| Sl No | Description | Qty | Unit | kamladityya construction pvt. ltd. L1 | M/s Daroga Pradhan L2 | BALKRISHNA BHALOTIA CONST.PVT.LTD L3 | M/S RAM KRIPAL SINGH CONSTRUCTION PRIVATE LIMITED L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | EARTH WORK
Earth Work in excavation in Foundation Trenches in Ordinary soil (vide classification of soil item -B) and disposal of excavated earth as obtained to a distance upto 50 M including all lift, leveling ramming the foundation trenches, removing roots of tree shrubs all complete as per approved design, building specification and direction of E/I | 15,079 | cum | - | - | - | - |
| 2.00 | Extra for earth work in hard soil as per specification & direction of engineer in charge (Vide classification of soil item B) | 15,079 | cum | - | - | - | - |
| 3.00 | Extra rates for quantities of works, executed :In or under water and/or liquid mud, including pumping out water as required. | 15,079 | cum | - | - | - | - |
| 4.00 | Earth filling in foundation trenches and plinth in layer not exceeding 150mm thick will watered rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenched with a lead of 50mm and lift of 1.5M all complete as per building specification and direction of E/I. (Mode of measurement compacted volume). | 2,272 | cum | - | - | - | - |
| 5.00 | Removal & disposal of surplus excavated earth by mechanical transport including loading unloading stacking and spreading at all lift and lead up to 5km to spoil dump approved by local authority. | 12,808 | cum | - | - | - | - |
| 6.00 | Jungle clearance including weeding out shrubs & small trees upto 150mm dia (girth) & their removal as per specification & direction of Engineer in charge | 13,010 | SQM | - | - | - | - |
| 7.00 | Providing coarse clean local SAND IN FILLING in foundation trenches or in plinth including ramming and watering in layer not exceeding 150 mm thick with all leads and 1.5 M lifts including cost of all materials, labours, royalty and taxes all complete as per building specification and direction of Engineer In charge (Mode of measurement compacted volume) | 66 | cum | - | - | - | - |
| 8.00 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diaMTR.er holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor With Chlorpyriphos/Lindane E.C. 20% with 1% concentration | 2,210 | SQM | - | - | - | - |
| 9.00water bond macadam Providing, laying spreading & compacting stone aggregates of specific size to water bond macadam specification including spreading in uniform thickness hand packing, rolling with vibratory roller 8-10 tone / smothery wheeled steel roller in stages to proper gate & chamber, applying and booming requisite type of screening / binding materials to fill up the interstices of course aggregate, water and compacting to the required density. | |||||||
| 10.00(B) By mechanical means | |||||||
Tender Value
₹48.0 Cr
EMD Value
₹48.0 L
Closing Date
17 Jun 2019, 5:00 pmClosed
Municipal Commissioner
DMC, MADA BUILDING, LUBY CIRCULAR ROAD, DHANBADl
Construction of Dhanbad Municipal Building at Dhanbad, Jharkhand.
2019_UDD_38875_1
DMC/02/2019-20
Open Tender
Civil Works - Buildings
720 days
DHANBAD
Please refer Tender documents.
3 documents required · 3 mandatory
₹25,000
Chief Executive Officer, DMC, Dhanbad
₹48.0 L
DHANBAD
23 Jul 2020
4 Jun 2019
19 Jun 2019
4 Jun 2019
17 Jun 2019
11 Jun 2019
10 Jun 2019
Amount
EARTH WORK Earth Work in excavation in Foundation Trenches in Ordinary soil (vide classification of soil item -B) and disposal of excavated earth as obtained to a distance upto 50 M including all lift, leveling ramming the foundation trenches, removing roots of tree shrubs all complete as per approved design, building specification and direction of E/I
Extra for earth work in hard soil as per specification & direction of engineer in charge (Vide classification of soil item B)
Extra rates for quantities of works, executed :In or under water and/or liquid mud, including pumping out water as required.
Earth filling in foundation trenches and plinth in layer not exceeding 150mm thick will watered rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenched with a lead of 50mm and lift of 1.5M all complete as per building specification and direction of E/I. (Mode of measurement compacted volume).
Removal & disposal of surplus excavated earth by mechanical transport including loading unloading stacking and spreading at all lift and lead up to 5km to spoil dump approved by local authority.
Jungle clearance including weeding out shrubs & small trees upto 150mm dia (girth) & their removal as per specification & direction of Engineer in charge
Providing coarse clean local SAND IN FILLING in foundation trenches or in plinth including ramming and watering in layer not exceeding 150 mm thick with all leads and 1.5 M lifts including cost of all materials, labours, royalty and taxes all complete as per building specification and direction of Engineer In charge (Mode of measurement compacted volume)
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diaMTR.er holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
water bond macadam Providing, laying spreading & compacting stone aggregates of specific size to water bond macadam specification including spreading in uniform thickness hand packing, rolling with vibratory roller 8-10 tone / smothery wheeled steel roller in stages to proper gate & chamber, applying and booming requisite type of screening / binding materials to fill up the interstices of course aggregate, water and compacting to the required density.
(B) By mechanical means
(b) Using screening Type - A (13.2mm Agg.) with vibratory roller
CONCRETE WORK
Providing P.C.C. M-75with nominal mix of (1:4:8) in foundation with approved quality of stone MTR.al grade - III (50 mm to 25mm size) clean coarse sand of F.M 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position vibrating, skirting, curing, taxes and royalty all complete all complete as per building specification and direction of Engineer-in-charge.
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:1½:3 (1 cement:1½ coarse sand:3 graded stone aggregate 20 mm nominal size)
R C C WORK Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge.
NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately
(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC.
All works upto plinth level
All works above plinth level upto floor V level
Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for Each four floors or part thereof.
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
Centering and shuttering including strutting, propping etc. and removal of form for Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform
Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers
Centering and shuttering including strutting, propping etc. and removal of form for :Columns, Pillars, Piers, Abutments, Posts and Struts
Centering and shuttering including strutting, propping etc. and removal of form for Stairs, (excluding landings) except spiral-staircases
Extra for shuttering in circular work (20% of respective centring and shuttering items )
Centering and shuttering including strutting, propping etc. and removal of form for : Cornices and mouldings
Suspended floors, roofs, landings, balconies and access platform. with water proof ply 12 mm thick
Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
Providing Tor steel reinforcement as per approved design & drawing
Providing Tor steel reinforcement of all dia bar as per approved design and drawing
TMT bar Fe 500
BRICK WORK
Providing designation 100A brick work with flyash lime brick (FLAG) confirming to IS 12894-1990 (9"x425"x3") in C.M. (1:4) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints costs of screening materials, raking out joints to 15mm depth curing taxes and royalty all complete as per building specification and direction of E/I.
Providing designation 100A brick work with flyash lime brick (FLAG) confirming to IS 12894-1990 (9"x4.5"x3") in C.M. (1:4) in super structure with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints costs of screening materials, scaffolding, raking out joints to 15mm depth curing taxes and royalty all complete as per building specification and direction of E/I.
Providing designation 112mm thick reinforced designation 100A brick work with flyash lime brick (FLAG) in (1:4) in superstructure with approved quality of clean coarse sand of F.M. 2 to 2.5 including the cost of screening carriage of materials, scaffolding, raking out joints to 15mm depth, curing, taxes and royalty (but excluding the cost of reinforcement) all complete as per building specification and direction of E/I.
Extra for brick work for each consecutive floor above first floor including watering & scaffolding all complete as per direction of E/I
Extra for providing & placing in position 2 no 6mm dia ms bar every 3rd corse of half brick masonary
WOOD WORK
Supplying, fitting and fixing good quality, well dressed and well seasoned Sal wood work in choukhat in doors, windows, skylights, fanlights and C/W celestial window openings, including wedge over all clamps complete includingapplicationof two coatsof wood preservativeof approved quality on the surface butting walls and lintels all completeas per building specificationand direction of E/I
Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes, including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws.Second class teak wood,35 mm thick
Supplying, fitting and fixing 35mm thick solid core type decorative double leaf flush door shutter with one sides teak decorative and another side commercial veneered with black board core bended with high quality phenol formal dehydes synthetic resin of standard make with Aluminium fittings such as hinges, tower bolts, handle, cleats and sand blocks and taxes all complete as per building specification and direction of E/l. MAKE ARCHIDPLY,Green ply, Marino, Century
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
Extra for cutting rebate in flush door shutters (Total area of the shutter to be measured).
Providing and fixing wooden moulded beading to door and window frames with iron screws, plugs and priming coat on unexposed surface etc. complete :
Providing, fitting and fixing oxidised iron fitting of approved quality and make to door and window all complete as per building specification and direction of E/I necessary screws etc. complete. 300 mm sliding door bolt
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.
Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineerin-charge.
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge
Melamine polishing on wood work (one or more coat).
Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1mm), with wall thickness 2.0 mm (± 0.2 mm), corners of the door frame to be Jointed with galvanized brackets and stainless steel screws, joints mitred and Plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer’s specification and direction of Engineerin- charge
30 mm thick factory made Polyvinyl Chloride (PVC) door shutter made of styles and rails of a uPVC hollow section of size 60x30 mm and wall thickness 2 mm (± 0.2 mm), with inbuilt decorative moulding edging on one side. The styles and rails mitred and joint at the corners by means of M.S. galvanised/ plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 25x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of 'H' section, a uPVC hollow section of size 100x30 mm and 2 mm (± 0.2 mm) wall thickness fixed to the shutter styles by means of plastic/ galvanised M.S. 'U' cleats.
The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness . The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer's specification and direction of Engineer-in-charge.
Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item):
With float glass panes of 5.50 mm thickness
Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge (Dash fastener to be paid for separately). except bottom. (Door will be commercial ply finish only.)
Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge (panneling to be paid for separately).
Providing and fixing glazing in fire resistant door shutters, fixed panels, ventilators and partitions etc., with G.I. beading of appropriate size, made out of 20 SWG G.I.sheet (zinc coating not less than 120 gm/m2), fire resistant sealant, including applying a coat of approved fire resistant primer on G.I. beading etc., complete all as per direction of Engineer-incharge. With clear fire resistant glass panes 6mm thick of approved brand, having minimum 60 minutes fire resistance
STEEL WORK
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including:
(a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design.
(b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc.
(c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site,
cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding,
having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places."
FLOORING WORK
providing and laying, floor tiles in diiierent sizes (thickness to be i specrfred by lhe maiirifacturer) with water absorption less than 0.08% I arrcl conformrng to lS 15622f of {pupiJu1h'*ake. in all cotours and I shacjes laid on 20mrn tlrick'cement mortar 1 4 (1 cement:4 coarse I sancl) lointing witir grey cement slurry @ 3.3 kg/ sqm including I grouting tiie joints v/ith v/hite cement and matching pigments etc., I cornplete Size of l-ile 600x600 mm
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Providing and fixing granite 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for flooring, kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Granite of any colour and shade Area of slab over 0.50 SQM
Providing edge moulding to 18 mm thick marble/granite stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Mirror polishing on marble work/Granite work/stone work where ever required to give high gloss finish complete.
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.Granite Stone of approved shade
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
Providing and laying 1st quality Ceramic glazed wall tiles thickness to be specified by the manufacturer) in walls over 12mm cement mortar (1:3) and jointed with grey cement slurry flush pointed with white cement including rubbing polishing and cost of curing, taxes and royalty all complete as per building specification and direction of E/I.
Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/SQM including pointing in white cement complete.8mm thick Granite of any colour and shade
Providing and fixing dry cladding with 30 mm thick gang saw cut stone with (machine cut edges) of uniform colour and size upto 1mx1m, fixed to structural steel frame work and/ or with the help of cramps, pins etc. and sealing the joints with approved weather sealant as per Architectural drawing and direction of Engineer-in-charge. (The steel frame work, stainless steel cramps and pins etc. shall be paid for separately) sand stone
Providing and fixing adjustable stainless steel cramps of approved quality, required shape and size, adjustable with stainless steel nuts, bolts and washer (total weight not less than 260 gms), for dry stone cladding fixed on frame work at suitable location, including making necessary recesses in stone slab, drilling required holes etc complete as per direction of the Engineer-in-charge.
Providing 50mm thick cement concrete flooring (1:2:4 with 20mm to 6mm size grade stone chips finish with flooring coat of neat cement in panels including cost of curing, finishing the surface smooth by rubbing with carborandum stone, taxes & royality with all complete as building specification and direction of E/I
Providing and laying 8mm thick wooden laminated flooring of Krono / Kronotex-Germany/Pergo or equivalent make of 8.0mm thick,AC-4,laid over underlay of polyurethane sheet and foam complete with nosing and all accessories etc,with 4 inch skirting all around all complete as per direction of Engineer-in-charge. i/c 1 ) Flooring, 2) Skirting, 3) A.profile Foam, 4) polythenes etc. Freight & cartage (Base Rate 7500/SQM)
Extra for filling grooves with polysulphide 6mm wide, 20mm deep.
ROOFING & WATER PROOFING WORK
Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :In 75x75 mm deep chase
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
Roof/Terrace Water proofing: Water proofrng for Old and New Roof Slab :- Providing and laying water prooflng treatment on roof slab by applying two Component, factory a designed ready to use, acrylic modified flexible,material, applied with brush,roller or spray for water proofing coating as per manufacturer specifications With following steps :-
(a)surface preparation :-Providing and cleaning of concrete surface to remove dust, oil, grease including removal of existing loose paint / coating, and cement laitance by cleaning with compressed air & water jet including all materials, labour, tools complete. Ponding test to be done after plugging all outlets and to be checked from soffit to identify seepage, leakage. On identification of seepage, cement grouting to be done with non shrink expanding admixture of Sika lndia Pvt.Ltd.
/ MYK Schomberg / Dr Fixit/Fosroc or equrivallent. Providing and reparing of all corners and joints such as those between the parapet wall and the roof slab etc shall be chamfered with '150mm X '150 mm fillet of mortar (Cement: sand - 1:4) admixed with acrylic polymer of Sika/ Fosroc/MYK Schomberg / Dr Fixit or equivalent Before chamfering a prime coat shall be given with the slurry acrylic polyrner Repairing surface irregularities, damaged concretein base slab, dead cracks if any, with an acrylic polymer modilied repair moriar including a coat of bonding agent of the same with ceme nt slurry including all material, labour, tools complete.
(b)1st Coat :- Apply 1st coat of two component acrylic modified, ready to use, fexible cementitious material on surface saturated dry roof and inside wall of Parapet wall upto 600 mm by brush or roller. After 1st coat of application ,45 gsm oI Fibre glass cloth to lay when the first layer is still green. 1st coat should be applied @1.50 kg/Sqmt/coat For the purpose of measurement the entire treated surface will be measured."
(c) :2nd Coat :- apply the 2nd coat of two component acrylic modified, ready to-use, flexible cementitious material right angle to the '1st coat over the glass fibre laicl surface. 2nd coat should be applied @0.7 kgl Sqrt/coat. For the purpose of measurement the entire treated surface will measured." Alter three days of drying the 2nd coal , the rain water outlets to be plugged and ponding test to be done for 48 hours to identify seepage, leakage from soffit and if found necessary rectification to be done as per satisfaction of E/C.
The Water proofing coating to be protect from damage before screed over it. water proofig brand sika topseal 10hi / Fosroc Brushbond RFX/ Dr Fixit Pidiffin 2Kl MYK Aquafin TG Product Performance - Chemical Base Part A.Acrylic copolymer, Part B Specially graded cementitious powder -Density 1.6 KG/l (mixid density) at +270C Tensile Strength -2 N/mm2 after 28 Days (with Fibre cloth) (According to ASTM D 2370) Prillcut Bond Streric;tl-r '-2 I'J/mm2 (concrete lajlqry) (Aqgcrdlglq ISO
a624) Slant-Shear Bond Strength -4 N/mm2 (According to FIP 5.'15) Elongation at Break -35% without Fibre Cloth and 20% wilh Fibre Cloth (Accordrng to ASTM D 2370)
with pcc :- The treated surface shourd be covered with 25mm/50mm PCC of M-20 grade(1:1.5:3) with proper slope ( '1:120) towards tlre rain outlets in alternatepanels of 2 mlxZml l<eeping 6 mrn gap betuieen the paneljoint. lntegralwater proofing admixture conforming to lS 2645 @ of 100 ml perbag of of cement to beacicjed in the scree d concrete(pard separately for thts ltems
ltems).-flll cc,rners shall be char.-rfered vrith 150mm X 150 mm fillet. The rainwateroutlets shall be just leveled with the screed concrete to ensure smooth discharge of water - the peripheral gaps between pvc pipe outlet and concrete surface slrould be packed properly with rich concrete and the peripheral mouih to be sealed with moisture insensitive epoxy putty of Sika lndia Pvt.Ltd / IVIYK Schomberg / Dr FixiUFosroc .For the purpose of rreasurement the entire treated surface will be measured."
(e)Groove of PCC surface should be filled with Polysulphide Sealant (Paid Separately) Brand - Sika lndia Pvt Ltd / MYK Schomberg / Dr Fixit/Fosroc
Covering of treated surface wrth PCC :- Providing 25 mm thick Cement Concrete M20(1:'1.5:3) r'naintaining slope in alternate 2 mIx 2 mt panels with aaproved quality of stone chips of 20 mm to 6 mm size graded and clcaned sand of F M 2 5 io 3 including screening,shuttering,and mixing cerite nt c0ncrete in mixer with admixture of integral water proofing and placing rn position,strikirrg cLrring,t-a]glgnd royality all complete as per buildirrg specifictionJand direction of E/l.Panels that has been left should be casteci nextday.-lhere should be 6 mm gap between Panels.Brand- Sika *Plastocrate plus,MYK proof WP10, Fosroc- Conplast X421ic , Dr Frx,t Prdiproof LWr
Provrding and filling of Groove between 25 mm PCC Panels with PolysLrlphide Sealant (Poring Grade)as per drawings and technical specifications and dii-ection of E in Charge (with 1B% GST).Brand:-Sika- Polysulphide, Fosroc-l-hioflex 600 Dr. Fixit Pidiseal PS(42P),MYK Seal PS or Euivallent
Toilet/Kitchen Water proofing:
1) Surface preparation by grinding machine, cleaning , crack filling etc. complete
Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying :
(a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours.
(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry
note: in case of sunk area more than 100mm, brick bat coba rates will be charged separately
Basement waterproofing
Basement waterproofing:(Treatment below Raft) 1) Clean all dirt, loose material and kept dry. In case of pot holes/cracks, the same shall be repaired with cement putty using Dr. Fixit Pidicrete URP. (Sand cement to be provided free of cost at site)
Providing and laying of 1.5 mm thick self adhesive waterproofing membrane topped with HDPE valeron film, Dr. Fixit Samshield XL1500, The system includes; Base preparation of cleaning, brushing and removal of any loose/flacky materials, in case of pot holes/cracks, the same shall be repaired with polymer modified cement mortarusing Dr. Fixit Pidicrete URP. Priming the surface with cold applied, solvent based bituminous primer Dr. Fixit TorchshieldPrimer, ApplyingDr. Fixit Samshield XL 1500and properly sealing the joints & maintaining 50 mm overlap between the membrane selvedge & 100 mm overlap on the end joints of the membrane over the slab etc.The entire application procedure to be carried out as per manufacturer’s recommendations only.
Providing and laying a protection layer with 120 gsm Geotextile membrane and application as per manufacturer’s Pouring of a 50 mm thick horizontal concrete protection screed over the layer of Geotextile Membrane to complete the application.
Retaining wall
Providing and laying of 1.5 mm thick self adhesive waterproofing membrane topped with HDPE valeron film, Dr. Fixit Samshield XL1500, The system includes base preparation of cleaning, brushing and removal of flacky materials, grouting the porous area with cementitious grout, proper coving between horizontal and wall junctions, priming the surface with cold applied bituminous primer, properly sealing the joints & maintaining 50 mm overlap between the membrane selvedge & 100 mm overlap on the end joints of the membraneover the slab etc.. complete.
Membrane Protection:The laid membrane shall be protected with an protection of 6mm thick expanded polyethylene board or Dimple board of compressive strength not less than 200N/mm2(or as decided by engineer-in-charge). All systems to be installed as per manufacturer's recommendations, etc. complete with all lead and lift for all materials and labour and as directed by Engineer in-charge.
Providing aluminium flashing, wherever required for termination of Dr. Fixit Samshield XL 1500 membrane at all locations . Item shall include rates for membrane termination on the Vertical retaining wall at height as specified in drawings for
FINISHING WORK Providing 12mm thick cement plaster (1:4) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per specification and direction of E/I.
Providing 6mm thick cement plaster (1:4) in ceiling with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per specification and direction of E/I.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
Finishing walls with water proofing cement paint of required shade :
New work (Two or more coats applied @ 3.84 kg/10 SQM) SQM 57.85
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 SQM) over and including priming coat of exterior primer applied @ 2.20kg/10 SQM
Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and m anufacture, including applying additional coats wherever required, to achieve even shade and colour.Two coats
Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour.Two coats
Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour.Two coats
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
ALUMINIUM WORK Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately):For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete.
Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including:
a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:
b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/ structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent biMTR.allic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers.
c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the periMTR.er for holding glass.
d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight.
e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having
all the performance characteristics etc. all omplete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineerin-Charge.
Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this subhead. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in SQM. up to two decimal places.
Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 SQM from the certified laboratories accreditated by NABL (National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories
1. Performance Laboratory Test for Air Leakage Test (-50pa to – 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing MTR.hod for a range of testing limit 1 to 200 mVhr” 2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331- 09 testing MTR.hod for a range up to 2000 ml.” 3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing MTR.hod for a range upto 2000 ml” 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME- 330-10 testing MTR.hod for a range upto 50 mm”
5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing MTR.hod for Qualitative test” Tests to be conducted on site 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000ml”
Providing, assembling and supplying vision glass panels (SGUs) comprising of hermetically-sealed 6mm insulated glass ( glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The SGUs shall be assembled in the factory/ workshop of the glass processor.“(Payment for fixing of SGUS Panels in the curtain glazing is included in cost of item No.25.2)“For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.“
Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineerin- Charge.
Providing and supplying aluminium extruded tubular and other aluminiun sections as per the architectural drawing and approved shop drawings,the aluminiun quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in -Charge .( The item includes cost of material such as cleats ,sleeves,screws etc necessary for fabrication of extruded aluminiun frame work.Nothing extra shall be paid on this account.)
Providing and fixing of Glass Fiber Reinforced Concrete (GFRC) Screen with borders 50mm thick and inner portion 35mm thick in approved size, pattern, Design, thickness and color. The Screen should be made From 53 grade white Portland cement/ 43 grade OPC or PPC gray cement manufactured by J.K. Cement or equivalent having minimum compressive Strength of 40N/mSQM, Quartz, Fine Silica Sand, Alkali Resistant Glass Fiber manufactured by Sant Gobain,Owens corning or equivalent, super plasticizers and polymers manufactured by BASF, Sika, MYK Schomburg or equivalent. The material casting should take place in Synthetic Rubber / FRP Mould manufactured by Reckli or equivalent. The Fixing of Column should be Dry Fixing i.e. to be done with Stainless Steel (SS-304)/ MS Frames, dash fasteners, Self-screw and pins. Approved Make- Dalal Tiles or Equivalent.
Providing and fixing of Glass Fiber Reinforced Concrete (GFRC) Column in approved size, pattern, Design, thickness and color The Column should be made From 53 grade white Portland cement/ 43 grade OPC or PPC gray cement manufactured by J.K. Cement or equivalent having minimum compressive Strength of 40N/mSQM, Quartz, Fine Silica Sand, Alkali Resistant Glass Fiber manufactured by Sant Gobain, Owens corning or equivalent, super plasticizers and polymers manufactured by BASF, Sika, MYK Schomburg or equivalent. The material casting should take place in Synthetic Rubber / FRP Mould manufactured by Reckli or equivalent. The Fixing of Column should be Dry Fixing i.e. to be done with Stainless Steel (SS-304)/ MS Frames, dash fasteners, Self-screw and pins.
Note :- MS frame Structure for GFRC column to be provided as per design Note:- Rate to be paid after approval of drawings/design & quotations
LIFT WORK
Passenger Lifts 13 Passenger 884 kgs Basement+5, Power operated, ACVVVF, 1.5 speed M/Sec. of approved design and make
Passenger Lifts 13 Passenger 884 kgs basement +6, Power operated, ACVVVF, 1.5 speed M/Sec. of approved design and make
FALSE CEILING & PARTITIONS
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/SQM (both side inclusive) as per IS: 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm Each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction,
including fixing periMTR.er channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the periMTR.er of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and periMTR.er channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of periMTR.er channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with: 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- Part I
Providing and fixing GI Clip in MTR.al Ceiling System of 600x600 mm module which includes providing and fixing 'C' wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the periMTR.er of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of GI steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used.
GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation.
Providing & Fixing laminated wooden false ceiling , made in 50x50mm Hard wood frame (Mirandi) centre to centre 600mm both ways, hang to ceiling with help of hanger support 'L' type G.I angle (25x25mm) and anchor bolt etc. over fixed 11mm thick MDF board with 10x8mm deep groove finish with lacquer polish, 1.0 mm thick approved shade laminate to fixed on MDF board, defects free bubbles free with help of adhesive. as per drawing and to the entire satisfaction of Engineer in charge. ( MDF Board & Laminate Make Green ply/Century /Merino or Equivalent ,Adhesive make Pidilite or equivalent)
Providing and fixing 75mm thick wooden laminated full hight partition upto false celling made in mirandi hard wood frame 50x50mm c/c 600mm (maximum) horizontally /vertically fixed over 12mm thk. commercial Ply from both sides and fixed with 1mm thick laminate having 1.0mm groove using adhesive along with necessary hardware including provision of electrical conduting wiring/ cutting for electrical switches, wherever required all complete as per technical specification, defects free/ bubbles free etc. as per drawing & instruction of Engineer in charge (Make:- com. ply & Laminate Green ply/ Century/Merino OR Equivalent) ) (adhesive make Pidilite or equivalent)
Toughened glass 12 mm thickness
Providing and Fixing MDF Wall Panneling made in hard wood frame (mirandi) 35mm x 50mm thick c/c 600mm horizontally & vertically, fixed to wall/columns with wooden plugs,then 11 mm thick Medium Density Fiber Board fixed on top of frame with 10x8 mm deep Groove & same finished with 1.0 mm thick laminate of approved quality pasted with the help of adhesive & nails screws etc. All grooves to be finished with lacquer polish maching with laminate shade as per Technical specification, drawing and instructions of Engineer in charge. (MDF Board & Laminate Make Green ply/Century /Merino or Equivalent, Adhesive make Pidilite or equivalent,
SH EXPANSION JOINT
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical locations in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions.
The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge. (Material shall conform to ASTM 6063).Floor Joint of 100 mm gap
Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall conform to ASTM 6063.)Wall Joint of 100 mm gap
Providing and fixing of expansion joint system of approved make and manufacture for various roof locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded aluminum base members with, self aligning and self centering arragement support plates as per ASTM B221-02. The system shall be such that it provides water tight roof to roof /roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminum base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions.
The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063.)Roof Joint of 100 mm gap
CARRAIGE OF MATERIALS CEMENTS (UPTO 3KM LEAD)
SAND (UPTO 35KM LEAD) BARAKAR RIVER
CHIPS (UPTO 17KM LEAD)
STEEL (UPTO 3KM LEAD)
BRICKS (UPTO 8KM LEAD)
HORTICULTURE (A)
Supplying and stacking of good earth at site including royalty and carriage up to 1 km (earth measured in stacks will be reduced by 20% for payment).
Supplying and stacking at site dump manure from approved source, including carriage up to 1.0 km (manure measured in stacks will be reduced by 8% for payment)
Screened through sieve of IS designation 20 mm
Screened through sieve of IS designation 16 mm
Screened through sieve of IS designation 4.75 mm
Supplying and stacking of well decayed cattle manure at site including royalty and carriage up to 5.0 km (cattle manure measured in stacks will reduced by 8% for Payment)
PREPARATION WORKS Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly levelling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or / and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure)
Rough dressing the trenched ground including breaking clods
Uprooting weeds from the trenched area after 10 to 15 days of its flooding with water including disposal of uprooted vegetation
Fine dressing of the ground
Mixing earth and sludge or manure in the required proportion specified or directed by the Engineer-in-charge
Spreading of sludge, dump manure and / or good earth in required thickness as per direction of Engineer-in-charge (cost of sludge, dump manure and / or good earth to be paid separately).
Uprooting rank vegetation and weeds by digging the area to a depth of 60 cm, removing all weeds and other growth with roots by forking repeatedly, breaking clods, rough dressing, flooding with water, uprooting fresh growths after 10 to 15 days and then fine dressing for planting new grass, including disposal of all rubbish with all leads and lifts
Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% : one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, levelling etc including stacking and disposal of materials declared unserviceable and surplus earth by spreading and levelling as directed, within a lead of 50.0 m, lift up to 1.50 m complete (cost of sludge, manure or extra earth to be paid for separately)
Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately)
Holes 60 cm diameter and 60 cm deep
PLANTING WORKS
In rows 5 cm apart in both directions
MAINTENANCE WORKS
Renovating lawns including weeding, cheeling the grass, forking the ground, top dressing with sludge or manure, mixing the same with forked soil, watering and maintaining the lawn for 30 days or more till the grass forms a thick lawn free from weeds and fit for mowing and disposal of rubbish as directed, including supplying good earth if needed but excluding the cost of sludge or manure (the good earth shall be paid for separately)
SHRUBS FICUS BENJAMINA
MURRAYA
CALLIANDRA HAEMATOCEPHALA
FRANCISCEA LATIFOLIA
CAMELLIA
ACALYPHA
CHINESE HAMELIA
BOUGAINVILLEA
PULMERIA ALBA
ROYSTONEA REGIA
ROAD Excavation in soil using Hydraulic Excavator CK 90 and Tippers with disposal up to 1000 meters. (excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including setting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the embankment location within al lifts and lead up to 1000m) including Royalty @ Rs. 24.00 per cum, cost of watering, rolling & compaction.
Granular sub-base with coarse graded material (Table 400-2) (construction of granular sub base by providing coarse graded material, spreading in uniform layers with motor graded in prepared surface, mixing by mix in place method with rotator ta OMC and compacting with vibratory roller to achieve the desired density, complete as per clause 401)
wet mix macadam ( providing laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the material with water at OMC in mechanical mix plant carriage of mixed material by tipper to site, laying in uniform layers with paver in sub - base / base course on well prepared surface and compacting with vibratory roller to achieve desired density. With Vibratory Roller
Prime coat ( providing and applying primer coat with bitumen emulsion on prepared surface of granular base including clearing of road surface and spraying primer at the rate of 0.60kg/sqm using mechanical means.
Providing and applying teck coat with bitumen emulsion using emulsion pressure distributor at the rate of 0.20kg per sqm on the prepared bituminous / granular surface cleaned with mechanical broom. (i) on granular surface treated with primer
(ii) on bituminous surface.
Dense Graded bituminous macadam ( providing and laying dense bituminous macadam with 100 - 120 TPH batch type HMP producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder @ 4.0 to 4.5% by weight of total mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and aligment, rolling with smooth wheeled, vibratory and tandem rollers to achive the desired compaction as per MoRTH specification clause no. 507 complete in all respects. with modifed graded bitumen.For Grading II ( 19MM nominal size )
Semi-Dense bituminous concrete ( providing and laying dSemi-Dense bituminous concrete with 100 - 120 TPH batch type HMP producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder @ 4.0 to 4.5% of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and aligment, rolling with smooth wheeled, vibratory and tandem rollers to achive the desired compaction as per MoRTH specification clause no. 508 complete in all respects. For Grading I ( 13 MM NOMINAL SIZE)
Cast in Situ Cement Concrete M20 kerb (Construction of cement concrete kerb with top and bottom width 115 and 165 mm respectively, 250 mm high in M 20 grade PCC on M-10 grade foundation 150 mm thick, foundation having 50 mm projection beyond kerb stone, kerb stone laid with kerb laying machine, foundation concrete laid manually, all complete as per clause 408 Using Concrete Mixer
Retro- reflection traffic signs ( providing and fixing of retro- reflectorised cautionary, mandatory and informatory sig as per IRC" 67 made of high intensity grade sheeting vide clause 801.3, fixed over aluminium sheeting , 1.5mm thick supported on mild steel angle iron post 75 mm x 75mm x 6mm firmly fixed to the ground by means of properly designed foundation with m15 grade cement concrete 45cm x 45cm 60cm, 60cm below ground level as per approved drawing.( i) 90cm eguilteral traingle
PCC WORK Providing P.C.C. M - 75 with nominal mix of (1:4:8) in foundation with approved quality of stone metal grade III (50 mm to 25 mm size) clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing, taxes and royalty all complete as per building specification and direction of E/l.
oviding designation 75 B one brick flat soling joints filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/l.
BRICK WORK Providing designation 75 B brick work in C.M. (1:6) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/l.
STEEL WORK Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Carriage of material CEMENTS (UPTO 3KM LEAD)
SAND (UPTO 35KM LEAD)
CHIPS (UPTO 17KM LEAD)
METAL (UPTO 23KM LEAD)
BRICKS (UPTO 8KM LEAD)
BOUNDARY WALL Earth Work in excavation in Foundation Trenches in Ordinary soil (vide classification of soil item -B) and disposal of excavated earth as obtained to a distance upto 50 M including all lift, leveling ramming the foundation trenches, removing roots of tree shrubs all complete as per approved design, building specification and direction of E/I
Earth filling in foundation trenches and plinth in layer not exceeding 150mm thick will watered rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenched with a lead of 50mm and lift of 1.5M all complete as per building specification and direction of E/I. (Mode of measurement compacted volume).
Removal & disposal of surplus excavated earth by mechanical transport including loading unloading stacking and spreading at all lift and lead up to 13km to spoil dump approved by local authority.
CONCRETE WORK Providing P.C.C. M-75with nominal mix of (1:4:8) in foundation with approved quality of stone MTR.al grade - III (50 mm to 25mm size) clean coarse sand of F.M 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position vibrating, skirting, curing, taxes and royalty all complete all complete as per building specification and direction of Engineer-in-charge.
R C C WORK Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately).
All works upto plinth level
All works above plinth level upto floor V level
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers
Centering and shuttering including strutting, propping etc. and removal of form for :Columns, Pillars, Piers, Abutments, Posts and Struts
Providing TMT steel reinforcement as per approved design & drawing.
Brick Work Providing Designation 100A B/W with Fly Ash Lime Brick (FALB) conforming to IS 12894-1990 (9"x4.5"x3") in cement mortar (1:6) in Superstructure with clean coarse sand of F.M. 2 to 2.5 including 10mm thick mortar joints,cost of screening, raking out joints to 15 mm depth, curing, taxes and royalty all complete as per building specification and direction of E/l.
STEEL WORK Supplying, fitting and fixing M.S. grill gate with M.S. grills made of 20x6mm M.S. flats or 16mm square bars fitted on 25x25x6mm M.S Angle frame including cost of fabrication , providing necessary locking arrangement with haskal and domny duly fixed in P.C.C. (1:2:4) blocks of required size, applying a priming red lead paint over steel work, taxes all complete as per drawing specification and direction of E/l.
FINISHING WORK Providing 12mm cement plaster (1:6) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/l.
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 SQM) over and including priming coat of exterior primer applied @ 2.20kg/10 SQM
Providing two coats of synthetic enamel paint of approved shade and make over steel surface including cleaning the surface thoroughly, scaffolding and taxes all complete as per building specification and direciton of E/l.
Carriage of material CEMENTS (UPTO 3KM LEAD)
SAND (UPTO 35KM LEAD)
CHIPS (UPTO 17KM LEAD)
STEEL (UPTO 3KM LEAD)
BRICKS (UPTO 8KM LEAD)
PLUMBING/SANITARY WORKS Providing and fixing male ended 15 mm dia brass bib cock of approved quality ( wt not less than 350 gms ) with extra socket all complete as per specification and direction of E/l .
Providing and fixing 15 mm dia male ended C.I .Body brass spindle valve and seat bib cock of approved quality (wt not less than 400 gms ) with extra socket all complete as per specification and direction of E/l .
Providing and fixing 15 mm dia male ended C.I push cock (wt not less than 400 gms ) of approved quality with extra socket all complete as per specification and direction of E/l .
Providing and fixing brass / C.I. Stop cock of approved quality all complete as per specification and direction of E/l . A) BRASS STOP COCK (a) 15 mm dia
(b) 20 mm dia
Providing and fixing 15 mm dia and 45 cm. long P. V .C connection pipe with heavy quality brass coupling at both ends etc. all complete as per specification and direction of E/l .
Providing and fixing 15mm size C.P brass pillar cock (Weight not less than 350 gms) C.I body brass spindle pillar cock of approved quality as per spcification and direction of E/l. (b) C.I. body brass spindle
Providing and fixing Gun metal full way valve of approved qualtiy, all complete as per specification and direction of E/l (a) 15 mm dia wt not less than 300 gms
(a) 20mm dia wt not less than 400 gms
(a) 25 mm dia wt not less than 500 gms
(a) 32 mm dia wt not less than 700 gms
(a) 40 mm dia wt not less than 1kg
(a) 50 mm dia wt not less than 1.5 kg
Cutting drain width wise above G.L for laying G.I pipes and restoring with brick in cement mortar (1:4) 12mm cement plaster in (1:4) with neat cement punning as per specification and direction of E/l
Cutting chajja or cornice for laying G.I pipe and restoring the same with R.C.C (1:2:4) brick work in cement mortar (1:4) and cement plaster (1:4) as per specification and direction of E/l.
Supplying, fitting and fixing the following items complete with all materials as per specification and direction of E/l. (a) Glass shelf with C.P brass rail
(b) Mirrors of 4 mm thick plate glass bevelled edge mirror including C.P brass revolving fittings, 3 mm plywood board and C P hinges to fix with mirror (1)600x450 mm
( c) C.P brass towel rail 20 mm x 600 mm with bracket container
(2) C.P brass shop dish container medium quality with screw and hinges etc.
(3) C.P brass liquid shop container
Supplying, fitting and fixing 40 mm high viterous white glazed earthen ware E.W.C. with "p" trap of Parry Hindustan or any other I.S.S. make including supplying & fixing 15 litres C.I. mosquito proof low down flushing cistern of approved make with complete fittings with C.I. handle and R.S. or bracket with telescopic flush pipe with brass coupling and plumbers joints spindle stop cock of approved quality weight not less than 450 grms. , 15 mm P.V.C. alkathene pipe 45 cm long with brass coupling at both ends and white/ black plastic solid state seal and lead of commander/ cuckoo or other I.S.S. make with hinges or screw etc. painting pipe and cistern etc. with 2 coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of E/l.(b)12.5 lit. low level P.V.C. cistern
Supplying, fitting and fixing white glazed fire clay sink of approved make with overflow arrangements supported on C.l. or R.S. painted brackets 40 mm dia C.P. brass waste with C.P. brass chain and rubber plug, 40 mm dia P.V.C. waste pipe about 750mm long with brass coupling at one end and 15 mm C.I. body brass spindle bib cock of approved quality of weight not less than 450 grms. including cutting wall and making good the same etc. all complete as per specification and direction of E/l.(b) Kitchen sink of size 600 mm x 450 mm x 250 mm
Supplying fitting and fixing H.C.I, pipes with ear of approved make confirming to I.S.I. 1729 including supplying nails and bobins short pieces, cutting loose collars, lead and yarn for making lead chaulked joints, cutting pipes to size including earth work or scaffolding where neccessary etc. all complete as per specification and direction of E/l. (a) 100 mm dia
(b) 75 mm dia
(c) 50 mm dia
Supplying and fixing H.C.I, fittings of approved make confirming to I.S.S. 1729 including supplying nails and bobins lead and yarn for making lead chaulked joints including earth work or providing scaffolding as the case may be all complete as per specification and direction of E/l. (A) H.C.I, single junction with door but without ear except socket (i) 100mmdia(Wt. 10.5 Kg. app.)
(ii) 80 mm dia (Wt. 7 Kg. )
(B) H.C.I. Heal Rest Bend (i) 100 mm dia (Wt. 5.5 Kg. app.)
(ii) 80 mm dia (Wt. 4 Kg. app.)
(iii) 50mm dia (Wt. 3.5 Kn. app.)
(C) 100mm dia H.C.I."P" TRAP with Anti syphonage Horn (Wt. 8.5 Kg. app.)
(D) H.C.I, double junction with door and ear
(i) 100 mm dia (Wt. 15.5 Kg. app.)
(ii) 80 mm dia (Wt. 15.5 Kg. app.)
(iii) 50 mm dia (Wt. 6 Kg. app.)
(E) H.C.I, double inverted Jn.
(100 mm x 50 mm x 50 mm size)
(F) H.C.I, offset with ear
(i) 100 mm dia (Wt. 6 Kg. app.)
(ii) 80 mm dia (Wt. 4 Kg. app. )
(iii) 50 mm dia (Wt. 3.26 Kg. app.)
(G) H.C.I, bend with door and ear
(i) 100 mm dia (Wt. 6.5 Kg. app.)
(ii) 80 mm dia (Wt. 4.5 Kg. app.)
(iii) 50 mm dia (Wt. 4 Kg. app.)
(H) H.C.I plain bend with ear
(i) 100mm dia (Wt. 5.5 Kg. app.)
(ii) 80 mm dia (Wt. 3.75 Kg. app.)
(iii) 50 mm dia (Wt. 3.25 Kg. app.)
(I) Floor trap with gratings
(i) 100 mm dia
(J) Norton patent H.C.I, cowl
(i) 100 mm dia (Wt. 3.25 Kg. app.)
(ii) 80 mm dia (Wt. 2.25 Kg. app.)
(iii) 50 mm dia (Wt. 1 Kg. app.)
ID H.C.I. pass over
(i) 100 mm dia
(iii) 50 mm dia
(M) H.C.I, sinqle inverted junction with ear
(100 mm x50 mm)
Making holes in wall for laying H.C.I, pipe and restoring the same after pipe laying as per specification and direction of E/l.
(i) 125 mm dia
(ii) 250 mm dia
(iii) 375 mm dia
(iv) 500 mm dia
(v) R.C.C. chajja
Supplying materials and labours for painting the exposed H.C.I, pipes and fittings with 2 coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of E/l.
(i) 50 mm dia
(ii) 80 mm dia
(iii) 100 mm dia
Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes confirming to IS : 13592 Type A including jointing with seal ring confirming to IS : 5382 leaving 10mm gap for thermal expansion.
110mm dia
Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised - Rigid PVC rain water pipes confirming to IS : 13592 Type A including jointing with seal ring confirming to IS : 5382 leaving 10mm gap for thermal expansion.
Coupler 110 mm dia
Single Tee with door
Bend 87.5 deg 110 mm
Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised - Rigid PVC rain water pipes confirming to IS : 13592 Type A including jointing with seal ring confirming to IS : 5382 leaving 10mm gap for thermal expansion.
PVC Shoe
Providing and fixing unplasticised- PVC pipe clip of approved desing to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwes with M.S. Screw of required length including cutting brick work and fixing in cement mortar 1:4 ( 1 Cement : 4 Coarse sand ) and making good the wall etc. complete.
110mm dia
Providing and fixing white vitreous china battery based infrared sensor operated urinal of appx.size 610x390x370mm having pre & post flushing with water (250ml & 500ml consumption) having water inlet from back side,including fixing to wall with suitable brackets all as per manufacturers specification & direction of Engineer-in charge.
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end):
65 mm nominal bore
Providing and fixing C.P. bass angle valve for basin mixer and geyser points of approved quality conforming to I.S:8931.
15 mm nominal bore
Supplying pig lead at site of work
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15cm diameter and weighting not less than 440 grams.
Providing and placing on terrace (at all floor levels) storage tank ISI : 12701 marked indicating the BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank [Sintex, Electroplast, Star, Lotus or equivalent having valid ISI license].
Excavating trenches of required width for pipe, cables etc including excavation for sockets ,& dressing of sides ,ramming of bottoms ,depth upto 1.5m including getting out the excavated soil,& then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming ,watering, etc and disposing of surplus excavated soil as directed, within lead of 50m.
Pipes 80 mm to 300 mm diameter
Pipes 80 mm to 300 mm diameter
Providing and laying Non pressure NP 2 class (light duty) RCC pipe with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1cement : 2 fine sand) including testing of joints etc. complete.
150 mm. dia. RCC Pipes
250 mm. dia. RCC Pipes
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) alround SW pipes including bed concrete as per standard design.
150 mm. dia. RCC Pipes
250 mm. dia. RCC Pipes
Construction brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand) RCC top slab with 1:2:4 mix (1 cement : 2 coarse sand 4 graded stone aggregate 20mm nominal size) foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design.Inside size 90 x 80 cm and 45 cm deep including CI cover with frame(medium duty) 500mm internal diameter, total weight of cover and frame to be not less than116 kg (weight of cover 58 kg and weight of frame 58 kg).-With FPS bricks of class designation 75.
Inside size 120 X 90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg).With FPS bricks of class designation 75
Size 90x80cm with FPS bricks of class designation 75
Size 120x90cm with FPS bricks of class designation 75
Providing M.S. foot rests including fixing in manholes with 20*20*10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size) as per standard design : with 20 x 20 mm square bar.
Providing and fixing square mouth SW gully trap class SP-1 complete CI grating brick masonry chamber and water tight CI cover with frame of 300 x 300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.7 kg. as per standard design.100x100mm size P type
With common burnt clay F.P.S (non modular) bricks of class designation 7.5.180x150mm size P type
With common burnt clay F.P.S (non modular) bricks of class designation 7.5.
Providing and fixing wash basin with CI brackets,15mm brass pillar taps,32mm CP brass waste of standard pattern, including painting of fittings and brackets,cutting and making good the walls wherever required.
White vitreous china wash basin size 630 mm x 450 mm with a single 15mm CP brass pillar tap.
Constructing brick masonry road gully chamber 50 X 45 X 60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500 X 450 mm precast R.C.C. horizontal grating with frame complete as per standard design :
With common burnt clay F.P.S (non modular) bricks of class designation 7.5.
Boring/drilling bore well of required dia for casing / strainer pipe, by suitable method prescribed in IS:2800 (part-1) including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of engineer-in-charge, upto 90 metre depth below ground level. 300mm dia
Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS : 12818, including hire & labour charges, fittings & accessories etc, all complete, for all depths, as per direction of engineer-in-charge.100mm nominal size dia
Supplying & filling, sepreading & leveling stone boulders of size range 5cm to 20cm, in the recharge pit, in the required thickness, for all leads & lifts, all complete, for all depths, as per direction of engineer-in-charge.
Supplying & filling, sepreading & leveling gravels of size range 5mm to 10mm, in the recharge pit, over the existing layer of boulders, in the required thickness, for all leads & lifts, all complete, as per direction of engineer-in-charge.
Supplying & filling, sepreading & leveling coarse sand of size range 1.5mm to 20mm, in the recharge pit, in the required thickness over gravel layer, for all leads & lifts, all complete, as per direction of engineer-in-charge.
Providing and fixing Bail plug / Bottom plub of required dia to the bottom of pipe assembly of tubewell as per IS : 2800 (part -1) 100mm dia
Providing and fixing in position pre-cast RCC manhole cover and frame of required shape & approved quality Circular shape 560 mm internal diameter-EHD-35
Providing & fixing in position storage type hot water electrical geyser (vertical or horizontal-1.5 kw) including making connection in all respects.-Venus/Racold make.Cap-25 lts
Supply installation testing and commissioning R.O.water purifier comprising 5 micron filter and UV steriliser on cold water supply to work on single phase 230 volts 50 HZ AC power supply with capacity 120 lph.-Kent/approved equal make.
Providing & fixing Sink Mixer with Swinging Casted Spout (Wall Mounted Jaquar model CON-319 KNB/approved equal) with 450mm long copper pipes & brass nuts.
Providing & fixing Hand Shower (Health Faucet) with 8mm dia, 1M long PVC tube and wall hook. (Jaquar model no. ALD-573 L 1500).
Constructing Oil & Grease Chamber size 2100x 1000mm internal size of 1000mm depth with first class brick work in cement mortar (1:5) Inside 12mm thick with cement mortar 1:3 with floating coat of neat cement and rough plaster on outside, RCC top slab with 500mm dia medium duty manhole cover with frame (weight of cover 58 kg. & weight of frame 58 kg.),200X200mm SS plate with perforations &4mm dia lifting rod,150mm thick foundation concrete (1 :4 : 8), necessary excavation, dewatering, refilling, watering, ramming and removing the surplus excavated material and making good the same complete as required.
Supply & erection of ISI marked portable fire extinguishers, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions of Engineer-in-charge.
(MAKE : Minimax / Cease Fire / Safex / Padmini / Newage)
Water CO2 gas nozzle type. 9 Lt.capacity (IS:15683)
Mechanical Foam gas cartridge type. 9 LIT. capacity (IS:15683)
ABC dry powder stored pressure type 6 kg. capacity (IS:15683)
Supply, erection and testing of ISI marked M.S. pipes (Class C - heavy duty) and specials etc. (as per IS:1239) for above ground laying for hydrants and sprinkler system including transportation of materials upto the worksite, cutting the pipes to required length, edge preperation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges, expansion joints wherever required, washers, nuts, bolts etc. in proper position including all supports. jointing by welding, aligning the pipe line, painting with two primer coat by zinc chromate primer and two coats of synthetic enamel fire red colour, providing tapping for pressure gauges and for other instruments etc. Hydrostatic testing of system as specified, flushing & cleaning by water etc. complete as per drawings & direction of the Engineer-in-charge.
The pipes and accessories will be provided with all type of supports (Maximum Support spacing = up to 25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m, 150 mm & above dia @ 3 m) by minimum 3 mm thick G.I. clevis / sprinkler hangers / clamps / Tie rod supports with G.I. nuts, bolts, anchor / dash fastner and washer for hydrant / sprinkler piping, for 100 & 150 mm dia pipe the support will be through 50x50x6 mm painted / pre galvanized MS angle iron along with G.I. U clamp, nuts, washers, anchor fasteners etc as the case may be.
upto 50mm dia. pipe threaded fittings and threaded joints shall be provided and for 65mm dia & above pipes welded joints shall be used. The G.I. / MS fittings shalll be suitable for test pressure of 25 kg/sq cm.
(Pipe make : Jindal (Hissar) / Bharat / Prakash Surya)
(Fitting make : VS / KS)
25 mm dia ( IS 1239, 4.05mm thick)
32 mm dia ( IS 1239, 4.05mm thick)
40 mm dia ( IS 1239,4.05mm thick)
50 mm dia ( IS 1239, 4.47mm thick)
65 mm dia ( IS 1239, 4.47mm thick)
80 NB (IS: 1239, 4.8 mm thick)
100 NB (IS: 1239, 5.4 mm thick)
150 NB (IS: 1239, 5.4 mm thick)
200 NB (IS: 1239, 6.0 mm thick)
Supply & installation of ISI marked single headed 63 mm dia. Stainless steel Hydrant Valve, 80 mm dia flanged inlet with 63 mm female instantaneous outlet confirming to IS : 5290 on the fire wet riser/down comer, including making 80 NB pipe connection with riser, fixing the landing valves in proper positions, including supply of nuts, bolts, gaskets, caps, chains etc. testing the hydrant and completing the work in all respect as per directions of the Engineer-in-charge. (MAKE : Newage / Safeguard / Padmini )
Supply & fixing in position ISI marked cast iron double flanged butterfly valves (PN 1.6 MPa) as per IS:13095, with SS disc, shaft, seating rings, nitrile rubber lining, internal fastening, nuts, bolts including transporting to worksite, 3 mm thick rubber gaskets etc. including testing, Complete as per drawings & directions of the Engineer-in-charge.
(MAKE : Kirlosker / IVC / Zoloto / Venus / Audco / Advance)
50 mm dia
65 mm dia
200 mm dia(gear operated)
Supply, fixing, testing & commissioning of 20 mm bore and 30 meter long hose (high pressure rubber braided hose pipe as per IS:444) and hose reel suitable for 10 kg/sqcm operating pressure for first aid fire fighting conforming to IS : 884, with 180o full swing drum, fixing brackets, 5 mm dia shut off Stainless steel nozzle, connecting directly from the riser through 40 mm dia. MS (Class C) pipe with sockets, elbows, nipples, 40x20 mm reducer, 20 dia pipe, 20 mm dia. hand lever operated isolating ball valve, etc. including providing operating instructions on a metal plate and fixing it near hose reel. The system shall be complete in all respects as per drawings and directions of Engineer-in-charge. (MAKE : Newage / Safeguard / Padmini).
Providing Stainless steel ISI marked 63 mm. dia. male Instantaneous pattern short branch pipes with 20 mm dia. Nozzle as per IS : 903, suitable for 10 kg/sqcm operating pressure and suitable for interconnections to hose pipe coupling as required. (MAKE : Newage / Safeguard / Padmini).
Providing ISI marked RRL (IS : 636, type-A) fire hose pipe 15 meter long and 63 mm dia with ISI marked (IS : 903) Stainless steel male and female coupling bound and rivetted to hose pipes with copper rivets and copper wire complete as required. (MAKE:Jayshree / Newage / Padmini)
Providing & fixing standard carbon steel fireman axe with rubber insulated handle tested to 20000 Volts.
Providing and fixing weather proof standard fire hose cabinet (900 mm x 1800 mm x 600 mm) outdoor type made of not less than 14 SWG MS sheet having glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing hydrant valve, two nos.15 meter long fire hose pipes, branch pipe as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted on self standing mounted type painted MS Angle iron frame as required. The words "FIRE HOSE" to be painted on the box.
Providing and fixing signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+ -10%) containing lumigen II as base chemical, covered under UV stablized coating and of appropriate size (Glo-lite or eq. Make) including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats anchor fasteners etc. complete in all respacts as diercted by Engineer-in-charge
Providing and fixing inlet breaching having C.I. body four way gun metal 63 mm dia instantaneous inlets conforming to IS 903 fitted with non return valves, 25 mm dia gun metal drain cock, blank cap, brass chains and 100 mm dia flanges with all accessories suitable for local fire tender complete as required.
Providing & fixing C.P.brass quartzoid bulb sprinklers of size 15mm dia to be operated at 68Deg.C complete.
Pendent type
Upright type
Sidewall type
Providing, fixing, testing & commissioning of MS air vessel fabricated from 8mm thick MS plate, 450 mm in diameter and 1.8 m in height with dished ends fabricated from 10mm thick MS plate,2coats of synthetic enamel paint over a coat of primer with Air release valve with stop cock, flanged inlet connection and drain arrangement with 50mm dia valve, pressure guage with gun metal stop cock complete with all accessories as required.
Providing & Fixing of installation control valve with turbine type automatic Alarm Gong to be connected with control valve, drain & test valve all flanged connections as per manufacturer's specifications complete.a) 150 mm dia
Providing, jointing and testing of sprinklers through flexible connections(internal diameter 25mm & outlet connection15mm dia.) as per requirement at site.Make-SeungJin-Korea.The flexible connectors shall be supported through false ceiling through clamps or as directed at site.The flexible connector shall be suitable for working pressure 20 kg/sqcm .
a) 1000 mm long
b) 1500 mm long
Providing, laying, jointing and testing in trenches the following sizes of M.S. class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, G.I. nuts, bolts and washers and providing 150mm thick fine sand layer all around the pipe, including excavation in all kind of soil, refilling, ramming and removing the excavated surplus material and making good the same complete as required. 'Providing protection to embedded M.S pipes and fittings by wrapping 4mm thick pypkote protection including proper overlaps on joints.
a) 80 mm dia ( 4.85mm thickness)
b) 100 mm dia ( 5.40mm thickness)
c) 150 mm dia ( 5.40mm thickness)
Providing and fixing of G.M. Fire Brigade adopter assembly with 150 mm dia outlet, suitable for local fire tender complete as required.
Providing and fixing weather proof cabinet of size not less than 0.9 x 0.6 x 0.5 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and 4 mm thick glazed glass doors (Two nos.) suitably marked on the outside 'with the letters "FIRE HOSE" including necessary locking arrangement and painting in red colour suitable to accomodate, external yard hydrant valve, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle and fire man's axe. It shall be mounted on boundary wall complete as required.
Providing & fixing cast iron foot valve complete with flange.-150mm dia.
Supply, Fixing, Testing & Commissioning of fire authority approved electrical motor driven fire pump, suitable for automatic operation consisting of following : (Main Pump for hydrant system) (MAKE : Kirloskar / Mather + Platt)
(a) Horizontally mounted, multi stage, split casing Centrifugal fire pump with operating speed not exceeding 1500 rpm, as per IS:1520 complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 35 meter at the highest and farthest outlet at the specified flow complete with necessary strainers, 100 mm dia dial pressure gauge of calibration 0-15 kg/sq cm including bypass arrangement for periodic testing of the working of the pumpset as well as testing of automation with required length and size of MS pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately balanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel.
(b) Squirrel cage, TEFC induction motor as per IS : 325, suitable for 415 V +/- 10%, 3 Phase, synchronous speed 1500 rpm, IP 55 protection and class 'F' insulation, vaccume impregnated windings with heat and moisture resisting varnish for the above pump and flexible coupling with the pump. The motor shall be rated for continuous duty and shall have HP rating necessary to drive the pump at 150% of it's rated discharge at 65% of rated head.
(c) Common bed plate of fabricated mild steel channel or cast iron type, coupling, coupling guard ets as required.
(d) Suitable cement concrete pump foundation and vibration clamping arrangement as required. with foundation bolts, anti vibration pads, washers etc.
(e) Pressure switch for automatic operation of motor including necessary wiring upto control panel.
Discharge : 2280 liter per minute
Head : 88 meter
(Make : Mather & Platt or Kirloskar)
Supply, Fixing, Testing & Commissioning of fire authority approved Diesel Engine driven Fire Pump, suitable for automatic operation consisting of following : (Standby pump). (Make : Kirloskar / Mather+Platt with Kirlosker / Cummins engine)
(a) Horizontally mounted, multi stage, split casing Centrifugal fire pump with operating speed not exceeding 1500 rpm, as per IS:1520 complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 35 meter at the highest and farthest outlet at the specified flow complete with necessary strainers, 100 mm dia dial pressure gauge of calibration 0-15 kg/sq cm including bypass arrangement for periodic testing of the working of the pumpset as well as testing of automation with required length and size of MS pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately balanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel.
(c) Diesel engine Exhaust system of required length of Class `B' MS pipe of suitable diameter with bends, expansion joints including providing suitable supporting arrangements at suitable intervals, with glass wool insulation 50 mm thick on all sides of exhaust pipe and silencer, with chicken mesh wrapping and 1 mm thick aluminium sheet cladding complete as required.
(d) Supply, installation, testing and commissioning of AMF autostart complete with necessary relays like no volt relay, over voltage and low voltage relays, contactors, timer, pressure switch etc. as required for the auto start of the diesel engine in case of power failure complete with all accessories, wiring & cabling including connection to diesel engine complete as required all in conformity with the local Fire regulations. The diesel engine driven fire pump will start automatically in the event of pressure drop beyond preset limit or on mains failure or failure of electric driven pumps to start.
(e) Common bed plate of fabricated mild steel channel or cast iron type, coupling, coupling guard ets as required.
(f) Suitable cement concrete pump foundation and vibration clamping arrangement as required. with foundation bolts, anti vibration pads, washers etc.
(g) Pressure switch for automatic operation of motor including necessary wiring upto control panel.
Discharge : 2280 liter per minute
Head : 88 meter
(Make : Mather & Platt or kirlosker)
Supply, Fixing, Testing & Commissioning of fire authority approved electrical motor driven fire pump, suitable for automatic operation consisting of following : (JOCKEY PUMP). (MAKE : Kirloskar/Mather + Platt)
(a) Horizontally mounted, end suction type, Centrifugal fire pump with operating speed of 2900 rpm, as per IS:1520 complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 35 meter at the highest and farthest outlet at the specified flow complete with necessary strainers , 100 mm dia dial pressure gauge of calibration 0-15 kg/sq cm including bypass arrangement for periodic testing of the working of the pumpset as well as testing of automation with required length and size of MS pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately balanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel.
(b) Squirrel cage, TEFC induction motor as per IS : 325, suitable for 415 V +/- 10%, 3 Phase, synchronous speed 2900 rpm, IP 55 protection and class 'F' insulation, vaccume impregnated windings with heat and moisture resisting varnish for the above pump and flexible coupling with the pump. The motor shall be rated for continuous duty and shall have HP rating necessary to drive the pump at 150% of it's rated discharge at 65% of rated head.
(c) Common bed plate of fabricated mild steel channel or cast iron type, coupling, coupling guard ets as required.
(d) Suitable cement concrete pump foundation and vibration clamping arrangement as required. with foundation bolts, anti vibration pads, washers etc.
(e) Pressure switchs (for both upper and lower levels) for automatic operation of motor including necessary wiring upto control panel.
Discharge : 180 liter per minute
Head : 88 meter
Supply, Fixing, Testing & Commissioning of fire authority approved electrical motor driven fire pump, suitable for automatic operation consisting of following : (CURTAIN SPRINKLER PUMP). (MAKE : Kirloskar/Mather + Platt)
(a) Horizontally mounted, end suction type, Centrifugal fire pump with operating speed of 2900 rpm, as per IS:1520 complete for delivery of under mentioned discharge against desired mentioned head so as to ensure a minimum pressure of 35 meter at the highest and farthest outlet at the specified flow complete with necessary strainers , 100 mm dia dial pressure gauge of calibration 0-15 kg/sq cm including bypass arrangement for periodic testing of the working of the pumpset as well as testing of automation with required length and size of MS pipe and control valves for proper completion of work. The pump shall be capable of giving 150% of rated discharge at head not less than 65% of rated head. The pump shall be provided with Mechanical seals. The impeller shall be enclosed type and accurately balanced dynamically. The pump casing shall be of cast iron, impeller shall be of bronze and shaft shall be of stainless steel.
(b) Squirrel cage, TEFC induction motor as per IS : 325, suitable for 415 V +/- 10%, 3 Phase, synchronous speed 2900 rpm, IP 55 protection and class 'F' insulation, vaccume impregnated windings with heat and moisture resisting varnish for the above pump and flexible coupling with the pump. The motor shall be rated for continuous duty and shall have HP rating necessary to drive the pump at 150% of it's rated discharge at 65% of rated head.
(c) Common bed plate of fabricated mild steel channel or cast iron type, coupling, coupling guard ets as required.
(d) Suitable cement concrete pump foundation and vibration clamping arrangement as required. with foundation bolts, anti vibration pads, washers etc.
(e) Pressure switchs (for both upper and lower levels) for automatic operation of motor including necessary wiring upto control panel.
Discharge : 1800 liter per minute
Head : 50 meter
Design, manufacture, supply, storing, inspection, handling, assembling, installation in correct alignment, position, affecting proper connections, testing and commissioning of 14 SWG CRCA sheet steel fabricated cubical type Electrical Control Panel for fire fighting pumps, floor mounting, dust & vwrmin proof, front operated construction, enclosure class - IP 52, powder coated after proper treatment with 7 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc. The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable required. Cost shall include cable / wiring from each pump to electrical panel, cable trays, earthing for all pumps.
The panel shall be provided with interlocking arrangement between electric motor driven and diesel engine driven pumps so that only one pump can operate at one time and in case of any failure in electric motor driven pump the diesel engine driven pump shall operate automatically. The system controller should be capable to control operation of various pumps in sequence as per standards consisting of relays, timers, sensors, annunciation window for fault indication complete in all respects.
Provisions shall be made for providing potential free contacts to all pump starters for connection to building automation system / Fire alarm control panel.
The rates shall include necessary interconnecting armoured copper control cables of suitable sizes within the panel and from panel to various motors and engines, pressure switches, level switches of water tanks, cable trays etc required to complete the entire installation upto the satisfaction of engg-in-charge.
The fault withstanding capacity of panel shall be 35 KA rms for 1 sec.
Following Fire fighting pumps shall have to be controlled -
2 set of Electric motor driven pump
1 set of diesel engine driven stand by pump
2 set of electric motor driven jockey pump
1 set of curtain sprinkler pump
(Switchgears Make : ABB / L&T / Siemens / Schneider)
Incomer :
Bus Bar :
630 AMP TPN, 415 volt, 3 phase, 4 wire, 50 HZ electrolitic high conductivity Copper with SMC / DMC supports, with colour coading and insulated by heat shrinkable sleeves and clips on shrouds for joints. The current density of copper bus bar shall not exceed 1.25 amp/sqmm.
Outgoings :
1 no. 250 AMP TP MCCB as spare
1 no. 63 AMP FP MCB as spare
1 no. 25 AMP DP MCB for supply to annunciation/AMF panel of diesel engine driven stand by fire pump. The diesel engine driven fire pump will start automatically in the event of pressure drop beyond preset limit or on mains failure or failure of electric driven pumps to start.
Control panel as described above
Providing and fixing inspectors test assembly complete with test valve, sight glass sectional drain valve, union with corrosion resistant orifice all complete strictly as per drawing.a) 50 mm dia
Providing, fixing, testing & commissioning of MS air cushion tank on top of each riser fabricated from 6mm thick MS plate, 250 mm in diameter and 1.2 m in height with dished ends fabricated from 8mm thick MS plate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25mm dia valve, pressure guage with gun metal stop cock complete with all accessories as required.
Providing and fixing electrically operated flow indicating switches with threaded connection for indicating water flow in sprinkler branch line on each floor with necessary local junction box installed in an accessible place close to flow switch with 2 core 1.5 sqmm FRLS copper cable from flow switch to junction box including all materials for fixing the junction box/cables.
Providing and fixing 2 core x 1.5 sq.mm copper conductor PVC sheathed insulated cable in 20 mm dia conduit including cost of conduit and clamping the same with M.S. clamps painted with 3 coats of enamel paint over a coat of primer complete in all respects. (for connection from each floor to annunciation panel installed in the fire control panel).
Providing and fixing 25 zone Annunciation panel for the Sprinkler System on A.C. supply with standby battery complete in all respects.
Providing & fixing Curtain nozzles complete with all accessories.
Providing, jointing and testing of automaticaly operated Halotron fire extinguishers(cap-5kg,temperature rating-5kg,temperature rating-68degc,test pressure-30bar) complete with all accessories/fittings.
Supply & fixing in position ISI marked cast iron double flanged non return valves (PN 1.6 MPa) as per IS:13095, with SS disc, shaft, seating rings, nitrile rubber lining, internal fastening, nuts, bolts including transporting to worksite, 3 mm thick rubber gaskets etc. including testing, Complete as per drawings & directions of the Engineer-in-charge.
(MAKE : Kirlosker / IVC / Zoloto / Venus / Audco / Advance)
WATER SUPPLY
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes having thermal stability for hot & cold water supply including all (CPVC) plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Internal Work - Exposed on Wall
15 mm nominal outer dia pipes.
20 mm nominal outer dia pipes.
25 mm nominal outer dia pipes.
32 mm nominal outer dia pipes.
40 mm nominal outer dia pipes.
50 mm nominal outer dia pipes.
62.5 mm nominal inner dia pipes.
Providing and fixing Chlorinate Polyvinyl Chloride (CPVC) pipes having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This including jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the the same including testing of joints complete as per direction of engineer in charge.
Concealed work including cutting chases and making good the walls etc.
15 mm nominal outer dia pipes.
20 mm nominal outer dia pipes.
25 mm nominal outer dia pipes.
32 mm nominal outer dia pipes.
Providing and fixing Chlorinate Polyvinyl Chloride (CPVC) pipes having thermal stability for hot & cold water supply including all (CPVC) plain & brass threaded fittings. This including jointing of pipes & fittings with one step CPVC solvent cement , trenching, refilling & testing of joints complete as per direction of Engineer in charge.External work.
20mm Nominal outer dia pipes
25 mm nominal outer dia pipes.
32 mm nominal outer dia pipes.
40mm Nominal outer dia pipes
50mm Nominal outer dia pipes
62.50 mm nominal inner dia pipes.
Fixing water meter and stop cock in G.I pipe line including cutting and threading the pipe and making long screws etc. complete (cost of water meter and stop cock to be paid separately).
Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for sluice valve, with C.I. surface box 100mm. top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size),i/c necessary excavation foundation concrete 1:5:10 (1 Cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 Cement : 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design:
a) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
Providing and fixing C.P brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 grams with threaded end for hose connection.
Providing and fixing gun metal non- return valve of approved quality (screwed end).
50 mm dia nominal bore-vertical
65 mm dia nominal bore-vertical
80 mm dia nominal bore-vertical
Supplying and fixing C.I. cover without frame for manholes:
500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg.
Providing, fixing, installation, testing and commissioning of Solar Hot Water indirect Heating system using approved type of heating liquid medium comprising of flat plate solar panels, with single sheet absorber fin ,screw less construction of panel,including all interconnecting insulated GI piping, primary and secondary recirculation pumps, pressure type insulated hot water tank wit PUF insulation, sacrificial magnesium anode with steel core including valves on inlet, outlet, Y strainer and a water meter on the inlet, air release valve all mounted on galvanized MS sections complete as required with connection with existing piping. (connect the system to hot water mixing tank via 50 mm dia pipe) (make: Solarhart ,Tata BP ).
Supply, Instalation, Testing & Commissioning of 1000 LPD flat plate solar collector panels of 2 x 1m size each approx. the panels enclosed in insulated collected boxes with single piece toughened glass 3.5mm thick and fixed with heat resistant.panel Should have a single sheet absorber and screwless design. (make:Solar hart ,Tata BP ).
a) 1000 lts MS insulated tank 2coats of primer & painted (sheet thickness 4mm).
b) Inter-connected insulated GI piping insulated with 9mm thick nitrile rubber heat resistant insulation sections (Vidoflex or equivalent) and valves with outer mechanical protection of aluminium sheet cladding.
Providing and fixing M.S. puddle flanges fabricated out of 6 mm thick M.S. plate of size 200 x 200mm plus dia of pipe of 600 mm long pipe pieces to R.C.C. water tanks / R.C.C. walls. The entire fitting shall be painted with black Japan paint .
25 mm dia
80 mm dia
100 mm dia
150 mm dia
250 mm dia
Providing & fixing fully submersible sump pumps for dewatering with C.I casing & shaft suitable for operation on 400 / 440 V pH 50 cycle A/C power supply.
Sump Pumps( For basement Drainage ) Cost shall include electrical control panel(1no. for each set of 2 pumps) with wiring,cabelling,control cabelling & all accessories. Control panel shall be compatible with BMS control system. Cyclic operations shall be provided for each set of 2 pumps.
Location- Inside drainage sump in basement
Number of pumps = 2 nos.
Solid handling-15mm
Flow rate(each pump)=3Lps, Head(each pump) 12 Mts
Sump pumps & associated works as described above
Providing & fixing fully submersible sump pumps for sewage lifting with C.I casing & shaft suitable for operation on 400 / 440 V pH 50 cycle A/C power supply.
Sump Pumps( For basement toilet Drainage ) Cost shall include electrical control panel(1no. for each set of 2 pumps) with wiring,cabelling,control cabelling & all accessories. Control panel shall be compatible with BMS control system. Cyclic operations shall be provided for each set of 2 pumps.
Location- Inside sewage sump in basement
Number of pumps = 2 nos.
Solid handling-40mm
Flow rate(each pump)=3Lps, Head(each pump) 12 Mts
Sump pumps & associated works as described above
Providing & fixing horizontal centrifugal pumps for domestic water lifting with CI casing bronze impeller suitable for operation on 400 / 440 V pH 50 cycle A/C power supply.Cost shall include electrical control panel with all controls to make the pumps to operate automaticaly.Sequencing shall be provided for the pumps.Pumps shall start /stop automatically depanding upon water level in overhead tank.
Domestic water Pumps
Location - Inside pump room
Capacity 3 LPS each
Head 55 Mts
HP(appx) - 5.0
Pumps & associated works as described above
Providing & fixing horizontal centrifugal pumps for flushing water lifting with CI casing bronze impeller suitable for operation on 400 / 440 V pH 50 cycle A/C power supply.Cost shall include electrical control panel with all controls to make the pumps to operate automaticaly.Sequencing shall be provided for the pumps.Pumps shall start /stop automatically depanding upon water level in overhead tank.
Flushing water lifting Pumps
Location - Inside pump room
Capacity 2 LPS each
Head 55 Mts
HP(appx) - 5.0
Pumps & associated works as described above
RAIN WATER PIT
Earth Work in excavation in Foundation Trenches in Ordinary soil (vide classification of soil item -B) and disposal of excavated earth as obtained to a distance upto 50 M including all lift, leveling ramming the foundation trenches, removing roots of tree shrubs all complete as per approved design, building specification and direction of E/I
Extra for earth work in hard soil as per specification & direction of engineer in charge (Vide classification of soil item B)
Extra rates for quantities of works, executed :
In or under water and/or liquid mud, including pumping out water as required.
Earth filling in foundation trenches and plinth in layer not exceeding 150mm thick will watered rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenched with a lead of 50mm and lift of 1.5M all complete as per building specification and direction of E/I. (Mode of measurement compacted volume).
Removal & disposal of surplus excavated earth by mechanical transport including loading unloading stacking and spreading at all lift and lead up to 5km to spoil dump approved by local authority.
Providing coarse clean local SAND IN FILLING in foundation trenches or in plinth including ramming and watering in layer not exceeding 150 mm thick with all leads and 1.5 M lifts including cost of all materials, labours, royalty and taxes all complete as per building specification and direction of Engineer In charge (Mode of measurement compacted volume)
90 mm to 45 mm size stone aggregate
Stone screening 11.2 mm nominal size (Type B)
CONCRETE WORK
Providing P.C.C. M-75with nominal mix of (1:4:8) in foundation with approved quality of stone MTR.al grade - III (50 mm to 25mm size) clean coarse sand of F.M 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position vibrating, skirting, curing, taxes and royalty all complete all complete as per building specification and direction of Engineer-in-charge.
R C C WORK
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge.
NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately
(2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC.
All works upto plinth level
Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform
Providing Tor steel reinforcement as per approved design & drawing
8mm (TMT Fe500)
10mm (TMT Fe500)
12mm (TMT Fe500)
16mm (TMT Fe500)
Providing Tor steel reinforcement of 20 mm, 25mm, 28mm, 32mm dia bar as per approved design and drawing
20/25/32 mm dia TMT bar Fe 500
BRICK WORK Providing designation 100A brick work with flyash lime brick (FLAG) confirming to IS 12894-1990 (9"x425"x3") in C.M. (1:4) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints costs of screening materials, raking out joints to 15mm depth curing taxes and royalty all complete as per building specification and direction of E/I.
STEEL WORK Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
FINISHING WORK 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour.Two coats
MISCELLANEOUS WORK Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 450 mm dia RCC pipes.
560 mm dia cover without frame (Heavy duty)
Plastic encapsulated M.S. foot rest 30x20x15 cm
Boring/drilling bore well of required dia for casing / strainer pipe, by suitable method prescribed in IS:2800 (part-1) including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of engineer-in-charge, upto 90 metre depth below ground level. 300mm dia
Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS : 12818, including hire & labour charges, fittings & accessories etc, all complete, for all depths, as per direction of engineer-in-charge. 100mm nominal size dia
Providing and fixing Bail plug / Bottom plub of required dia to the bottom of pipe assembly of tubewell as per IS : 2800 (part -1) 100mm dia
CARRAIGE OF MATERIALS
CEMENTS (UPTO 5KM LEAD)
SAND (UPTO 16KM LEAD)
CHIPS (UPTO 22KM LEAD)
BRICKS (UPTO 8KM LEAD)
ELECTRICAL WORK HT PANEL , TRANSFORMER , DG SETS and BATTERY CHARGER
Supply and installation testing & commisioning of 1250kVA transformer step down outdoor type complete with standard fittings HT 11 KV 3 phase 4 wire copper wound, delta/star connected (vector group-DYn -11), Off circuit Tapp Changer on HV side , oil immersed, naturally oil cooled (ONAN), Distribution transformer complete with following:-
Silica gel breather with connecting pipe and oil seal.
Air release plugs.
Pressure release device. Explosion vent, should be double diaphragm type.
150mm dial magnetic oil level gauge with low level alarm contact.
150 mm dial oil temperature indicator with maximum reading pointer and electrically separate contacts for trip and alarm.
150 mm dial winding temperature indicator with maximum reading pointer and electrically separate sets of contacts for trip and alarm.
Thermometer pockets.
Oil conservator with filter cap, drain plug and plain oil level gauge (with coloured prismatic front).
Double float Buchholz relay with gas release cock, shut-off valve on either side and separate sets of contacts for trip and alarm.
Sampling valve/ Filter valve with threaded adopted (top and bottom).
Drain valve with threaded adopted.
Jacking pads, handling and lifting lugs.
Cover lifting eyes.
Bi-directional rollers and skids( 4 Nos. Roller)
Radiators (Detachable type).
Clamping devices.
Two grounding pads.
Weatherproof marshalling box for housing control equipment and terminal connections.
Rating and terminal marking plates.
LT Neutral bushing with 50x6 cu flat suitably supported
Outdoor HT cable box (Detachable type) suitable to terminate 3C-240 sq. mm 11kV HT cable.
LT side suitable for LT cable Connection( 10 Nos. 3.5C-300 Sq. mm XLPE Arm cable)
1250 KVA Transformer as per above
11kV HT Panel Supply , Installation, Testing and Commissioning of 11 kV, 350 MVA (18.4 kA), 630A, HT, Single Panel Vacuum circuit breaker Switchboard cubicle type, made out of 2mm thick sheet steel, totally enclosed, IP 4X, 50 deg. C ambient temperature, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, powder coated painting, suitable for operation on 11 kV , 3ph, 50 Hz AC system with copper busbars, Vacuum circuit breaker mounted on horizontally withdrawable truck complete with following and as per technical specifications and enclosed SLD
1 Vacuum Circuit Breaker - 630 A, 3 pole, 18.4 kA
Breaker control switch.( TNC)
24 V DC Tripping coil
24 V DC Closing coil
240 V AC spring charge motor
Set of ON/OFF indicating lamps , R-Y-B Indication Lamps , Spring Charged Indication Lamp and Auto Trip Indication lamp
Clear lamp for trip circuit health supply.
8 Parameter Energy Analyser
3 Nos. VAA33 aux. relay for transformer faults , Alarm and trip suitable for 230V AC supply
1 No. Anti Pumping Device
Trip circuit supervision relay.
Master Trip relay.
IDMT Relay with 2 O/C and 1 E/F Element with hand reset contacts and indicator( Flag) ( O/C Settings 400-1600% and E/F Setting 200 - 800%) with highest instantaneous protection for O/C and E/F ( Self powered Version)
Earth fault relay range 20 – 80% with series stabilizing resistor and PS class CT’s.
3 Nos. Cast resin CTs of dual ratio 75 / 5 Amps CL:1 ( For Metering) , 5P20( For protection) , 15 VA.
Alarm annunciator with 9 windows and buzzer, ACK, rest, test push button for transformer faults and electrical faults.
Suitable space and Brass Gland for termination of 1 No. 3C x 240 sq.mm XLPE cable as incoming.and Outgoing
11kV HT panel as described above and complete as required
Supply of cable XLPE -PVC insulated PVC sheathed galvanised steel strip armoured electric power cable with aluminium conductor 11000 volt grade of size 3CX240 sqmm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required 3c x 240 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/STONE WARE / METAL pipe as required. 3c x 240 sqmm
Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 240 sq. mm
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 240 sq. mm
Supply, installation, testing and commissioning of 1000 KVA, at 0.8 P.F. (lagging), aircooled radiator type diesel engine alternator set mounted on common base frame complete with accessories as per specification and layout, drawing with battery charger, battery and battery rack residential silencer, stainless steel bellows, 990 Ltrs. day fuel tank, spring loaded GERB cush pads, logic control panel, governor etc including Accoustic Enclosure suitable for outdoor installation complete as required.
Supply, installation, testing and commissioning of 500 KVA, at 0.8 P.F. (lagging), aircooled radiator type diesel engine alternator set mounted on common base frame complete with accessories as per specification and layout, drawing with battery charger, battery and battery rack residential silencer, stainless steel bellows, 990 Ltrs. day fuel tank, spring loaded GERB cush pads, logic control panel, governor etc including Accoustic Enclosure suitable for outdoor installation complete as required.
Supply, laying of following sizes of MS Piping for Exhaust including providing suitable bends, reducers & supporting arrangement at suitable intervals including insulation on entire length of exhaust pipe with 50mm thick Rockwool insulation & painting etc. as required. 250mm (NB) MS ERW pipe
125mm (NB) MS ERW pipe
Supply, installation, testing and commissioning of 200 AH capacity 24 volts DC hermetically sealed maintenance free batteries duly charged including battery charger unit with provisions of Boost Charging, and Float charging. Suitable for 240 V, including DC DB single phase AC 50 Hz as per specifications
Supplying of following 1100 volt grade XLPE insulated PVC sheathed aluminium / Copper conductor armoured cables as per specification as required. 3.1/2 core 300sq. mm.
3.1/2 core 240sq. mm.
3.1/2 core 185sq. mm.
3.1/2 core 120sq. mm.
3.1/2 core 95sq. mm.
3.1/2 core 70sq. mm.
3.1/2 core 50sq. mm.
3.1/2 core 35sq. mm.
3.5 core 25sq. mm.
4 core 16sq. mm.
4 core 10 sq. mm.
4 core 16 sq. mm.(Copper)
3 core 35 sq. mm.(Copper)
4 core 6 sq. mm.(Copper)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 25 sq. mm
Above 25 sq. mm and upto 120 sq. mm
Above 120 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 25 sq. mm
Above 25 sq. mm and upto 120 sq. mm
Above 120 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ STONE WARE / METAL pipe/ Cable Trays as required. Upto 25 sq. mm
Above 25 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing mansory open duct as required
Upto 25 sq. mm
Above 25 sq. mm and upto 400 sq. mm
Supplying and making end termination of following sizes with brass compression gland including providing and crimping solderless plugs/ferrules of sizes PVC insulated PVC sheathed aluminum conductor armoured cable 1.1 KV grade. 3.1/2 core 300sq. mm.
3.1/2 core 240sq. mm.
3.1/2 core 185sq. mm.
3.1/2 core 120sq. mm.
3.1/2 core 95sq. mm.
3.1/2 core 70sq. mm.
3.1/2 core 50sq. mm.
3.1/2 core 35sq. mm.
3.1/2 core 25sq. mm.
4core 16sq. mm.
4 core 10sq. mm.
3 core 35 sq. mm.(Copper)
4 core 16 sq. mm.(Copper)
4 core 6 sq. mm.(Copper)
Cable Trays Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.( Powder coated shall be of Siemens Grey Colour- RAL 7032) 450mm width X 50mm depth X 1.6 mm thickness
300mm width X 50mm depth X 1.6 mm thickness
150mm width X 50mm depth X 1.6 mm thickness
100mm width X 50mm depth X 1.6 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17 .5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. 450mm width X 50mm depth X 1.6 mm thickness
300mm width X 50mm depth X 1.6 mm thickness
150mm width X 50mm depth X 1.6 mm thickness
100mm width X 50mm depth X 1.6 mm thickness
Supply, erection, testing & commissioning of prefabricated MS ladder type cable trays including Tees / Bends / Crossing / Reducers / Couping to be laid in cable trench, overhead on wall or hanged from ceiling complete with all accessories as required including support at every 1500mm as required 900 (W) x 75 (H) x 2mm (T)
750 (W) x 75 (H) x 2mm (T)
600 (W) x 50 (H) x 2mm (T)
450 (W) x 50 (H) x 2mm (T)
SUB-HEAD III:- 415V MAIN DISTRIBUTION BOARDS Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of MV Panels fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA painted sheet steel in cubicle formation with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary for large meter boards. Cable gland plates shall be provided at top and bottom both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter & meter to MCB shall be done by using adequately rated flexible single core copper wire. The boards shall be treated with all anticorrosive process before painting as per standards with final approved shade of powder coated as approved, 2 nos. earthing terminals shall be provided for all panels. The boards shall be suitable for 415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to match with site conditions.
An approval shall be taken for each panel before manufacturing. Galvanised hardwares with zinc passivation shall be used in fabrication of boards.
Note: The following provisions shall be required to be made in the switchboard detailed below
The Switchboard shall have provision for entry of all PVCA cables/bus duct from the top/bottom as required.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used.
Suitable tinned copper extension links for incoming/outgoing cables shall be provided wherever required
Positive isolation of all breakers.
All fault level breaking capacity indicates shall be IC.S value at 415 volts (ICS = ICU = ICW = 100%).
Space Heater/ light/air filter shall be provided for each vertical compartment
Padlocking facility shall be provided on all outgoing feeders.
All ACB’s shall have all standard accessories such as CT’s, Arc Chute, Safety Shutters etc.
All inter Panel wiring from PLC to DG / Transformer / Bus Couplers as required.
Link and drops from ACB/MCCB shall be designed for full rated current of ACB/MCCB ratings at same current density as of Main Bus Bar
2 nos. GI earth strip throughout the panel. Main LT Cum Change Over Panel ( As per Enclosed Drawing No. 1066_DMC-VC-EL-09 and Complete in all respects)
450 kVAR Capacitor Panel( As per Enclosed Drawing No. 1066_DMC-VC-EL-10 and Complete in all respects)
MDB type #1 ( As per Enclosed Drawing No. 1066_DMC-VC-EL-10 and Complete in all respects)
MDB type #2 ( As per Enclosed Drawing No. 1066_DMC-VC-EL-10 and Complete in all respects)
MDB Forth and Fifth Floor ( As per Enclosed Drawing No. 1066_DMC-VC-EL-10 and Complete in all respects)
Terrace MDB ( As per Enclosed Drawing No. 1066_DMC-VC-EL-10 and Complete in all respects)
UPS MDB( As per Enclosed Drawing No.1066_DMC-VC-EL-10 and Complete in all respects)
Basement MDB ( As per Enclosed Drawing No.1066_DMC-VC-EL-10 and Complete in all respects)
Transformer Local panel-1 ( As per Enclosed Drawing No. 1066_DMC-VC-EL-09 and Complete in all respects)
DG Local panel-1 ( As per Enclosed Drawing No. 1066_DMC-VC-EL-09 and Complete in all respects)
DG Local panel-2 ( As per Enclosed Drawing No. 1066_DMC-VC-EL-09 and Complete in all respects)
EXTERNAL LIGHTING FEEDER PILLAR (10 kA) Design, fabrication, supply of Feeder Pillar fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof outdoor type double door with reinforcement of suitable size angle iron, channel 'T' irons and / or flats wherever necessary. Cable gland plates shall be provided at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications with 2 coats of PU paint primer and final approved shade of PU paint coating. 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 15% spare space, lifting hooks shall also be provided in case of large panels.
Approval shall be taken for each panel before fabrication. Galvanized hardwares with zinc passivation shall be used in fabrication of panels.
INCOMING
1 no. 63 Amp TPN MCCB, 10 KA with thermal magnetic protective releases.
1 set of phase indicating lamps with MCB.
BUSBAR
100A, TPN Al. Bus Bar of suitable length having Current density 1Amp/sq.mm & having high conductivity electrical grade suitable to withstand symmetrical fault level of 10 kA. Neutral busbar shall be of 100% capacity.
OUTGOING
2 No. 40A FP MCB
2 No. 40A DP MCB
2 No. 20A DP MCB
2 Nos. single phase bank each consisting of 1 No. 24 Hr Programmable timer , contactor and 4 nos. 10A/20A amp DP MCB, 10 KA with thermal magnetic protective releases as outgoings.
Installation, testing and commissioning External lighting Feeder Pillars as mentioned in item No. 1 above fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof outdoor type double door including providing & making brick masonry foundation (including plastering etc.) of suitable size with all fixing accessories as required.
SUB-HEAD IV: EARTHING AND LIGHTNING PROTECTION
Earthing with copper . Earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc.( without charcoal or coke and salt).
Earthing with G.I. Earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. ( without charcoal or coke and salt).
Extra for using coke and salt for GI/Copper plate earth electrode complete as required.
Extra for using charcoal and salt for GI/Copper plate earth electrode complete as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm Cu. strip in 40 mm dia G.I. pipe from earth electrode
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
Providing and fixing earth bus of 50mmX 5mm copper strip on surface for connections etc. as required
Prividing and Fixing of copper lightning conductor Finial made of 25mm dia 300 mm Long GI tube , having single prone on top with 85mm dia 6mm thick GI base plate including holes etc complete as required
Providing and fixing GI-tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor as required.(for vertical run)
Providing and fixing GI-tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor as required.(for horizontal)
Providing and fixing testing joint, made of 20 mm x 3 mm thick gi strip, 125 mm long with 4 Nos. brass bolts, nuts check nuts and spring washers etc. complete as required.
Providing and laying GI tape, 32 mm x 6 mm thick from earth electrode directly in ground as required.
SUB-HEAD V: SUPPLY AND INSTALLATION OF LIGHT FIXTURES AND EXHAUST FANS Supply of following Light Fixtures 6W Round Recessed mounted type LED Luminiare
12W Round Recessed mounted type LED Luminiare
12W Square Recessed mounted type LED Luminiare
10W Round surface mounted type LED Luminiare
10W LED Bulkhead fixture
Recessed Mounted LED Panel ( 600mmX600mm)-36W
70W External Lighting Fixture
LED Battern ( 20W/22W)
Indoor type LED Cove Light Strip( 10W / Meter)
Installation , testing and commisioning of pre wires internal light fittings on all types complete with all accessories including connectiob with 1.5Sq, mm FR Wires
Fans Supply and fixing circular/ hexagonal M.S. sheet ceiling fan box with clamp of internal dia 140mm, 73 mm height, 3mm thick rim top lid of 1.5mm thick M.S sheet lidss shall be screwed into M.S. box by means of 3mm round headed screws, clamps shall be made of 12 mm dia M.S bar bent to be shape as per standard drawing with over all length as 80 cm
Supply and fixing of step type electronic fan regulator on existing modular plate switch box including connection but excluding modular plate etc as required.
Installation, testing and commissioning of ceiling fans/bracket fan of all sizes including wiring the down rod .of standard length (up to 30 cm ) with 1.5 sq.mm FR PVC insulated copper conductor single core cable etc as required.
Supplying of 1200mm dia decorative type ceiling Fan
Supplying of 400mm dia wall bracket fan
Supplying of 300mm Exhaust Fan
Installation of exhaust up to 450mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required
Extra for fixing the louvers/ shutters complete with Frame for a exhaust fan of all sizes
SUB-HEAD VI: TELEPHONE, TV ,DATA and RACEWAYS :
Providing, fixing, connecting and testing of following pair solderless telephonetag block, with powder coated box (Krone make ) of required size box with hinged lockable cover and clamps for dressing of wires etc as required. 200 Pair box
50 Pair box
30 Pair box
Supply and laying of following 0.61mm dia annealed tinned copper conductor PVC insulated and PVC sheathed unarmoured telephone cable in existing conduit in concealed/ surface system complete as required 50 pair Cable
30 pair Cable
Providing, fixing, connecting, testing and commisssioning of zinc passivated box with moulded plate in recess or on surface moulded type with following including all necessary materials etc. as required. 2 Pair telephone cord outlet (RJ-11)
TV antina Socket outlet
Supply and fixing 1 or 2 module ( 75mm X 75mm ) GI Box along with modular base and cover plate for modular switches in recess etc as required
Supply and fixing of Computer terminal (RJ-45) outlet in existing box with modular plate
Supplying and fixing of following size PVC conduit alongwith the accessories in surface / recess including painting in case of surface conduit or cutting and making good the same in case of recessed conduit as required as per specification. 20mm dia
25mm dia
32mm dia
Providing and fixing of UTP CAT 6 COMPUTER LAN CABLE WITH STAR SEPARATOR in existing conduits .
Supplying and drawing co-axial TV cable RG-6 grade, copper conductor PE insulated, with PVC shield in the existing surface/ recessed PVC conduit as required.
Supplying, drawing, of 0.5mm dia (2 pair) FR PVC insulated copper conductor , unarmoured telephone cable in existing surface/ recessed PVC conduit as required
Supplying, drawing, of 0.5mm dia (3 pair) FR PVC insulated copper conductor , unarmoured telephone cable in existing surface/ recessed PVC conduit as required
Supplying and Fixing in floor with all accessories , 2 mm thick steel sheet factory fabricated post galvanized floor recessed raceway of the following sizes 300 mm wide x 38 mm deep raceway
225 mm wide x 38 mm deep raceway
100 mm wide x 38 mm deep raceway
Providing and fixing 400 x 400 x 50 mm deep 2 mm thick GI sheet junction box including providing 3 mm thick stainless steel cover as required
Providing and fixing 300 x 300 x 50 mm deep 2 mm thick GI sheet junction box including providing 3 mm thick stainless steel cover as required
Providing and fixing 150 x 150 x 50 mm deep 1.6 mm thick GI sheet junction box including providing 3 mm thick stainless steel cover as required
SUB HEAD- VII- SPEAKERS , FIRE ALARM AND DETECTION SYSTEMS Supplying and fixing of following size PVC conduit alongwith the accessories in surface / recess including painting in case of surface conduit or cutting and making good the same in case of recessed conduit as required as per specification. 25mm dia
32mm dia
Supplying and laying of following sizes FR PVC insulated single core copper wire in existing conduit complete as required. 2x1.5 sq mm
2x2.5 sq mm
Supply, installation, testing and commissioning of plug-in type intelligent photoelectric smoke detectors including the cost of supplying base plate, mounting accessories etc. complete as as required.
Supplying, installation, testing and commissioning of analogue addressable rate of rise cum fixed temperature heat detector with built-in fault isolator as required.
Supplying, installation, testing and commissioning of addressable manual call station complete as required.
Supplying, installation, testing and commissioning of addressable Response Indicator complete as required.
Supply installation, testing and commissioning of Fault isolator Base / Module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected
Supplying, installation, testing and commissioning of hooter cum strobe with control module complete as required.
Supply, installation, testing & Commissioning of micro processor based 2 wire fault tolerant loop, 4 loop networkable type (each loop accessing minimum 125 detectors and 125 modules ) fire alarm/detection control panel. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module when ever any alarm is triggered. The panel shall have rectifier, Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects.The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 8 hours with battery charger complete as required.and as per specifications including 8 Channel Integrated Digital Voice Evacuation and Two Way Fire Fighter Telephone communication System capable of supervision of all the speaker circuits, with required suitable digital amplifiers, mic and acessories required to compelete the system. The system shall be of the same make as the panel and shall be UL Listed. The system shall also have capability to be integrated with EPBAX.
Supply, installation, testing and commissioning of intelligent analogue addressable dry contact Monitor Modules to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. The module may also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. The item cost shall include the cost of surface mounted backbox for fixing of the module, mounting accessories and complete as required.
Supply, installation, testing and commissioning of recess/surface mounting intelligent analogue addressable Fire Fighter's Telephone Module/ jack with stainless steel face plates for connections of Fireman's handsets including the cost of supplying all the required control modules, mounting accessories and complete as per specifications and as required
Supply ,installation,testing and commissioning of 2 way communication Fire Fighter's handset complete as required.
Supply and installation Round speaker for ceiling mounting arrangement (0-2 watts) with multiple taping complete as required
Supplying, installing, testing and commissioning of 2X1.0 SQMM IND. 1.1KV SPEAKER CABLE in existing conduit.
Supply and installation Wall mounted speaker with mounting arrangement with multiple taping complete as required
SUB-HEAD VIII: INTERNAL WIRING AND FINAL DISTRIBUTION BOARDS COPPER WIRING IN PVC CONDUITS Wiring for Light point / Fan point / Exhaust Fan point / Call Bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit , with modular switch ,modular plate ,suitable GI box as required a) Group - C
Wiring for twin controlled light point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit , with 2 way modular switch ,modular plate ,suitable GI box etc as required.
Wiring for group controlled ( Looped ) light/ceiling fan/exhaust fan/call bell point ( With out independent switch etc.) with 2x1.5 sq.mm PVC insulated stranded copper conductor cable alongwith 1 No. 1.5 sq.mm PVC insulated copper conductor cable for earthing in surface/recessed steel conduit as required. (Point shall be controlled / looped From existing point). a) Group - C
Wiring with 2 x 2.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 2.5 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.( For primary 5A Socket , Primary MCB Point and Circuit Wiring)
Same as above but in existing conduits / Raceways
Wiring with 2 x 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 1.5 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.( For Secondary MCB Points and 5A Secondary Points)
Same as above but in existing conduits / Raceways
Wiring for light / power plug point with 2 x 4 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC Medium Class conduit alongwith 1 No. 4 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.( For 16A Socket)
Same as above but in existing conduits / Raceways
Wiring for light / power plug point with 2 x 6 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 6sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.( For A/C Sockets)
DB SUBMAIN WIRING IN PVC CONDUITS Wiring for DB submain with 4 x 16 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 2 No. 16sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for DB submain with 4 x 10 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 2 No. 10sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for DB submain with 2 x 10 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 10 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for DB submain with 2 x 6 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 6 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.
POWER SOCKETS Supplying and fixing suitable size GI box with modular plate and cover in Front on surface or in recess ,including providing and fixing 3 pin 5 / 6 amps modular socket outlet and 5 / 6 amps modular switch,connection,painting etc.as required.
Supplying and fixing suitable size GI box with modular plate and cover in Front on surface or in recess ,including providing and fixing 6 pin 15 / 16 modular socket outlet and 15 / 16 amps modular switch,connection,painting etc.as required.
Geyser point consisting of following :- - 1 No. 6 pin No 6/16A Modular Socket in 2 Module Box with modular Plate near Geyser - 1 No 6/16A Modular Switch in 2 Module Box with Modular plate near entry at switch board level - Wiring between Socket and Switch board with 3 Nos. 4.0 Sq. mm Cu Wire in conduit including connections at both ends
Supplying and fixing 20 Amps ,240 Volts , SPN industrial type , Socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 amps , 2Pole, RCCB in sheet steel enclosure , on surface or in recess with chained metalcover for the socket out let and complete with connections, testing and commissioning etc. as required. 20A, 3 pin socket outlet controlled by 20A 2P RCCB
FINAL DISTIRIBUTION BOARD Supplying installation, testing and commissioning of surface-recess mounting type three pole and neutral,prewired, sheet steel, MCB distribution board 415 volt, tinned copper busbar, common netrul link, earth bar, din bar for mounting MCB detachable gland /knock out plate,, phosphatized and powder coated and complete with MCBs . RCCBs , Isolator etc as required
TPN DB( Double door) A. TP&N D.B (Vertical TYPE)
i) 1 No. 63 Amps 4P MCB Isolator + RCCB
iv) 24 Nos. 6-32 Amps SP MCBs as outgoing
A. TP&N D.B (HORIZONTAL TYPE)
i) 1 No. 40 Amps 4P MCB Isolator
ii) 1 No. 40 Amps 2P RCCB -3Nos
iii) 18 Nos. 6-32 Amps SP MCBs as outgoing
A. TP&N D.B (HORIZONTAL TYPE)
i) 1 No. 40 Amps 4P MCB Isolator
ii) 1 No. 40 Amps 2P RCCB -3Nos
iii) 12 Nos. 6-32 Amps SP MCBs as outgoing
TPN DB( Double door)
A. TP&N D.B (Vertical TYPE)
i) 1 No. 63 Amps 4P MCB Isolator + RCCB
ii) 30 Nos. 6-32 Amps SP MCBs as outgoing
Supplying installation, testing and commissioning of surface-recess mounting type Siingle pole and neutral,prewired, sheet steel, MCB distribution board 240 volt, tinned copper busbar, common netrul link, earth bar, din bar for mounting MCB detachable gland /knock out plate,, phosphatized and powder coated and complete with MCBs . RCCBs , Isolator etc as required
SP&N D.B (HORIZONTAL TYPE)-Double Door
i) 1 No. 40 Amps 2P RCCB -1Nos
ii) 12 Nos. 6-32 Amps SP MCBs as outgoing
SP&N D.B (HORIZONTAL TYPE)-Double Door
i) 1 No. 40 Amps 2P RCCB -1Nos
ii) 10 Nos. 6-32 Amps SP MCBs as outgoing
SP&N D.B (HORIZONTAL TYPE)
i) 1 No. 25 Amps 2P RCCB -1Nos
ii) 6 Nos. 6-32 Amps SP MCBs as outgoing
Supply and installation of 2.5 kVA Inverter with Maintenance free batteries and 30 Min Power Back up
SUB-HEAD IX : EXTERNAL LIGHTING AND CABLING WORKS Supplying materials and labours for constructing inspection chamber of designation class 75B bricks size 750mm deep, 600x450mm internal dimension having 250mm wall thickness in cement mortar (1:6) including 12mm cement plaster (1:4) with punning on inside and cement plaster (1:6) with600x475mm G.I. Cover with frame (weight not less than 36kg.) alongwith earth work in excavation and 80 mm thick P.C.C. (1:3:6) in foundation and refilling all complete as per specification and direction of E/I. 600 mm X450 mm X 750mm Deep Man hole
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia
150 mm dia
250 mm dia
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required 63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
Supply of 7.0 Mtr High Octagonal pole ( Hot Dip Galvanized) BOP-7030 with top dia 70mm and bottom dia 130mm and made of 2mm thick base plate of size 200mmX200mmX12mm ( LXBXT) and with suitable size of foundation bolts and complete as required
1.0 Mtr Arm suitable for above pole
Erection Of metallic street light standard pole of length exceeding 6.5mtrs but not exceding 8.5mtrs in in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregated 40mm nominal size) foundation with cement concerete collar of size 0.4m dia X 0.5m dia height to accomodate the looping type cable end box including excabation and refilling etc as required
Supply of following sizes sizes of PVC insulated PVC sheathed aluminium conductor armoured 1.1 KV grade as as required. 2C x 6 sq mm
2C x 10 sq mm
2C x 16 sq mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 25 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 25 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ STONE WARE / METAL pipe/ Cable Trays as required. Upto 25 sq. mm
Supplying and making end termination of following sizes with brass compression gland including providing and crimping solderless plugs/ferrules of sizes PVC insulated PVC sheathed aluminum conductor armoured cable 1.1 KV grade. 2C x 6 sq mm
2C x 10 sq mm
2C x 16 sq mm
Supplying and fixing of outdoor type junction box( IP 67 ) suitable to incoming and outgoing 3C-16 sq. mm Al Armoured Cable. The juction box shall also be suitable for 3 Nos. outgoing circuits each consisitng of 3 Nos. 2.5 sq mm copper wired wires
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc as required
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc as required ( but with out charcoal/coke and salt )
Extra for using charcoal and salt for pipe earth electrode complete as required.
Supplying and fixing 50mm dia GI pipe on the pole for cable entry to junction box as required.
Wiring with 2 x 2.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 2.5 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required
Wiring with 2 x 4.0 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit alongwith 1 No. 4.0 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required
SUB-HEAD X: IP BASED CCTV SYSTEM( COLOURED) Honeywell or equivalent make only Supply, installation, testing and commissioning of UL Listed 1.3 Megapixel CMOS Vandal-proof, Network Dome Camera (1280 × 960) resolution, 1/3” Progressive scan CMOS, [email protected], AGC ON. 0 Lux with IR on, IR cut filter with auto switch, IR range up to 30 mtrs, H.264 / MJPEG, Dual stream, motion detection, Bit rate 32 Kbps-16Mbps, 3D DNR, DWDR, 12 VDC ± 10%, PoE , IP66, K-10, with fixed lens between (2.5 - 12mm), size of lens shall be as per site requirement & mockup. ONVIF, SIP, NMS, Profile S supported, connectors complete as required in dome shape fixed type for mounting recessed in false ceiling or mounted on wall complete as required.
Supply, installation, testing and commissioning of UL Listed 1.3 Megapixel CMOS, Vandal-proof, Network Bullet Camera,(1280x960)resolution, 1/3” Progressive scan CMOS, [email protected], AGC ON. 0 Lux with IR on, IR cut filter with auto switch,, H.264 / MPEG4 , Dual stream, Bit rate 32 Kbps-16Mbps, Standard IP66, PoE , with Fixed Lens between (2.5 - 12mm), size of lens shall be as per site requirement & mock-up ,IR range Up to 50 mtr, motion detection, with ONVIF, SIP, NMS, Profile S supported, connectors complete as required IR Bullet fixed type for mounting on wall or surface mounted with back box and adapter plate complete as required.
Supply, installation, testing and commissioning of UL Listed 1.3 Megapixel CMOS, Vandal-proof, Network Bullet Camera,(1280x960)resolution, 1/3” Progressive scan CMOS, [email protected], AGC ON. 0 Lux with IR on, IR cut filter with auto switch,, H.264 / MPEG4 , Dual stream, Bit rate 32 Kbps-16Mbps, Standard IP66, PoE , with Fixed Lens between (2.5 - 12mm), size of lens shall be as per site requirement & mock-up ,IR range Up to 30 mtr, motion detection, with ONVIF, SIP, NMS, Profile S supported, connectors complete as required IR Bullet fixed type for mounting on wall or surface mounted with back box and adapter plate complete as required.
Supply, installation, testing and commissioning of UL Listed 1.3 Megapixel CMOS Vandal-proof, Network Mini Dome Camera (1280 × 960) resolution, 1/3” Progressive scan CMOS, [email protected], AGC ON. 0 Lux with IR on, IR cut filter with auto switch, IR range up to 10 mtrs, H.264 / MJPEG, Dual stream, motion detection, Bit rate 32 Kbps-16Mbps, 3D DNR, DWDR, 12 VDC ± 10%, PoE , IP66, K-10, with fixed lens between (2.5 - 8mm), size of lens shall be as per site requirement & mockup. ONVIF, SIP, NMS, Profile S supported, for Lift Inside Camera
Supply, Installation, testing and commissioning of the wireless Access point for lift camera( transmitter & reciever pair)
Supply, installation, testing and commissioning of Professional Video management and recording software and hardware comprising 32Ch. NVR to record output of all cameras mentioned above in Item no 1,2,3 Third-party network cameras supported, H.264 Compression - Up to 5 Megapixels resolution recording, multiple Hard Disk 8 SATA with each having maximum storage capacity of 6 TB , as required for minimum 30 days recording required for recording when in 80% motion @ 720p 25 Frames per second(Real Time) or for recording when not in motion @720p 12.5 Frames per second, with RAID-5 Storage ,10/100/1000 MBps network interface with each NVR, 2 USB2.0, HTTP Networkable, backup by USB/DVDWR, required Client software included, 6 Nos Client licenses and required Camera licenses for each camera complete as required. All the components to be of same make as Camera.
Supply,installation,testing and commissioning of 32” CCTV colour LED screen including all accessories complete as required.
Supply, installation, testing and commissioning of Layer 3 switch HP/ Cisco make with 16 ports PoE managed, 10/100/1000 EB core switches to support all IP cameras & Access Control System , with 2 Fibre uplinks Port module only complete as required.
Supply, installation, testing and commissioning of Layer 2 switch HP/ Cisco make with 32 ports PoE managed, 10/100/1000 EB core switches to support all IP cameras & Access Control System , with 2 Fibre uplinks Port module only complete as required.
Supplying and installation of 19" 42U APW President Rack with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate systems equipment and accessories as mentioned in the BOQ above and including all connections and terminations as required
Supply and Laying of Cat-6 Cable in existing conduits for Cameras
Supply and Laying of 3C-2.5 Sq. mm unarmoured copper Power Cable in existing conduits for Cameras power supply
Supply and Laying of 3C-1.5 Sq. mm unarmoured copper Power Cable in existing conduits for Cameras power supply
Supply , Installation , testing and commisioning of 4.0kVA UPS ( 1 Phase input and 1 Phase output) with 15 Minutes back up complete with batteries etc.
Supplying and fixing of following size PVC conduit alongwith the accessories in surface / recess including painting in case of surface conduit or cutting and making good the same in case of recessed conduit as required as per specification. 20mm dia
25mm dia
32mm dia
Part A : High Side works HVAC
Screw Chiller (With VFD)
Supply , Installation, testing and commissioning of Imported/ Indian Water Chilling units ( AHRI certified, with unit mounted VFD , UL and CE Marked) each complete with specified actual capacity screw compressor, motor, water cooled condenser, insulated chiller, vibration isolators, integral refrigerant piping, control wiring and all accessories as required and called for automatic and safety controls mounted in central console panel and all mounted on a steel frame complete as per given specifications.Motor shall be suitable for 415 V ± 10% 50 cycles, 3 phase AC supply and starter shall be provided in the Control Panel.
It shall be BMS compatible and all necessary provision to be provided in this connection. Plz coordinate with BMS agency to find requirements.
IKW/TR - 0 .71 , COP >=5.7 , IPLV <= 0.4
Cooling Capacity - 250 TR (Actual at rANCHI Conditions)
Chiller In/Out - 54˚F/44˚F
Condenser IN/Out - 90˚F/97.5˚F
Chiller FF (FPS) - 0.0005 ft2-F-hr/Btu
Condenser FF (FPS) - 0.001 ft2-F-hr/Btu (2Working+1StandBy)
Cooling Towers
Supply, Installation, Testing and commissioning of Induced Draft Cooling Tower of FRP construction . Each tower shall be complete with piping, FRP Body with Internal SS supports, FRP Basin, Fan Motor with rain protection arrangement, suitable to operate through VFD, Drive, Sprinkler, Fill Media, Distribution Basin, pipe connections including quick fill assembly with shut off valves and float valves, ladder etc. complete in accordance with CPWD specifications and drawings. All motors shall be EFF-1 .The cost shall include factory inspection of the equipment by the Clients Representative
Heat Rejection - 3.75X10⁶ BTU/Hr
Flow rate - 3.8 USGPM/ TR
Water In/Out - 97.5 ˚F/90 ˚F
Ambient WB - 83 ˚F
Fan Motor - 5.5 KW x 2 Nos for Each C.T (2Working+1StandBy)
Pumps
Insulated Primary Chilled Water Pumps
Supply, installation, testing and commissioning of Vertical split casing(End Suction) chilled water circulating pump sets complete with TEFC motor, base plate, mechanical seal etc. as per specifiations and drawings.Motor shall be EFF-1 .
Chilled water 600 USGPM at 12 M head, 7.5 KW Motor (2Working+1StandBy)
Insulated Secondary Chilled Water Pumps with Variable Speed System
Supply, installation, testing and commissioning of vertical split casing(End Suction) Secondary chilled water pumping system with variable speed drive complete with TEFC motor, base plate, mechanical seal etc.as per CPWD specifications and drawings.Motor shall be EFF-1 .
The System shall be complete in all respects and suitable for following ratings:-
Chilled water Pump 600 USGPM at 20 M head, 7.5 KW Motor (2Working+1StandBy)
Adjustable variable frequency drive suitable for BMS & interfacing with other system components & Auto/manual changeover arrangement for pumps.Frequency drive shall be complete with necessary fitting and wiring in a 14G MS powder coated enclosure including locks arrangement (wall mounted/floor mounted) with display glass for reading.
a) 7.5 KW - 3 Nos
b) Differential pressure sensor with control wiring upto VFD on pumps (appx. 200 Mtrs) - 2 Nos
c) Microprocessor based Logic controller common for all pump set complete with necessary software. - 1 No
All VFD shall be installed /fixed within the enclosure (floor mounted/wall mounted) fabricated from 14 gauge M.S. sheet powder coated with visible glass panel. The panel shall have IP-55 Protection .
Condenser Water Pumps
Supply, installation, testing and commissioning of Vertical split casing(End Suction) chilled water circulating pump sets complete with TEFC motor, base plate, mechanical seal etc. as per CPWD specifiations and drawings.The motor shall be EFF-1 .
Condenser water 950 USGPM at 22 M head, 22 KW Motor (2Working+1StandBy)
Hot Water Generator
Supply , Installation , Testing and Commissioning of package type BMS compatible electric Hot Water Boilers with MS shell , heater , electric control panel , controls , safety controls , pressure guages , thermometer , insulation complete with fittings and accessories as per specificatons and drawings. The cost shall include factory inspection of the equipment by the Clients Representative
Type : Vertical
Construction : M.S Body 08mm Shell 10mm Dish ends, Top openable with thick M.S. flat plate and sufficient number of Nut Bolts.
Heating Elements : Electrical Resistance Immersion Type , Copper Tube Chromplated
Capacity : 25KW x 2Nos. Into 5Steps Total 250 KW
Controls : Step Controller, Pressure Gauges with Ball Valves, Pressure relief Valve, Low Level cutout, with sight Glass and Auto vent
Insulation : 50mm Thick Resin Bounded Fiber Glass wool cladded with 0.6mm Aluminum Sheet on M.S Frame welded to Generator Body.
Note : The entire Hot Water generator is Factory assembled and tested requiring only connection to Water Supply and Electrical Main Supply.
Part B: Low Side Works
Air Handling Units / TFA Units
Supply, installation, testing & commissioning of Double skin type horizontal/vertical floor mounted/ceiling suspended air handling units of extruded aluminium section with 0.8 mm preplasticized/precoated GI sheet outside and 0.8 mm plain Galvanized sheet inside with , 25 mm thick PUF insulation , DIDW centrifugal fans with TEFC motors, 4R/6R/8R copper cooling coils, with aluminium fins, 25 mm filters having efficiency of 90% down to 10 microns particle size. The drain pan shall be constructed out of 18G SS-304 sheet duly insulated. All the AHU's installed under this tender shall have IE-3 motor. All the cooling coils shall be AHRI / Eurovent Certified .The AHU shall have suitable provision to install Air Cleaner (as specified in item no 1.4), behind the Filters in return air path. The cost shall include factory inspection of the equipment by the Clients Representative
Air Handling Units (Floor Mounted Type) 20400 CMH , 6 RD, 50 MM SP (mm H2O) (Approx. 30 TR)
Air Handling Units (Ceiling Suspended Type) 13600 CMH, 6 RD, 35 MM SP (mm H2O) (Approx. 20 TR)
9350 CMH , 6 RD, 35 MM SP (mm H2O) (Approx. 13.0 TR)
8500 CMH , 6 RD, 35 MM SP (mm H2O) (Approx 15.0 TR)
6800 CMH , 6 RD, 35 MM SP (mm H2O) (Approx 10.0 TR)
3400 CMH , 6 RD, 35 MM SP (mm H2O) (Approx. 5.0 TR)
Digital Heating/Cooling Thermostat for Air Handling Units
Fan Coil Units Supply, Installation, testing & commissioning of single skin type Ceiling Suspended Silent type High Static/ Low Static Fan Coil Units complete with fan, motor, cooling coil, filter plenum, filters etc as per specification & drawings. The Fan Coil Units should have 3 RD cooling coil. The cost shall include factory inspection of the equipment by the Clients Representative Ceiling Suspended FCUs 1360 CMH (2.0 TR)
Ball valves without strainer 25 mm dia
Ball valves with Strainer 25 mm dia
Ventilation and Exhaust System
Axial Flow Fans
Fan and Motor shall be suitable for operation at minimum 300 deg C for 2 hrs. Certificate of conformity for 300 deg for 2 hours operation as per EN 12101-3 : 2015 issued by Internationally recognized Independent Fire Laboratory or UL listed.
All fans should have fire retardant flexible canvas connection at the inlet and outlet . The cost should include in the cost .
All ceiling suspended fans shall have vibration isolator as a part of unit price.
All floor mounted fans shall have vibration pads as a part of unit price.
Basement 1 (Exhaust) 22000 CFM; SP 30 mm of wg; Power 15 KW, 6 Pole, 1250 mm dia for Basement Exhaust.
5000 CFM; SP 20 mm of wg; Power 1.1 KW, 4 Pole, 560 mm dia for Pump Room Exhaust / Fresh Air(Axial )
10000 CFM; SP 30 mm of wg; Power 3.75 KW, 4 Pole, 800 mm dia for - STP Exhaust (Axial )
10000 CFM; SP 20 mm of wg; Power 3.75 KW, 4 Pole, 710 mm dia for - STP Fresh Air (Axial )
20000 CFM; SP 20 mm of wg; Power 7.5 KW, 4 Pole, 1120 mm dia for -HVAC Plant Room Exhaust (Axial )
5000 CFM; SP 20 mm of wg; Power 3.75 KW, 4 Pole, 710 mm dia for LT Room Exhaust/ Fresh Air (Axial )
12000 CFM; SP 20 mm of wg; Power 2.25 KW, 4 Pole710 mm dia for - Staircase & Liftlobby Pressurization(Axial )
8000 CFM; SP 20 mm of wg; Power 1.5 KW, 4 Pole, 710 mm dia for - Liftwell Pressurization (Axial )
10000 CFM; SP 20 mm of wg; Power 1.5 KW, 4 Pole, 710 mm dia for - Liftwell Pressurization (Axial )
37000 CFM; SP 30 mm of wg; Power 15.0 KW, 4 Pole, 1250 mm dia for - Smoke Extraction (Exhaust) Axial
37000 CFM; SP 30 mm of wg; Power 15.0 KW, 4 Pole, 1250 mm dia for - Smoke Extraction (Fresh Air) Axial
All the fans shall be AMCA Certified for Air & Sound
The outlet velocity of normal exhaust/ fresh air fans should not exceed 13 m /s and for smoke exhaust fans should not exceed 18 m /s.
The sound level of Normal exhaust/ fresh air fans should be within 80dB.
The motor shall be suitable to operate through VFD if required.
All Exhaust / Fresh Air fans shall have back draft dampers inbuilt in the cost of the fan
Package Type Air Washers Supply, installation, testing and commissioning of Double Skin Packaged Type Air Washer with 25mm injected PUF insulation of 48KG/m3 , G.I. blower section, DIDW Blower (Backward Curved) with motors , base , drive arrangement ,Filter, cooling pad section, stainless steel sump tank and housing, motor drive, water circulation pump, piping, valves & fittings etc. suitable for Indoor Application as per specifications and drawings . 20000 CFM ; SP 40 mm of wg;Power (4.0 + 0.75 ) kW for HVAC Plant Room Fresh Air Supply
Inline Fans 500 CFM Inline Fan @ 10 MM SP
Propeller Fans 300 mm dia
Fans Section (Double Skin) 3000 CFM @ 30 mm SP (For Toilet Exhaust)
4000 CFM @ 30 mm SP (For Toilet Exhaust)
Chilled Water Piping
Insulation Chiller water Piping (Nitrile rubber Insulation)
(In Risers and Floors)
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.
Note:-The Pipes of sizes 150 mm & below shall be M.S. 'C class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
250 mm dia. (32 mm thick insulation)
200 mm dia. (32 mm thick insulation)
150 mm dia. (32 mm thick insulation)
125 mm dia. (32 mm thick insulation)
100 mm dia. (32 mm thick insulation)
80 mm dia. (32 mm thick insulation)
65 mm dia. (32 mm thick insulation)
50 mm dia. (32 mm thick insulation)
40 mm dia. (32 mm thick insulation)
32 mm dia. (19 mm thick insulation)
25 mm dia. (19 mm thick insulation)
Insulation Chiller water Piping
(expanded polystrene insulation) (In Basement, HVAC Plant Room and Terrace)
Supplying, laying/ fixing, testing and commissioning of followingnominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints repairing of damage to building etc. as per specifications and as required complete in all respect.
Note:-The Pipes of sizes 150 mm & below shall be M.S. 'C class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
300 mm dia. (75 mm thick insulation)
250 mm dia. (75 mm thick insulation)
200 mm dia. (75 mm thick insulation)
150 mm dia. (75 mm thick insulation)
100 mm dia. (75 mm thick insulation)
80 mm dia. (50 mm thick insulation)
65 mm dia. (50 mm thick insulation)
50 mm dia. (50 mm thick insulation)
40 mm dia. (50 mm thick insulation)
Insulated Valves Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Butterfly Valve (Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified 150 mm dia.
125 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. 150 mm dia.
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. 150 mm dia.
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. 150 mm dia.
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Providing & fixing in position the mercury in glass industrial type thermometres.
Flow Switch For Chillers
Condenser Water Piping
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.
Note: The Pipes of sizes 150 mm & below shall be M.S. 'C class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm and above.
250 mm dia
200 mm dia.
150 mm dia.
100 mm dia.
65 mm dia.
Drain Piping
Providing and fixing of GI 'B' class drain piping complete with fittings, supports, 9 mm thick closed cell elastomeric insulation as per specifications and drawings. 40 MM
Valves Without Insulation Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Butterfly Valve (Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating as specified 200 mm dia.
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified. 200 mm dia.
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. 200 mm dia.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Providing & fixing in position the mercury in glass industrial type thermometres.
Flow Switch For Chillers (Condenser side)
Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20 mA electric signal and providing similar transduced feedback output to control system as required. 200 mm dia
Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum. 65 mm dia.
50 mm dia
40 mm dia.
32 mm dia.
DUCTING, GRILLS, DIFFUSER AND INSULATION Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 0.63 mm sheet
0.80 mm sheet
1.00 mm sheet
1.25 mm sheet
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 0.63 mm sheet
0.80 mm sheet
1.00 mm sheet
1.25 mm sheet
Dampers Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.
Supply, installation, testing and commissioning of GI Back Draft damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., complete with 18 Gauge Frame and 20 Guage blades. as per specifications.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
Supplying, installation, testing & commissioning of thermal insulated flexible duct of following sized duly supported at regular interval as per site requirement etc. complete as required as per specifications 200 mm dia.
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Damper
Actuator
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m3, with 25 mm X 25 mm GI section of 1.25 mm thick, at
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50 mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610 mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications.
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. 19mm
Providing and fixing of powder coated extruded aluminium exhaust air louvers/ fresh air louvers with bird screen and mounting arrangement as per specification and drawings.(80 mm Format) a) Fresh Air/ Exhaust Louvers with Bird Screen
Expansion Tank (PVC) Providing and Fixing PVC Expansion Tank with 50 mm thick insulation of self adhesive Trocellene make foam with aluminium foam on one side as per specifications and drawings including all fittings. 1000 Ltrs.
Making suitable cutouts in wall for passing of ducts and suitably repairing the as required.
Panel-A01 (HVAC Plant Room )
INCOMER
2 Nos. 800 Amps FP MCCB
2 No. Digital Type Ammeter 0-1250 A with C.T.'s
2 Set of RYB indication lamps with control MCB
2 No. of 1500 Amps Aluminium conductor 25kA bus bar duly sleeved as required.
1 No. 1250 Amps Bus Coupler
BUS Coupler
1 Nos. 800 Amps FP MCCB
Interlocking
Incomers and Bus Coupler shall be Mechanically interlocked
BUS BAR
800 Amps FP aluminim bus bar 25 kA
OUTGOING
3 No.630 Amps MCCB for Chiller .
2 No. 400 Amps TP MCCB for Hot Water Generator .
6 Nos. 32 Amps MPCB for Cooling Towers .
3 Nos. 40 Amps TP MPCB for Chilled Water Primary Pumps
3 Nos. 63 Amps MPCB for Secondary Chilled Water Pumps
3 Nos. 80 Amps MPCB for Condensor Water Pumps .
1 No. 80 Amps MPCB for Air Washer .
1 No. 16 Amps TP MCB for Air Washer Pump
1 No. 63 Amps MPCB for Plant Room Axial Fan .
6 Nos. DOL Starter for 5.5 Kw Motor (Cooling Tower)
3 Nos. Star Delta starter for 7.5 KW motor. (4 Nos. Primary Chilled Water Pumps)
3 Nos. Star Delta starter for 18 KW motor. (3 Nos. Secondary Chilled Water Pumps)
3 Nos. Star Delta starter for 22 KW motor .(4 Nos Condensor Water Pumps )
1 No. Star Delta starter for 15 KW motor .(1 Nos Air Washer )
1 No. DOL starter for 1.5 KW motor (1 No. Air Washer Pump)
1 Nos. Star Delta starter for 7.5 KW motor .(1 Nos Exhaust Fans )
20 Nos. of single phase preventor (current based-MPRD2)
19 Nos. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A02
INCOMING/OUTGOING
1 No. 32 Amps MPCB
1 No. DOL starter for 5.5 KW motor .
1 No. of single phase preventor (current based-MPRD2)
1 No. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A03
INCOMING/OUTGOING
1 Nos. 32 Amps TP MCB
1 Nos. DOL starter for 7.5 KW motor .
1 Nos. of single phase preventor (current based-MPRD2)
1 Nos. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A04
INCOMING/OUTGOING
1 No. 16 Amps MPCB
1 No. DOL starter for 2.25 KW motor .
1 No. of single phase preventor (current based-MPRD2)
1 No. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A05
( 1 x 3.75 KW) LT Panel Room
INCOMING/OUTGOING
1 No. 16 Amps MPCB
1 No. DOL starter for 3.75 KW motor .
1 No. of single phase preventor (current based-MPRD2)
1 No. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A06
( 1 x 1.5 KW) - AHU & Pump Room
INCOMING/OUTGOING
1 No. 16 Amps MPCB
1 No. DOL starter for 1.5 KW motor .
1 No. of single phase preventor (current based-MPRD2)
1 No. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel Type A07(Basement Ventilation Panel) ( 2 x 15.0 ) KW
INCOMER
1 No. incoming 100 Amps TPN MCCB.
1 Set of RYB indication lamps
1 No. of 120 Amps Aluminium conductor bus bar duly sleeved as required.
OUTGOING
2 Nos. 63 Amps MPCB outgoing for Axial fans-11.0 KW
2 Nos. Star Delta starter for 11.0 KW of Fan Motors .
2 Nos. of single phase preventor (current based-MPRD2)
2 Nos. direct reading digital ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light, A/M Switch.
1 No. Digital Type Ammeter 0-32 A with C.T.'s
1 Set of RYB indication lamps with control MCB
Panel-A08
STP Fresh Air/ Exhaust / Fresh Air Fans at 4th Floor
INCOMER
1 No. incoming 32Amps TP MCB
1 No. Digital Type Ammeter 0-16 A with C.T.'s
1 Set of RYB indication lamps with control MCB
1 No. of 40 Amps Aluminium conductor 25kA bus bar duly sleeved as required.
OUTGOING
2 Nos. 16 Amps MPCB
2 Nos. DOL starter for 3.75 KW motor .
2 Nos. of single phase preventor (current based-MPRD2)
2 Nos. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A09
Liftwell , Liftlobby & Staircase Pressurisation
(6 x 2.25 KW + 4 x 1.5 KW)
INCOMER
1 No. incoming 63 Amps TP MCB
1 No. Digital Type Ammeter 0-80 A with C.T.'s
1 Set of RYB indication lamps with control MCB
1 No. of 80 Amps Aluminium conductor 25kA bus bar duly sleeved as required.
OUTGOING
10 Nos. 16 Amps MPCB
6 Nos. DOL starter for 2.25 KW motor .
4 Nos. DOL starter for 1.5 KW motor .
10 Nos. of single phase preventor (current based-MPRD2)
10 Nos. direct reading Digital Type Ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light
Panel-A10
Toilet Exhaust Fan Section
INCOMER
1 No. incoming 20 Amps TPN MCCB.
1 Set of RYB indication lamps
1 No. of 32 Amps Aluminium conductor bus bar duly sleeved as required.
OUTGOING
2 Nos. 16 Amps MPCB outgoing for AHU Fan Section
2 Nos. DOL Starter for 1.5 KW of Fan Motors .
2 Nos. of single phase preventor (current based-MPRD2)
2 Nos. direct reading digital ammeter
Each star-delta/DOL starter consists of current operated MN type over load relay, contactor, push button, ON/OFF indication light, A/M Switch.
Weather Proof Isolators Supply, installation, testing and commissioning of out door weather proof switch box of continuous welded construction, fabricated out of 2 mm thick G.I. sheet complete with water tight gasket with front openable and lockable door including earthing, painting, glands,danger boards etc.suitable for mounting on wall with M.S. angle iron frame of size 40x40x6 mm consisting of relevant I.S. specifications and drawings. 40 Amps TPN Isolator for cooling tower
16 Amps TPN Isolator
Cables
Supplying, laying, testing and commissioning of XLPE insulated aluminium conductor armored cables of 1.1 KV grade of following sizes directly on wall/structural frame/ cable trays or racks using approved type of clamps,With/ Without End terminations with Double Compression type glands on both ends, double earthing with GI strip/wire of suitable size and hardware as per specifications including terminatio of cables to feeders complete in all respect.
3 C x 10 Sq. mm
3 C x 6 Sq. mm
3 C x 4 Sq. mm
Control Cabling(Copper) Unarmoured
2C x 1.5 sqmm
3C x 1.5 sqmm
GI perforated Cable tray to carry Cables from panel to Fans , all inclusive
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts& nuts, painting suspenders etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 50 mm depth X 2.0 mm thickness
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Supplying of following 1100 volt grade XLPE insulated PVC sheathed aluminium / Copper conductor armoured cables as per specification as required. 3.1/2 core 185sq. mm.
3.1/2 core 95sq. mm.
3.1/2 core 70sq. mm.
3.1/2 core 50sq. mm.
3.5 core 25sq. mm.
4 core 16sq. mm.
4 core 10 sq. mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ STONE WARE / METAL pipe/ Cable Trays as required.
Upto 25 sq. mm
Above 25 sq. mm and upto 400 sq. mm
Supplying and making end termination of following sizes with brass compression gland including providing and crimping solderless plugs/ferrules of sizes PVC insulated PVC sheathed aluminum conductor armoured cable 1.1 KV grade.
3.1/2 core 185sq. mm.
3.1/2 core 95sq. mm.
3.1/2 core 70sq. mm.
3.1/2 core 50sq. mm.
3.1/2 core 35sq. mm.
3.1/2 core 25sq. mm.
4core 16sq. mm.
4 core 10sq. mm.
LOOSE FURNITURE WORKS
Providing /placing (T1) MAYOR/COMMI. Table Main desk - 2500X1100X750, Eru + Ped 406X550X640 + Credenza - TABLE TOP & Gable end : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
Providing /placing (T2) HEAD- Table Main desk - 2700X1000X750, Eru + Ped 406X550X640 WITH Credenza -TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color. Leg with powder coated finish.
Providing /placing (T3) SUB. HEAD- Table Main desk - 2100 x 2250 x 750 + Ped 406X550X640 Credenza 1800X425X1215 .TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
Providing /placing (T5,T4) EXECUTIVE- Table Main desk - 1804X750X750 , Eru 1380X480X700 + Ped 406X550X640 Credenza - 1804X450X750 Table Main desk - 2100 x 2250 x 750 + Ped 406X550X640 Credenza 1800X425X1215 .TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate
Providing /placing (T6) JUNIOR/P.A- Table Main desk - 1650X700X743 With low ht. credenza- 1500X425X1215. TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate
Providing /placing (T8) JUNIOR- Table Main desk - 1650X700X743, + Ped 406X550X640.TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate
Providing /placing (T9) JUNIOR- Table Main desk - Table Main Desk- 1200 x 600 x 743 + Ped 406X550X640 + Credenza 1210X425X1215 .TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate
Providing /placing (T10) COURT ROOM TABLE - 2200X1190X750, + Ped 406X550X640..TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate
L - SHAPED WORKSTATION
TABLE TOP : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.
MAIN SPINE :- 45 mm thick panel based systems 1200mm(HT).Base shall be formed as approved powder coating on aluminium & fabric panel.
GABLE :-25 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SIDE UNIT WITH SHUTTERS (900X450X750 MM ): 18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SIZE:- 1450X600X750/1200MM - Ground Floor
SIZE:- 1450X600X750/1200MM - First Floor
SIZE:- 1450X600X750/1200MM - Second Floor
SIZE:- 1450X600X750/1200MM - Third Floor
SIZE:- 1450X600X750/1200MM - Fourth Floor
SIZE:- 1450X600X750/1200MM - Fifth Floor
LINEAR WORKSTATION
TABLE TOP : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.
MAIN SPINE :- 45 mm thick panel based systems 1200mm(HT).Base shall be formed as approved powder coating on aluminium & fabric panel.
GABLE :-25 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
MOVABLE DRAWER (2D+1F): 18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SIZE:- 1650X600X750/1200MM - First Floor
SIZE:- 1650X600X750/1200MM - Second Floor
SIZE:- 1650X600X750/1200MM - Fourth Floor
KIOSK- Manager Module (2400 x 1500) TABLE TOP : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.LEGS& BEAM:- 50mm x 50mm CRC square pipe with powder coated finish as per approved shade.MODESTY PANEL :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color. PARTITION :- 45 mm thick panel based systems 1200mm(HT).Base shall be formed as approved powder coating on aluminium & fabric panel.
RECEPTION TABLE- First Impression TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate .metal perforted panel with powder coated.
Providing /placing (BT) Conference Room Table make - coustmized TABLE TOP : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.BASE Metal under structure with powder coated finish. (Size:- 750X600X750MM Per Seat )
Providing /placing (BT1) Board Room Table make - coustmizedTABLE TOP : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.BASE Metal under structure with powder coated finish (Size:- 750X600X750MM Per Seat )
Providing /placing (MT) Board Room Table -10 seater, DIA - 1500 TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate.
Providing /placing (MT1) Board Room Table 08 seater TABLE TOP & Gable End : 25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color. Rest All :-18 Mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate.
WORKSTATION & RECEPTION- Model No AFC- 206 Providing & Placing Model -Cushion chair on tubular frame with arm cantilever type made of dia 2.5cm X 14BG MS ERW round Tube with black powder coated paint, seat height 43cm, back height 80 cm.
SIDE TABLE- Corner Table Model No. AFC -748
CENTER TABLE- Providing /placing (CT3) center table size 1000X600X560mm .Center Table Model No. AFC -749
Providing /placing (SD2) 1 seater sofa size 930X850X890mm 1 -Seater MODEL NO AFC-608
Providing /placing (SD1) 2 seater sofa size1250X850X890mm 2 seater MODEL NO AFC-608
Providing /placing (SD) 3 seater sofa size1820X850X890mm 3 Seater MODEL NO AFC-608
3 Seater Chair with following specification: Seat Shell - Seat shell is welded assembly of seat, Back & side frame. Seat & back are made of 0.12±0.013cm thk CR steel sheet with oblong perforations. They are welded to side frame of size 3.2±0.05cm X 0.5±0.05cm thk HR steel. Welded assembly is powder coated (DFT 40-60 microns). Seat has a front warefall edge for comfortable seating and also has a buttock support curve. Understructure Assembly - Consists of connecting beam & leg assembly made of MS ERW oblong tube size 7.5±0.03cm X 5.0±0.03cm X 0.02±0.016cm thk and is powder coated (DFT 40-60 microns). Leg assembly is fitted with shoes and levellers in Nylon. Leg assembly is designed with minimal area of contact close to ground providing easy access for cleaning purposes. Connecting beam is fitted with snap locking end capfor side by side understructure alignment. Arm Rest Assembly - Consists of arNSIest frame & arNSIest pad.ArNSIest frame is made up of size 3.175±0.05cm X 0.47±0.027 cm thk HR steel and is powder coated (DFT 40-60 microns). ArNSIest pad is injection moulded in nylon and is fitted onto the arNSIest frame. Model No. AFC-611
CAFÉ TABLE - 900 DIA MODEL NO. AFC - 730
CAFÉ TABLE - 1125 DIA - MODEL NO. AFC - 730
CAFÉ CHAIR -Providing /placing (DC1) Dining Chaire
CABINS & CUBICALS- Providing /placing (CV1) CHAIRE Mid Back MODEL NO . AFC- 145
CABINS & CUBICALS- Providing /placing (CV2) CHAIRE Visitor MODEL NO . AFC- 148
MAYOR & COMMISSIONER- Providing /placing (CK) CHAIRE High Back MODEL NO . AFC- 144
MAYOR & COMMISSIONER- Providing /placing (CK1) CHAIRE Mid Back MODEL NO . AFC- 145
STORAGE OF 600 WX750 H
TOP:25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.
SHUTTER :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SHELF :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
STRUCTURE :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
STORAGE OF 450 WX750 H
TOP:25mm thick PLPB board with 2mm thick PVCedge banding finish with as per approved laminate color.
SHUTTER :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SHELF :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
STRUCTURE :18mm thick PLPB board with 2mm thick PVCedge banding.Finish with as per approved laminate color.
SOLAR SYSTEM CUMULATIVE PLANT CAPACITY 80 KW. all complete as per building specification and direction of E/l.
M/s Daroga Pradhan
BALKRISHNA BHALOTIA CONST.PVT.LTD
M/S RAM KRIPAL SINGH CONSTRUCTION PRIVATE LIMITED
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.19 MB
BOQ_50454.xls
BOQ • 1.09 MB
SBD-DHANBADBUILDING.pdf
Tender Documents • 13.15 MB
Download all tender documents and submit your bid