Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.4 LAccepted-AOC | ₹6.4 L Quoted ₹6.6 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹6.9 L+₹22,690 (3.42%)Rejected-Finance | ₹6.9 L+₹22,690 (3.42%) | L2 | Rejected-Finance Second lowest |
| 3 | L3₹8.5 L+₹1.9 L (28.6%)Rejected-Finance | ₹8.5 L+₹1.9 L (28.6%) | L3 | Rejected-Finance Third lowest |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
25 Mar 2021, 6:00 pmClosed
Maj Sameer Wadekar
Holta Camp Palampur Kangra H.P 176061
REPAIR/MAINTENANCE OF INTERNAL WIRING MCBs DBs SUB MAIN WIRING AND ELECTRICAL FITTINGS IN OTM ACCN AT ALHILAL MIL STATION
2021_MES_429576_1
GEP_ /2020-21
Open Tender
Civil Works
Item Rate
180 days
Alhilal
As per tender documents
8 documents required · 8 mandatory
₹500
Yes
GE Palampur
₹26,000
Yes
31 Mar 2021
10 Mar 2021
27 Mar 2021
10 Mar 2021
25 Mar 2021
13 Mar 2021
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc removing materials to store for keeping in safe custody for reuse if serviceable or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as directed.
Point wiring with 1.5 Sqmm PVC (FRLS-H) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 1.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in & incl PVC surface casing 'N' capping double lock type to be fixed with the help of rawal plugs & screws incl all fittings such as Tee, connector pieces, L-junction etc on joints including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for one light/fan/bell point controlled by one switch and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
All as per item No 2 above but for 5 pin switch socket outlet 5 Amp on independent board complete all as specified.
All as per item No 2 above but for 5 pin switch socket outlet 5 Amp on same board with other switches, complete all as specified.
Point wiring with 2.5 Sqmm PVC (FRLS-H ) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 2.5 Sqmm PVC (FRLS-H) insulated unsheathed multi stranded copper conductor cable draw in & incl PVC surface casing 'N' capping double lock type to be fixed with the help of rawal plugs & screws incl all fittings such as Tee, connector pieces, L-junction etc on joints including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for 3 pin switch socket outlet 15/20 Amp on independent board and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
Point wiring with 4 Sqmm PVC (FRLS-H) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 4 Sqmm PVC (FRLS-H) insulated unsheathed multi stranded copper conductor cable draw in & incl PVC surface casing 'N' capping double lock type to be fixed with the help of rawal plugs & screws incl all fittings such as Tee, connector pieces, L-junction etc on joints including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for 3 pin switch socket outlet 15/20 Amp on independent board and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
Point wiring with 1.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 1.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in existing conduit including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for one light/fan/bell point controlled by one switch and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
All as per item No 7 above but for 5 pin switch socket outlet 5 Amp on independent board complete all as specified.
All as per item No 7 above but for 5 pin switch socket outlet 5 Amp on same board with other switches, complete all as specified.
Point wiring with 2.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable 1100 volts grade single core conforming to IS-694-1990 and including one run of continous earth wire to common earth and connected to earth with 2.5 Sqmm PVC (FRLS) insulated unsheathed multi stranded copper conductor cable draw in existing conduit including CI/MS/PVC sunk boxes for mounting switches, sockets, regulators etc with 3 mm thick plastic laminated sheet cover of adequate size for 3 pin switch socket outlet 15/20 Amp on independent board and making good disturbed surfaces with CM (1:4) to match with the existing surface complete all as specified and directed.
Supply and fixing switch piano flush button types 5 Amp single pole one way complete all as specified.
Supply and fixing Socket outlet 5 pin, 5amp, flush type complete all as specified.
Supply and fixing socket outlet 2 in 1, 3 pin, 5 and 15 Amp, flush type universal Complete all as Specified.
Supply and fixing switch piano flush button types 15 Amp single pole one way complete as specified.
Supply and fixing bell push complete all as Specified. Make - CG/Havalls/Anchor/Cona
Supply and fixing electronic bell ding dong type complete all as Specified. Make:- CG/Havalls/Anchor/Cona
S&F LED batten with LED rod complete T-8, 1x18 W including provn of flexible cable 3 core, 23/.0076 from ceiling rose to connector complete all as specified and directed. Make:- Polycab/Wipro/Halonix/Havells.
Supply & fixing LED tube light fitting 1x8 W complete including provn of flexible cable 3 core of size 23/.0076 from ceiling rose to connector complete all as specified and directed. Make : Polycab,/Wipro/Halonix/Havells.
Taking down old burnt out bulk head fitting any type and installaton LED Bulk Head 10W with pressure plastic housing with clear prismatic diffuser, high efficient LEDs IP66 complete all as specified and directed. Make:- Polycab/Wipro/Halonix/Havells/C&S.
S&F recess mounting LED 2X2 fittings 36 W incl provn of flexible cable 3 core, 23/.0076 from ceiling rose to connector complete all as specified and directed. Make- Halonix/ Polycab/CG/Havells/Bajaj
Supply and fixing batton holder with LED 3 W complete all as Specified. Make-CG/BAJAJ/HAVELLS/ANCHOR
Supply and fixing regulator for fan 1200/1400mm sweep electronic type 230 Volt AC , 300 W complete all as Specified.
Ceiling rose 3 terminal bakelite 65mm x50mm surface type complete all as specified and directed.
M&L sub main wiring with proper colour coding, FRLS PVC insulated copper conductor, unsheated, multi-stranded, copper conductor, cable of two runs, 6 Sqmm for phase and neutral and one run of 6 Sqmm for earth wire, drawn through and including PVC casing and caping with all fittings like tee, bends, junction box/terminal box fixed on wall/ground/ceiling etc and connected complete all as specified and directed. Note :- Phase should be of Red/Yellow/Blue, neutral should be of black and earthing wire should be of green colour. Two run of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length.
All as per Srl item No 24 here- in- before but 4 Sqmm for phase and neutral and one run of 4 Sqmm for earth wire
Supply and fix distribution board iron clad, vertical DB double door with IP-43 protection suitable for MCB TPN as incommer and MCB as outgoing 415 Volts 3 phase 50 Hz 4 way, complete with appropriate size copper busbar and neutral link complete with one MCB TPN 415 Volts 63 Amps rating, 16 KA breaking capcity of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site and including taking down old unserviceable existing DB any type/size complete all as specified and directed. Make:- Indo Asian Cat Part No-811870 for DB and 811220 for MCB TPN or equivalent in Legrand/Schneider/Siemens/C&S
S&F sheet metal enclosures distribution board single pole and natural 12 way with 200 Amps rated bus bar 240 V, metallic double door IP-42 protection including taking out of old MCB DB of any type/size and removing from site to MES store for reuse if serviceable or for credit complete all as specified and directed. Make- Indo Asian/Standard/Havells/C&S
S&F sheet metal enclosures distribution board single pole and natural 8 way with 200 Amps rated bus bar 240 V, metallic double door IP-42 protection including taking out of old MCB DB of any type/size and removing from site to MES store for reuse if serviceable or for credit complete all as specified and directed. Make:- Indo Asian/Standard/Havells/C&S
S&F sheet metal enclosures distribution board single pole and natural 4 way with 200 Amps rated bus bar 240 V, metallic double door IP-42 protection including taking out of old MCB DB of any type/size and removing from site to MES store for reuse if serviceable or for credit complete all as specified and directed. Make:- Indo Asian/Standard/Havells/C&S
Supply and fix MCB SPN 240 volts, 10kA, 50 Hz of capacity 40-63 Amps 'C' series all as specified and directed. Make:- Indo Asian (Optipro) or equivalent in Standard / Havells/C&S.
Supply and fix MCB, SP 240 Volts, 6 to 32 Amps 'B' series10 KA, complete all as specified and directed by Engr-In - Charge. Make:- Indo Asian (Optipro) or equivalent in Standard/Havells/C&S.
Taking down old unserviceable electric storage water heater any type/size, supply and installation of electric storage water heater (vertical type geysers), five star rating, 50 litres capacity, 240 Volts, AC Single phase capacity having stainless steel inner tank, including heavy duty pin type fasteners 4" long as per site requirement and making necessary inlet/outlet water connections and making good disturbed surface of walls to match with existing surface complete all as specified and directed. Make : Bajaj/ Recold/Usha Lexus/Crompton Greaves/ Havells/ Morphy Richords. Note : Old unserviceable electric storage water heater to be deposited in MES store yard.
Taking down old unserviceable electric storage water heater any type/size, supply and installation of electric storage water heater (vertical type geysers), five star rating, 25 litres capacity, 240 Volts, AC Single phase capacity having stainless steel inner tank, including heavy duty pin type fasteners 4" long as per site requirement and making necessary inlet/outlet water connections and making good disturbed surface of walls to match with existing surface complete all as specified and directed. Make : Bajaj/ Recold/Usha Lexus/Crompton Greaves/ Havells/ Morphy Richords. Note : Old unserviceable electric storage water heater to be deposited in MES store yard.
Taking down old unserviceable exhaust fans any type/size, supply & fixing exhaust fans AC single phase 230V of size 250 mm (PVC body) with louvers shutter including making/repairing hole in brick/stone wall as per site reqmt and making good disturbed surfaces, complete all as specified and directed. Make:- Bajaj, Model- Maxima Dx 250 mm or equivalent in CG/Havells/Usha. Note : Old unserviceable exhaust fan to be deposited in MES store yard.
Supply & fixing temper proof electronic meter (with Backlit LCD Display) accuracy class 1.0 (ISI Marked), Three phase, 3 wire, 240 volts (+) 20%, (-) 40% of capacity 10 to 60 Amps (Measures & Displays kWh, V, I, KW, six months history of Energy & MD in kW), 50 Hzs, anti temper proof features as specified including necessary sealings and connection with suitable size of PVC insulated copper cable multistrand with appropriate size of copper lugs at no extra cost including carefully, complete all as specified and directed. Make : HPL, Cat Part No Cat Part No TPPL15100000000CH1. Note : Old unserviceable energy meters to be deposited in MES store yard.
Supply & fixing temper proof electronic meter (with Backlit LCD Display) accuracy class 1.0 (ISI Marked), single phase, 2 wire, 240 volts (+) 20%, (-) 40% of capacity 5 to 10 Amps (Measures & Displays kWh, V, I, KW, six months history of Energy & MD in kW), 50 Hzs, anti temper proof features as specified including necessary sealings and connection with suitable size of PVC insulated copper cable multistrand with appropriate size of copper lugs at no extra cost including carefully, complete all as specified and directed. Make:- HPL, Cat Part No SPPB1310000002OC00. Note:- Old unserviceable energy meters to be deposited in MES store yard.
Supply, laying commissioning & testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with multi stranded aluminium conductor of size 10 sq mm 4 core complete all as specified and directed. Note:- Earth work, sand cushioning & bricks shall be measured and paid separately.
Supply, laying commissioning & testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with multi stranded aluminium conductor of size 16 sq mm 4 core complete all as specified and directed. Note:- Earth work, sand cushioning & bricks shall be measured and paid separately.
Supply, laying commissioning & testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with multi stranded aluminium conductor of size 10 sq mm 2 core complete all as specified and directed. Note:- Earth work, sand cushioning & bricks shall be measured and paid separately.
Supply, laying commissioning & testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with multi stranded aluminium conductor of size 16 sq mm 2 core complete all as specified and directed. Note:- Earth work, sand cushioning & bricks shall be measured and paid separately.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m deep in any type of soil for laying cables,foundation of poles etc. and getting out complete all as specified and as directed.
Returning, filling in (soil), including spreading, levelling, watering and well ramming in layers not exc. 25cm, complete all as specifed and as directed.
Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc. 1.5m above the starting point complete all as directed.
Sub class 'B' brick, old size as cable protection cover, laid dry, flat, transversally along the length of cable on sand cushioning with width equal to the length of the brick, complete all as specified and directed.
Sand cushioning to under ground cable with a layer of sand 8cm before laying the cable and 15cm after laying the cable (10cm punned thickness above the top of the upper most cable, total 18 cm), complete all as specified and directed.
M&L for 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1m apart including 4mm dia suspension GI wire with stranded conductor 10 sqmm twin core cable flat or circular including taking down old unserviceable cable and stacking at site, complete all as specified.
Earthing with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit less than 2.25 mtr deep below normal ground level) with top edge of the earth plate not less than 1.5 mtr deep below normal ground level, connected to 4mm dia galvanized iron wire as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel complete with 15mm dia light grade protection pipe, 20mm dia GI light grade watering pipe with funnel including char coal dust, salt, PCC 1:2:4 in pit with precast RCC M-15 cover reinforced with XPM not less then 4.00 Kg per sqm including necessary earth work in any type of soil, removal of surplus soil to a distance not exc 50m, returning filling in complete as shown in electrical plate No 3 of SSR Part-I (2009), and connected to earthing test point all as specified or indicated, testing on completion including taking down old unserviceable earthing complete all as specified and directed. NOTE: The rates for earthing includes the cost of earth lead and protection pipe upto 7.50m length.
S&F in repairing switch piano flush button type 5 Amp single pole one way complete as specified.
S&F in repairing socket outlet 5 pin, 5 Amp, flush type universal complete all as Specified.
S&F in repairing switch socket combination 2 in 1, outlet 5 pin, 5 Amp, flush type universal complete all as specified.
S&F in repairing switch socket combination 2 in 1 pin, 5 and 15 Amp, flush type universal complete all as specified.
S&F in repairing switch piano flush button types 15 Amp single pole one way complete as specified.
S&F in repairing socket outlet 5 pin, 15 Amp, flush type universal complete all as Specified.
S&F in repairing electronic fan regulator 100W, 230V step type single pole, complete all as specified and directed.
S&F in repairing modular switch 6 Amp single pole one way, complete all as specified and directed. Make : Indo Asian, Cat Part No. 800000 or equivalent in Anchor/Havells/Plaza/ Cona
S&F in repairing modular socket outlet 6 Amp 3 Pin, complete all as specified and directed. Make: Indo Asian, Cat Part No. 800020 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing modular switch 16 Amp single pole one way, complete all as specified and directed. Make: Indo Asian, Cat Part No. 800002 or equivalent in Anchor/Havells/Plaza/ Cona
S&F in repairing modular socket outlet 6/16 Amp 3 Pin, complete all as specified and directed. Make: Indo Asian, Cat Part No. 800022 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing modular electronic fan regulator 120W, 230V step type single pole, complete all as specified and directed. Make - Indo Asian, Cat Part No. 800041 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing capacitor 2.5 mfd suitable for ceiling fan 1200/1400 mm sweep complete all as specified and directed.
S&F in repairing LED rod 18 watt, 4 feet complete all as specified. Make-Polycab,/ Halonix/CG/Havells/Bajaj
S&F in repairing batten holder PVC body suitable for pin type CFL, complete all as specified. Make- CG/Havells/Bajaj/Anchor.
S&F in repairing electronic choke 14 watt complete all as specified. Make-CG/Bajaj/Havells/Polycab/Halonix
S&F in repairing electronic choke 28 watt complete all as specified. Make:- Polycab, Cat Part No PCBE 128 T HFC or equivalent in CG/Bajaj/Havells/Polycab/Halonix
S&F in repairing electronic control gear/driver 36 watt complete all as specified and directed. Make-CG/Bajaj/ Havells/Halonix
S&F in repairing tube rod 14 watt complete all as specified. Make-CG/Bajaj/ Havells/Halonix
Supply and fixing in replacement heating element of 1.50/2.00 KW ISI marked for water heater complete all as specified and directed.
Supply and fixing in replacement PVC connecting pipes with brass adopters 18” long complete all as specified and directed.
S&F indigating lamp suitable for electric storage water heater of capacity 25/50 ltr ISI marked including taking down old unserviceable indigating lamp complete all as specified and directed.
S&F in repairing MCB SPN 240 volts, 10kA, 50 Hz of capacity 40-63 Amps 'C' series all as specified and directed. Make:- Indo Asian (Optipro) or equivalent in Havells/Plaza/Cona/Standard.
S&F in repairing MCB, SPN 240 Volts, 6 to 32 Amps 10KA, 'C' series complete all as specified and directed. Make:- Indo Asian (Optipro) or equivalent in Havells/Plaza/Cona/ Standard.
S&F in repairing MCB, SP 240 Volts, 6 to 32 Amps 10 KA, 'C' series complete all as specified and directed. Make:- Indo Asian (Optipro) or equivalent in Havells/Plaza/Cona/ Standard.
S&F in repairing modular plates white colour 1 or 2 module complete all as specified and directed. Make:- Indo Asian, Cat Part No. 800061 and 800062 or equivalent in Anchor/ Havells/Plaza/Cona.
S&F in repairing modular plates white colour 3 module complete all as specified and directed. Make - Indo Asian, Cat Part No. 800063 or equivalent in Anchor/Havells/ Plaza/Cona.
S&F in repairing modular plates white colour 4 module complete all as specified and directed. Make - Indo Asian, Cat Part No. 800064 or equivalent in Anchor/Havells/ Plaza/Cona.
S&F in repairing modular plates white colour 6 module complete all as specified and directed. Make:- Indo Asian, Cat Part No. 800066 or equivalent in Anchor/Havells/ Plaza/Cona.
S&F in repairing PVC surface box suitable for modular switches and plates 1 or 2 module complete all as specified and directed. Make:- Indo Asian, Cat Part No. 800182 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing PVC surface box suitable for modular switches and plates 3 module complete all as specified and directed. Make:- Indo Asian, Cat Part No. 800183 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing PVC surface box suitable for modular switches and plates 4 module complete all as specified and directed. Make:- Indo Asian, Cat Part No. 800184 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing PVC surface box suitable for modular switches and plates 6 module complete all as specified and directed. Make - Indo Asian, Cat Part No. 800186 or equivalent in Anchor/Havells/Plaza/Cona.
S&F in repairing plug top 15 Amp 230 Volt complete as specified.
M/S MALHI CONSTRUCTIONS
M/s Raj Construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .