| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.9 LAccepted-AOC 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹43.0 L+₹157 (<0.01%)Rejected-Finance 65 RANJEET NAGAR NEAR SAI HOSPITAL AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹48.7 L+₹5.7 L (13.2%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
26 Jun 2023, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
REPAIR MAINT OF LT ELECTRIC DISTRIBUTION SYSTEM AT ORS JCOS MD ACCN AND UNITS LOCATED UNDER ALFA POWER HOUSE UNDER GE UTILITY AMBALA CANTT
2023_MES_593368_2
CA NO GE U AMB T 34 OF 2023-24
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹96,000
12 Jul 2023
5 Jun 2023
28 Jun 2023
5 Jun 2023
26 Jun 2023
12 Jun 2023
5 Jun 2023 - 8 Jun 2023
Amount
Excavation in trenches n.exc 1.5 Mtr wide and n,exc 1.5 Mtr in depth loose/soft and greating out for underground cable/erection of poles, stays etc complete all as specified and as directted by Engeer-in-Charge.
Earth work in excavation by mechanical means (Hydraulic excavator) means over areas (exceeding 1.5 m in width but n.exc 1.5 m depth as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5m, as directed by Engineer-incharge.
All as per Srl Item No. 2 here in before but exceeding 1.5 mtr deep but not exc 3.0 mtr deep.
Material and labour sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and as directed.
Supply and laying bricks common burnt clay sub classs 'B' old size for cable protection
All as per item Ser No 5 here in before but except bricks Note : Old bricks retrieved from item No 22 & 35 here in after shall be used after cleaning and washing.
Material & labour for cement concrete in foundations, filling and mass concrete PCC as foundation to poles, type D2, 1:4:8 using 40 mm graded stone agregate as foundations to poles all as specified.
Material & labour for Cement concrete, filling and mass concrete, PCC type C1, 1:3:6 using 20 mm graded aggregate including necessary form work complete all as specified.
Material & labour for cement concrete as coping to poles, PCC type B1, 1:2:4 using 20 mm graded stone aggregate all as specified.
Returning, filling in (Soil) including spreading, levelling, watering and well ramming in layers not exc 25CM thick layers complete all as specified and as directed by Engineer-in-Charge.
Removal of excavated material n,exc 50 Mtr away and depositing depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge
Supply erection of PCC pole 9.0 mtr long in true vertical position 102x172 mm at top 102x279 mm at bottom class-10 incl providing black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip including taking down old pole complete all as specified and as directed by Engr-in-Charge. Note: Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply erection (in true vertical position) Steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts & screws all as specified of type 410 SP-31 ( 9.0 mtr length) complete all as specified in IS 2713 (Part-II) 1980 including one coat of red oxide primer and two coats of aluminium paint to exposed surfaces incl providing of two coats of black and white radium tape strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip and with black bituminus paint for embedded portion of pole including taking down old poles compete all as specified and as directed by Engr-in-Charge. Note: Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.50 x 400 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work shall be measured and paid seperately.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work shall be measured and paid seperately.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as directed by Engr-in-Charge. Note: Earth work shall be measured and paid seperately.
M&L for drilling hole of any size manully as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as per direction of Engr-in-Charge. Note: Pipe shall be measured and paid for seperately.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, watt etc.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc, Note : (i) Earth work, sand , bricks removing, returning filling Aluminium thimbles/lugs will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per item ser No 23 here in before but for 3.5 core 25 Sqmm
All as per item ser No 23 here in before but for 3.5 core 35 Sqmm
All as per item ser No 23 here in before but for 3.5 core 50 Sqmm
All as per item ser No 23 here in before but for 3.5 core 70 Sqmm
All as per item ser No 23 here in before but for 3.5 core 95 Sqmm
All as per item ser No 23 here in before but for 3.5 core120 Sqmm
All as per item ser No 23 here in before but for 3.5 core 150 Sqmm
All as per item ser No 23 here in before but for 3.5 core 185 Sqmm
All as per item ser No 23 here in before but for 3.5 core 240 Sqmm
All as per item ser No 23 here in before but for 3.5 core 300 Sqmm
All as per item ser No 23 here in before but for 1 core 400 Sqmm
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, will etc and locate the fault, rectify, the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminium conductor heavy duty 1100 volts including and testing for any size complete as directed by Engr-in-charge (Excavation/earth work & sand cushioning, brick and joint shall be measured & paid for seprately).
Supply and fixing in replacement stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv. Note: Only excavation and PCC work will be measured and paid seperately.
M & L in replacement cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primercoat, one under coat and one finishing coat of paint.
M & L in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed by Engineer-in-Charge.
M & L in replacement for pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm hight and 65 mm dia with GI spindle two washer and one GI nut complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as per direction of Engr-in-charge.
M&L for aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified by Engr-in-charge.
M&L in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as directed by Engr-in-Charge.
Dismantling and taking down old u/s earthing and material and labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick burind directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of rarth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and as directed by Engr-in-charge. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, RCC cover shall be 50mm thick in PCC 1:2:4 type B-1 using 8mm TMT bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
Dismantling and taking down old u/s earthing and material and labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick burind directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of rarth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, cover 50mm thick RCC 1:2:4 type B-1 using 8mm for steel bars @ 10 cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20 mm bore nedium grade , funnel, wire mesh, also including earth work, common salt, charcol dust complete all as specified and as directed by Engr-in-charge. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, RCC cover shall be 50mm thick in PCC 1:2:4 type B-1 using 8mm TMT bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost
M&L for fixing in replacement GI tubing 50 mm bore light grade, on poles, on walls, under floors, road crossing as reqd at site complete all as directed by Engr-in-Charge. Note : Clamps, Nut bolts, saddle etc will be measured and paid seperately.
All as per item No. 45 here in before but 80 mm dia.
Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 630 Amps, 415 Volts, 50 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type incl complete connection all as per direction of Engr-in-Charge.
M&L for detecting fault in cable of any type with fault locator equipment which is capable to supply as per cable of serviceable to cable Note :- (a) The fault which is detected through cable fault locater will only be paid under this item (b) Charges of Cable fault locator and DG set including transportation charges deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single fault no delay on this account will be acceptable otherwise penality will leived Rs 500/- per day. (d) Necessary testing of cable after making joint will be deemed to be including in the cost of relevent item. However necessary earth work cable cutting, joint making joint will be paid under relevant item.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete as per direction of Engr-in-Charge.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete as per direction of Engr-in-Charge.
Re-streteching existing/retrieved ACSR conductor on LT pole and building conductor on insulator properly using new binding wire/jumper wire complete all as directed at site by Engr-in-Charge. Note : (i) Each Run of line conductor shall be measured & paid for separetly.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185 sqmm incl dismantling old thimbles of any type.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm incl dismantling old thimbles of any type.
Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete, all as specified and as directed.
Material & Labour for painting cleaning and repair of LT panel size upto 0.6 x 0.6 x0.6 mtr after cleaning of surface including removing rusted particles removing dust, tightening nut, bolts wlding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as directed. Note : (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates.
Material & Labour for painting cleaning and repair of LT panel size upto 1.2 x 1.2 x0.6 mtr after cleaning of surface including removing rusted particles removing dust, tightening nut, bolts wlding and painting on complete panel two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as directed. Note : (i0 Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates.
Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles , painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl reparing and painting on coping with cement base white paint complete all as directed. Note : (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC
Material & Labour for cement base paint for PCC pole 9 mtr including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc incl incl reparing and painting on coping with cement base white paint complete all as directed. Note : (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the reparing of coping with cement / PCC
M&L for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge
Supply and fixing in repair on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of Lithium based Energy Efficient Integrated Solar Street Light of 25 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 64/66Wp , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700°K - 6500°K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10°C to (+)55°C, weight not more than 16-18kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 4-6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed Make:-Surya/ Axxon/ Phillips/ Bajaj/ Wipro/ Havells
Taking down old unsv switches and S & F of Automatic street light control with infrared sensor based NATRURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) . Three phase load of 8 KW for automatic switching of street lights. Nature switch operation should be based on Natural light Lux level . Required illuminance level for switching ON is < 30 Lux and for switching OFF < 10 Lux. The sensor should also have part night operation facility of min, 4 hrs to max 12 hrs, VMS should have adjustable over & under voltage trip level and protection against phase loss, Beutral loss & phase reverse incl power contractors (63Amos) and incoming-outgoing MCB rating of 63 Amps & main load circuit wiring (Copper) of minimum 16 sqmm. The sensor, VSM power contractor, MCBs incl connected items should be enclosed in a pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP54. The circuit should also have provision for manual operation (i.e sensor & VMS by pass option) Model swadeep-02EC8kW1P-VMS or equivelent in Schneider/Havells/Legrand. Make (i) Nature switch : Kakatiya Energy Systems/Healer/Bajaj (ii) Power contractor - L&T / BCH/Schneider (iii) Voltage Controlling Device - L&T (iv) MCB- Hager/Schneider/L&T/Legrand, (v) Enclosure & circuit sheet - Sintex (shock proof , rust proof, termite proof, FR rade) (v) Circuit wiring-Polycab/Finolex Note (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 yers . (iii) The test certificate and warranty cirtificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
M&L Chemical spray (DC>2.26 having container 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed by Engr-in-Charge.
Supply, Install, Test and Commissioning of LT feeder piller box outdoor type fabricated of size 0.6x0.6x0.5M,out of 3.00 mm thick CRCA sheet, CPRI approved complete with powder coating with seven tank process mounted on MS angle frame of size 40x40x5mm, duly grounted with PCC using concrete 1:2:4 type B-1 reqd with the following
S & F copper bus bar 200 Amp with coloured heat shrinkable insulated sleeve 415 volts as per IS of suitable size mounted on DMC/epoxy insulator (not than 50mmx50mm conicle type at a maximum interval of 500 mm - 01 Set.
S&F MCCB FP 63 Amps 10 KA - 01 No For Main incoming
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
Panel drawing shall be got approved before placing of order from Engr-in-Charge.
The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.
Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate.
Cable will be entered in panles through gland.
Dismantling and taking down old unsv LT Panel and Supply, Install, Test and Commissioning outdoor type cubical panel board of size 2.0 x1.5 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl Copper bus bar of 1000 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat 7 stage painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-
Supply and fixing MCCB 630 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming) - 01 Nos
Supply and fixing MCCB 400 Amps, 415 volt 4 pole breaking capacity 36 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos
Supply and fixing MCCB 315 Amps, 415 volt 4 pole breaking capacity 36 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos
Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos
Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 03 Nos
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.
Dismantling and taking down old unsv LT Panel and Supply, Install, Test and Commissioning outdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl Copper bus bar of 630 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat 7 stage painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-
Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming) - 01 Nos
Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 36 KA,Adjustable type , ISI marked all. Outgoing) - 04 Nos
Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.
Dismantling and taking down old unsv LT Panel and Supply, Install, Test and Commissioning outdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl Copper bus bar of 630 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat 7 stage painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-
Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming) - 01 Nos
Supply and fixing MCCB 315 Amps, 415 volt 4 pole breaking capacity 35 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos
Supply and fixing MCCB 200 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
Supply and fixing MCCB 100 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.
Dismantling and taking down old unsv LT Panel and Supply, Install, Test and Commissioning outdoor type cubical panel board of size 1.2 x1.0 x0.5M, outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl Copper bus bar of 630 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-
Supply and fixing MCCB 400 Amps, 50 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming) - 01 Nos
Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 03 Nos
Supply and fixing MCCB 100 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 01 Nos
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete.
Dismantling and taking down old unsv LT Panel and Supply, Install, Test and Commissioning outdoor type cubical panel board of size 1.2 x 1.0x0.5M ,outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platfrom 60 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley ( Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad locking on both doors incl 2 No of pad locks of three keys shall be used to make the outer shall completely vermin proof suitable for 3 phase 4 wire 415 volt, 50 Hz, incl AL bus bar of 500 A, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction conforming to IS 8623/93 comprising of the following :-
Supply and fixing MCCB 315 Amps, 36 KA 4 pole 415 Volts AC, Adjustable type , complete all as directed by Engr-in-Charge. (Incoming) - 01 Nos
Supply and fixing MCCB 250 Amps, 415 volt 4 pole breaking capacity 25 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
Supply and fixing MCCB 100 Amps, 415 volt 4 pole breaking capacity 16 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
Supply and fixing MCCB 63 Amps, 415 volt 4 pole breaking capacity 10 KA,Adjustable type , ISI marked all. Outgoing) - 02 Nos
RYB indication LED type 22.5 mm dia protected with MCB SP 2 Amp showing 3 phase supply - 03 Nos
Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, Sleeves, glands etc complete. Note for item No 70 to 74
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
Panel drawing shall be got approved before placing of order from Engr-in-Charge.
The bus bar connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated.
Cost of making description on the front door as per direction of Engr-in-Charge is encl in quoted rate.
Cable will be entered in panles through gland.
Cost of marking descreption on the front door as per direction of Engr-in-Charge
Dismantling and taking down UNSV LED street light/security/flood lights upto 90 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections all as directed by Engr-in-charge. Note : (i) Cost of repair and driver is incl in quoted rate. (ii) If repair is not possible then replacement of street/security light will be measured and paid seperately under relevent items.
Dismantling and taking down UNSV LED street light/security/flood lights upto 200 watt after disconnection electric supply and fix again after repairing of unsv AC/DC drivers incl proper connections all as directed by Engr-in-charge. Note : (i) Cost of repair and driver is incl in quoted rate. (ii) If repair is not possible then replacement of street/security light will be measured and paid seperately under relevent items.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 70 watt system wattage and high pressure die cast aluminium housing with sealed toughened glass cover, TOP opening separare driver compartment with frame, IP 66 protection suitable for pole mounting SMD LED array with lense, cool white 6500 K, LED efficacy>120lm/W and system efficacy 90 lm/w 240 volts AC, 50 Hz CRI>70% operating voltage range 160 V-270 V, power factor>0.95, working temperature range -20 degree C to 60 degree C, built in surge protection of more than 5kv with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting, welding, drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
All as per item No. 77 here in before but for 90 Watt LED street light.
All as per item No. 77 here in before but for 100 Watt LED street light.
All as per item No. 77 here in before but for 200 Watt LED street light.
Supply and fix in repair 1100 volt grade heavy duty cable PVC insulated aluminium stranded conductor PVC sheathed suspended by insulating hanger not more than 1 mtr apart including 4mm suspension, cable size 10 sqmm twin core stranded conductor
Supply and fix in repair or passing through pipe, 1100 volts grade heavy duty PVC insulated flat twin core cable of size 4 sqmm nominal cross section with connection in sintex box flood light complete all as specified and directed by Engr-in-charge. Note : PVC pipe will be measured and paid seperately under relevent items.
Supply and fix of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Note : PVC pipe will be clamed at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates.
M&L for fixing of new street light bracket made out of GI pipe medium grade 25 mm bore suitable to fit with LED street light approx length not less than 120cm bent to shape including new clamps made of MS flat of size 30x4 mm thick including cutting, welding holes, nut, bolts washers etc including two coat of aluminium paint over one coat of red oxide primer on MS work complete all as specified and as directed.
Supply, fixing and testing of auto day/ night on and off photocell.LDR sensor switch 6amps for lighting on and off photocell, LDR sensor switch 6amps for lighting on and off water proof 220volt 50HZ,AC supply, model No Quick Sense QS-301 complete with all accessories internally pre-wired including connection with 1.5Sqmm copper conductor from main supply to sensor, sensor to fittings complete all as specified and directed by Engr-in-Charge.
Note:- Amount of credit of Rs 205561.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.
BAL SINGH AND SONS
Gopal Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .