Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹98,000Accepted-Finance | ₹98,000 | L1 | Accepted-Finance As per Comparative BOQ Chart |
| 2 | L2₹1 L+₹2,000 (2.04%)Accepted-Finance | ₹1 L+₹2,000 (2.04%) | L2 | Accepted-Finance As per Comparative BOQ Chart |
| 3 | L3₹1.3 L+₹34,500 (35.2%)Accepted-Finance | ₹1.3 L+₹34,500 (35.2%) | L3 | Accepted-Finance As per Comparative BOQ Chart |
| Sl No | Description | Qty | Unit | M/s INFO ENGINEERING WORKS L2 | Asif Engineering Works L3 | EHAN ELECTRICALS/ MECHANICALS L1 |
|---|---|---|---|---|---|---|
| 1.00Water Cooling Arrangement | ||||||
| 1.01 | Dismantling of VT 15 HP Dewatering Pump Casing, Shaft and Shaft Seal, Cable of Motor and Motor Adapter, Mechanical Pump, Suction Pipe, Drain Pipe etc. | 1 | Job | 3,500 ₹3,500 Lowest | 4,500 ₹4,500 | 12,000 ₹12,000 |
| 1.02 | Repair/Rewinding of 15 HP Motor using Super Enamelled Copper Wire with Class F insulation | 1 | Job | 19,500 ₹19,500 Lowest | 25,500 ₹25,500 | 21,000 ₹21,000 |
| 1.03 | Replacement of its Bearings with heavy-duty, anti-friction ball/roller Bearings (SKF/FAG or equivalent) | 2 | Job | 1,250 ₹2,500 Lowest | 2,500 ₹5,000 | 9,000 ₹18,000 |
| 1.04 | Repairing /Maintenance of Dewatering Pump by way of Cleaning of Machinery using Diesel and Dhoti Cloth, Greasing, Machining wherever necessary and Replacement of worn-out parts like Gun Metal Bushes, Replacement of Impeller (Cast Bronze/Gunmetal), Rubber Bushes, Impeller Bushes, Rubber Washers, Nuts /Bolts of Sizes, Shaft Seal, Channel Ring, Rubber Washers etc. | 1 | Job | 25,000 ₹25,000 | 30,000 ₹30,000 | 11,000 ₹11,000 Lowest |
| 1.05 | Reinstallation of Dewatering Pump Complete Including Testing (dry run test followed by a load test at the tail pool to verify discharge and head) and Commissioning of Dewatering Pump. | 1 | Job | 3,500 ₹3,500 Lowest | 4,500 ₹4,500 | 13,000 ₹13,000 |
| 1.06 | SITC of Auto/Mannual Control Panel housed in a 14/16 SWG CRCA sheet, powder-coated (IP65 rated), fully Automatic Star-Delta Starter with appropriately rated contactors and thermal overload relays, Automatic logic using conductivity probes to trigger ON/OFF based on tail pool water levels, Single Phase Preventer, Under-voltage and Over-voltage protection, Dry Run Protection to safeguard the pump if water levels drop below the suction inlet, Digital Ammeter and Voltmeter with Phase Selector switches and LED status indicators | 1 | Job | 33,000 ₹33,000 | 45,000 ₹45,000 | 15,000 ₹15,000 Lowest |
| 1.07 | Supply of 4 Core 16 mm2 copper armoured PVC/XLPE Cable (IS:7098) | 10 | Mtr | 1,300 ₹13,000 | 1,800 ₹18,000 | 800 ₹8,000 Lowest |
Tender Value
₹1 L
EMD Value
₹2,000
Closing Date
29 Jun 2026, 2:30 pmClosed
Executive Engineer Gas Turbine Division Pampore
Pampore Pulwama
Overhauling of 15 HP Tail Pool Dewatering Pump at MHEP Pahalgam including SITC of Auto-Control Panel
2026_SPDC_312107_1
GTD/PDC/TS/08 of 2026-27
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
30 days
Pahalgam
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
CP and AO Srinagar JKSPDC
₹2,000
Yes
Pampore
11 Jul 2026
10 Jun 2026
30 Jun 2026
11 Jun 2026
29 Jun 2026
15 Jun 2026
13 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Water Cooling Arrangement | |||||
| 1.01 | Dismantling of VT 15 HP Dewatering Pump Casing, Shaft and Shaft Seal, Cable of Motor and Motor Adapter, Mechanical Pump, Suction Pipe, Drain Pipe etc. | - | Job | - | - |
| 1.02 | Repair/Rewinding of 15 HP Motor using Super Enamelled Copper Wire with Class F insulation | - | Job | - | - |
| 1.03 | Replacement of its Bearings with heavy-duty, anti-friction ball/roller Bearings (SKF/FAG or equivalent) | - | Job | - | - |
| 1.04 | Repairing /Maintenance of Dewatering Pump by way of Cleaning of Machinery using Diesel and Dhoti Cloth, Greasing, Machining wherever necessary and Replacement of worn-out parts like Gun Metal Bushes, Replacement of Impeller (Cast Bronze/Gunmetal), Rubber Bushes, Impeller Bushes, Rubber Washers, Nuts /Bolts of Sizes, Shaft Seal, Channel Ring, Rubber Washers etc. | - | Job | - | - |
| 1.05 | Reinstallation of Dewatering Pump Complete Including Testing (dry run test followed by a load test at the tail pool to verify discharge and head) and Commissioning of Dewatering Pump. | - | Job | - | - |
| 1.06 | SITC of Auto/Mannual Control Panel housed in a 14/16 SWG CRCA sheet, powder-coated (IP65 rated), fully Automatic Star-Delta Starter with appropriately rated contactors and thermal overload relays, Automatic logic using conductivity probes to trigger ON/OFF based on tail pool water levels, Single Phase Preventer, Under-voltage and Over-voltage protection, Dry Run Protection to safeguard the pump if water levels drop below the suction inlet, Digital Ammeter and Voltmeter with Phase Selector switches and LED status indicators | - | Job | - | - |
| 1.07 | Supply of 4 Core 16 mm2 copper armoured PVC/XLPE Cable (IS:7098) | - | Mtr | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.11 MB
BOQ_1010302.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .