| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC | ₹13.5 L Quoted ₹13.7 L | L1 | Accepted-AOC L1 BIDDER |
| 2 | L2₹15.2 L+₹1.4 L (10.5%)Rejected-Finance | ₹15.2 L+₹1.4 L (10.5%) | L2 | Rejected-Finance Not Lowest |
| 3 | L3₹15.6 L+₹1.9 L (13.6%)Rejected-Finance 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | ₹15.6 L+₹1.9 L (13.6%) | L3 | Rejected-Finance Not Lowest |
| 4 | L4₹17.2 L+₹3.5 L (25.4%)Rejected-Finance | ₹17.2 L+₹3.5 L (25.4%) | L4 | Rejected-Finance Not Lowest |
| 5 | L5₹17.6 L+₹3.9 L (28.1%)Rejected-Finance | ₹17.6 L+₹3.9 L (28.1%) | L5 | Rejected-Finance Not Lowest |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
12 Feb 2021, 6:00 pmClosed
Garrison Engineer P Navy Kalinga Visakhapatnam
Garrison Engineer P Navy Kalinga Military Engineer Services INS Kalinga PO Visakhapatnam 531 163
REPAIR AND MAINTENANCE TO CERTAIN SUB STATION, LT DISTRIBUTION SYSTEM CAPACITOR BANKS AND OTHER ALLIED WORKS AT INS KALINGA
2021_MES_413022_1
GE (P)/N/K/8762 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer P Navy Kalinga Visakhapatnam
Class E, Category b (i)
6 documents required · 6 mandatory
₹500
Garrison Engineer P Navy Kalinga Visakhapatnam
₹40,000
Yes
18 May 2021
15 Jan 2021
15 Feb 2021
15 Jan 2021
12 Feb 2021
30 Jan 2021
Amount
Excavation in trenches in soft / loose soil not exceeding 1.5 Mtr in wide and not exc. 1.5m in depth for taking out / laying of under ground cable in trenches or cable ducts all complete all as specified.
Returning, filling in including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick in soil after repairing / jointing and laying and testing of cables complete all as specified
Removing surplus soil to a distance not exceeding 50 Mtr and deposited at a level not exceeding 1.5 mtr above from the starting point complete all as specified
M&L for natural river sand as cushioning of cables including spreading and punning down all as per clause No 19.75 of MES SSR part -I all as specified. (Note : Punned thickness shall be measured for payment purpose)
Supply and lay fly ash brick of size 200x100x80mm locally available as protection of cable in trenches complete all as specified and as directed by Engineer in charge
Labour charges for re-laying of serviceable bricks of any size and type recovered during taking out of old cable , over newly laid or re-laid cables all complete as specified and as directed.
M&L for cutting existing road / PCC drain for taking out / laying of underground cable and including necessary earth work and making good to match with the existing surface with PCC 1:3:6 type CI using 20mm graded aggregates complete all as specified
M&L for 50mm dia GI pipe medium grade galvanised for cable protection and sealing both ends including taking out old pipe complete all as specified.
M&L for 80mm dia GI pipe medium grade galvanised for cable protection and sealing both ends including taking out old pipe complete all as specified.
M&L for 100mm dia GI pipe medium grade galvanised for cable protection and sealing both ends including taking out old pipe complete all as specified.
Taking down or out existing cable of sizes 2/3.5/4 core 10 sqmm to 70 sqmm from the trenches / ducts/ along walls / poles / through poles / under roads/ inside sub station including segregation the serviceable cable by cutting down defective portion after testing by meggar (insulation tester ) , stacking and rolling unserviceable cable for further disposal all as directed by Engineer in charge (Note :(1) Excavation / cutting of road or floor/ GI pipe & laying / relaying of cable etc shall be measured and paid separately under respective item of this schedule)
All as per Item No 11 here-in-before but for cable of size 3.5 core 95 sqmm to 300 sqmm
Relaying only serviceable cable obtained from taking out in same or new location or through cable ducts inside sub station of size 2/3.5/4 core 10 to 70 sqmm in trenches / ducts / along walls / poles / under road etc including necessary cable lugs, glands etc complete all as specified and as directed (Note :- Lugs and Glands will be measured and paid separately)
All as per Item Sl Item No 13 here-in-before but for cable of size 3.5 core 95 to 240sqmm
S&F in repair XLPE insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 16 sqmm 4 core including necessary cable lugs, glands, insulation tape etc complete all as directed and specified.
All as per Item Sl Item No 15 here-in-before but for cable of size 16 sqmm 2 core
All as per Item Sl Item No 15 here-in-before but for cable of size 25 sqmm 4 core
All as per Item Sl Item No 15 here-in-before but for cable of size 35 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 50 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 70 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 95 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 120 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 185 sqmm 3.5 core
All as per Item Sl Item No 15 here-in-before but for cable of size 240 sqmm 3.5 core
M&L straight through joint (Heat Shrinkable) for under ground PVC insulated and PVC sheathed armoured heavy duty XLPE cables with aluminium conductor including jointing kit, including making joints for the cable of size 10/16 sqmm x 2/4 core cables including testing and commissioning complete all as specified and as directed.
All as per Item Sl Item No 25 here-in-before but for cable of size 25 to 50 sqmm x 3.5 / 4 core, as per the size of existing UG cable.
All as per Item Sl Item No 25 here-in-before but for cable of size 70 to 120 sqmm x 3.5 / 4 core, as per the size of existing UG cable.
All as per Item Sl Item No 25 here-in-before but for cable of size 150 to 185 sqmm x 3.5 / 4 core, as per the size of existing UG cable.
All as per Item Sl Item No 25 here-in-before but for cable of size 240 to 400 sqmm x 3.5 / 4 core, as per the size of existing UG cable.
M&L LT outdoor End joint (Heat Shrinkable) for under ground PVC insulated and PVC sheathed armoured heavy duty cables with aluminium conductor including jointing kit, including making joints for the cable of size 185 sqmm x 3.5 / 4 core cables including disconnecting the cable from the 433 Volt LT side of the transformer, reconnecting it to the transformer after the fixing of the joint, testing and commissioning complete all as specified and as directed.
S&F in repair 400 Amp, 4 Pole MCCB, 50 KA, 415V, 50 Hz, AC supply, Ics=100% Icu, adjustable Overload 80-100%, thermal magnetic release mechanism including necessary cable lugs & wire etc complete all as specified and directed.
All as per Item Sl Item No 31 here-in-before but of capacity 250 Amp, 4 pole MCCB, Icu=35/36 KA
All as per Item Sl Item No 31 here-in-before but of capacity 250 Amp, 3 pole MCCB, Icu = 35/36 KA
All as per Item Sl Item No 31 here-in-before but of capacity 200 Amp, 3 pole MCCB, Icu = 26 KA
All as per Item Sl Item No 31 here-in-before but of capacity 200 Amp, 4 pole MCCB, Icu = 26 KA
All as per Item Sl Item No 31 here-in-before but of capacity 125 Amp, 4 pole MCCB, Icu = 18 KA
All as per Item Sl Item No 31 here-in-before but of capacity 63 Amp, TP MCCB, Icu = 18 KA
S&F in repair resin cast wound/ring type CT 50A / 5A class 1.0 in 433 Volt LT panel boards after disconnecting the old ones from site all complete as specified and directed.
S&F in repair aluminium lugs suitable for 240 Sqmm LT UG XLPE aluminium conductor Cable including nuts, bolts and washers complete all as specified and as directed.
All as per Item Sl Item No 42 here-in-before but for cable of size 185 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 120 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 95 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 70 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 50 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 25 Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 16 Sqmm Sqmm
All as per Item Sl Item No 42 here-in-before but for cable of size 400 Sqmm Sqmm
M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised earth strip 32x6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3, connected to earthing point of outdoor panel boards all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber & RCC 1:2:4 type B1 cover 40mm thick, with 8mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 20mm dia GI medium grade pipe for watering , water funnel, complete all as specified and testing on completion.
S&F in repair 400 Amp, 4 Pole Change over switch, 50 KA, 415V, 50 Hz, AC supply, I - O - II operation, manual type, open construction or closed type construction as per site requirement, adjustable type of thermal and magnetic setting, handle, including necessary cable lugs & wire etc complete all as specified and directed.
S&F in repair 250 Amp, 4 Pole Change over switch, 50 KA, 415V, 50 Hz, AC supply, I - O - II operation, manual type, open construction or closed type construction as per site requirement, adjustable type of thermal and magnetic setting, handle, including necessary cable lugs & wire etc complete all as specified and directed.
S&F in repair 160 Amp, 4 Pole Change over switch, 50 KA, 415V, 50 Hz, AC supply, I - O - II operation, manual type, open construction or closed type construction as per site requirement, adjustable type of thermal and magnetic setting, handle, including necessary cable lugs & wire etc complete all as specified and directed. MAKES : Legrand / Siemens / ABB/C&S/ L&T / Havells
M & L for testing of XLPE UG cables, for continuity or/and insulation resistance by Meggar and/or other testing machines and finding of faults in 433 Volt system and rectifying the fault and making the electric supply line serviceable all complete as specified and directed by Engr-in-Charge. Note : (i) Items like cables, lugs, and cable joints, excavation, refilling of soil will be paid through the specific Sch 'A' items in this schedule. (ii) M&L has to be made available on the site on emergency basis when the fault occurs, irrespective of the time of the day. (iii) Contractor should take necessary night permission for his technicians, and supervisors after the awarding of the contract. (iv) The quoted rate must include the cost of minor consumables like, insulation tapes etc.
S&F in repair double compression weatherproof brass cable gland heavy duty , nickel plated of size OD 23mm-26mm (cable size 10/16 sqmm) all complete as specified and as directed (Note: The quoted rate is inclusive of disconnecting the existing cable from electrical panel board and reconnecting it to the panel board after replacing the gland.)
All as per Item Sl Item No 56 here-in-before but of size OD 26mm - 30mm (cable size 25/35 sqmm)
All as per Item Sl Item No 56 here-in-before but of size OD 33mm - 37mm (cable size 50/70 sqmm)
All as per Item Sl Item No 56 here-in-before but of size OD 41mm - 46mm (cable size 95 / 120 sqmm)
All as per Item Sl Item No 56 here-in-before but of size OD 52mm - 61mm (cable size 185/240 sqmm)
M&L for disconnecting, remove the electric supply of existing APFC panel, complete repairs and servicing the panel including remove and replacement of power factor contactors, relays, CT, indication lamps, capacitor banks, any make/ any capacity and calibration of APFC relay changing of copper wire for control wiring, for indication lamps, lugs, bolts and nuts and decarbonising, blowing with blower the panel board complete all specified and directed of capacity up to 250 KVR capacitor bank, complete testing and commissioning the panel all as directed and specified by Engineer in charge. (Note: - Capacitor, contactor, indication lamps, CT and APFC relay, shall be measured and paid separately.)
Supply only Cylindrical capacitor super heavy duty 15 KVAr, 3Phase, 50Hz, 440V to fixed in repairs, complete all as directed by Engineer in charge. (Make : HAVELLS Cat Part No. QHSTCC5015X0 or equivalent as approved by GE)
Supply only Cylindrical capacitor super heavy duty 12.5 KVAR, 3Phase, 50Hz, 440V to fixed in repairs, complete all as directed by Engineer in charge. (Make : HAVELLS Cat Part No. QHSTCC5012X5 or equivalent as approved by GE)
Supply only Cylindrical capacitor super heavy duty 25 KVAR, 3Phase, 50Hz, 440V to fixed in repairs, complete all as directed by Engineer in charge. (Make : HAVELLS Cat Part No. QHSTCC5025X0 or equivalent as approved by GE)
R AND A ASSOCIATES ENGINEERS CONTRACTORS
suresh electricals
SAI ENGINEERING WORKS
SWATHI CONSTRUCTIONS
SATYAM ENGINEERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .