Executive Engineer
Dist Hospital Campus Saktinagar Krishnagar Nadia
EI work for the Establishment of blood bank of old isolation ward in the dist of Nadia SITC of Online 10 KVA UPS
2025_WBPWD_822481_1
WBPWD/EE/NED/NIQ/e-T/96/ (1st Call)24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
25 days
Dist Hospital Campus Saktinagar Krishnagar Nadia
Please refer Tender documents.
5 documents required · 5 mandatory
₹11,000
Nadia Electrical Division
30 Apr 2025
3 Mar 2025
19 Mar 2025
3 Mar 2025
17 Mar 2025
5 Mar 2025
5 Mar 2025
Amount
Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3% Output Frequency: 50 Hz +/- 0.1% Output Power Factor: 0.9 Crest Factor: 3:1 THDu: < 2% (linear load), < 5%(non linear load) Birdge: Microprocessor based and IGBT Technology Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute. Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms Overall Efficiency: 94% Battary Cabinet: With power coated MS angle with MS sheet suitable dimention and gadge, well air ventilation to ensure the battery optimum life cycle.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary accessories. Battery : 12 V, Mono Block batteries. SMF VRLA DC Bus : Minimum 192V or above, 60 mim back up required (Minimum 15600 VAH) Battery. Battery Make: Exide/ Amar Raja (Quanta) Protections: Input & Output Over / Under Voltage, Single Phasing DC - High / Under Voltage, Battery Charging Over Current, Output Overload / Short Circuit / Over Temp., UPS auto ON on Mains recovery
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch Termination: Input, Battery, Output & Bypass Enclosure: IP 20 Operating Temp: 0 to 40 Deg C Humidity: Upto 95% Rh (non-condensing) Cooling: Forced Air Noise: < 70 dB Cold Start : Provided
Parallel Redundant facitities should be present for each unit with Accessories Communication: RS 232, RS 485, Dual input Kit, Monitoring Software: UPS Monitoring Software on Windows XP Platform Certification : ISO 9001: 2008, ISO 14001: 2004, ISO 18001, RoHS and OHSAS 18001 CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture) Parallel Redundant facitities should be present for each unit with Accessories Monitoring Software: UPS Monitoring Software on Windows XP Platform Warranty-2-Years on UPS & 2-Years on SMF Batteries
LOKNATH ENGINEERING (BID ID -6226665)
T.D.K. ENTERPRISE (BID ID -6238421)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .