for MS Pipe based on the ex.works price of HR Coil as Rs.67,500.00 per MT-Without GST (
Above 3.15 mm to 10 mm) & Rs.68,000.00 per MT without GST( Above 10 mm) on Feb-22.( WPI
Index of H.R.coil of Jan-22 is 155.8)
2 Providing, supply and Delivery of Ductile Iron flanged 'ended fittings / specials conforming to relevant
IS, to 'store or site of work including freight, loading, 'unloading, stacking all taxes, insurance and
including 'jointing with jointing materials like 'gaskets, nuts and bolts etc. as required for ductfoot
bend, bell mouth etc for inlet,outlets, overflows, washout etc.
A Upto 300mm dia 200 155.00 Kg.
B Above 300mm dia 5,700 158.00 Kg.
3 Providing & fixing M.S.Flanges
(a) Ring flange - M.S.Special Flanged ends
Upto 300 mm dia. 250 98.00 Kg
300 mm dia and above 2,000 98.00 Kg
b) Blank flange - M.S.Special Flanged ends
Upto 300 mm dia 150 98.00 Kg
300 mm dia and above 250 98.00 Kg
4 Lowering Laying jointing & welding in position to correct line & level MS pipe with Inside Solvet
Free Liquid Epoxy lining on pedestral or chair upon prepared formation or prepared bedding in
trenches the rate including conveyonce from store to site of work , loading unloading, heat shrink
slvee jointing hydrotesting etc complete.
a) Inlet & Over Flow, Outlet Pipe 350 mm dia 100 444.00 Rmt
c) Wash out Pipe 200 mm dia 50 293.00 Rmt
5 Providing 406 Micron epoxy coating to inside pipe line Providing epoxy coating to inside pipe line 790 332.00 Smt
with two parts of Solvent free high build liquid epoxy lining as per AWWA C210-07 Suitable for
potable water application & shall be approved by CFTRI- lndia/BS 6920-UK/international
standard /NSF/ANSI/-61 2004 to be fit for contact with potable water for human consumption with
406 micron thickness. inclusive of necessary materials , labour ,Equipment ,Contractor's
overhead charges and profit and including all taxes
6 Providing and applying 3 LPE coating outsie 3 layers polyethelene (LPE) coating with required 395 808.00 Smt
thickness as per DIN_30670 or its latest revision or amendment and detail specification with necessary
material & Labour and Equipments etc.
7 Providing, supplying,delivery & Laying & Fixing of suitable water hammer control devices for use on 1 1,12,511.00 No
various pumping main of following class and dia. Incl. all taxes, insurance, transporation,
freightscharges, octroi, inspection charges,loading, unloading, conveyance to departmental stores
complete at the inlet pipe of ESR, for sudden shut down of
pump set. 350 mm dia- M.S. Body (Class-15)
8 Providing,supplying ,fixing ISI mark C.I. D/F SLUICE VALVE including taxes, insurance,
transportation, fright charges, Octroi Inspection, charges, loading , unloading, conveyance to site
stacking, etc. complete valve with ISI mark only
(I) Inlet & Over Flow Pipe 350 mm dia 2 30,125.00 No.
(II) Wash out Pipe 200 mm dia 1 9,813.00 No.
8A SITC of CI/DI Electric Actuator operated Double Flanged, Sluice Valve confirming to IS 14846, PN 1 1,35,833.00 No.
1.0 of following sizes with SS 304 seat rings with hot dipped galvanised hardwares, bolts, nuts &
washers etc. as per IS and Specification & complete the work in all respects. Size : 350 mm NB,Outlet
Sr. No. Item Description Qty. Rate without Unit Amount
9 Labour charges for installing and jointing Sluice Valves including loading, transporting from owner's
store, lowering in location to the required with excavation refilling alignment by crane / tripod and
chain block including cost of total nos.of nuts,bolts,Necessary gaskets and excluding fixingof tail
pieces with lead & jute etc complete as directed by Engg. in charge
(I) Inlet and Over Flow Pipe 350 mm dia 2 1,742.00 No.
(II) Wash out Pipe 200 mm dia 1 742.00 No.
10 Providing and supplying C. I./D.I. temper proof /Bi stream Air valves with SS 304 float gun metal
nozzle of approved make & quality with isolation sluice valve of following class and diameter
including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading,
unloading, conveyance to departmental stores, stacking etc. complete.
Double Acting Temper Proof Air Valves with Isolation Sluice Valve PN
11 Lowering, laying & jointing in position following Valves including cost of all labour, jointing
materials likenut, bolts, washers, rubber packing, etc. & giving satisfactory hydraulic testing, etc.
Double Acting Temper Proof Air Valves with Isolation Sluice Valve PN
12 Providing, supply and Delivery of Ductile Iron Socket and Spigot'ended fittings / specials conforming
to relevant IS, to 'store or site of work including freight, loading, 'unloading, stacking all taxes,
insurance and including 'jointing with jointing materials like 'gaskets, nuts and bolts etc. as required
for inlet,'outlets, overflows, washout etc.
(I) up to 300 mm dia. 1000 148.00 Kg
(II) Above 300 mm dia 1500 151.00 Kg
13 Labours charges for collecting specials from Municipals store loading , transportation, unloading to 2500 21.43 Kg
the site, laying and fixing CI specials inclusive of all jointing materials like lead, spun etc.and labour,
exacavation re-filling and nece. dewatering as per instrucation of engg. incharge.
14 Labours charges for collecting specials from Municipals store loading , transportation, unloading to 2500 12.50 Kg
the site, laying and fixing DI specials inclusive of all jointing materials like lead, spun etc.and labour,
exacavation re-filling and nece. dewatering as per instrucation of engg. incharge.
15 Construction of chambers in brick masonry, locally available in C.M. 1 : 6, foundation concrete
mm thick in C.C. 1:4:8 of trap metal size 25 mm to 40 mm thick, inside cement plaster in C.M. 1:3
and cement pointing outside in C. M. 1 :3 & top cover of precast RCC slab 100 mm thick upto 1 mt.
depth from G.L. but excl. cost of excavation and refilling. With cast in situ RCC slab in two piece
with fixing FRC frame and cover etc. complete(excluding cost of frame & cover ) with 23 mm thick
brick masonry wall in C.M.1:6
(1) For Sluice Valve & Air Valve
a) 0.9 x 0.9 mt. and 1.0 mt. deep chamber 4 7,738.00 No
b) for 1 m. extra depth 4 4,479.00 Rmt
16 Excavation for trenches with shoring & strutting if required as per required gradient and line
including all safety provision using site rails and stacking excavated stuff including up to all required
lead cleaning the site etc. complete for all lift and strata as specified. (For Chamber)
In all sort of soils and soft murrum
A) 0 to 1.5 mt. Depth 40 89.00 Cmt
B) 1.5 to 3.0 mt. Depth 25 98.00 Cmt
Sr. No. Item Description Qty. Rate without Unit Amount
17 Refilling the trenches including ramming, watering, consolidating disposal of surplus stuff as directed 50 22.00 Cmt
within a radius of 3 Km.
18 Providing & Fixing FRC Manhole frame & cover medium duty Chamber seat cover (FRC) cover 706 3 1,830.36 No
x556 x 50 mm rectangular cover frame size 600 x 450 mm clear opening outer size 816 x 666 x
mm (MD-10).Carting and Fixing Seat and Cover in line and level to match existing road level in C.C.
1:2:4 and finishing smooth, watering and protecting for 7 days etc. complete as directed. M.H. seat
cover will be supplied by A.M.C.(from any store)
19 Providing & Fixing FRC Manhole frame & cover (heavy duty) cover size 730 mm. & 90 mm thick 3 1,633.93 No
circular cover 20 M.T. design load and frame size 560 mm clear opening size 890 x 890 x
mm.Carting and Fixing Seat and
Cover in line and level to match exisisting road level in C.C.
1:2:4 and finishing smooth, watering and protecting for 7 days etc. complete as directed. M.H. seat
cover will be supplied byA.M.C.(from any store)
20 Gas cutting ( Either square cut or V cut) pipes, plates etc. complete for following thickness plate
a) Above 10 mm thickness plate 150 72.00 Rmt.
b) 5 to 10 mm thickness 150 56.00 Rmt.
21 Welding in all positions with required number runs, for M.S.Pipes internally and/or externally
including gauging wherever necessary, fixing appurtenances and other accessories in connection with
pipe laying work as per specification 4 mm to 7 mm
a) Above 7 mm thickness plate 150 729.00 Rmt
b) 4 to 7 mm thickness 150 681.00 Rmt
22 BUTTERFLY VALVE 1 1,11,144.00 Nos
Supply, installation, testing and commissioning of Electric Actuator operated CI DF Butterfly Valve
with extended spindle and head stock, conforming to IS 13095 / BS EN 593, PN 1.0 with SS
renewable seat ring , indicator, gear box with bolts, nuts & washers, gaskets, etc. as per specifications.
Size: 350 mm NB-Outlet pipe
23 EXPANSION BELLOWS 1 12,840.00 Nos
Supply, installation, testing and commissioning of Flange ends Expansion Bellow as per EJMA
standards of overall length of min. 300 mm , designed for 15 mm axial compression and 5 mm axial
extension with tie rods etc. of pressure ratings PN 1.0 and with MOC of bellows and Internal Sleeve
in SA 240 Gr. 304, Weld ends and flanges in IS 2062 Gr.B drilled as per IS 6392 and limit rods &
Nuts of CS-IS 1367, etc. and as per specs. and complete in all respect.
Size: 350 mm NB
24 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED 1 1,85,900.00 Nos
Supply, installation, testing and commissioning of Full Bore Electromagnetic flow meter comprising
of IP-68 Sensor , IP-65/66 remote type transmitter with 30 m cable between sensor and transmitter
along with all mounting accessories, Required Qty. of Power and Signal cable between Flow meter
and ICP Cubicle, Weather proof enclosure for transmitter, hardware, mounting stand, etc. as per
specification and to complete the work in all respect as per site condition necessary connection with
pipe and shall have following sizes.
Meter Size : 350 mm
Pipe Size : 350 mm
Sr. No. Item Description Qty. Rate without Unit Amount
25 Chamber for Valve
Construction of chamber in RCC M20 with Ordinary portlandcement with TMT Fe-500
Reinforcement,PCC150mm thick in M15, thick inside cement plaster in C.M.1:3 and depth of
chamber from G.L.to pipe invert including complete civil works and inclusive of the cost of
excavation,refilling and PVC foot steps including providng RCC slab in one single piece with fixing
of FRC (heavy duty) manhole frame and cover or RCC 25 precast slan in parts with key hole
b) PCC M-15 5 4,906.00 Cmt
RCC Wall 25 6,779.00 Cmt
RC.C. Top Slab 10 6,504.00 Cmt
RC.C. Raft & Footing 5 5,520.00 Cmt
d) TMT Fe-500 Reinforcement 4 77,504.00 MT
e) 15 mm thick Inside Cement
Plaster in CM 1 : 3 75 174.83 Smt
f) FRC Manhole (Medium duty) 5 1,633.93 Nos.
g) Refilling 85 22.00 Cmt
h) PVC steps 45 87.00 Nos.
26 Making connection of outlet of ESR of any dia MS/DI/HDPE Pipe with existing distribution network 1 90,000.00 Nos.
including cutting the pipe to required annular shape of any mm dia. by electro welding and jointing
any mm dia DI/MS/HDPE pipe, including dewatering, excavation, refilling etc. with all required
materials such as welding rods and other necessary required materials including giving a satisfactory
leakage proof test.
27 Demolition and disposal of stacking of serviceable materials and disposal of unserviceable materials 15 1,047.38 Cmt
with all lead and lift (i) R.C.C work
28 Supplying Electric breakar machine for RCC slab or Asphalt demolishing work on site by using 5 1,071.43 Shift
operator, fuel, power supply etc. complete as directed.(no payment should be allowed for non working
condition of machinary and for pipeline excavation and M.H. work.allowed only for break down
work)(based on previously approved rate by CE Sir)
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULES OF QUANTITIES AND RATES FOR
DISTRIBUTION NETWORK LABOUR WORKS
TRANSPORTING, LOWERING AND LAYING DI WATER DISTRIBUTION NETWORK FOR COMMAND
AREA OF NEW WATER DISTRIBUTION STATION FOR KAMOD GAM LAMBHA WARD IN SOUTH ZONE
Sr. Items Quantity Rate in Rs. Unit Amount
1 Excavation for foundation in all type of hard and soft soil including
sorting out stacking of useful material and disposing of excavated stuff
upto 50 mt. lead loose or soft soil) for valve chamber and MS pipeline
2 Excavation for trail pit of maximum diamension of 1.5 mt x0.75 x 1.5 25.00 223.21 No
mt depth for location of existing line including excavation but excluding
cost asphalt cutting but including refilling, watering etc. comp as per
instruction of Engg in charge.
3 Transporting from AMC store and laying spigot and socket New DI
pipe line DI-K-9 pipe of various classes with CI/DI/MS specials of
following diameters. Rate includes excavation up to minimum 1.0 mt.
depth from top of pipe/as per requirement in any soil, refilling after
laying pipe, covering and temptation of carting surplus earth up to
mt. lead and watering and compaction. Clearing the site. All Joint shall
be made tight & leak free etc.comp.
a) 100 mm dia rider line 300.00 64.29 Rmt.
4 Only removing recover of existing CI/DI pipe lines & specials
removing any type of joint, carting it to the Muni. Store as & where
directed as per instruction of Engg. In charefge with excavation &
a) 80 mm Dia 10.00 63.39 Rmt.
b) 100 mm Dia 10.00 64.29 Rmt.
c) 150 mm Dia 10.00 77.68 Rmt.
Sr. Items Quantity Rate in Rs. Unit Amount
5 Removing & relaying of existing CI/DI pipe line & Specials, Cleaning
of Pipe & Specials from inside , inclding excavation refilig etc. Comp.
in the line & level with any type of joint as per instruction of engg. In
a) 100 mm Dia 10.00 64.29 Rmt.
b) 150 mm Dia 10.00 77.68 Rmt.
6 Labour charges for installing and jointing Sluice valve/Scour Valve
including loading, transporting from AMC's store,lowering in location
to the required with excavation refilling alignment by crane/tripod and
chain block including cost of total nos. of nuts, bolts, Necessary gaskets
and excluding fixing of tail pieces with lead & jute etc complete as
directed by Engg. In charge.
7 Labour charges for removing and recover of ex. C.I. Sluice valve with
tail pieces and carting it up to muni. Store or site as per instruction of
Engg. In charge item include necessary Excavation, removing or
making joints, refilling etc. comp. as directed by Engg. in charge.
8 Providing and supplying CI/DI Tamper proof /Bi Stream Air valves
with SS 304 Float gun metal nozzle of approved make & quality of
following class and diameter including all taxes, transportation, freight
charges, octroi, inspection charges, loading, unloading, conveyance to
the departmental stores, stacking etc. complete. With Isolating Sluice
9 Lowering, laying & jointing in position following air Valves including
cost of all labour, jointing material, including nut bolts & giving
satisfactory hydraulic testing, etc. complete. With Isolating Sluice
Sr. Items Quantity Rate in Rs. Unit Amount
10 Labour charges for collecting specials from Municipals store loading, 8600.00 21.43 Kg
transportation, unloading to the sie, laying and fixing CI specials
inclusive of all jointing materials like lead, spun etc. and labour,
excavation re-filling and nece. Dewatering as per instruction of engg.
11 Labour charges for collecting specials from Municipals store loading, 26500.00 12.50 Kg
transportation, unloading to the sie, laying and fixing DI specials
inclusive of all jointing materials like lead, spun etc. and labour,
excavation re-filling and nece. Dewatering as per instruction of engg.
12 Manufacture, Supply,Delivery & Fixing of Ductile Iron Socket Spigot
Bends, tees, reducers or any other specials as per BS-EN-545/1995
Class-A series K12 suitable for use with D.I Pipes manufactured as per
IS:8329/1994 delivery of specials is to be made to GWSSB store or site
of works any where in Gujarat including fixing, all taxes, loading,
unloading, carting, stacking, insurance, inspection charges, octroi etc.
a) For 100 to 300 mm dia 6000.00 148.00 Kg
b) Above 300 mm dia 100.00 151.00 Kg
13 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to 20.00 4906.00 m3
prop. 1:2:4) (proportions as per mix design or as per Table 9 of IS456
2000 in masses by weigh batching ) using granite, quartzite trap metal
of size 6 mm to 20 mm for RCC work, including scaffolding centering,
form work, needle vibrated consolidation, curing comp. up to 6 meter
depth or height (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. comp. for structure for
other than water retaining.(With formwork)
14 Providing and casting in situ C.C. in grade M-20 (proportions as per 25.00 5520.00 m3
mix design or as per table9 of IS456 2000 in masses by weigh batching
) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC
work, including scaffolding centering, formwork, needle vibrated
consolidation, curing complete up to 6 meter depth or height (excluding
cost of reinforcement and neat finishing) with centering and
shuttering/deshuttering etc. complete for structure other than water
retaining (Below G.L) .(With formwork)
Sr. Items Quantity Rate in Rs. Unit Amount
15 Providing and casting in situ C.C. in grade M-25 (proportions as per 25.00 8077.00 m3
mix design or as per table9 of IS456 2000 in masses by weigh batching
) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC
work, including scaffolding centering, formwork, needle vibrated
consolidation, curing complete up to 6 meter depth or height (excluding
cost of reinforcement and neat finishing) with centering and
shuttering/deshuttering etc. complete for structure for water retaining
(Below G.L) .(With formwork)
16 Supplying cutting, bending, binding and placing in position steel as per 2.00 77504.00 MT
plan and design and as per ISS 2502 including cost of steel and binding
wire for reservoirs/structures only including lift up to 6 meter height or
depth below G.L. for all diameters Fe - 500 grade for all diameters.
17 Construction of chambers in brick masonary, locally available in C.M.
: 6, foundation concrete 150 mm thick in C.C. 1:4:8 of trap metal size
25 mm to 40 mm thick, inside cement plaster in C.M. 1:3 and cement
pointing outside in C. M. 1 :3 & top cover of precast RCC slab 150 mm
thick upto 1 mt. depth from G.L. but excl. cost of excavation and
refilling. With cast in situ RCC slab in two piece with fixing FRC
frame and cover etc. complete(excluding cost of frame & cover ) with
23 mm thick brick masonary wall in C.M.1:6 For Sluice Valve, Air
a) 0.9 x 0.9 x and 1.0 mt. deep chamber 55.00 7738.00 No.
b) For Extra depth 27.50 4479.00 Rmt.
c) 1.3 m x 0.9 m x 1 m deep chamber 3.00 9389.00 No.
d) For Extra depth 2.00 5282.00 Rmt.
e) 1.3 x 1.3 x and 1.0 mt. deep chamber 0.00 11351.00 No.
f) For Extra depth 2.00 6084.00 Rmt.
18 Providing and fixing PVC coated steps as per directed 290.00 87.00 No
Sr. Items Quantity Rate in Rs. Unit Amount
19 FRC Manhole Cover Providing F.R.C. MH seat cover incl. carting to 58.00 2125.00 No
the work site etc. comp. Directed. F.R.C. Extra Heavy Duty (EHD-35)
Manhole Covers & Frames Cover: 728mm ø & 100 mm thick circular
cover, 35.00MT load design,100 x 2mm MS flat all round,16mm ø
plain round bar for lifting the cover & should be fitted with plastic cups.
Frame:560mm ø clear opening, -888 x 888 x 175mm. On the upper
periphery off rame 25x3 mm wide MS flat should be well embed in
concrete to protect the edges off rame. FRC E.H.D.-35 manhole cover
& frame described as above.
20 FRC heavy duty cover size 730 mm. & 90 mm thick circular cover 20 15.00 1830.36 No
M.T. design load and frame size 560 mm clear opening size 890 x 890 x
21 Carting and Fixing M.H., Chamber or Catchpite Seat and Cover in line 20.00 750.00 No
and level to match exisisting road level in C.C. 1:2:4 and finishing
smooth, watering and protecting for 7 days etc. complete as directed.
M.H. seat cover will be supplied byA.M.C.(from any store) (Based on
Drainage SOR 2009-10)
22 Filling with available excavated earth (excluding rock) in trenches, 5000.00 129.10 m3
plinth, sides of foundation in layers not exceeding 20 cm in depth
consolidating each deposited layer by ramming and watering.
23 Conveyance charge of earth, lime, murrum, building rubbish, manual 500.00 415.76 m3
garbage, sludge, excavated rock, fly ash, aggregate of any kind etc.
Upto 5.0 Km lead.
24 Extra rate over item of excavation of earth for excavation of asphalt
pavement/RCC of following thickness including demolishing the asphalt
carpet, metal, soiling/cutting Reinforcement etc. comp. with stacking the
material as directed.
(a) up to 0.20 meter thickness (By Manual) 5000.00 71.43 m2
(b) up to 0.30 mt (by any type of Breaker Machine or R.C.C Cutter 500.00 178.57 m2
machine including cost of operator, fuel & transportation etc complete.
(c) 0.30 mt & above (by any type of Breaker Machine or R.C.C Cutter 250.00 312.50 m2
machine including cost of operater, fuel & transportation etc complete.)
Sr. Items Quantity Rate in Rs. Unit Amount
25 Reinstatement of asphalt road/pavement using same material for soling 5750.00 231.47 m2
and new metalling grouting with tack coat etc complete as directed.
26 Cutting of existing pipelines of following diameters including carting of
nece. specials from AMC store to site and from site to AMC store
(recovered materials) nace. labours for excavation, jodan & backfilling
fitter, supervisor, etc. complete. Rate also includes electric cutter,
dewatering pump fuel and transportation of machineries, chain pulley
block if requires working at an instructed specific time of day or night
a) 100 (CI/DI) mm dia. 1.00 1446.43 No
b) 150 (CI/DI) mm dia. 1.00 1464.29 No
c) 200 (CI/DI) mm dia. 1.00 2455.36 No
d) 250 (CI/DI) mm dia. 1.00 3169.64 No
e) 300 (CI/DI) mm dia. 1.00 5142.86 No
f) 350 (CI/DI) mm dia. 1.00 5544.64 No
g) 400 (CI/DI) mm dia. 1.00 6598.21 No
h) 450 (CI/DI) mm dia. 1.00 10187.50 No
i) 500 (CI/DI) mm dia. 1.00 11580.36 No
j) 600 (CI/DI) mm dia. 1.00 14285.71 No
27 Brick work using common burnt clay building bricks having crushing 50.00 4011.66 m3
strength not less than 35 kg / Sq. Cm. in foundation and plinth in cement
mortar 1:5 (1 cement : 5 coarse sand) etc. complete
28 Providing & applying . 15 mm. thick cement plaster in single coat on 250.00 222.56 m2
rough side of single or half brick wall for interior plastering upto floor
two level and finished even and smooth in Cement mortar 1:3 (1 cement
: 3 sand) etc. comp
29 Demolition of Brick work & stone masonry including stacking of 50.00 544.95 m3
serviceable materials and disposal of unserviceable materials with all
lead and lift. (i) In cement Mortar.
30 Demolition and disposal of unserviceable materials with all lead and 50.00 603.23 m3
lift.(i) Unreinforced cement concrete
31 Demolition and disposal of stacking of serviceable materials and 50.00 1047.38 m3
disposal of unserviceable materials with all lead and lift
32 Supplying Electric breakar machine for RCC slab or Asphalt 50.00 1071.43 Shift
demolishing work on site by using operator, fuel, power supply etc.
complete as directed.(no payment should be allowed for non working
condition of machinary and for pipeline excavation and M.H.
work.allowed only for break down work)(based on previously approved
rate by CE Sir)
Sr. Items Quantity Rate in Rs. Unit Amount
33 Providing and supplying JCB machine on rental basis in case of 100.00 535.71 hr
imergency situation and break down type work and also during on
unavodable condition as per instruction of engineer incharge, rates
include all necesary shifting, fuel and operating charges and staking o
usefull and non usefull material separatly up to store.(no payment
should be allow for non working condition of machinary and for pipe
line excavation and laying work)( SOR-(Jan-2016)
34 Supplying, fabricating and embedding M.S. anchor bolts, channels, 500.00 82.50 kg
angles chequered plates (6 mm thick), all other type of inserts, ladder,
precast trench cover etc. in concrete members during concreting as per
drawings and instructions in all positions and at any level including
keeping them in correct position and alignment, including adjustment of
reinforcement and shuttering, etc. complete and including two coats of
approved oil paint over one coat of zinc-rich primer over exposed
surfaces of above mentioned inserts after embedment, etc. all as
35 Manufacture, Supply & Delivery, Laying of Electric Resistance
Welded (Up to 400mm)/ Submerged Arc Welded(Above 400mm)
M.S.Pipe having beveled ends plate or coil conforming to IS-3589-2001
or its latest revision/ ammendment for following thickness outside
diameter at GWSSB store or site anywhere in Gujarat State including all
taxes, insurance, transportation, freight charges, octroi, inspection
charges, loading, unloading conveyance to Departmental stores,
stacking etc. all complete. (Rate forMS Pipe based on the ex. works
price of HR Coil as Rs.54500.00 per MT (Above 3.15 mm to 10 mm) &
Rs. 55000.00 per MT (Above 10 mm) as on March-21 .( WPI Index of
H. R Coil of February-21 is 132.6)
i) upto 914mm OD & upto 10mm Thickness of Plate/Pipe 2000.00 70.67 Kg
ii) Above 914mm OD & Above 10mm Thickness of Plate/Pipe 500.00 71.17 Kg
36 Providing 406 Micron epoxy coating to inside pipe line Providing 100.00 332.00 m2
epoxy coating to inside pipe line with two parts of Solvent free high
build liquid epoxy lining as per AWWA C210-07 Suitable for potable
water application & shall be approved by CFTRI- lndia/BS 6920-
UK/international standard /NSF/ANSI/-61 2004 to be fit for contact
with potable water for human consumption with 406 micron
thickness. inclusive of necessary materials , labour ,Equipment
,Contractor's overhead charges and profit and including all taxes
37 Gas cutting ( Either square cut or V cut) pipes, plates etc. complete for
following thickness plate
(a) Above 10 mm thickness plate 100.00 72.00 Rmt.
(b) 5 to 10 mm thickness 100.00 56.00 Rmt.
38 Welding in all positions with required number of runs, for M.S. pipes
internally and / or externally including gauzing wherever necessary,
fixing appurtenances and other accessories in connection with pipe
laying work as per specification. Butt joints with convex fillet welds
(a) Above 7 mm thickness plate 100.00 729.00 Rmt.
(b) 4 to 7 mm thickness 100.00 681.00 Rmt.
Sr. Items Quantity Rate in Rs. Unit Amount
39 Providing and fixing M.S.Flanges to M.S. Pipe as per IS specification
and as directed by Engineer in charge.
(a) Ring flange - M.S.Special Flanged ends
(i) Upto 300mm dia. 250.00 98.00 kg
(ii) 300 mm dia and above 150.00 98.00 kg
(b) Blank flange - M.S.Special Flanged ends
(i) Upto 300mm dia. 250.00 98.00 kg
(ii) 300 mm dia and above 100.00 98.00 kg
40 Dewatering by pumping set of required capacity including temporary 500.00 18.32 HP/hr
platform carting pumping at site and fixing the same in position
including all accessories, and fuel and labour etc. complete.
41 Making holes on existing C.I./ D.I./MS water pipe line including
necessary GI fittings item also includes necessary excavation,
dewatering and refilling as per instruction engg. In charge etc. comp.
42 Supply , installation , testing & commissioning of Bourdan pressure 1.00 1412.00 No
gauge having 150 mm dia with necessary syphon & S.S. cock and shall
be provided at each pump outlet & pump header as per specification
and data sheet. Range 0-5kg/sq.cm
43 Providing and fixing to wall, ceiling and floor galvanised Mild steel
tubes (Medium grade) of the following nominal bore, tube fitting and
clamps including making good the wall ceiling and floor.((At any floor
(a) 15 mm dia GI Pipe 5.00 244.13 Rmt.
(b) 20 mm dia GI Pipe 5.00 297.25 Rmt.
(c) 25 mm dia GI Pipe 5.00 393.93 Rmt.
(d) 40 mm dia GI Pipe 5.00 596.73 Rmt.
(e) 50 mm dia GI Pipe 5.00 779.60 Rmt.
44 Providing and laying in trenches galvanised mild steel tubes (Medium
grade)of the following nominal bore, tube fittings (Earthwork in
trenches to be measured and separately)
(a) 15 mm dia GI Pipe 5.00 150.91 Rmt.
(b) 20 mm dia GI Pipe 5.00 190.97 Rmt.
(c) 25 mm dia GI Pipe 5.00 279.39 Rmt.
(d) 40 mm dia GI Pipe 5.00 421.12 Rmt.
45 Providing laying and jointing in true line and level following Dia
U.P.V.C. Pipe (SCH-40) for cold water including fittings as approved
by Engineer In Charge. Pipe shall be fixed on the wall with the help of
clamp at every two metre C/C or shall be concealed as directed
including necessary fittings etc. including testing of pipe and joints and
fixing the same with adhesive solvent, including cost of all materials.
a) 15 mm Dia uPVC Pipe 25.00 71.93 Rmt.
b) 25 mm Dia uPVC Pipe 25.00 90.93 Rmt.
c) 40 mm Dia uPVC Pipe 50.00 146.65 Rmt.
d) 50 mm Dia uPVC Pipe 50.00 193.73 Rmt.
Sr. Items Quantity Rate in Rs. Unit Amount
46 Manufacturing, testing, supplying, loading, transporting to worksite,
unloading, Loweing in trenches, laying and jointing RCC pipes
following class with Socket and spigot joints as per IS 458 -2003
including EPDM Rubber ring as per IS 5382-1985 etc. comp. As
Directed by Engineering in charge.
(iii) 600 mm dia. 10.00 1268.75 Rmt.
47 Providing And Jointing Stoneware Pipes Incl. Excavation Up to 2 Mt.
Refilling, Transporting Pipes To Work Site, Unloading, Lowering In
Trench, jointing material Such As Cement, sand, Hemp Bitumen As
Directed, Incl. Watering The Trenches Spreading And Carting away Of
Surplus material as directed by engineer in charge.
(ii) 150 mm dia 10.00 163.39 Rmt.
(iii) 230 mm dia 10.00 344.64 Rmt.
48 Repairing of damaged MH including removing damaged brick &
repairing by masonry in C.M. 1:5 & plaster in C.M.1:3 & fixing C.I.
Steps & excluding seat & Cover in C.C.1:2:4 rate also includes
removing debris from MH & carting the same as directed.
a) Up to 0.15 M ( @ two coarse) 5.00 732.14 No
b) Up to 0.35 M ( @ two coarse) 5.00 1160.71 No
c) Up to 0.65 M ( @ two coarse) 5.00 1794.64 No
49 Providing, laying, spreading and compacting graded stone aggregate to
wet mix macadam specification including premixing the Material with
water at OMC in mechanical mix plant carriage of mixed Material by
tipper to site, laying in uniform layers in subbase / base course on well
prepared surface and compacting with vibratory roller to achieve the
desired density as per MoRTH clause
(a) Production & Supply of WMM 500.00 1495.54 m3
(b) Laying of WMM 500.00 31.25 m3
50 Construction of granular Sub base by providing coarse graded material
spreading in uniform layers with motor grader on prepared surface
mixing by mix in place method with front end loader at OMC and
compacting with vibratory roller to achieve the desired density,
complete as per Clause 401. For all grade
(a) Production & Supply of GSB (Natural) 250.00 628.57 m3
(b) Laying of GSB 250.00 30.36 m3
Sr. Items Quantity Rate in Rs. Unit Amount
51 Providing and Laying of Rubber Moulded Paver Block Grey/Coloured 500.00 383.04 m2
60 mm thick, M-35 Grade of any size shape (Usually Uni-Paver
Blocks) using black trap good quality aggragate of 20 mm nominal size
for footpath, parking areas, service lanes and other areas as mentioned
in the rawing / instruction of engineer in charge. Cost includes
formworks using rubber mould, Rate providing and laying paver blocks
as per required grading and specification. The paver block shall be
mechanically compacted. The work of paving blocks shall be executed
in line and level by skill mason of flooring work only. It should be laid
in such a way that the no cutting of the paver block to be necessary. if
cutting of paver block necessary then it should be cut byvmachine only
and carting. The finished surface of the paver block shall have
resonably good, plain finished. Paver blocks shall be compacted and
shall be relaid if necessary. Gravel or such type of materials shall not be
allowed for production. Laying on 5 cms thick sand bedding.)
52 Labour work for fixing above interlocking blocks on up to 50mm th 500.00 69.64 m2
sand bedding,levelling,watering anf fixing. Rate incl. average 30cm
depth for excavation and or filling,carting away debries/excavated
material up to 5 km and cleaning the site etc.comp. as directed.
53 Labour charges for doing washout of water pipe line at end including 10.00 669.64 No
necessary excavation refilling the pit. Allowing the water to flow for
minutes twice or thrice as per site condition during supply hour,
dewatering the pit and plugging with existing wooden butch. etc. comp.
as per Engineer In Charge
54 Supplying wooden taper plug from jungly wood (like limda, ambo ) etc.
(a) 15 mm dia to 20mm dia 2.00 13.39 No
(b) 25 mm dia to 37mm dia 2.00 17.86 No
( d) 80 mm dia to 100 mm dia line 2.00 312.50 No
55 Barricading the entire break down or excavated area on rental basis 250.00 80.36 Rmt.
using wooden ballies / M.S.angles at max. 2.00 meter centre to centre,
C.G.I. Sheet, reflective paint / Board out side to avoid accident & for
smooth traffic diversion & movement including cautionary board etc.
Item also includes for making temporary sufficient nos of lighting
arrangement through out the work with necessary required arrangement.
..The same shall be removed after completion of work. (Only for break
down work from start to complete)
56 Labour Charges for repairing the joint leakage in the existing C.I./DI
Pipe line with specials incl. required materials such as jute and lead etc
nece. excavation in any type of soil, refilling, nacessary trust block
etc.comp. as per instruction of engg.in charge.(Joint reparied under this
item should not be paid in next four months under normal condition)
(A) 80 MM dia. to 100 MM dia 5.00 379.46 joint
(B) 150 MM dia. to 250 MM dia. 5.00 446.43 joint
Sr. Items Quantity Rate in Rs. Unit Amount
57 Drilling of Horizontal bore hole for water main pipeline under the
Railway tracks /Road / Canal etc in all strata with required length
including fixing of following dia MS casing pipe Rate including the
cost of Drilling of bore hole, Providing & Fixing Casing pipe incl.
Welding and pushing etc. complete but excluding the cost of Carrier
pipe, valve and other items, Entire work should be as per Approved
Drawing and as per Instruction of Railway / Road/Irrigation or other
authority for following diameter of bore hole.
a) Horizontal Drilling 1300 & Providing, fixing and welding and pushing 10.00 41189.38 Rmt
MS Casing Pipe of 1200 mm Dia Thickness 16mm
b) Horizontal Drilling 900 & Providing, fixing and welding and pushing 10.00 22358.84 Rmt
MS Casing Pipe of 800 mm Dia Thickness 12mm
c) Horizontal Drilling 600 & Providing, fixing and welding and pushing 10.00 11604.16 Rmt
MS Casing Pipe of 500 mm Dia Thickness 8mm
58 Drilling of Horizontal bore hole for water main pipeline under the
Railway tracks /Road / Canal etc in all strata with required length
including fixing of following dia RCC casing pipe Rate including the
cost of Drilling of bore hole, Providing & Fixing Casing pipe incl.
pushing etc. complete but excluding the cost of Carrier pipe, valve and
other items, Entire work should be as per Approved Drawing and as per
Instruction of Railway / Road/Irrigation or other authority for following
diameter of bore hole.
a) Horizontal Drilling 900 without water main & with MS casing pipe 10.00 25240.76 Rmt
b) Horizontal Drilling 600 without water main & with MS casing pipe 10.00 11679.80 Rmt
c) Horizontal Drilling 500 without water main & with MS casing pipe 10.00 9063.20 Rmt
d) Horizontal Drilling 300 without water main & with MS casing pipe 10.00 4363.53 Rmt
59 Filling in plinth with sand under floors incuding watering, ramming, 250.00 455.63 m3
consolidation and dressing complete.
60 Construction of chambers in RCC M30 with Ordinary Portland cement
with TMT Fe-500 reinforcement, PCC150 mm thick in M 15 ,15 mm
thick inside cement plaster in C.M.1:3 and depth of chamber from G.L.
to pipe invert level including complete civil works and inclusive of the
cost of excavation, refilling and PVC foot steps including providing
RCC Slab in one single piece with fixing of FRC (heavy duty) manhole
frame and cover or RCC 30 Precast slab in parts with key hole etc.
RCC M 30 in OPC Cement
RC.C. Top Slab 10.00 5194.89 m3
RC.C. Base Slab 10.00 4899.06 m3
TMT Fe-500 Reinforcement 2.00 75460.00 MT
Sr. Items Quantity Rate in Rs. Unit Amount
15 mm thick Inside Cement
Plaster in CM 1 : 3 80.00 174.83 m2
FRC Manhole Frame & Cover 4.00 2294.00 No.
Refilling 100.00 22.00 m3
PVC steps 36.00 87.00 No.
61 Dismentaling of the existing structure including removing and stacking 50.00 877.28 m3
the dismentelled materials as and where directed (a) R.C.C Work
62 Construction of 200 mm thick un-reinforced plain cement concrete 250.00 1,811.00 m2
pavement with M - 30 grade of concrete including provision of
contraction, construction and longitudinal joints, joint filler, , sealant
primer, joint sealant, finishing to lines and grades as per drawing as per
MoRTH clause 602 over a 200 mm thick WMM with necessary
excavation/loosening and recompacting ground as per respective
MoRTH specification and as directed by engineerin charge
Total Amount of Distribution Network Labour Work Rs.
Total Amount of Distribution Network Labour Work Rs.
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULE OF QUANTITIES & RATES FOR AUGMENTATION WORK OF MECHANICAL WORKS FOR WDS IN TP-154, FP-58
(KAMOD GAM) AT LAMBHA WARD OF AMC.
DESCRIPTION QTY UNIT AMOUNT
1.1.1 SUBMERSIBLE CENTRIFUGAL PUMP-MOTOR SET (VERTICAL MOUNTING) 2 Set 11,48,280
SITC of Submersible Centrifugal Pump of following duty parameters alongwith LV AC
dry air filled TEWC induction energy efficient motor integrally mounted on volute type
casing and class F insulation & IP 68 protection. Pump-motor set shall be of specified
materials of construction and must have all required accessories viz. automatic coupling
device, double guide pipes with supports, chain with shackles (shall be with dual hook /
shackles at approx. every 1.5m C-C distance) & of length as per sump height + min. 3m,
suction strainer, RCC foundation blocks (as recommended by pump vendor) for duck foot
bend, submersible power & control cables (copper flexible & stranded type conductor of
reqd. cores & size for each pump motor set) & length of sump height + min. 10 m long
each run with necessary electrical termination connection at junction box / starter panel,
pump monitoring unit etc. as per equipment technical specifications and also including in
scope any other parts / accessories / fittings requried to complete the work in all respects &
satisfactory operation of pump set.
Pump Capacity: 625 m3/hr. (1W+1S),
Nominal Speed: Max. 1500 RPM,
Minimum Acceptable Overall Pump-Motor Efficiency at Duty Point: 70.5 % &
Motor Rating: Minimum 90 kW (or higher as recommended by pump manufacturer).
2.1.1 SITC of CI/DI manually operated Double Flanged, Sluice Valve confirming to IS 14846, 1 No. 3,052
PN 1.0 of following sizes with SS 304 seat rings with hardwares, bolts, nuts & washers etc.
as per IS and Specification & complete the work in all respects.
Size : 80 mm NB (for header drain)
2.2.1 SITC of CI/DI Electric Actuator operated Double Flanged, Sluice Valve confirming to 3 Nos. 1,35,833
IS 14846, PN 1.0 of following sizes with SS 304 seat rings with hot dipped galvanised
hardwares, bolts, nuts & washers etc. as per IS and Specification & complete the work in
Size : 350 mm NB (at delivery of each Sub. CF Pump set & header of Sub. CF Pump sets)
2.3.1 SITC of CI/DI double flanged Dual Plate Check Valve conforming to API 594, Class 125 2 Nos. 62,921
with Cast Steel dual door, hinge pin & stop pin of SS 410, springs of AISI 304 and seat of
SS 304, along with all required accessories, gaskets and hardwares, etc. and as per
specification & complete the work in all respects.
Size : 350 mm NB (at delivery of each Sub. CF Pump set)
2.4.1 SITC of CI/DI Temper proof Flanged Air Valve with Isolation Sluice Valve as per 1 No. 14,200
AWWA / IS 14845 PN-1.0 & IS-14846 PN-1.0 respectively with SS304 float, gun metal
nozzle, complete hardware's, bolts, nuts & washers, gaskets etc. complete as per IS and
Size : 80 mm NB
3.1.1 SITC of Flange ends Expansion Bellow (PN 1.0) as per EJMA standards and as per specs. 3 Nos. 12,840
and complete in all respect.
Size : 350 mm NB X 300 mm L (at delivery of each Sub. CF Pump set & header of Sub.
4.1.1 CI D/F PIPES 3900 KG 58
Supply, installation, connection, testing and commissioning of double flanged, CI pipes
conforming to IS 1536 / 1537, Class B with connection as per tender drawing & any other
pipe / fittings requried to complete in all respect.
Size: 350 mm to 650 mm dia. (Del. & header Line up)
4.2.1 CI D/F FITTINGS & SPECIALS 1800 KG 58
Supply, installation, connection, testing and commissioning of CI Flanged, Fittings and
Specials like 90 deg. Bend, Blind Flanges, Reducer / Enlarger, Duck foot bend, TEE, etc.
conforming to IS 1538 with connection as per tender drawing & any other pipe / fittings
requried to complete in all respect.
Size: 350 mm to 650 mm dia. (Del. & header Line)
SCHEDULE OF QUANTITIES & RATES FOR AUGMENTATION WORK OF MECHANICAL WORKS FOR WDS IN TP-154, FP-58
(KAMOD GAM) AT LAMBHA WARD OF AMC.
DESCRIPTION QTY UNIT AMOUNT
4.4.1 G.I. PIPES & FITTINGS: 50 RMT 716
Supply, installation, connection with equipments as required, testing and commissioning of
GI pipe conforming to IS-1239, Heavy Duty with coupling, tee, bend, union, elbow,
flanges, etc. as all required fittings for connection complete with gaskets, hardware, and
required accessories as per IS & Specifications
Size: 80 mm NB (For AV)
5.1.1 Flanged Joints of Pipes, Fittings and Specials: 1 No. 434
Supply, Installation, Making of Flanged DI /CI / GI / MS Pipes, Fittings and Specials
Joints with all jointing materials, rubber packing, nut bolts, labour etc.for complete
Size: 80 mm dia.
5.1.2 --- Item description as above --- 16 Nos. 1,442
Size: 350 mm dia.
6.1.1 SITC of Electrically Operated Chain Hoist & Electrically operated Trolley , suitable to 1 Set 3,74,024
operate on Mono Rail Girder having motorised motion in vertical lifting & cross travel,
manufactured as per IS:6547-1972-Class-II & IS-3177- Class-II, complete with
electrically operated chain hoist & Electically operated geared trolley, brake, chain-gear,
motors, safety device, pendant push button, starter panel, cables from motor to starter panel
and all other required accessories like limit switches, panel, power supply system (Fastoon
cable type), fasteners, epoxy painting, etc. tested for over load as per IS complete as per
specifications and complete in all respect.
Capacity : 3 Ton. Min. (for Submersible Centrifugal Pump-Motor set lowring-lifting)
'Lift : 10.0 m as mini. or as per site req.
Bay Length : 8.50 m min. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
Note: (1) Minimum as specified capacity or higher as per requirement such that ECH
capacity is min.1.25 times of the pump/motor OR single heaviest component to be lifted
within pump house.
7.1.1 Providing, Supply of Structure Steel at site of work with freight, loading, unloading 2000 KG 64.838
carting, etc. including all taxes and duties complete such as joints, channels, angles, MS
Grill, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates (min. 8 mm
Thickness) for cable trench etc. required for support structure of all Electro-mechanical
equipment, piping, etc. for support on floor / wall / beam / brackets etc. as per site
requirement / condition and complete in all respect.
7.1.2 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS 2000 KG 11.365
such as joints, channels, angles, Iron Rails, MS Grill, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates, for cable trench etc Complete with two coats of red oxide and two coats
of approved colour shade of epoxy paint as per relevant IS and as per specification.
SCHEDULE OF QUANTITIES & RATES FOR AUGMENTATION WORK OF MECHANICAL WORKS FOR WDS IN TP-154, FP-58
(KAMOD GAM) AT LAMBHA WARD OF AMC.
DESCRIPTION QTY UNIT AMOUNT
8.1.1 CHLORINATION SYSTEM 2 Plant 2,10,642
SITC of Wall mounted, FRP cabinet type, Vacuum operated Chlorination plants complete
in all respects with required piping, fitting, valves, safety and testing kit, etc. Complete
system combining the Two plants complete in all respect as per IS and as per specification.
(Without Chlorine Cylinder).
Capacity: 5 kg/hr. (Cabinet Type) for each plant.
Each plant shall include the followings:
(1) 1 No. Submersible monoblock Pump motor set with continuous Cable from pump to
starter panel without any Joint with proper conduit piping and clamping.
(2) 1 No. Diffusers (3) 1 No. Ejector (4) 1 No.Chlorinator, (5) 1 No. Vacuum Regulators
(6) 1 No. Strainer (7) 1 No. NRV on solution line (8) 1 No. Non Return Valve on Booster
Pump del. line (9) 1 No.Yoke clamp (1 No. for each cylinder) (10) 1 No. Pressure Gauge
with require piping and isolation valve for booster pump (11) 1 No. Chlorine Gauge at Cl2
manifold with isolation valve (12) 1 Lot of piping, fittings, valves & instruments (13) Total
5 nos. or higher as required Isolation valve on gas manifold (14) Vacuum Gauge (15) MS
support of 50 mm x 50 mm x 4 mm thk.
(1) Filled 100 kg. Chlorine Cylinder in the scope of Client.
(2) 1 no. Gas filter shall be provided per manifold.
(3) 1- lot inter connecting piping of identical pipe size of Cl2 booster pumps delivery line
with required no. isolation valves.
(4) 1 no common 3/4" gas manifold of Carbon steel suitable for two cylinder.
(5) Any other as required to complete the work in all respects.
8.2.1 Supply of safety kit & testing as specified in the specifications. 1 Set 83,241
(1) 1 Set Chloroscope,
(2) 1 set. Air breathing apparatus for 45 min as per IS,
(3) 1 set. Emergency tool kit,
(4) 1 No. Amonia Torch, etc.
8.3.1 AUTO SHUT OFF CHLORINE CYLINDER VALVE SYSTEM 1 Lot 4,83,000
SITC of Automatic Chlorine cylinder shut off valve for single chlorine cylinder (100 kg)
for chlorination system comprising of :
(1) 1 No. Pneumatic Auto shut off chlorine cylinder route valve with actuator system
with Air line filter, Solenoid Valve, Air motor, Yoke clamp, etc. of required capacity, size,
(2) 1 Lot, Control panel cum PLC with interconnecting cables/wiring for Auto Shutt Off
chlorine Valve of Cylinder,
(3) 1 No, Air Compressor,
(4) 1 Lot, uPVC-SCH 40, Air piping for Auto Shut off valve as required,
(5) 1 Lot, Interconnecting instrument & Power cable,
(6) 1 No. Chlorine leak detector,
(7) 1 No. Industrial Hooter etc. & any other as required to complete the work in all
SCHEDULE OF QUANTITIES & RATES FOR AUGMENTATION WORK OF MECHANICAL WORKS FOR WDS IN TP-154, FP-58
(KAMOD GAM) AT LAMBHA WARD OF AMC.
DESCRIPTION QTY UNIT AMOUNT
8.4.1 TRAY FOR CHLORINE SOLUTION uPVC PIPES 25 RMT 360.57
Providing & Fixing approved make Perforated C type tray made from CR sheet along with
required accessories to sustain the weight of uPVC pipe with bends, tees and clamps for
fixing of uPVC pipe and all the fittings as required as per site condition. The Perorated
type tray shall be single or double needed as per required and as per IS 2062/1079 and shall
be coated with hot deep galvanised as per IS 2629/4759 with coupler plate/Fish plate and
complete hardware's, Hot dip galvanised (HDG) bolts, nuts & washers, gaskets etc. erected
providing support as per specification and as per instruction of E-I-C.
Size: 100 x 50 x 1.6 mm thk.
A TOTAL OF MECHANICAL WORK WITHOUT GST
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULE OF QUANTITIES & RATES FOR SITC OF ELECTRICAL, MECHANICAL & INSTRUMENTATION WORKS
WITH 5 YEARS FOR WDS IN TP-154, FP-58 (KAMOD GAM) AT LAMBHA WARD OF AMC.
Item Description Qty. Unit Amount, Rs.
1.1 ELECTRICAL WORK 1 Set 39,391.46
TPN MCCB (For LT Service Obtaining Requirement)
SITC of 250A TPN microprocessor MCCB, LSIG (50kA) with inbuilt O/L, S/C & E/F
protection with Extended rotary handle, Terminal spreader, Auxiliary change over &
Trip contact, with Outdoor Enclosure with canopy 2mm thick , Single/double door &
Wall mounted/ stand mounted as per site requirement (with incoming & outgoing cable
entry at bottom )with Cable end boxes with RYB indicating lamp, Digital voltmeter,
VSS,ON,OFF & Trip indicating lamp etc as per Power supply company requirements &
location. Including all civil works for fixing of panel on wall.
(Wall mounted at Location as per PSC req.)
2.1 MEDIUM VOLTAGE PANEL BOARD (PMCC /APFC) 1 Set 9,39,194.00
SITC of PMCC Panel (50kA), compartmentalized, Stand mounted, operating height
maximum 1800/1900 mm, Extensible on both ends, suitable for Manual & Auto
operation -Local & through PLC/SCADA operation as per site conditions complete in all
respects as per Tender SLD / Specification / IS and including following as minimum:
(1) One no. Incoming feeder FP 250A Microprocessor MCCB (50kA), LSIG, with
inbuilt O/C, S/C, & E/F protection for I/c with Digital Voltmeter, Voltmeter selector
switch, Digital Ammeter, Ammeter selector switch, Power Factor Meter, MFM with RS-
485 of Class-0.5, Indicating lamps R,Y,B,On,off,Trip, 3nos. 250A/5A, Cl.-0.5 metering
CT, CL 0.5 CT for APFC relay etc. Constant voltage/control voltage transformer
1500VA, 415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB complete
in all respects.
(2) 250A TPN Main Aluminium busbars. (Main busbars size with current density
(3) APFC separate cubical compartment (minimum 75 KVAr) having 1 no. 200A
TPN Thermal magnetic MCCB 50KA with adjustable overload and adjustable short
circuit, 12 step APFC relay with RS 485, 1 no. 200 A/5A, Cl.-1.0 CT for Ammeter,
Digital Ammeter, ASS, 2 nos. 20 kVAR capacitor with 63A TPN MCCB with capacitor
Duty Contractor, 2 nos. 10 kVAR capacitor with 32A TPN MCCB with capacitor Duty
Contractor, 2 nos. 5 kVAR capacitor with 16A TPN D curve MCB with capacitor Duty
Contractor, 2 nos. 2 kVAR capacitor with 16A TPN D curve MCB with capacitor Duty
Contractor, 1 no. 1 kVAR capacitor with 16A TPN D curve MCB with capacitor Duty
Contractor, A/M switch, On delay timer, Push Buttons etc. Complete in all respects as
per Specification, IS & SLD.
(4) SOFT STARTER FOR 90 KW MOTOR (Subm. Pump) : 2 NOS : (1W+1S) : rate incl in
Each feeder comprising of Soft Starter with Internal/External bypass contactor for 90kW above price
Motor or higher as per pump manufacturer reco. with soft starter rating minimum (181A
@ 50deg C) with suitable derating with detachable type door mounted display key pad
and with 250A TPN MP MCCB (LSIG), 250A, AC3 duty Line contactor, Semi
conductor fuse, MFM with RS-485, Resin Cast CT Cl: 0.5, SPP, Cooling fan, PMU as
per pump vendor Reco., A/M, L/R switch, ON, OFF, TRIP Indication &(Start & E-Stop)
pushbutton etc. & LCS (PBS) for Actuator-valve with 16A FP MCB, open,close,stop
PB, open,close,trip & L/R indication & 2 nos. terminal strip, SP MCB etc.
Note : For Actuator LCS (PBS) shall be provide potential free contact for
(open,close,trip & L/R ) indication and terminal for Open,close and stop command
because actautor shall be operator from PLC Panel also in addition to LCS (PBS).
(5) 63A TPN TM MCCB FEEDER : 2 Nos. (1 no. for Chlorination panel, 1no. for
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating
(6) 32A TPN TM MCCB FEEDER : 2 Nos. (1 no. for EOT with ECH at Pump
House, 1 no. spare)
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating
Item Description Qty. Unit Amount, Rs.
(7) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 1 set: rate incl in
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc. above price
a) 4 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Indoor LDB, 1 no. for ICP/PLC
Panel, 2 nos. Spare)
b) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders
(for Outdoor LDB)
d) 3nos. LCS (PBS) with 16A FP MCB, indicating lamp,Push Button, A/M,L/R switch,
SP MCB, etc. (1no. MOV at Header, 1no. MOV ESR outlet, 1no. at ESR bypass)
Note : For Actuator LCS (PBS) shall be provide potential free contact for
(open,close,trip & L/R ) indication and terminal for Open,close and stop command
because actautor shall be operator from PLC Panel also in addition to LCS (PBS).
(8) Multiplication relay as required for dry run protection of pumps.
NOTES: (1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L
and Adj.S/c (LSIG for MP MCCB),Extended rotary handle, Terminal spreader,
Auxiliary Change over contact and trip contact as required.(2) All MFM, ACB, Soft
Starter,Temp.Scanner etc shall be with inbuilt RS 485.(3)For Actuator LCS (PBS) shall
be provide potential free contact for (open,close,trip & L/R ) indication and terminal for
Open,close and stop command because actautor shall be operator from PLC Panel also
in addition to LCS (PBS).
2.3 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,568.94
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting &
Outdoor Lighting Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
3.1 LOW VOLTAGE (LT) CABLES 30 Mtr. 1,161.50
Supply, laying, testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE
insulated (IS 7098) AL / Cu stranded conductor, Extruded innersheath cables as per
specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick
& sand protection/in DWC pipes as per specified method and shall be laid in prepared
trench/ on cable tray when laid inside the building.
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
3.2 SITC of 4C x 10 sq. mm. A2XFY(X) Cable (1 no.for Chlorination panel) 50 Mtr. 138.37
3.3 SITC of 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. for Outdoor 85 Mtr. 124.23
LDB, 1 no. for EOT with ECH at Pump House)
3.4 SITC of 4C x 2.5 sq. mm. 2XWY(X) Cable (2 nos. MOV at pump Delivery, 1 no. 350 Mtr. 269.67
MOV at Header, 1no. MOV at ESR outlet, 1no. MOV at ESR bypass, 1 no. ICP/PLC
Panel & for 4 nos. street light)
3.5 SITC of 12C x 2.5 sq.mm. 2XWY(X) Cable (2 nos. MOV at pump Delivery, 1 no. MOV 255 Mtr 419.15
at Header, 1no. MOV at ESR outlet, 1no. MOV at ESR bypass)
3.6 SITC of Single core 95sq. mm. PVC insulated circular unsheathed copper conductor 20 Mtr 875.67
flexible Cable (For Power supply Metering Panel to I/c MCCB Unit)
4.1 CABLE END TERMINATION AND CONNECTION: 2 Nos. 838.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic
lugs / sockets with necessary tools and equipments as specified in specifications and IS.
The glands and lugs / sockets shall be suitable for cable size and type mentioned below
& as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also
connecting to common earth bar.
2) The job also includes, if necessary, supply & fixing of extension busbar of same
material on MCCB or panel board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size unit. The job also includes
earthing the glands and armour of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site requirement)
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
Item Description Qty. Unit Amount, Rs.
4.2 Same as above but, 4C x 10 sq. mm. A2XFY(X) Cable (1 no.for Chlorination panel) 2 Nos. 128.00
4.3 Same as above but, 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. for 6 Nos. 111.00
Outdoor LDB, 1 no. for EOT with ECH at Pump House)
4.4 Same as above but, 4C x 2.5 sq. mm. 2XWY(X) Cable (2 nos. MOV at pump Delivery, 20 Nos. 65.65
1 no. MOV at Header, 1no. MOV at ESR outlet, 1no. MOV at ESR bypass, 1 no.
ICP/PLC Panel & for 4 nos. street light)
4.5 Same as above but, 12C x 2.5 sq.mm. 2XWY(X) Cable (2 nos. MOV at pump Delivery, 10 Nos. 260.00
1 no. MOV at Header, 1no. MOV at ESR outlet, 1no. MOV at ESR bypass)
4.6 Same as above but, Single core 95sq. mm. PVC insulated circular unsheathed copper 10 Nos. 47.47
conductor flexible Cable (For Power supply Metering Panel to I/c MCCB Unit)
5.1 CABLE TRAY 60 Mtr. 556.51
SITC of G.I. (hot dip galvanised )Ladder type medium duty (2mm thick) Cable Tray
with necessary bends, tees, reducers, covers and clamps for fixing. All material shall be
Hot dip galvanised as per Specification. And including all accessories.
300 x 100 mm - Ladder type
5.2 Same as above but, 150 x 50 mm - Ladder type 150 Mtr. 278.76
5.3 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated 125 Mtr. 144.00
pipes (DWC) of polyethelene (confirming to IS-14930 II) with necessary connecting
accessoies of same material at required depth for laying of cable below ground / road
surface for enclosing cable and back filling the same to make ground as per original. (LT
5.4 Cable Trench, Laying & Installation of Cable: Making cable trench in soft soil of 80 Mtr. 46.46
suitable width of 90cms deep for laying cable, Sand cushioning and brick protection
on sides and on top all over the run and back filling the same and making the surface
as normal ground as per IS & Specification. (For laying of LT cable in ground)
5.5 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or 50 Mtr. 134.33
cement tiles laid cover the cable (top) & also on both side with sand bedding/cusioning
of 75mm.& covering of 150mm Layer of sand above cable (16 bricks per meter.) as per
IS & Tender Drg/ Specification. (For HT/LT cable protection) complete in all respects
as instructed by EIC.
6.1 CHEMICAL EARTHING SYSTEM 2 Set 10,593.89
SITC of Maintenance free chemical earthing (copper) with earthpit of minimum bore
size dia. 225mm Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-
3043:1987 /Tech spec. made of corrosion free Pipes having Outer pipe dia of 48 mm
having 250 Micron copper plating, Inner corrosion free Hot dip galvanised (80 to
micron) pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia
with constant ohmic value surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical installation & of 3Mtr.
length of Pipe with two nos. 25Kg. bag of Back filling compound. (2nos. for ICP)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
6.2 SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 6 Set 7,095.25
225mm Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987
/Tech spec. made of corrosion free Hot dip Galvanised (min 150 Microns) Pipes having
Outer pipe dia of 76 mm , Inner corrosion free Hot dip galvanised (80 to 100 micron)
pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with
constant ohmic value surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical installation & 3Mtr. length
of Pipe with two nos. 25Kg. bag of Back filling compound. (2 nos. for LT panel & 4nos.
for all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
Item Description Qty. Unit Amount, Rs.
6.3 SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip 345 Kg. 77.77
including supply & fixing using GI spacers, saddles when laid inside the building and
inclusive of excavation & refilling of earth when laid outside the building &
interconnection with earth pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m, 2.3x150Mt.=345kg.)
6.4 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip 60 Kg. 77.77
galvanized GI Strip including supply & fixing using GI spacers, saddles when laid inside
the building and inclusive of excavation & refilling of earth when laid outside the
building & interconnection with earth pit & all electro-mechanical equipments. (25X3
G.I Strip, 0.6 Kg/m, 0.6x100Mt.=60Kg.)
6.5 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes Copper Strip including 15 Kg. 794.87
supply & fixing of bolts, saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the building & interconnection with
earth pit & PLC Panel (25X3 Cu. Strip, 0.761 Kg/m, 0.761 x 20 mtr.=15.22Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual
eqp. Bitumen shall be used at the place of joint/welding. (For PLC Panel to Earthing)
6.6 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB,LCS, etc.) 21 Kg. 77.77
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 200Mt.=20.6 Kg.)
7.1 INTERNAL WIRING 50 Mtr. 78.78
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI
marked flexible stranded copper conductor wires with medium class min. 25mm. dia.
Electrical grade PVC pipe and accessories to be erected concealed in / to be run on
surface / wall / ceiling with following sizes as mentioned below. The unit rate wirings
shall be with connector, PVC junction box, wires, holder, ceiling rose, angle holder,
switch, sockets, switch board, brass chromium / cadmium plated machine screws, phase
and neutral wires, green Earth continuity wires etc. as required to complete wiring from
LDB panel to the final outlet termination points. The wiring shall be as per IS:732,
IS:4648 and as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
7.2 same as above, but (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender 60 Mtr. 96.96
specification & IS.
7.3 same as above, but (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender 60 Mtr. 86.86
specification & IS.
7.4 same as above, but (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender 80 Mtr. 120.19
specification & IS.
7.5 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & 17 Nos. 329.26
earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC
insulated multistrand copper wires , pipe to be erected concealed in flushed on wall /
ceiling, complete with 6A Tissino Type ISI marked flush type switch / bell push &
accessories erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) /
Acrylic sheet with necessary lamp holder / ceiling Rose / H. D. connector as directed
with medium class Rigid PVC pipe & accessories.
7.6 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire 2 Nos. 290.88
of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be
erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on Metal / PVC box covered
with 3 mm thick PC(Polycarbonet) / Acrylic sheet. (2 nos. LT Room cum PH.)
Item Description Qty. Unit Amount, Rs.
7.7 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire 2 Nos. 570.65
of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be
erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on Metal / PVC box covered
with 3 mm thick PC(Polycarbonet) / Acrylic sheet. (2 nos. LT Room cum PH.)
7.8 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 7 Nos. 570.65
2nos. 4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI
marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class
Rigid PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked
3Pin socket and tissino type switch erected with earth continuity connection erected on
Metal / PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point
shall be near Ex.Fan.
7.9 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball 6 Nos. 3,082.52
bearing, M.S.blades, mounting frame, forearms, suitable to operate on 230V,50 HZ AC
supply conforming to IS: 2312.Fan shall be painted with epoxy grey colour controlled by
one 6 A flush type switch on board and 6A plug point near Ex. fan.
7.10 SITC of 300mm sweep 960 R.P.M exhaust fan, capacitor type, having double ball 1 No. 2,054.34
bearing, M.S.blades, mounting frame, forearms, suitable to operate on 230V,50 HZ AC
supply conforming to IS: 2312.Fan shall be painted with epoxy grey colour controlled by
one 6 A flush type switch on board and 6A plug point near Ex. fan.
7.11 SITC of Sheets steel powder coated weather proof enclosure with One no. 32A, 415V 1 Nos. 772.65
4P MCB for Motor & Inductive load (C Curve) having 10 KA breaking capacity &
confirms to IS:
(1 no. for EOT with ECH at P.H.)
8.1 LED LIGHT FIXTURES & LIGHTING: 5 Nos. 295.93
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube
Light indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single
MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming
to IS: 513/CRCA polyester powder coated and high U.V. & corrosion resistance with
diffuser and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 20 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
(5 nos. at LT Room cum PH.)
8.2 Item description as per Sr. No.7.1 SITC of 7 watts LED Lamps integral type,cool white 2 Nos. 112.11
with PC diffuser suitable for B22 LAMP holder (1 no. LT Room cum PH., 1 no.
Chlorination room)
8.3 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, 2 Set 1,596.81
canopies, shackle, rubber bush, blades, electronic speed regulator, suitable to operate on
230V,50Hz AC supply conforming to IS: 374/1979.Fan shall be painted with white
colour.(2 nos. LT Room cum PH.)
Item Description Qty. Unit Amount, Rs.
8.4 SITC of 40W LED Surface / Wall mounted LED Flood Light fittings with High 2 Nos. 5,194.43
power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free High pressure die cast aluminum housing with
smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (at Pump House)
8.5 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 9 Nos. 558.53
cms x 20 cms x 3 mm thick M.S. base plate, erected on wall or corner for mounting
luminaries with necessary hardware materials duly painted for wall mounting indoor
flood light fixtures on Wall of Buildings & post top lantern.
8.6 SITC of 40watt, Cat-III Post Top Lantern LED fitting comprises of 650 MM TOP 2 Nos. 5,034.85
Diameter, 120 degree beam angle with 3 Nos. Supporting Ribs and with 0.5mt. G.I.
fitting pipe with complete painted with one coat of Red oxide / PU base primer and two
coats of Aluminium / PU paint for Post of lenturn pipe etc. (for Gate light)
9.1 EXTERNAL LIGHTING (Flood LIGHT): 5 Nos. 6,088.28
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White
LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than
130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish
powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/
lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (for area lighting)
9.2 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos. 10,719.13
SITC of Street Light Pole, steel tubular swaged type, 7.5 meter long with single arm &
M.S.base plate with pipe cap and over hung 1.5 m long having dia to suit the socket of
240V LED street light fixtures. Street light pole unit rate shall be with (i) IP 65 SMC
box of size 20 x 15 x 15 cms. with MCB & terminal strip inside the box with
hinged/sliding door (ii) 50mm dia, B class GI pipe bracket min.1.5mtr long for
Incoming & outgoing cable (iii)MS Cable Clamp of 25 x 3mm (iv)SITC of 1.5 Mtr.single
Arm bracket of medium duty MS pipe of 4.2 cms. Out side dia complete with suitable
sleeve tubing 45 cms. long of required size of pole top etc. and having spread of 1.5.mtr.
length with 110 deg.(v) Complete painted with one coat of Red oxide / PU base primer
and two coats of Aluminium / PU paint for Pole,Arm, pipe etc.
9.3 SITC of 70W LED Street light fittings with High power White LEDs wattage of 1Watt 4 Nos. 5,976.17
and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion
free High pressure die cast aluminum housing with smooth finish powder coated and heat
sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company
mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
Street Light (IP-65), Surge -4KV, 70 watt Cat-III
Item Description Qty. Unit Amount, Rs.
9.4 SITC of M-20 / 1:2:4 cement concrete foundation for Street light pole & 70 % PCC 4 Nos. 1,292.80
from bottom including excavation for the pole of size 60 x 60 x 120 cms. Deep in below
ground level with plinth of 45 cms x 45 cms(or 45 cms dia x 45 cms) high upper ground
level with necessary curing and finishing in approved manner.
10.1 SAFETY ACCESSORIES 1 No. 8,671.86
SITC of following safety accessories complete with necessary fixing brackets, other
accessories and tools etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with
necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall
(1 no. for LT Room cum PH.)
10.2 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds 1 No. 299.97
due burn, crepe bandage, guage bandage, medicated ready to use bandage (Band-aid)
adhesive tape for medicinal user, scissors, antiseptic solution (Savlon or similar) etc. (All
above contents shall be of standard makes)
(1 no. for LT Room cum PH.)
10.3 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and 1 No. 130.29
duly framed with front glasses, for treatment of person suffering from electric shock. (1
no. for LT Room cum PH.)
10.4 Supply and fixing of 20 W LED operated emergency light with maintenance free 1 No. 2,670.00
battery for 3 hours operation during mains power failure.
(1 no. for LT Room cum PH.)
10.5 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as 5 Sq.mtr 1,027.17
per IS:15652 and with good electrical insulation property for 1.1KV/3.3KV as per site .
requirement. (For LT Panel)
11.1 LIASONING CHARGES FOR OBTAINING NOC 1 Ls. 15,000.00
Power Liasoning Charges for obtaining N.O.C from Electrical Inspector / Statutory
authority for Power / Ele. Installation. (Fees shall be paid by tenderer for obtaining
N.O.C. from Electrical Inspector / Statutory authority on behalf of client and shall be
reimbursed on submission of original receipt to Client).
Liasoning Charges shall include preparing required attested documents & drawing for
obtaining NOC on behalf of client (Applicable Fees / deposits shall be reimbursed by
B TOTAL OF ELECTRICAL WORKS WITHOUT GST
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULE OF QUANTITIES & RATES FOR AUGMENTATION WORK OF MECHANICAL WORKS FOR
WDS IN TP-154, FP-58 (KAMOD GAM) AT LAMBHA WARD OF AMC.
DESCRIPTION QTY UNIT UNIT RATE AMOUNT
1 Supply, installation, testing & commissioning of Bourden type Pressure Guage glycerene 3 Nos. 2,213.00
filled having 150 mm dial with necessary fittings/accessories (Manifold valve, nipples, etc.
shall be in SS 316 only) as per specifications & complete in all respects.
Range : 0 - 6 Kg/cm2 (at each Pump delivery line & common header)
2.0 LEVEL MEASURING SYSTEM FOR SUMP 1 No. 59,436.00
Supply, installation, testing and commissioning of Ultrasonic type Level Transmitter with
remote type transmitter 4-20 mA HART o/p with 10 meter cable between Sensor and
Transmitter along with all required accessories, Weather proof enclosure for transmitter,
mounting stand , etc. complete in all respects with local and remote display at HMI/SCADA, as
per specification and having following measurement ranges for liquid (Water) application:
Meas. Range: upto 10m (Sump)
The scope also includes providing 4" flanged puddle pipe approximate 300 mm long including
fixing of the same in civil structure slab of Sump for mounting of sensor. The work also
include all necessary work like make hole, repair / modification in slab, etc.
2.1 LEVEL MEASURING SYSTEM FOR ESR 1 No. 1,28,800.00
Supply, installation, testing and commissioning of Non-Contact Radar Type Level
Transmitter with local mounted process indicator (PI), (30 meter cable between Sensor and PI
with extension JB if required) & having 24V DC output supply for 2-wire transmitter & re-
transmission output of 4-20mA DC to feed to PLC , accessories, hardware, consumables,
mounting stand, etc. complete in all respects and as per specification etc. and having following
measurement ranges for Sewage application:
Meas. Range: upto 10m (at ESR)
The scope also includes providing 4" flanged puddle pipe approximate 300 mm long including
fixing of the same in civil structure slab of Sump for mounting of sensor. The work also
include all necessary work like make hole, repair / modification in slab, etc.
2.2 LARGE SIZE LED / LCD DISPALY 1 No. 20,526.00
Supply, installation, testing and commissioning LED display 8" digit size & Frame / Panel
size min. (320 mm H X 620 mm W X 50 mm D) or higher with 4-20 mA Input at Pump house
to monitor the level of ESR in Pump house with all required acessories complete in all respects
as per specification.
Note: For ESR Large Display shall be mounted in Pump house.
2.3 Supply, installation, testing and commissioning of Float type Level Switch along with 10 mtr. 1 No. 12,802.00
Cable and WP Junction Box (at sump for dry run protection of pumps through relay
multiplication in PLC), etc., complete in all respects and as per specification. The scope also
includes providing 4" flanged puddle pipe approximate 300 mm long including fixing of the
same in civil structure slab of Sump for mounting of level switch. The work also include all
necessary work like make hole, repair / modification in slab, etc.
Meas. Range: upto 10 m (at sump)
2.4 Supply, installation, testing & commissioning of Float & Board type level indicator along 1 No. 17,718.00
with all accessories, hardware, etc. complete in all respects as per specifications and having
following measurement ranges:
Meas. Range: upto 6 m, at sump
3.0 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED 1 No. 1,85,900.00
Supply, installation, testing and commissioning of Full Bore Electromagnetic flow meter
comprising of IP-68 Sensor, IP-66 remote type transmitter with 10 m cable between sensor and
transmitter along with all mounting accessories, Weather proof enclosure for transmitter,
hardware, mounting stand, etc.
as per specification and to complete the work in all respect as per site condition necessary
connection with pipe and shall have following size.
Meter Size :350 mm NB (At Common header of VT Pump )
Pipe Size : 350 mm NB
DESCRIPTION QTY UNIT UNIT RATE AMOUNT
4.0 INSTRUMENT CABLE & ACCESSORIES 150 Mtr. 179.00
'Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of
Instrument Cables as per specs.
The unit rate shall include
a) Supply, loading & unloading of the cable at site from store.
b) Shifitng of cable from site store to place of installation.
c) Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the
d) Excavation, back filling and levelling of ground alongwith laying of fine sand, protection
bricks and other necessary civil material for laying cables outside the building.
e) Testing and submission of sketches & reports of all the cables laid.
4.1 SIGNAL CABLE 150 Mtr. 133.00
4.2 CONTROL CABLE 100 Mtr. 299.00
5.0 CABLE END TERMINATION AND CONNECTION : 6 Nos. 287.00
'Supply, fixing, connection, testing and commissioning of double compression brass cable
glands and crimping type Bimetalic lugs / sockets with necessary tools and equipments as
specified in specifications and IS complete in all respects. The glands and lugs / sockets shall
be suitable for cable size and type mentioned above. The job also includes earthing the glands
and armour of the cable with common earth bar or flexible copper mesh as applicable.
5.1 SIGNAL CABLE 10 Nos. 287.00
5.2 CONTROL CABLE 10 Nos. 362.00
6.0 INSTRUMENT CABLE TRAY 50 MTR. 360.57
SITC of G.I. (hot dip galvanised ) Perforated C type Cable Tray with necessary bends, tees,
reducers, covers and clamps for fixing. All material shall be Hot dip galvanised. All hardware
shall be Electro-galvanized/ SS 304 complete in all respects as per Specification. And
including all accessories.
100 X 50 X 1.6 mm Thick - Perforated type
C TOTAL OF INSTRUMENTATION WORK WITH OUT GST
Note : PLC Panel not consider as per instruction of Client/AMC. PLC Panel shall be provide by Client/AMC as per site requirement.
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULE OF QUANTITIES AND RATES OF OFFICE FURNITURE FOR
WDS IN TP-154, FP-58 (KAMOD GAM) AT LAMBHA WARD OF AMC.
OFFICE FURNITURE
DESCRIPTION QTY. UNIT RATE AMOUNT
1.1 Office Wooden Table 1 No 16,694.64
1.2 Steel Chair with arm rest. 3 Nos 1,649.64
2.1 White Board of Size: 3 feet x 2 feet with Blue Pen 1 No 2,000.00
3.1 Ladder: Ladder shall be made out of light aluminium allow of good 1 No 15,000.00
strength. They shall be of step ladder, foldable, self supportig type
with sperader of metalic angles or high strength.
(i) 6 Meter long aluminium Ladder
4.1 Steel Cupboard (min. W x H x D: 900 mm x 1800 mm x 430 mm) 1 No 8,229.92
D1 GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & OFFICE FURNITURE WITH GST
D1 GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & OFFICE FURNITURE WITH GST
GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & OFFICE FURNITURE WITHOUT
GRAND TOTAL OF TOOLS, TEST EQUIPMENTS & OFFICE FURNITURE WITHOUT
Note: 1) Above items shall be handed over to AMC.
2) 12% GST consider.
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
NAME OF WORK : SITC WORK OF MECHANICAL, ELECTRICAL AND INSTRUMENTATION WORK WITH FIVE YEAR OPERATION & COMPREHENSIVE MAINTENANCE FOR WATER DISTRIBUTION
PUMPING STATION (WDS) IN TP-154, FP-58 (KAMOD GAM) AT LAMBHA WARD OF AMC.
E- Man Power For Operation & Maintenance
1st Year 2nd Year 3rd Year 4th Year 5th Year
Sr. No. Details
Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount
Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount
Helper cum Safaiman
(at General shift)
For First year as per minimum Wages Circular, for 2nd, 3rd, 4th & 5th year 7% rise is considered for making Estimate only. Actual Amount shall be paid as per time to time revised Minimum Wages by Govt. of Gujarat /
F- Repair & Maintenance Cost
1st Year 2nd Year 3rd Year 4th Year 5th Year
Sr. No. Details
Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount
Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount Qty. Rate/ Month Total Amount
4.5 Painting (MS Structure
4.6 Housekeeping
5 Chlorination Plant
6 Auto shut off valve
7 Caustic solution
replacement/ Top-up cost
8 Cylinder transportation OR
Total Amount for O&M work/ Month (I+II) 84,967.00 97,282.00 1,06,909.00 1,09,543.00
Total Amount for O&M work/ Month (I+II) 84,967.00 97,282.00 1,06,909.00 1,09,543.00
E Final O & M Amount for 5 years (Excluding GST)
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
SCHEDULES OF QUANTITIES AND RATES
CONSTRUCTION OF 5.0 LAKH LITER , 18 MT STAGING HEIGHT ESR (EPC BASIS) ON OPEN FOUNDATION FOR
NEW WATER DISTRIBUTION STATION AT KAMOD GAM LAMBHA WARD IN SOUTH ZONE OF AMС.
Sr. No. Item Description Qty. Rate without Unit Amount
,,,1.00 Designing, structurally (and aesthetically) complying Provisions of relevant Indian standards and constructing 5.0 Lac litre capacity 18 To be quoted
mt. staging height RCC Elevated Service Reservoir (RCC M-30 grade concrete and reinforcement CRS Fe-500 steel for entire ESR) of
the below mentioned size using latest S.B.C. of proposed site, Seismic zone-03, Wind speed Zone. Including
(1) Container shape any suitable type (or as specified).
(2) Staging consisting of column brace trestle / combination column- brace trestle and shaft/Shaft Supporting Structure as appropriate
(or as specified) and
(3) Appropriate foundation system. This includes excavation in all types of soil strata (including hard rock ). Casting100 mm thick P
C.C. levelling course in M-10. Refilling the pit with proper soil and disposing of the surplus stuff at all required lead..
(4) This will also include cement plaster in CM 1:3 with approved water proofing compound & Food Grade Epoxy Paint all over
inside container (i.e. walls, base, top slab/dome bottom etc. all).
(5) Providing and fixing of any accessories(specified) like Alluminium Pole ladder, Cl Manhole frame and covers, water level
indicator , lightening conductor/arrester, Gl Pipe railing around walk way, at roof level, at gallery and around landing of inside shaft,
Adequate cowl type ventilators or lantern type ventilator with stainless steel jali.
(6) Scope of work includes constructing RCC spiral staircase with adequate tie beams, staircase footing , ventilating shaft and
ventilators as well as door in shaft, SS grating to be provided to outlet pipe (Inside container) for safety, with proper arrangement of
bird screen to prevent the entry of birds from staircase.
(7) including providing and applying One Coat of Primer and Two coats of Weather Proof Exterior Emulsion Paint (as specified) to the
whole structure. (Including Inside of Shaft in case of Shaft Supporting Structure & Top of Top Dome)
(8) It also includes satisfactory water tightness test as per relevant I.S Code and painting name of scheme & capacity on the tank as per
direction of engineer in charge.
List of Indian Standard for design of ESR :
Note : The structural design of ESR shall be in accordance with provisions of relevant Indian Standards
1) I.S. 3370 part I & II 2009 or its latest revision (1:1) I.S. 3370 Part III & IV 1965 or its latest revision
2) IS 456-2000 or its latest revision
3) IS 11682-1985 or its latest revision
4) IS 1893-2002 Part I to V or its latest revision
5) Is 13920-1993 or its latest revision
6) IS 875 Part I to III, 1987 or its latest revision
7) IS 11089-1987 or its latest revision
General Specifications : To be quoted
1) The Min. concrete grade for RCC shall be M:30. Proportion of concrete ingredients shall be as per Mix design using weigh
2) TMT CRS Fe-500 or higher grade reinforcing bars confirming to IS:1786/1139 and TMT bars shall be used as per detailed
3) In case of column -brace trestle type staging having more than 6 columns internal horizontal bracing is obligatory.
4) Min. size/ thickness of various components shall be provided as per design criteria/specifications/IS Code (or as per std. practice).
Capacity of the ESR shall be considered excluding free board.
5) Minimum dimensions specified for various components in tender data /specifications should be provided.
6) The foundation shall be referred from latest SBC test report or tender datasheet. During execution If poor soil strata or ground
water table is encountered, the SBC shall have to be re ascertained and the design should be revised accordingly
7) Maximum spacing between horizontal bracings shall be 5 m (storey height)
8) The BB Masonry cabin with MS door shall be constructed around the Staircase.
9) RCC Staircase/ MS Staircase shall be provided and fixed for access to roof when height of roof from G.L. is up to 10 m. For ESR
having more than 10 m height proper RCC staircase or suitable RCC spiral staircase shall be constructed. Railing should be provided
through out the staircase and around the top ring beam also around the Inner & Outer Face of the Shaft Plateform inside Container.
10) For ESR-having staging height more than 15m the spiral staircase shall be provided inside the staging with effective tie beams in
more than one direction
11) Water level indictor shall be provided and fixed float type /electronic (as specified).
12) The rate shall include cost of dewatering during execution making all arrangement with any dewatering technique.
13) The structure shall be designed properly for uplift due to Ground water table specified in data or GWT encountered during
execution. No extra payment shall be paid for the same.
14) Effective curing shall be carried out up to required period as per specifications.
15) Agency shall engage quailfied (at least Post graduate) consulting engnieer for designing the structure and he/she shall visit the site
for guidance of work at all levels (i.e.below foundation, up to GL. above GL for all lifts up to container).
16) The Design of the Structure shall be in accordance with relevant IS 3370-1965 or as per latest revision.
17) If Water Retaining Structure is designed with limit state method, then crack width should not exceed 0.1 mm.
18) For Column – brace trestle type staging design shall be done with minimum 8 nos. of column.
19) Minimum size / thickness of various components shall be provided as per design criteria / specifications provided in the tender.
20) Defect liability for ESR will be considered for 10 years as per AMC Circular No 60/2 2020-21 Dt. 29/10/2022
Above conditions / general specifications Sr. No. 1 to 21 are part & parcel of tender(contract)
Cost of 5.0 lakh Lit Capacity ESR and 18 Mt stagging height (Seismic Zone - 3)
Signature of Contractor Addl. City Engineer (Water Project)
Name : Ahmedabad Municipal Corporation
Company’s seal :
Schedule-C-1 (Elevated Service Reservoir)
Sr. Description of Item % of total cost to be paid
No. on completion of these
1 On approval of design and drawing submitted by contractor 2%
2 Clearing site, excavation of foundation 3%
3 Providing PCC for base concrete, foundation work, RCC 20%
M-30 base slab, raft etc. upto finished ground level.
4 Providing R.C.C. M-30 column, beam, bottom dome, 20%
staircases, platforms (with railing) from ground level upto
the required level
5 Providing R.C.C. M-30 container and top dome 20%
6 Providing finishes such as plaster, paint & other fixtures 10%
7 Fixing of various sizes of pipes, valve, construction of 5%
8 Hydraulic testing & commissioning of work 20%
1) % total cost means cost quoted in Schedule-B
2) 2% amount of each running bill to be recovered and kept as a retention money
and release in final bill.
3) The contractor shall, after approval of his detailed designs and drawings furnish
to the Employer's Representative an initial bill of quantities to all major items, to
be reviewed and updated periodically with the Employer's Representative. This
bill of quantities will be used for assessment of percentage progress of the
component at any stage. By measurement jointly taken by the Employer's
Representative and the Contractor, mutually agreed and entered in the
measurement books in the form and by the method approved by the Employer's
Representative, and signed jointly by both the parties.
4) 70% payment will be paid after satisfactory cube results of 7th days from date of
casting of concrete upto 28 days. Balance payment will be claimed after
satisfactory cube results of 28 days. No payment will be claimed before 7 days.
I / We agree to abide by the above conditions fully.
Signature of Contractor
Name of Company Add. City Engineer (Water Project)
Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Technical bid.pdf
Technical specifications.pdf
Financial bid.pdf
SOIL REPORT KAMOD WDS .pdf
01.LAYOUT FOR KAMOD GAM WDS.pdf
02.GAD FOR KAMOD GAM WDS .pdf
03. KAMOD network_R0.pdf
04-Mech.GAD-WDS- KAMOD GAM-R0-29.10.2026.pdf
05-L.T. SLD-26.10.2026.pdf
06-LT Cable laying details.pdf
07-Typical Outdoor Lighting POLE Detail.pdf
08-Typical Earthing Layout-with Pipe in Pipe Type Technology.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .