Providing MEP like High Side Electrical, HVAC, Fire Fighting, Lifts, plumbing works and ELV works to the High Court building in Super block F of Amaravati Government Complex area in Amaravati Capital City, Andhra Pradesh
996721
22/MD/CE(ELE)AGICL/2026,Dt.28.09.2026
OPEN - NCB
Similar Work
GUNTUR, ANDHRA PRADESH
21 documents required · 20 mandatory · 1 optional
₹29,500
₹4.1 Cr
30 Sept 2026
30 Sept 2026
30 Sept 2026
7 Oct 2026
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections.Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client. As per specification, data sheet and directed by Engineer in charge . (Inside Toilet)15 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client. As per specification, data sheet and directed by Engineer in charge . . (Inside Toilet) 20mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (Inside Toilet) 25 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (Inside Toilet) 32 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Inside Toilet) 40 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Inside Toilet) 50 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (Inside Shaft) 25 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Inside Shaft) 32 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Inside Shaft) 40 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Inside Shaft) 50 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Basement and terrace piping) 20mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Basement and terrace piping) 25 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Basement and terrace piping) 32 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (Basement and terrace piping) 40 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 308-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (Basement and terrace piping) 50 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 309-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (For HOT WATER piping) 15 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 309-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (For HOT WATER piping) 20 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 309-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/Client As per specification, data sheet and directed by Engineer in charge . (For HOT WATER piping) 25 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 309-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (For HOT WATER piping) 32 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of approved make Polyethelene-Aluminium -Polyethelene (PE-AL-PEX) Composite pipes are manufactured as per IAPMO IGC-India 309-2014 sizes from 1216, (16MM OD), 1620,2025,2532,3240,4050,5063,6375,7590 to 90110 (110 MM OD) pipes UV resistant with carbon black having thermal stability and fittings are composite compression or Brass compression for hot and cold water supply. with clamps at 1.00 meter spacing. This includes testing of joints complete as per direction of the Engineer in charge These pipes will withstand continuous operation pressures up to 10 bar, with a thermal conductivity of 0.43 W/(m·K) The piping shall be installed and clamped within dry wall chases. Fittings, including tees, elbows, sockets, and reducers, shall have a two-layer construction: the inner layer made of hot-water-resistant PPSU and the outer layer of reinforced glass fiber PA-plastic for hot, cold, and flush water applications. End fittings (male and female adaptors) will also be PPSU, compliant with DIN EN 1982, and all termination points must utilize PPSU fittings for faucet connections. Cost shall be inclusive of all fittings as required Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. The cost includes GI hot-dip galvanized supports (U clamp) with an 85-micron coating. Installation shall strictly adhere to the manufacturer's technical guidelines and be approved by the Engineer/ClientAs per specification, data sheet and directed by Engineer in charge . (For HOT WATER piping) 40 mm make:ASTRAL (MULTIPEX) / SUPREME / PRINCE
Supply, Installation, testing and commissioning of 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) for CPVC hot water pipes. Note:This item is for hot water insulation only,pipe quantity for hot water exposed pipes has been considered. As per specification, data sheet and directed by Engineer in charge . 15 mm make: THERMAFLEX / ARMACELL / ARMAFLEX
Supply, Installation, testing and commissioning of 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) for CPVC hot water pipes.Note:This item is for hot water insulation only,pipe quantity for hot water exposed pipes has been considered.As per specification, data sheet and directed by Engineer in charge . 20 mm make: THERMAFLEX / ARMACELL / ARMAFLEX
Supply, installation and testing of 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) for CPVC hot water pipes.Note:This item is for hot water insulation only,pipe quantity for hot water exposed pipes has been considered. As per specification, data sheet and directed by Engineer in charge . 25 mm make: THERMAFLEX / ARMACELL / ARMAFLEX
Supply, installation and testing of 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) for CPVC hot water pipes.Note:This item is for hot water insulation only,pipe quantity for hot water exposed pipes has been considered. As per specification, data sheet and directed by Engineer in charge . 32 mm make: THERMAFLEX / ARMACELL / ARMAFLEX
Supply, installation and testing of 6mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) for CPVC hot water pipes.Note:This item is for hot water insulation only,pipe quantity for hot water exposed pipes has been considered. As per specification, data sheet and directed by Engineer in charge . 40 mm make: THERMAFLEX / ARMACELL / ARMAFLEX
Supplying, installing, testing and commissioning of 65 mm GI Heavy class (C class) Pipe of shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded fittings in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . (Transfer pipes, Incoming pipes and sump drain pipes,Vertical shaft,horizontal & ceiling level.) MAKE :TATA/JINDAL (STAR)/JINDAL (HISSAR)
Supplying, installing, testing and commissioning of 80mm GI Heavy class (C class) Pipe of shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel paint finish complete. Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . . (Transfer pipes, Incoming pipes and sump drain pipes,Vertical shaft,horizontal & ceiling level.). MAKE :TATA/JINDAL (STAR)/JINDAL (HISSAR)
Supplying, installing, testing and commissioning of 150 mm GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . (Transfer pipes, Incoming pipes and sump drain pipes,Vertical shaft,horizontal & ceiling level.). MAKE :TATA/JINDAL (STAR)/JINDAL (HISSAR)
Supplying, installing, testing and commissioning of 200 mm GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. 6.3mm thickness.Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . (Transfer pipes, Incoming pipes and sump drain pipes,Vertical shaft,horizontal & ceiling level.) MAKE :TATA/JINDAL (STAR)/JINDAL (HISSAR)
Supply, installation ,testing & Comissioning of in position Gun metal heavy type online Pressure reducing valves of 40mm with bye pass arrangement inluding necessary ball valves,connecting pipes, pressure gauges GI Fittings like elbows, tees, union including making connection to PB pipes with all neccesary acccessries. Pressure Class PN 16. As per specification, data sheet and directed by Engineer in charge . make:SANT,NVR,HONEYWELL
Supply, installation ,testing & Comissioning of in position Gun metal heavy type online Pressure reducing valves with bye pass arrangement inluding necessary ball valves,connecting pipes, pressure gauges GI Fittings like elbows, tees, union including making connection to PB pipes with all neccesary acccessries. Pressure Class PN 16. As per specification, data sheet and directed by Engineer in charge . 65mm make:SANT,NVR,HONEYWELL
Supply, installation ,testing & Comissioning of in position Gun metal heavy type online Pressure reducing valves with bye pass arrangement inluding necessary ball valves,connecting pipes, pressure gauges GI Fittings like elbows, tees, union including making connection to PB pipes with all neccesary acccessries. Pressure Class PN 16. As per specification, data sheet and directed by Engineer in charge . 80mm make:SANT,NVR,HONEYWELL
Supply, installation ,testing & Comissioning of in position Gun metal heavy type online Pressure reducing valves with bye pass arrangement inluding necessary ball valves,connecting pipes, pressure gauges GI Fittings like elbows, tees, union including making connection to PB pipes with all neccesary acccessries. Pressure Class PN 16. As per specification, data sheet and directed by Engineer in charge . 100mm make:SANT,NVR,HONEYWELL
Supply, installation ,testing & Comissioning of in position Gun metal heavy type online Pressure reducing valves with bye pass arrangement inluding necessary ball valves,connecting pipes, pressure gauges GI Fittings like elbows, tees, union including making connection to PB pipes with all neccesary acccessries. Pressure Class PN 16. As per specification, data sheet and directed by Engineer in charge . . 150mm make:SANT,NVR,HONEYWELL
Supply, Transportation and fixing of storage / Pressure type Vertical / Horizontal 230/250V single phase 2000watts ISI mark 5 Star rated water heater with SS tank and ABS plastic body of 15ltr capacity to withstand up to 6.5 bar of water pressure including all standard accessories and dead weight pressure reducing valve on out let side, including cost of 2 Nos nylon / PVC / Metallic hose pipe, testing and all labour charges etc., complete. As per specification, data sheet and directed by Engineer in charge . 15 ltr. Makes: JAQUAR / RACOLD / AO SMITH
Supply, Transportation and fixing of storage / Pressure type Vertical / Horizontal 230/250V single phase 2000watts ISI mark 5 Star rated water heater with SS tank and ABS plastic body of 25ltr capacity to withstand up to 6.5 bar of water pressure including all standard accessories and dead weight pressure reducing valve on out let side, including cost of 2 Nos nylon / PVC / Metallic hose pipe, testing and all labour charges etc., complete.As per specification, data sheet and directed by Engineer in charge . 25 ltr. ( Make: JAQUAR / RACOLD / AO SMITH
Supply, instalation, testing & commissioning of 15 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job. As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Supply, instalation, testing & commissioning of 20 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job. As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Supply, instalation, testing & commissioning of 25 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job.As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Supply, instalation, testing & commissioning of 32 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job. As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Supply, instalation, testing & commissioning of 40 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job. As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Supply, instalation, testing & commissioning of 50 mm full bore gun metal ball valve with SS Ball and SS spindle as per IS-Class-I, Indian make heavy type-, for following diameters., PN 16, with necessary specials, union, nipples etc., to complete the job. As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / HONEYWELL / ZOLOTO
Providing, installation, testing and commissioning of 80 mm dual Plate non - return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc as required (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT, ARMOFIRE, ZOLOTO
Providing, installation, testing and commissioning of 100 mm dual Plate non - return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc as required (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT, ARMOFIRE, ZOLOTO
Providing, installation, testing and commissioning of 150 mm dual Plate non - return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc as required (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT, ARMOFIRE, ZOLOTO
Providing, installation, testing and commissioning of 200 mm dual Plate non - return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc as required (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT, ARMOFIRE, ZOLOTO
Supplying, fixing, testing and commissioning of 65 mm butterfly valve PN 16, with Bronze / Gun metal seat duly ISI marked complete with Nuts, Bolts, Washers, gaskets, conforming to IS 13095 of following sizes as required. (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT / AUDCO / ARMOFIRE
Supplying, fixing, testing and commissioning of 80 mm butterfly valve PN 16, with Bronze / Gun metal seat duly ISI marked complete with Nuts, Bolts, Washers, gaskets, conforming to IS 13095 of following sizes as required. (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT / AUDCO / ARMOFIRE
Supplying, fixing, testing and commissioning of 100 mm butterfly valve PN 16, with Bronze / Gun metal seat duly ISI marked complete with Nuts, Bolts, Washers, gaskets, conforming to IS 13095 of following sizes as required. (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT / AUDCO / ARMOFIRE
Supplying, fixing, testing and commissioning of 150 mm butterfly valve PN 16, with Bronze / Gun metal seat duly ISI marked complete with Nuts, Bolts, Washers, gaskets, conforming to IS 13095 of following sizes as required. (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT / AUDCO / ARMOFIRE
Supplying, fixing, testing and commissioning of 200 mm butterfly valve PN 16, with Bronze / Gun metal seat duly ISI marked complete with Nuts, Bolts, Washers, gaskets, conforming to IS 13095 of following sizes as required. (PN 16) As per specification, data sheet and directed by Engineer in charge . Makes:( Make: SANT / AUDCO / ARMOFIRE
Supply, Installation, testing and commissioning of 100 mm BMS Campatible CI flanged water meters direct reading type calibrated in 'litres & kilolitres tested and approved by Municipal Corporation with dirt box (strainer) including making necessary flanged joints, testing etc.complete.As per specification, data sheet and directed by Engineer in charge . (Borewell, municipal inlet, surplus water outlet, domesatic and flushing outlet in pump room) MAKE:KROHNE / ROCKWIN / ADEPT
Supply, Installation, testing and commissioning of 150 mm BMS Campatible CI flanged water meters direct reading type calibrated in 'litres & kilolitres tested and approved by Municipal Corporation with dirt box (strainer) including making necessary flanged joints, testing etc.complete.As per specification, data sheet and directed by Engineer in charge . (Borewell, municipal inlet, surplus water outlet, domesatic and flushing outlet in pump room) MAKE:KROHNE / ROCKWIN / ADEPT
Supply, Installation, testing and commissioning of 200 mm BMS Campatible CI flanged water meters direct reading type calibrated in 'litres & kilolitres tested and approved by Municipal Corporation with dirt box (strainer) including making necessary flanged joints, testing etc.complete.As per specification, data sheet and directed by Engineer in charge . (Borewell, municipal inlet, surplus water outlet, domesatic and flushing outlet in pump room) MAKE:KROHNE / ROCKWIN / ADEPT
Constructing 914.4 mm x 457.2 mm (3'0"x1'6") brick in CM 1:6 prop. Masonry Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 914.4 mm x 457.2 mm (3'0"x1'6") C.I frame andcover of 40 Kg. As per specification, data sheet and directed by Engineer in charge .
Supply, installation, testing and commissioning of 25 /20mm dia Air Release Valve As per specification, data sheet and directed by Engineer in charge . Makes: LEADER / SANT / ZOLOTO
Supply, installation, testing and commissioning of cast iron Y – Stainer flanged end with SS mesh of following sizes confirming to IS specifications complete with rubber gasket, GI bolts , nuts, washers etc as required . As per specification, data sheet and directed by Engineer in charge . 80 mm MAKE:SANT,NVR,HONEYWELL
Supply, installation, testing and commissioning of cast iron Y – Stainer flanged end with SS mesh of following sizes confirming to IS specifications complete with rubber gasket, GI bolts , nuts, washers etc as required Makes:As per specification, data sheet and directed by Engineer in charge . 100 mm MAKE:SANT,NVR,HONEYWELL
Supply, installation, testing and commissioning of cast iron Y – Stainer flanged end with SS mesh of following sizes confirming to IS specifications complete with rubber gasket, GI bolts , nuts, washers etc as required Makes. As per specification, data sheet and directed by Engineer in charge . 150 mm MAKE:SANT,NVR,HONEYWELL
Supply, installation, testing and commissioning of cast iron Y – Stainer flanged end with SS mesh of following sizes confirming to IS specifications complete with rubber gasket, GI bolts , nuts, washers etc as required Makes. As per specification, data sheet and directed by Engineer in charge . 200 mm MAKE:SANT,NVR,HONEYWELL
Supply, Installation, testing and commissioning of automtic level controller (Hi/Low) including level float switch with 5mtr length cable,Control box 24V AC with indicator, with PLC based solenoid valve control panel(SCP) in overhead water tanks,Storage Flushing tank and Storage fire tanks as per the dimension of the water tanks including necessary electical and control cable cabling as per the drawing and connection to the pump panel. As per specification, data sheet and directed by Engineer in charge . MAKE:GRUNDFOS / TECHNICA / CIRRUS ENGINEERING
Supply, Installation, testing and commissioning of Motorised Solenoid Valve, pilot operated diaphram type screwed end with IP65 coil and manual override & flow regulator, with all required accessories including the Electrical control cabling (2Cx1.5 sq.mm FRLS cu multi standard screened ) between the valve and the solinoid valve control panel(SCP)/pump panel (laying in shaft with suitable clamping and tyies) as required in conjunction with the layout plans. As per specification, data sheet and directed by Engineer in charge . 32 mm dia make:HONEYWELL / SANT / NVR
Supply, Installation, testing and commissioning of Motorised Solenoid Valve, pilot operated diaphram type screwed end with IP65 coil and manual override & flow regulator, with all required accessories including the Electrical control cabling (2Cx1.5 sq.mm FRLS cu multi standard screened ) between the valve and the solinoid valve control panel(SCP)/pump panel (laying in shaft with suitable clamping and tyies) as required in conjunction with the layout plans. As per specification, data sheet and directed by Engineer in charge . 40 mm dia make:HONEYWELL / SANT / NVR
Supply, Installation, testing and commissioning of RO+UF+TDS CONTROLLER Water purifier of approved make, for attachment with water cooler 300 liter capacity, having purification capacity of 300 LPH, with filter cartridges; Sediment, Activated Carbon, Carbon Block, UF, Post Carbon.RO membrane-Filmtec 1812-75 GPD, UF membrane-0.01 Micron, including all accessories & necessary fittings complete with necessary platform to fix, connection of supply, drain etc.with all complete. (ASSUME) As per specification, data sheet and directed by Engineer in charge . make:KENT, AQUAGUARD, ZERO B
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete. As per specification, data sheet and directed by Engineer in charge . (Pipes inside toilet). 32 mm dia (agri 6 kg/cm2) can be used only for this item) make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete.As per specification, data sheet and directed by Engineer in charge . (Pipes inside toilet). 40 mm dia (agri 6 kg/cm2) can be used only for this item) make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete. As per specification, data sheet and directed by Engineer in charge . (Pipes inside toilet). 50 mm dia (agri 6 kg/cm2) can be used only for this item) make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete. As per specification, data sheet and directed by Engineer in charge . e.(Pipes inside toilet). 80mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete. As per specification, data sheet and directed by Engineer in charge . .(Pipes inside toilet). 110 mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC / SWR pipes(Type B pipes for waste pipe) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) . Making proper connection with cement solvent joint as per BIS/manufacturer. Fixing at wall/ceiling level supported by G.I. clamps, hangers etc .making holes in walls/floors & making good all complete. As per specification, data sheet and directed by Engineer in charge . .(Pipes inside toilet). 160mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of Centrifugal C.I.spun hubless pipe for soil, waste& vent pipes installation conforming to IS:15905cut to required lengths including all necessary fittings and specials such as Bends, junctions, offsets, access pieces (plain or door) & vent cowl. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. duly epoxy coated. Making proper connection with SS Coupling of required depth as per manufacturer. Cutting, chases/holes in floors / walls / slab. (for vertical waste and soil drainage stack) Providing MS pipe sleeves of suitable higher size wherever pipes crossing a fire rated wall/floor slab and sealing of space around pipe and pipe sleeve with glass wool in between and fire proof sealent at either end to the satisfaction of the Project Manager/ Consultants and making good the same after pipes have been duly laid and testing complete Cost shall also be inclusive of painting the pipes & fittings with two coats of synthetic enamel paint of approved shade over a coat of primer. As per specification, data sheet and directed by Engineer in charge . .(For lowermost floor in vertical and horizontal basement drainage pipes.) 100mm dia. make:NECO / KAPILANSH / SAINTGOBIAN
Supply, Installation, testing and commissioning of Centrifugal C.I.spun hubless pipe for soil, waste& vent pipes installation conforming to IS:15905cut to required lengths including all necessary fittings and specials such as Bends, junctions, offsets, access pieces (plain or door) & vent cowl. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. duly epoxy coated. Making proper connection with SS Coupling of required depth as per manufacturer. Cutting, chases/holes in floors / walls / slab. (for vertical waste and soil drainage stack) Providing MS pipe sleeves of suitable higher size wherever pipes crossing a fire rated wall/floor slab and sealing of space around pipe and pipe sleeve with glass wool in between and fire proof sealent at either end to the satisfaction of the Project Manager/ Consultants and making good the same after pipes have been duly laid and testing complete Cost shall also be inclusive of painting the pipes & fittings with two coats of synthetic enamel paint of approved shade over a coat of primer.As per specification, data sheet and directed by Engineer in charge . .(For lowermost floor in vertical and horizontal basement drainage pipes.) 150mm dia. make:NECO / KAPILANSH / SAINTGOBIAN
Supply, Installation, testing and commissioning of Centrifugal C.I.spun hubless pipe for soil, waste& vent pipes installation conforming to IS:15905cut to required lengths including all necessary fittings and specials such as Bends, junctions, offsets, access pieces (plain or door) & vent cowl. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. duly epoxy coated. Making proper connection with SS Coupling of required depth as per manufacturer. Cutting, chases/holes in floors / walls / slab. (for vertical waste and soil drainage stack) Providing MS pipe sleeves of suitable higher size wherever pipes crossing a fire rated wall/floor slab and sealing of space around pipe and pipe sleeve with glass wool in between and fire proof sealent at either end to the satisfaction of the Project Manager/ Consultants and making good the same after pipes have been duly laid and testing complete Cost shall also be inclusive of painting the pipes & fittings with two coats of synthetic enamel paint of approved shade over a coat of primer. As per specification, data sheet and directed by Engineer in charge . e.(For lowermost floor in vertical and horizontal basement drainage pipes.) 200mm dia. make:NECO / KAPILANSH / SAINTGOBIAN
Supply, Installation, testing and commissioning of Centrifugal C.I.spun hubless pipe for soil, waste& vent pipes installation conforming to IS:15905cut to required lengths including all necessary fittings and specials such as Bends, junctions, offsets, access pieces (plain or door) & vent cowl. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. duly epoxy coated. Making proper connection with SS Coupling of required depth as per manufacturer. Cutting, chases/holes in floors / walls / slab. (for vertical waste and soil drainage stack) Providing MS pipe sleeves of suitable higher size wherever pipes crossing a fire rated wall/floor slab and sealing of space around pipe and pipe sleeve with glass wool in between and fire proof sealent at either end to the satisfaction of the Project Manager/ Consultants and making good the same after pipes have been duly laid and testing complete Cost shall also be inclusive of painting the pipes & fittings with two coats of synthetic enamel paint of approved shade over a coat of primer. As per specification, data sheet and directed by Engineer in charge . .(For lowermost floor in vertical and horizontal basement drainage pipes.) 250mm dia. make:NECO / KAPILANSH / SAINTGOBIAN
Supply, Installation, testing and commissioning of UPVC SWR pipes (Type A pipes for Antisyphonage system) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door). Making proper connection with push fit ("O" ring ) rubber joints OR cement solvent jointas per BIS/manufacturer. Fixing at wall /ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . . (Exposed pipes / vertical down takes). 80 mm dia make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes (Type A pipes for Antisyphonage system) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door). Making proper connection with push fit ("O" ring ) rubber joints OR cement solvent jointas per BIS/manufacturer. Fixing at wall /ceiling level supported by G.I. clamps, hangers etcAs per specification, data sheet and directed by Engineer in charge . (Exposed pipes / vertical down takes). 110mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes (Type A pipes for Antisyphonage system) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door). Making proper connection with push fit ("O" ring ) rubber joints OR cement solvent jointas per BIS/manufacturer. Fixing at wall /ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . . (Exposed pipes / vertical down takes). 160mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for Soil, waste and rainwater downtake) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) .Making proper connection withpush fit ("O" ring ) rubber joints OR cement solvent jointas per BIS / manufacturer. Fixing at wall / ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . (Exposed pipes / vertical down takes). 80 mm dia make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for Soil, waste and rainwater downtake) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) .Making proper connection withpush fit ("O" ring ) rubber joints OR cement solvent jointas per BIS / manufacturer. Fixing at wall / ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . (Exposed pipes / vertical down takes). 110mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for Soil, waste and rainwater downtake) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) .Making proper connection withpush fit ("O" ring ) rubber joints OR cement solvent jointas per BIS / manufacturer. Fixing at wall / ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . (Exposed pipes / vertical down takes). 160mm dia. make:ASTRAL / SUPREME / FINOLEX
Supply, Installation, testing and commissioning of UPVC SWR pipes(Type B pipes for Soil, waste and rainwater downtake) confirming to IS : 13592 for above 75 mm dia pipe, and confirming to IS : 4985 for pipe upto 50 mm dia cut to required lengths including all necessary fittings and specials such as bends, junctions offsets, access pieces (plain or door) .Making proper connection withpush fit ("O" ring ) rubber joints OR cement solvent jointas per BIS / manufacturer. Fixing at wall / ceiling level supported by G.I. clamps, hangers etc As per specification, data sheet and directed by Engineer in charge . (Exposed pipes / vertical down takes). 250mm dia. make:ASTRAL / SUPREME / FINOLEX
Providing and fixing Upvc nahni trap with 110X75x75mm height size as per IS 1729 of self cleansing design with water seal not less than 50mm 'with or without vent, including setting the trap in 1:2:4 cement concrete, architect approved stainless steel grating etc. complete.As per specification, data sheet and directed by Engineer in charge . . make:ASTRAL,SUPREME,ASHIRWAD
Providing and fixing Upvc Multi floor trap with 110X75x100mm height size as per IS 1729 of self cleansing design with water seal not less than 50 mm 'with or without vent, including setting the trap in 1:2:4 cement concrete, architect approved stainless steel grating etc. complete.As per specification, data sheet and directed by Engineer in charge . make:ASTRAL,SUPREME,ASHIRWAD
Supply, Installation, testing and commissioning of Upvc Urinal trap with 110X75x100mm height size as per IS 1729 of self cleansing design with water seal not less than 50 mm 'with or without vent, including setting the trap in 1:2:4 cement concrete, architect approved stainless steel grating etc. complete.As per specification, data sheet and directed by Engineer in charge . make:ASTRAL,SUPREME,ASHIRWAD
SITC of Silent type P- trap with 75mm outlet and 100 mm inlet including silent type Height riserPolypropylene material & manufactured as per IS 14735 (UPVC SWR FITTING) with inlets of 75 mm & 50 mm and Bottom outlet of 110 mm. Jointing with push fit rubber ring socket fittings completeand S.S. grating with including all required accesoories.As per specification, data sheet and directed by Engineer in charge . make:ASTRAL,SUPREME,ASHIRWAD
Providing, laying, fixing & comissioning of PVC vent cowl of ISI approved make & complete in all vertical drainage pipes. As per specification, data sheet and directed by Engineer in charge . 80mm dia. make:ASTRAL,SUPREME,ASHIRWAD
Providing, laying, fixing & comissioning of PVC vent cowl of ISI approved make & complete in all vertical drainage pipes. As per specification, data sheet and directed by Engineer in charge . 110mm dia. make:ASTRAL,SUPREME,ASHIRWAD
Supply, Installation, testing and commissioning of PVC vent cowl of ISI approved make & complete in all vertical drainage pipes. As per specification, data sheet and directed by Engineer in charge . 160mm dia. make:ASTRAL,SUPREME,ASHIRWAD
Grease separator EasyClean free Mix & Pump NS 10 according to EN1825 / certification Z-54.1-474 Tank Manufactured from virgin, non-recycled polyethylene, for free standing installation in frost protected areas, with integrated sludge trap, sloped interior base improves cleaning and reduces disposal time, inlet flow calming system and outlet flow regulation device, inlet and outlet interchangeable, slanted twin access covers with quick release odour tight snap closures, inspection window with interior cleaning arm, 75 mm OD PN 10 pressure disposal pipe, with integrated fork lift grips at base of separator, low weight - compact design, 100 % corrosion free polyethylene body construction (20 year warranty). Disposal System Mix & Pump version -cleaning and refilling system at one touch of button, maintenance free macerating pump (stainless steel blades) for separator cleaning and disposal, includes closure valve for easy pump removal, pump floor mount included with installation hardware and anti-vibration matt, - pumping capacity 3.0 kW, 5 m cable length, top mounted water jet(s) for grease layer breakup and water spray nozzles for interior wall cleaning during disposal, 1 inch -valve for water refill, 1 inch interior threaded refill inlet with air gap. Control Unit with LCD display control settable in English, German, French, Italian, Dutch or Polish language and mains power safety on/off switch, with BMS connections. APPLICATION : (KITCHEN ) Delivery: System completely assembled. Certification number: Z-54.1-474 Size: NS 10 Sludge trap capacity: 1000 liter Total separator capacity: 1900 liter Grease storage capacity: 400 liter Inlet / Outlet: DN 150 (DA 160 mm) Weight: approx. 267 kg Make: ACO / KESSEL / GUARDIAN
Supply, Installation, testing and commissioning of cast iron rain water inlets with gravel guard dome type (bell mouth) grating specially cast,screwed with S.S-304 grade screws of required length including cutting brick work and fixing in cement mortar 1:4 (1 cement: 4 coarse sand) and making good the wall etc., generally conforming to drawings.complete. As per specification, data sheet and directed by Engineer in charge . . (250mm i/d pipes) make:Astral,Supreme,Finolex & Ashirvad
Earth work excavation including all soils for trench, Pole Pit and Earth Pit As per specification, data sheet and directed by Engineer in charge .
Supply, Installation, testing and commissioning of UPVC Foam Core SN-8 Drainage system conforming to IS:16098-2013 comprising pipes and fittings cut torequired lengths including all necessary fittings and specials such as Bends, junctions, offsets. Making proper connection with proper joints recommended by manufacturer and suitable for burying the pipes under the ground floor with 150 mm depth PCC bedding, 75 mm thick cement encasing and interconnecting pipe to chamber and complete in all.As per specification, data sheet and directed by Engineer in charge . (for burried pipes in ground, from building shaft to nearest chamber) PROVISION (150mm i/d) make:ASTRAL / SUPREME
Supply, Installation, testing and commissioning of UPVC Foam Core SN-8 Drainage system conforming to IS:16098-2013 comprising pipes and fittings cut torequired lengths including all necessary fittings and specials such as Bends, junctions, offsets. Making proper connection with proper joints recommended by manufacturer and suitable for burying the pipes under the ground floor with 150 mm depth PCC bedding, 75 mm thick cement encasing and interconnecting pipe to chamber and complete in all. As per specification, data sheet and directed by Engineer in charge . . (for burried pipes in ground, from building shaft to nearest chamber) PROVISION (200mm i/d) make:ASTRAL / SUPREME
Supply, Installation, testing and commissioning of UPVC Foam Core SN-8 Drainage system conforming to IS:16098-2013 comprising pipes and fittings cut torequired lengths including all necessary fittings and specials such as Bends, junctions, offsets. Making proper connection with proper joints recommended by manufacturer and suitable for burying the pipes under the ground floor with 150 mm depth PCC bedding, 75 mm thick cement encasing and interconnecting pipe to chamber and complete in all. As per specification, data sheet and directed by Engineer in charge . (for burried pipes in ground, from building shaft to nearest chamber) PROVISION (250mm i/d) make:ASTRAL / SUPREME
Supply, Installation, testing and commissioning of square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design.100x100 mm size P type. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 As per specification, data sheet and directed by Engineer in charge . make:Perfect Potteries, Jabalpur, Mahaveer Ceramic Industries & Bombay Iron Works (Patel Pattern)
Constructing Rectangular type Inspection Chamber of size 0.6 m x 0.9 m x 1.5m deep with 150mm thick RCC wall finished with a floating coat of neat cement, foundation concrete M15 mix (stone aggregate 20mm nominal size) and making necessary channel in cement concrete M20 (stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design.Thickness of chamber shall be as per NBC providing & fixing of FRP manhole recessed type of 40ton Point load as per EN124 clear opening 600 x900 mm , cover size 986 x 686x 45 mm thk, frame size 565 mmx 816 mm x 80 mm heigh. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be included in the total cost)
Constructing Rectangular type Inspection Chamber of size 1.2 m x 0.9 m x 2.5m deep with 150mm thick RCC wall finished with a floating coat of neat cement, foundation concrete M15 mix (stone aggregate 20mm nominal size) and making necessary channel in cement concrete M20 (stone aggregate 20mm nominal size) finished with a floating coat of neat cement all complete as per standard design.Thickness of chamber shall be as per NBC providing & fixing of FRP manhole cover Recessed type of 40ton Point load as per EN124 clear opening 1200 x900 mm , cover size 986 x 686x 45 mm thk, frame size 1116 mmx 816 mm x 80 mm heigh. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be included in the total cost
Supply, Installation, testing and commissioning of FRP / GRP COMPOSITE gully grating and fram of appropriate size and load capacity of approved brand confirming to BSEN - 124:1994. Gully grating shall have minimum 30% of water entrance area that of clear opening of the chmaber. Gully grating shall have top abrasion resistance layer of decorative grey granite finish, it shall also confrim permanent set criterion as per BSEN-124. product should be tested in test lab for load capacity and permanent set. As per specification, data sheet and directed by Engineer in charge . 300 mm wide x 700 lenght make:Everplast,Thermoset & Thermodrain
Supply, Installation, testing and commissioning of FRP / GRP COMPOSITE gully grating and fram of appropriate size and load capacity of approved brand confirming to BSEN - 124:1994. Gully grating shall have minimum 30% of water entrance area that of clear opening of the chmaber. Gully grating shall have top abrasion resistance layer of decorative grey granite finish, it shall also confrim permanent set criterion as per BSEN-124. product should be tested in test lab for load capacity and permanent set.As per specification, data sheet and directed by Engineer in charge . 600 mm wide x 500 length make:Everplast,Thermoset & Thermodrain
Supply, Installation, testing and commissioning of FRP/GRP COMPOSITE gully grating and fram of appropriate size and load capacity of approved brand confirming to BSEN - 124:1994. Gully grating shall have minimum 30% of water entrance area that of clear opening of the chmaber. Gully grating shall have top abrasion resistance layer of decorative grey granite finish, it shall also confrim permanent set criterion as per BSEN-124. product should be tested in test lab for load capacity and permanent set. As per specification, data sheet and directed by Engineer in charge . 600 mm wide x 600 lenght make:Everplast,Thermoset & Thermodrain
Supply, Installation, testing and commissioning of line Single slot polymer concreate channel with SS slot of size 130 x 75mmX 50mm side outlet shall be stainless steel brick slot of 20 ht with inspection unit and side outlet end cap for the maintenance purpose. The slot opening shall be 12mm. The grating is suitable for A15 load class. The drain channel will have with not less than 8kg with surface roughness not more than 25 microns. Provided with accessories like end plate & end plate with outlet suitable for DN 100. As per specification, data sheet and directed by Engineer in charge . make: MEA/KESSEL/ATT INOX
Supply, Installation, testing and commissioning of TS 1500 twin slot polymer concreate channel with SS slot of size 150 x 300mmX 100/75mm outlet shall be stainless steel brick slot of 20 ht with inspection unit and side outlet end cap for the maintenance purpose. The slot opening shall be 12mm. The grating is suitable for A15 load class. The drain channel will have with not less than 8kg with surface roughness not more than 25 microns. Provided with accessories like end plate & end plate with outlet suitable for DN 100. As per specification, data sheet and directed by Engineer in charge . make: MEA/KESSEL/ATT INOX
Supply, Installation, testing and commissioning of TL 1000 twin slot polymer concreate channel with SS slot of size 130 x 250mmX 100/75mm side outlet shall be stainless steel brick slot of 20 ht with inspection unit and side outlet end cap for the maintenance purpose. The slot opening shall be 12mm. The grating is suitable for A15 load class. The drain channel will have with not less than 8kg with surface roughness not more than 25 microns. Provided with accessories like end plate & end plate with outlet suitable for DN 100. As per specification, data sheet and directed by Engineer in charge . make: MEA/KESSEL/ATT INOX
Supply, installation, testing and commissioning of charcol filter For drainage air vent for Sewage. As per specification, data sheet and directed by Engineer in charge . 110 dia. Make: ASTRAL / SUPREME / ASHIRWAD
Supply, installation, testing and commissioning of IE-3 IGBC/GRIHA Sumbmersible pumps.(DRAIN SUMP) a) Control & power Panel with autochange over , b) All accessories required for the control of system as per control scheme. c) All interconnection piping as shown on drawing. d) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. e) Water Lvl sensers, dry run protection sensor etc.. f) Required cabling with terminations etc. g) With S.S. Chain Pully Arrangement for Pump lifting and maintanance h) All control panel should be OEM of pumps only. (Pnael should compitable to BMS for pump Controling and status) i) All panel should be BMS Compliance IP 55 J).body CI, Impeller SS & shaft SS. Basement water dischrge pump As per the DATA SHEET- SP-1 As per specification, data sheet and directed by Engineer in charge . Flow :- 400 LPM (1W+ 1S) Head :- 26 mt make: GRUNDFOS, WILO, XYLEM)
Supply, installation, testing and commissioning of IE-3 IGBC/GRIHA Sumbmersible pumps.(SEWER SUMP) a) Control & power Panel with autochange over , b) All accessories required for the control of system as per control scheme. c) All interconnection piping as shown on drawing. d) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. e) Water Lvl sensers, dry run protection sensor etc.. f) Required cabling with terminations etc. g) With S.S. Chain Pully Arrangement for Pump lifting and maintanance h) All control panel should be OEM of pumps only. (Pnael should compitable to BMS for pump Controling and status) i) All panel should be BMS Compliance IP 55 J).body SS, Impeller SS & shaft SS. Basement water dischrge pump As per the DATA SHEET- SP-1 As per specification, data sheet and directed by Engineer in charge . Flow :- 450 LPM (1W+ 1S) Head :- 26 mt make: GRUNDFOS, WILO, XYLEM) LOCATION : BASEMENT TOILET
Supply, installation, testing and commissioning of IE-3 IGBC/GRIHA Sumbmersible pumps. (DRAIN SUMP) a) Control & power Panel with autochange over , b) All accessories required for the control of system as per control scheme. c) All interconnection piping as shown on drawing. d) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. e) Water Lvl sensers, dry run protection sensor etc.. f) Required cabling with terminations etc. g) With S.S. Chain Pully Arrangement for Pump lifting and maintanance h) All control panel should be OEM of pumps only. (Pnael should compitable to BMS for pump Controling and status) i) All panel should be BMS Compliance IP 55 J).body CI, Impeller SS & shaft SS. As required and as directed by engineer in charge. Basement water dischrge pump As per the DATA SHEET- SP-1 As per specification, data sheet and directed by Engineer in charge . Flow :- 900 LPM (1W+ 1ASSIST) Head :- 26 mt make: GRUNDFOS,WILO,XYLEM
Supply, installation, testing and commissioning of IE-3 IGBC/GRIHA Sumbmersible pumps. (DRAIN SUMP) a) Control & power Panel with autochange over , b) All accessories required for the control of system as per control scheme. c) All interconnection piping as shown on drawing. d) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. e) Water Lvl sensers, dry run protection sensor etc.. f) Required cabling with terminations etc. g) With S.S. Chain Pully Arrangement for Pump lifting and maintanance h) All control panel should be OEM of pumps only. (Pnael should compitable to BMS for pump Controling and status) i) All panel should be BMS Compliance IP 55 J).body CI, Impeller SS & shaft SS. As required and as directed by engineer in charge. Basement water dischrge pump As per the DATA SHEET- SP-1 As per specification, data sheet and directed by Engineer in charge . Flow :- 2160 LPM (2W+1S) Head :- 26 mt make: GRUNDFOS, WILO, XYLEM)
Hydropneumatic System Supply, installation, testing and commissioning of Hydropneumatic system for domestic water supply, Flushing Water Supply comprising. a) FRP/M.S epoxy coated both internal as well as extenal periphory of the Vessel with replaceable bladder as per data sheet and specification. b) Pumps as per Data Sheet . All pumps shall be provided with individual variable frequency drive and all skid moumted pumps as per the vendor selection. c) Control Panel (OEM of pumps) IP66 with VFD of suitable rating as per pump data sheet and THDi less than 10% ( Pnael should compitable to BMS for pump Controling and status) d) All accessories required for the control of system as per control scheme. e) All interconnection piping as shown on drawing and control panel should be BMS compitible only. f) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. (Note: Refer the data sheets for Pressure vessel and Water Pumps with the corresponding number of floor being served as the suffix vessel or pump) As per specification, data sheet and directed by Engineer in charge . Hydropneumatic system for domestic water supply Flow :- 302 LPM system flow(3w+1s) Head :- 87 make: GRUNDFOS, WILO, XYLEM)
Hydropneumatic System Supply, installation, testing and commissioning of Hydropneumatic system for domestic water supply, Flushing Water Supply comprising. a) FRP/M.S epoxy coated both internal as well as extenal periphory of the Vessel with replaceable bladder as per data sheet and specification. b) Pumps as per Data Sheet . All pumps shall be provided with individual variable frequency drive and all skid moumted pumps as per the vendor selection. c) Control Panel (OEM of pumps) IP66 with VFD of suitable rating as per pump data sheet and THDi less than 10% ( Pnael should compitable to BMS for pump Controling and status) d) All accessories required for the control of system as per control scheme. e) All interconnection piping as shown on drawing and control panel should be BMS compitible only. f) Electrical connection to pumps from panel using suitable conductors and earthing of equipment. (Note: Refer the data sheets for Pressure vessel and Water Pumps with the corresponding number of floor being served as the suffix vessel or pump) As per specification, data sheet and directed by Engineer in charge . Hydropneumatic system for flushing water supply Flow :- 665 LPM system flow(3w+1s) Head :- 87 make: GRUNDFOS, WILO, XYLEM)
Supply, Installation, testing and commissioning of Carpark drain grating of size 300 X 300 mm with hinge grating, Bolted and removable one the MOC is CI suitable for D400 Loads class with slit basket suitable for DN 100 As per specification, data sheet and directed by Engineer in charge . make:ACO,Kessel - MEA & Geberit
Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - PLUMBING PANEL Incomer: 1 No. 800A 50KA 4P EDO ACB with LSING protection . Metering for Incomer: 1 No. Multifunction meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 800/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 800A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. Outgoings: 2 Nos. 125A TPN MCCB 25KA, 2 Nos. 100A TPN MCCB 25KA, 21 Nos. 63A TPN MCCB 25KA, , ., 1no. MCCB sutaible for 33.5kw motor, 1no. MCCB sutaible for 67.5kw motor All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - SUMP PUMP PANEL Incomer: 1 No. 400A 25KA 4P MCCB . Metering for Incomer: 1 No. Multifunction meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 500/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 set - Earth leakage relay. Bus bar: 1 set - 500A, 4Wire, 25KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. Outgoings: 2 Nos. 125A TPN MCCB 25KA , 22 Nos. 63A TPN MCCB 25KA., All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, laying and dressing of 3.5Core 120Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 3.5Core 50Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 3.5Core 70Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 4Core 16Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 4Core 6Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 3Core 10Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 3Core 16Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying and dressing of 3Core 6Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply & making of Cable end termination of the 3.5Core 120Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required and as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3.5Core 50Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3.5Core 70Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3Core 6Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required & as directed by Engineer In Charge and as per approved make for Plumbing works Makes: REYCHEM / 3M / DENSONS)
Supply and laying of 50 mm x 6mm GI Flat(2.5 Kgs /mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 6mm GI Flat (1.18Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 3mm GI Flat(0.656 Kgs/Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 8 SWG Copper wire(0.1155Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required & as directed by Engineer In Charge and as per approved make for Plumbing works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supplying Installation, testing and Commissioning of Electric driven main fire pump suitable for automatic operation and consisting of following Complete in all respect as required. a)Horizontal type, multistage, centrifugal, split casing pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq.cm. at highest and farthest outlet at specified flow of 2850 LPM and 120 Metres head conforming to IS 1520. b)Suitable HP SQ cage induction motor ( CLASS- IE3 MOTOR) TEFC, synchronous speed 1470 RPM, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325 c)M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. d)Suitable CC foundation of 1:2:4 ratio ( 1 Cement: 2 coarse sand : 4 graded stone aggregate 40 mm nominal size ) duly plastered and with anti vibration pads. As per specification, data sheet and directed by Engineer in charge . Main Pumps for Hydrant & Sprinkler Makes : Pumps : Pumps : KIRLOSKAR / MATHER & PLATT / KSB, Motors: KIRLOSKAR / ABB / KSB.
Supply,transporatation & installation of 300mm x 50mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete & as directed by Engineer In Charge and as per approved make for Plumbing workss Make- PROFAB,APARNA,ROLLFORM, GLOMETAL
Supply,transporatation & installation of 750mm x 50mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete & as directed by Engineer In Charge and as per approved make for Plumbing works Make- PROFAB,APARNA,ROLLFORM GLOMETAL
Supplying , installation , testing and commissioning of electric driven pressurisation / Jockey pump suitable for automatic operation and consisting of following : complete in all respect as required a) Horizontal type, multistage, centrifugal pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal and flow of 180 lpm at 120 Mtr head conforming to IS 1520 b) Suitable HP SQ cage induction motor ( CLASS- IE3 MOTOR) TEFC type suitable for operation on 415Volts, 3 phase 50 Hz. AC with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325 c) M.S. Fabricated common base plate, coupling, coupling guard, foundation bolts etc as required. d) Suitable cement concrete foundation duly plastered with anti vibration pads , As per specification, data sheet and directed by Engineer in charge . Jockey Pumps for Hydrant & Sprinkler Makes : Pumps : Pumps : KIRLOSKAR / MATHER & PLATT / KSB, Motors: KIRLOSKAR / ABB / KSB.
Supplying , installation, Testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following : complete in all respect as required. a) Horizontal type, multistage, centrifugal split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 Kg / sq.cm. at highest and farthest outlet at specified flow of 2850 lpm at 120 Mtr head conforming to IS 1520 b) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant BS & IS standard complete with auto starting mechanism, 12 Volts / 24 Volts electric starting equipment, Diesel Tank, exhaust pipe extended upto 1 m. outside pump house duly insulated with 50mm thick glass wool with 1.0mm thick alluminium sheet cladding, residential silencer, instruments and protection as per specification, stop solenoid for auto stop in the event of fault with audio indication c) M.S. Fabricated common base plate, coupling, coupling guard, foundation bolts etc as required. d) Suitable cement concrete foundation duly plastered with anti vibration pads. As per specification, data sheet and directed by Engineer in charge . Common stand by pumps for Hydrant and sprinkler Pumps ( Makes : Pumps : KIRLOSKAR / MATHER & PLATT / KSB, Diesel Engine : KIRLOSKAR, VOLVO, CUMMINS INDIA)
Supplying, installation, testing and commissioning of electric driven Terrace / Booster pump suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal type, multistage, centrifugal pump end suction back pullout of cast iron body & bronze impeller with stainless steel shaft, mechanical seal and flow of 900 lpm at 45 Mtr head conforming to IS 1520 b) Suitable HP SQ cage induction motor ( CLASS- IE3 MOTOR) TEFC type suitable for operation on 415Volts, 3 phase 50 Hz. AC with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325 c) M.S. Fabricated common base plate, coupling, coupling guard, foundation bolts etc as required. d) Suitable cement concrete foundation duly plastered with anti-vibration pads. As per specification, data sheet and directed by Engineer in charge .Makes : Pumps : KIRLOSKAR / MATHER & PLATT / KSB, Motors: KIRLOSKAR / ABB / KSB Booster pump.
Supplying , installation, Testing and commissioning of flexible expansion SS304 Metalic bellow at pump sunction and discharge. Including all accessories as required for (PN 16) 100mm dia , As per specification, data sheet and directed by Engineer in charge . Makes-EASYFLEX / RESISTOFLEX
Supplying , installation, Testing and commissioning of flexible expansion SS304 Metalic bellow at pump sunction and discharge. Including all accessories as required for (PN 20) 100mm dia , As per specification, data sheet and directed by Engineer in charge . Makes-EASYFLEX / RESISTOFLEX
Supplying , installation, Testing and commissioning of flexible expansion SS304 Metalic bellow at pump sunction and discharge. Including all accessories as required for (PN 16) 200mm dia , As per specification, data sheet and directed by Engineer in charge . Makes-EASYFLEX / RESISTOFLEX
Supplying , installation, Testing and commissioning of flexible expansion SS304 Metalic bellow at pump sunction and discharge. Including all accessories as required for (PN 20) 200mm dia , As per specification, data sheet and directed by Engineer in charge . Makes-EASYFLEX / RESISTOFLEX
Providing and fixing of Pressure Switch in the MS pipeline including connection etc as required. As per specification, data sheet and directed by Engineer in charge . SYSTEM SENSOR / SWITZER / HONEYWELL
Supply, installation, testing and commissioning of Bourdon type, stainless steel dial type pressure gauge with isolation valve and pipe having calibration of 0-16 kg/cm2 , as required and as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge . Makes- H. GURU / FIEBIG / FORBES MARSHALL
Supplying and fixing single headed Internal / External hydrant valve with instantaneous Gun metal couplings of 63mm dia with Cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gun Metal cap and chain . As per specification, data sheet and directed by Engineer in charge . Makes- NEWAGE (GUJARAT) / WINCO / SAFEX
Supplying, fixing, testing and commissioning of gear operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 300 mm . dia , As per specification, data sheet and directed by Engineer in charge . make: SANT / LEADER / ZOLOTO)
Supplying, fixing, testing and commissioning of gear operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 250 mm dia . As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / LEADER / ZOLOTO)
Supplying, fixing, testing and commissioning of gear operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 200 mm dia , As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / LEADER / ZOLOTO)
Supplying, fixing, testing and commissioning of lever operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 150 mm dia , As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / LEADER / ZOLOTO)
Supplying, fixing, testing and commissioning of lever operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 100 mm dia , As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / LEADER / ZOLOTO)
Supplying, fixing, testing and commissioning of lever operated butterfly valve PN 20, with.D.I. body, D.I. disc,EPDM seat and SS stem complete with Nuts, Bolts, Washers, gaskets, 80 mm dia , As per specification, data sheet and directed by Engineer in charge . ( Make: SANT / LEADER / ZOLOTO)
Providing, installation, testing and commissioning of FLANGED non - return valveas per the of following sizes complete with D.I. body,S.S. HINGE PIN, RUBBER SEATED, DRILLING AS PER: IS-1538 rubber gasket, GI bolts, nuts, washers etc as required (PN20). As per specification, data sheet and directed by Engineer in charge . 250mm dia ( Make: SANT / LEADER / ZOLOTO)
Providing, installation, testing and commissioning of FLANGED non - return valve of following sizes complete with D.I. body,S.S. HINGE PIN, RUBBER SEATED, DRILLING AS PER: IS-1538 rubber gasket, GI bolts, nuts, washers etc as required (PN20) , As per specification, data sheet and directed by Engineer in charge . 200 mm dia ( Make: SANT / LEADER / ZOLOTO)
Providing, installation, testing and commissioning of FLANGED non - return valve of following sizes complete with D.I. body,S.S. HINGE PIN, RUBBER SEATED, DRILLING AS PER: IS-1538 rubber gasket, GI bolts, nuts, washers etc as required (PN20) , As per specification, data sheet and directed by Engineer in charge . 150 mm dia ( Make: SANT / LEADER / ZOLOTO)
Providing, installation, testing and commissioning of FLANGED non - return valve of following sizes complete with D.I. body,S.S. HINGE PIN, RUBBER SEATED, DRILLING AS PER: IS-1538 rubber gasket, GI bolts, nuts, washers etc as required (PN20) , As per specification, data sheet and directed by Engineer in charge . 100 mm dia ( Make: SANT / LEADER / ZOLOTO)
Providing, installation, testing and commissioning of FLANGED non - return valve (as per IS 5312) of following sizes complete with D.I. body,S.S. HINGE PIN, RUBBER SEATED, DRILLING AS PER: IS-1538 rubber gasket, GI bolts, nuts, washers etc as required (PN20) , As per specification, data sheet and directed by Engineer in charge . 80 mm dia ( Make: SANT / LEADER / ZOLOTO)
Supplying and fixing 63mm dia, 15 mtr long RRL hose pipe with 63mm dia Male and Female Gun metal duly binded with GI wire, rivets etc conforming to IS 636 (Type -A) ,As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supply, installation, testing and commissioning of Ductile iron Y – Stainer flanged end with SS mesh 304 of following sizes confirming to IS specifications complete with rubber gasket,GI bolts , nuts, washers. As per specification, data sheet and directed by Engineer in charge . 250 mm dia ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Ductile iron Y – Stainer flanged end with SS mesh 304 of following sizes confirming to IS specifications complete with rubber gasket,GI bolts , nuts, washers. As per specification, data sheet and directed by Engineer in charge . 200 mm dia ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Ductile iron Y – Stainer flanged end with SS mesh 304 of following sizes confirming to IS specifications complete with rubber gasket,GI bolts , nuts, washers. As per specification, data sheet and directed by Engineer in charge . 150 mm dia ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Ductile iron Y – Stainer flanged end with SS mesh 304 of following sizes confirming to IS specifications complete with rubber gasket,GI bolts , nuts, washers. As per specification, data sheet and directed by Engineer in charge . 100 mm dia ( Make: SANT / LEADER / ZOLOTO)
Supplying and fixing First -Aid Hose Reel with MS construction spray painted in Post office Red, Conforming to Is 884 with upto date amendments, complete with the following as required. a) 36.6 Mtr Long 20mm (Nominal internal) dia water hose Thermoplastic / Textile reinforced / Rubber braided / Polypropylene Type - 2 as per IS:12585a) 36.6 Mtr Long 20mm (Nominal internal) dia water hose Thermoplastic / Textile reinforced / Rubber braided / Polypropylene Type - 2 as per IS:12585 b) 20mm (Nominal internal) dia gun metal ball/gate valve and nozzle. c) Drum and brackets for fixing the equipments on wall. d) Connections from riserwith 25mm dia stop valve (gun metal) & GI pipe. As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supplying and fixing of hose cabinet of size 750mm X 600mm x 250mm made of No 16 gauge SWG CRCA sheet with 6mm thick glazed glass door including necessary locking arrangement suitable to accommodate 2 Nos 15 mtr long Hose pipe, 1 No branch pipe, mounted on wall OR raised brick platform and duly painted with Post office red externally and white internally with synthetic enamel paint complete in all respect, for external hydrant as required. (ONLY FOR EXTERNAL) As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / MINIMAX / SAFEX
Supply and fixing 63mm dia Gun metal branch pipe with 20mm (Nominal internal diameter) size Gun metal / SS nozzle conforming to IS 903, suitable for instantaneous connection to interconnect hose pipe coupling. ,As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supply and fixing 4 way fire brigade connection of cast iron body with 4 Nos Gun metal Male instantaneous inlet couplings complete with cap and chain as required for 150mm dia GI pipe connection, conforming to IS 904 , As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supply, installation, testing and commissioning of 4- Way draw-out connection of cast iron body with 4 Nos Gun metal Male instantaneous inlet couplings complete with cap and chain as required for 150mm dia GI pipe connection, conforming to IS 904 as required. As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supply and fixing 2 way fire brigade siamese connection of cast iron body with 2 Nos Gun metal Male instantaneous inlet couplings complete with cap and chain as required for 100mm dia GI pipe connection, conforming to IS 904 as required. As per specification, data sheet and directed by Engineer in charge . Makes: NEWAGE (GUJARAT) / WINCO / SAFEX
Supply and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25mm dia Gun metal wheel valve, with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. as required and As per specification, data sheet and directed by Engineer in charge . make:PENTAIR /AVENTURA / FLUIDTECH
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. 6.3mm thickness. (Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 250 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion.The pipe works shall be including necessary support at intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. (Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 100 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. (Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 50 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. (Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 40 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion. The pipe works shall be supported at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete. (Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 32 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supplying, installing, testing and commissioning of GI Heavy class (C class) Pipe shall be in compliance with IS 1239 Part-I upto 150 mm dia. /3589 above 150mm dia. and GI forged welded fittings upto 50mm dia. and above 50mm butt welded firttings. in compliance with IS 1239/3589 Part-II which includes elbow, Tee, Reducer, coupling, back nuts, bends, clamps, plugs, socket etc. on wet or dry walls/ ceiling/ floors. The Pipe and fittings shall have embossed ISI mark, The installation works shall include drilling, chasing and making good/finish in all respect the demolished portion.The pipe works shall be including required size support at necessary intervals as per specification, all supports shall be Hot Dip Galvanized with 85 micron Galvanization. The tagging of pipe works shall be done as per specifications.The pipe works shall have two coats of etch primer and and two coats of enamel pain finish complete.(Internal Hydrant, Sprinkler, Terrace, Basement and pump room piping.) Including necessary hydraulic calculations as part of the shop drawings preparation. As per specification, data sheet and directed by Engineer in charge . 25 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supply. Insallation, testing and commissioning of GI Class C Pipe with G.I. fittings of below size with all accessories like fittings, flanges, bedding, one coat of primer and two coat of enemal paints etc. All jointing shall be - 50 mm and below - forged Socket weld, 65 mm and above - GI Seamless Butt welded. The fittings shall include tees, elbows, reducers, unions, end cap, etc.. Cost shall be inclusive of dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. . All work complete As per specification, data sheet and directed by Engineer in charge . 150 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supply. Insallation, testing and commissioning of GI Class C Pipe with G.I. fittings of below size with all accessories like fittings, flanges, bedding, one coat of primer and two coat of enemal paints etc. All jointing shall be - 50 mm and below - forged Socket weld, 65 mm and above - GI Seamless Butt welded. The fittings shall include tees, elbows, reducers, unions, end cap, etc.. Cost shall be inclusive of dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. . All work complete As per specification, data sheet and directed by Engineer in charge . 80 n.b make:TATA / JINDAL (HISSAR) / JINDAL STAR
Supply, installation, testing and commissioning of uPVC pipes (Class-V - 10.0 kg/cm2) as per IS 4985, solvent joint with moulded fittings as per IS-7834, concealed in wet or dry walls including all fittings such as bends in proper alignment, Y Tee, junction, offset, access pieces (Plain or door), etc. As per approved shop drawing. Cost shall include fixing at wall / ceiling level making holes complete with necessary hydraulic test. As per specification, data sheet and directed by Engineer in charge . (Application: For shaft drain) 80 n.b make:ASTRAL / SUPREME / FINOLEX
Supply and fixing Gunmetal (GM) Ball valve with SS Ball and SS Spindle as per IS 19315 - Class - I, Indian make heavy type - 15 mm NB Size as required and As per specification, data sheet and directed by Engineer in charge . 15 n.b ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing, commissioning of forged full bore brass Ball Valves complete with all fittings, pipe supports, clamps, painting etc. As per specification, data sheet and directed by Engineer in charge . Pressure class PN 16. As per specification, data sheet and directed by Engineer in charge . 25 n.b ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing, commissioning of forged full bore brass Ball Valves complete with all fittings, pipe supports, clamps, painting etc.as per specification. Pressure class PN 16. (For ARV) As per specification, data sheet and directed by Engineer in charge . 32 n.b ( Make: SANT / LEADER / ZOLOTO)
Supply, installation, testing, commissioning of forged full bore brass Ball Valves complete with all fittings, pipe supports, clamps, painting etc.as per specification. Pressure class PN 16. As per specification, data sheet and directed by Engineer in charge . 40 n.b ( Make: SANT / LEADER / ZOLOTO)
Supplying and wrapping the anticorrosive material for buried pipes with coating of Primer and wrapping with 4 mm thick polymer corrosion resistant tape as per IS : 10221 with 15 mm overlap as per specificatios. As per specification, data sheet and directed by Engineer in charge . a) 200mm nominal dia Make:IWL / RUSTECH
Supplying and wrapping the anticorrosive material for buried pipes with coating of Primer and wrapping with 4 mm thick polymer corrosion resistant tape as per IS : 10221 with 15 mm overlap as per specificatios.As per specification, data sheet and directed by Engineer in charge . b) 150mm nominal dia Make:IWL / RUSTECH
Supplying and wrapping the anticorrosive material for buried pipes with coating of Primer and wrapping with 4 mm thick polymer corrosion resistant tape as per IS : 10221 with 15 mm overlap As per specification, data sheet and directed by Engineer in charge . d) 80mm nominal dia Make:IWL / RUSTECH
Providing, fixing, testing, commissioning of installation control valve of Cast iron body and brass / Bronze working parts(ICV) comprising of water, motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when the Wet riser/ Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass , test control box, ball valves, GI pipe of required size, flanges, orifice plate, gasket etc of size 150mm dia As per specification, data sheet and directed by Engineer in charge . Makes: SANT / LEADER / ZOLOTO
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish as per specifications complete As per specification, data sheet and directed by Engineer in charge . make:VICTAULIC / TYCO / VIKING
Supply, installation, testing and commissioning of sprinklers complete with Satandard Response Standard Coverage, Pendant Sprinkler, K-5.6,1/2”NPT,68 Degree C, Chrome finish , UL listed & FM Approved As per specification, data sheet and directed by Engineer in charge . make:VICTAULIC / TYCO / VIKING
Supply, installation, testing and commissioning of sprinklers complete with standard Response Standard Coverage, Pendant Sprinkler, K-8,1/2”NPT,79 Degree C, Chrome finish , UL listed & FM Approved as required and As per specification, data sheet and directed by Engineer in charge .. make:VICTAULIC / TYCO / VIKING
Supply, installation, testing and commissioning of sprinklers complete with Standard Response Standard Coverage, Upright Sprinkler, K-5.6,1/2”NPT,68 Degree C, Chrome finish , UL listed & FM Approved As per specification, data sheet and directed by Engineer in charge . make:VICTAULIC / TYCO / VIKING
Supply, installation, testing and commissioning of sprinklers generally as specified complete with Standard response Standard Coverage, Upright Sprinkler, K-8,1/2”NPT,79 Degree C, Chrome finish , UL listed & FM Approved As per specification, data sheet and directed by Engineer in charge .. make:VICTAULIC / TYCO / VIKING
Supply, installation, testing and commissioning of Wafer type gear operated Butterfly valve with tamper switch as per (PN 16) following MOC : • Body : Cast iron • Disc : SS304 • Seat : EPDM As per specification, data sheet and directed by Engineer in charge .. 65 n.b (Sprinkler at tapping) Makes: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Wafer type gear operated Butterfly valve with tamper switch as per (PN 16) following MOC : • Body : Cast iron • Disc : SS304 • Seat : EPDM As per specification, data sheet and directed by Engineer in charge .. 80 n.b (Sprinkler at tapping) Makes: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Wafer type gear operated Butterfly valve with tamper switch as per (PN 16) following MOC : • Body : Cast iron • Disc : SS304 • Seat : EPDM As per specification, data sheet and directed by Engineer in charge .. 100 n.b (Sprinkler at tapping) Makes: SANT / LEADER / ZOLOTO)
Supply, installation, testing and commissioning of Wafer type gear operated Butterfly valve with tamper switch as per (PN 16) following MOC : • Body : Cast iron • Disc : SS304 • Seat : EPDM As per specification, data sheet and directed by Engineer in charge . 150 n.b (Sprinkler at tapping) Makes: SANT / LEADER / ZOLOTO)
Supply,installation,testing and commissioning of vane type flow switches complete with : i) flow switch & Press indicator,sight glass ii) Control wiring till control panel(lumpsum)iii) Orifice plate with flange to maintain a pressure of 2.2 ksc at the tap-off as required.iv) Drain assembly includes drain valve, sight flow indicator as shown in drawing and complete with all necessary accessories . As per specification, data sheet and directed by Engineer in charge . 65 n.b Makes: SYSTEM SENSOR / SWITZER / HONEYWELL
Supply,installation,testing and commissioning of vane type flow switches complete with : i) flow switch & Press indicator,sight glass ii) Control wiring till control panel(lumpsum) iii) Orifice plate with flange to maintain a pressure of 2.2 ksc at the tap-off as required.iv) Drain assembly includes drain valve, sight flow indicator as shown in drawing and complete with all necessary accessories . As per specification, data sheet and directed by Engineer in charge . 80 n.b Makes: SYSTEM SENSOR / SWITZER / HONEYWELL
Supply,installation,testing and commissioning of vane type flow switches complete with : i) flow switch & Press indicator,sight glass ii) Control wiring till control panel(lumpsum)iii) Orifice plate with flange to maintain a pressure of 2.2 ksc at the tap-off as required.iv) Drain assembly includes drain valve, sight flow indicator as shown in drawing and complete with all necessary accessories . As per specification, data sheet and directed by Engineer in charge . 100 n.b Makes: SYSTEM SENSOR / SWITZER / HONEYWELL
Supply,installation,testing and commissioning of vane type flow switches complete with : i) flow switch & Press indicator,sight glass ii) Control wiring till control panel(lumpsum)iii) Orifice plate with flange to maintain a pressure of 2.2 ksc at the tap-off as required.iv) Drain assembly includes drain valve, sight flow indicator as shown in drawing and complete with all necessary accessories . As per specification, data sheet and directed by Engineer in charge . 150 n.b Makes: SYSTEM SENSOR / SWITZER / HONEYWELL
Supply, installation, testing & commissioning of sprinkler flexible pipe (braided type) (UL Listed & FM APPROVED) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stock bar of following sizes complete as required. As per specification, data sheet and directed by Engineer in charge . 750mm to 800 mm Makes:HD FIRE / TYCO / NEWAGE
Supply, installation, testing & commissioning of sprinkler flexible pipe (braided type) (UL Listed & FM APPROVED)of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stock bar of following sizes complete as required. Makes: As per list of recommended brands. As per specification, data sheet and directed by Engineer in charge . 1000 mm to 1200 mm Makes:HD FIRE / TYCO / NEWAGE
Supply, installation, testing & commissioning of sprinkler flexible pipe (braided type) (UL Listed & FM APPROVED) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stock bar of following sizes complete as required. Makes: As per list of recommended brands. As per specification, data sheet and directed by Engineer in charge . . 1500 mm Makes:HD FIRE / TYCO / NEWAGE
Supply, fabricating , installing structural steel supports for fixing all sizes of GI pipes and fire accessories from ceiling / wall with MS Channels, Angles, Flats, Rods, as required at site with anchor fasteners, Clamps, threaded rods, nuts, bolts,washers etc complete with painting. Appx. Assume. (FOR EXTERNAL HOSE CABINET) as required and As per specification, data sheet and directed by Engineer in charge . make:VIZAG,JINDAL,SAIL)
Supply, installation, testing and commissioning of Armaprotect Firestop mortar system, with minimum 2 hours fire rating . The system must be tested in accordance with UL 1479/ASTM-E 814 standards, for horizontal openings in floors or slabs after passing service lines like cables bundles, conduits, cable trays Bus duct. The mortar shall be a lightweight cementitious product and the product shall be tested on durability and serviceability according EOTA TR 024. The durability class is set to Z2 (tested in accordance with EOTA TR 024) with reaction to fire class A1 and the operating temperature from 5°C to 200°C & 2000kg/m3 with filler mastic sealant. The system shall be UL listed & classified and product shall bear the UL logo. If none of UL test certificate comply with actual application, an EJ document will be provided based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. For conduit application an intumescent firestop wrap should be provided. The Firestop mortar system can be painted on the surface if required. For Floor application will be cast over Mineral Wool board of 150 kg/m³ having 60 mm thickness for minimum 2 hours fire rating.(Cabe Trays & Bus Bar,Through Penetration on Floor with Penetrants like cables bundles, conduits and cable tray, Bus duct) As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of ablative board system on both sides of wall for 2 hours fire rating when tested in accordance with ASTM E 814/UL 1479 standards. overlapping of 20mm should be done on both sides. The surface the penetrants should be wrapped with Intumescent Wrap if the penetrant is combustible. This system is to seal all fire rated openings in wall made of concrete, masonry, gypsum partition, after passing service lines like cables bundles, conduits, and cable tray. The system shall be UL listed & classified and product shall bear the UL. If none of UL test certificate comply with actual application, an EJ document based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Armacell Firestop training and in accordance with Armacell guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. The system is flexible for repenetrating by cutting hole into the board and resealing it with mineral wool/ filler with mineral wool after inserting the penetrating item.the system will not emit any dangerous substances after installation (tested in accordance with ETAG 026-02). The ablative firestop coating and ablative firestop filler are resistant against humidty, frost-dew-change and UV radiation(Cable Tray, loose Cables & Bus Ducts,hrough Penetration on Wall with Penetrants like cables bundles, conduits, cable tray & Bus ducts.)As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of' ablative board system on both sides of wall for 2 hours fire rating when tested in accordance with ASTM E 814/UL 1479 standards. Or provide mineral wool board of 60mm thick firmly place it in the opening with fillers on both side and apply the Ablative Paint on the surface of the mineral board. overlapping of 20mm should be done on both sides. This system is to seal all fire rated horizontal in floor/wall made of concrete, masonry, gypsum partition, after passing service lines like HVAC ducts. The system shall be UL listed & classified and product shall bear the UL. If none of UL test certificate comply with actual application, an EJ document prepared by qualified personnel and based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with Armacell guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. The system is flexible for repenetrating by cutting hole into the board and resealing it with mineral wool/ filler with mineral wool after inserting the penetrating item. The system will not emit any dangerous substances after installation (tested in accordance with ETAG 026-02). The ablative firestop coating and ablative firestop filler are resistant against humidty, frost-dew-change and UV radiation. Intumescent wrap to be installed first over the insulation surface before installation of the ArmaProtect Coated board system.(HVAC DUCT with Insulation,Through Penetration on Wall by HVAC duct installed with Insulation) As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of ablative board system on both sides of wall for 2 hours fire rating when tested in accordance with ASTM E 814/UL 1479 standards. Or provide mineral wool board of 60mm thick firmly place it in the opening with fillers on both side and apply the Ablative Fire Paint on the surface of the mineral board. overlapping of 20mm should be done on both sides. This system is to seal all fire rated horizontal in floor/wall made of concrete, masonry, gypsum partition, after passing service lines like HVAC Chilled Water/Refrigerant/Condensate Piping with insulation. The system shall be UL listed & classified and product shall bear the UL. If none of UL test certificate comply with actual application, an EJ document prepared by qualified personnel and based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. The system is flexible for repenetrating by cutting hole into the board and resealing it with mineral wool/ filler with mineral wool after inserting the penetrating item. The system will not emit any dangerous substances after installation (tested in accordance with ETAG 026-02). The ablative firestop coating and ablative firestop filler are resistant against humidty, frost-dew-change and UV radiation. Intumescent wrap to be installed first over the insulation surface before installation of the ArmaProtect Coated board system.(HVAC Pipe with Insulation,Through Penetration on Wall by HVAC Chill Water/Refrigerant/Condensate Pipe line with Insulation) As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of Armaprotect Firestop mortar system, with minimum 2 hours fire rating . The system must be tested in accordance with UL 1479/ASTM-E 814 standards, for horizontal openings in floors or slabs after passing service lines like cables bundles, conduits, cable trays Bus duct. The mortar shall be a lightweight cementitious product and the product shall be tested on durability and serviceability according EOTA TR 024. The durability class is set to Z2 (tested in accordance with EOTA TR 024) with reaction to fire class A1 and the operating temperature from 5°C to 200°C & 2000kg/m3 with filler mastic. The system shall be UL listed & classified and product shall bear the UL logo. If none of UL test certificate comply with actual application, an EJ document will be provided based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. For conduit application an intumescent firestop wrap should be provided. The Firestop mortar system can be painted on the surface if required. For Floor application will be cast over Mineral Wool board of 150 kg/m³ having 60 mm thickness for minimum 2 hours fire rating.(Metallic Pipe ( Fire Fighting Pipe,Through Penetration on Floor by Metallic pipe for Plumbing or Fire Fighting) As per specification, data sheet and directed by Engineer in charge . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of Firestop mortar system, with minimum 2 hours fire rating . The system must be tested in accordance with UL 1479/ASTM-E 814 standards, for horizontal openings in floors or slabs after passing service lines like cables bundles, conduits, cable trays Bus duct. The mortar shall be a lightweight cementitious product and the product shall be tested on durability and serviceability according EOTA TR 024. The durability class is set to Z2 (tested in accordance with EOTA TR 024) with reaction to fire class A1 and the operating temperature from 5°C to 200°C & 2000kg/m3. The system shall be UL listed & classified and product shall bear the UL logo. If none of UL test certificate comply with actual application, an EJ document will be provided based on approved systems like UL test certificates & in accordance with IFC guidelines shall be produced by manufacturer. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with guidelines and UL system test certificates or approved EJ document. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. For conduit application an intumescent firestop wrap should be provided. The Firestop mortar system can be painted on the surface if required. For Floor application will be cast over Mineral Wool board of 150 kg/m³ having 60 mm thickness for minimum 2 hours fire rating.G3(None,Top/Head of Wall (Linear) Joint between top surface of wall & Bottom surface of slab.) As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply, installation, testing and commissioning of Fire Collar a solid metal sleeve which is equipped with several layers of the intumescent material to maintain the fire resistance performance of fire penetrations in walls and floors for combustible pipes in accordance to EN 1366-3. Highly intumescent with a expansion factor of 12 - 22.5 times. Reaction to fire class A1 (housing) / class E (inlay) and the operating temperature is from -40 °C to 70 °C. The system shall have ETA and CE marking. A firestop submittal shall be produced by manufacturer, in accordance with approved passive fire protection method statement. Firestop installation shall be done by certified installers gone through Firestop training and in accordance with guidelines. Firestop Specialty Contractor needs to submit work completion certificate along with installation report for periodic inspection & maintenance purpose. (PVC Pipe,Through Penetration on Wall or Floor by (Combustible)Plastic pipe.) As per specification, data sheet and directed by Engineer in charge . . make:HILTI / FISCHER / 3M
Supply and fixing of ISI mark (IS:15683) Mono ammonium phosphate powder 90 (MAP) 6 Kg Fire extinguisher, stored pressure type, pressure gauge, gross wt. 9.4 kg, empty wt.3.4 kg, Discharge time minimum 13 sec, controllable discharge mechanism, range min. 4 mts applicable on classes A,B, C & electrically started fire, A rating -4 A, B rating -34 B, can construction: Deep drawn and Co2 MIG welding, Valve construction: Forging & Machining, internal coating of can: Epoxy powder coating, External coating of Can: Epoxy polyester powder coating, sheet metal thickness:1.60mm, Helium leak detection tested with 5 years warranty Including transportation, all taxes and all labour charges etc complete. As per specification, data sheet and directed by Engineer in charge . . make: CEASE FIRE / MINIMAX
Supply and fixing of Co2 type Fire Extinguishers 4.5 Kg capacity confirming to IS 2878 made from ISI marked steam less cylinder confirming to IS:7285 & CE certified and fitted with ISI marked controlled valve confirming to IS:3224, high pressure 1 Mtr discharge hose & horn complete with initial gas charged with carrying handle with wheels and wall mounting bracket. Squeeze lever discharge, used un-used indicator, epoxy coated paint (Red) with 93% gloss with 2 years warranty including transportation, all taxes and all labour charges etc complete. As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply, installation, testing and commissioning of 5 kg Automatic type Fire Extinguishers "Chemours UL listed & FM approved FE-36 (HFC-236 fa) gas which is Electrically nonconductive, non corrosive, colorless and non-residual clean agent Suitable for Class A, B, C, and electrical fires approved with US EPA (Environmental Protection Agency) , listing under USA Signification New Alternative Policy ( SNAP ), FM Approved & also approved by UL , compliant with ASTM -D6541-11. KANEX FE-36 Fire Extinguishers having Zero Ozone Depletion Potential (ODP), low toxicity, also its replacement for Halon 1211, Halon 1201, UGTS Pressure Gauge, Empty Weight 2.64 kg, Full weight 7.64 kg. Can Height 375mm, Diameter 230 ± 10mm, Sheet metal thickness : 2 mm, Body Construction Deep Drawn with MIG Welding technology, External Pure polyester and Internal Epoxy polyester powder coated, Brass forged sprinkler valves, Heat Sensitive Glass bulb of 68 ° C. Area covered will be 5.3 m2 and volume of coverage is 6 m3. As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply, installation, testing and commissioning of 6 ltr. Fire Extinguisher K Class Kitchen Wet chemical (Blend of Potassium Acetate, Potassium citrate or Potassium carbonate), Smooth and Polished Stainless Steel body, Applicable fire class K, UGTS Pressure Gauge, Can Height 550 mm, Diameter 150 ± 10mm, Discharge Time 13 Sec, Jet Range 2 Meters, Average Discharge is 90%, Controllable discharge mechanism with EPDM Hose & Specially designed Nozzle that allows a broad, dispersed discharge of agent that delivers a high volume, low velocity delivery of wet chemical which doesnt cause the cooking oil to splash. CE Marked Valve with inbuilt NRV & Safety Release Provision and safety Pin is of SS material, Sheet metal thickness : 0.9 to 1 mm. CE Marked.as required and as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply, installation, testing and commissioning of 9 kg CO2 High Pressure trolly mounted Fire Extinguisher, filled with Co2 Gas as per IS 15222, Gross Weight 36 Kg, empty weight 27 Kg, Control discharge mechanism fitted with minimum 1.5 Meter Wire Braided Hose & Flat Horn with DiffuSERNozzle for dispersed discharge of CO2, Discharge Time 30 Sec, Average Discharge is 95%, applicable on Class B, C and electrically started Fire, Internal coating is not applicable & External coating is of enamel spray painting, Valve Confirm to IS 3224 ISI Marked, CO2 Cylinder construction: hot spinning by seamless pipes & bearing ISI mark, Body confirms to IS 7285 and PESO APPROVED, Extinguishers confirmed to IS 16018:2012 and ISI maked. Fire Rating: 55B as required and As per specification, data sheet and directed by Engineer in charge . . make: CEASE FIRE / MINIMAX
Supply, installation, testing and commissioning of 9 ltr. Mechanical Foam stored pressure type Fire Extinguisher filled with AFFF Foam confirms to IS 4989 (Part-II). Applicable fire class A & B, UTGS Pressure Gauge, Gross Weight 12 Kg, empty weight 4.3 Kg, Can Height 575mm, Diameter 180 ± 10mm, Discharge Time 35 Sec, Controllable discharge mechanism, Jet Range 7 Meters, Average Discharge is 95%, Fire Rating- 4A:144B, Can Construction : Deep drawn & CO2 Mig welded, Controllable discharge mechanism with EPDM Hose & Air aspirated Nozzle, External Pure polyester powder coated (UV resistant) and Internal Plastic lining, Brass forged valves with safety Pin is of SS material, Sheet metal thickness : 2 mm, As pe IS 15683:2018 and ISI Marked. As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply, installation, testing and commissioning of 5kg Automatic Modular Type Fire Extinguisher (Ceiling Mounted) complete with heat-sensitive glass bulb, mounting bracket, charged with ABC dry powder, nitrogen pressurised, suitable for automatic operation at 68°C, including all accessories, as per relevant Indian Standards such as IS 15683 and extinguishing media conforming to IS 4308, ISI/BIS marked, complete in all respects. make: CEASE FIRE / MINIMAX
Supply and fixing of Cease fire or its equivalent Escape gear Mild Steel box size 425mmx360mmx140mm Epoxy powder coated to protect it from Weathering , smoke hood tested to Eupropean Standard EN 403 1993-S known to reduce Carbon Monoxide, propend(acrloein), hydrogen chloride, hydrogen Cyanide and Solid and liquid toxic particles to manageable level for atleast 15 minutes shall with stand tempeartures upto 80 degrees single use only Fire Blanket size 1.2m x1.8m used to cover any vessel containing used to Extinguish a clothing fire wrap blanket around the victim.make as required and As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply and fixing of 4Nos of 9 Ltrs capacity round bottom sand buckets along with bucket sand, Fire buckets with round bottom type enamel painted, white inside & red out side and letter FIRE inblack out side & Handle with mounting bracket. as required and As per specification, data sheet and directed by Engineer in charge . make: CEASE FIRE / MINIMAX
Supply and fixing of Fire bucket stand fabricated by M.S. angles to install for Four numbers of buckets as per local fire officers standards.as required and As per specification, data sheet and directed by Engineer in charge .
Supply, installation, testing and commissioning of' R.C.C. Plain ended pipes conforming to B.I.S 458/2003 ,Ex-factory, excluding transportation and all taxes.as required and as directed by engineer in charge. NP - 3 Class - 300 mm i/d As per specification, data sheet and directed by Engineer in charge . make:Jain Spun Pipe CO/ Pranali / Deccan concrete
Supplying , installation, Testing and commissioning of 25mm dia Air Release Valve Including all accessories as required (PN 16) as required and As per specification, data sheet and directed by Engineer in charge . . Makes: SANT / LEADER / ZOLOTO
Supplying , installation, Testing and commissioning of 150 mm dia Pressure Relief Valve Including all accessories as required (PN 16) as required and as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge . Makes: SANT / LEADER / ZOLOTO
Providing, fixing, jointing, testing and commisioning of Deluge valve Station (with bypass valve arrangement) flanged ductile iron body Aluminium bronze Clapper and Latch, EPDM Clapper seal, Nitrile rubber bushing and seat O ring, S.S Shaft and EPDM diaphragm complete with 1. wet pilot basic trim asembly (horizontal mounting) 2. weather proof electric release trim assembly with two way solenoid valve. 3. Drain and drip trim 4. Test and alarm trim The cost shall be inclusive of flanges of appropriate class, PTFE gasket, washers, nut and bolts, including 24V DC power and control wiring upto panel & ON/OFF arrangement and all other associated works complete as required. 50 mm dia Makes: SANT / LEADER / ZOLOTO
Providing, fixing, jointing, testing and commisioning of Deluge valve Station (with bypass valve arrangement) flanged ductile iron body Aluminium bronze Clapper and Latch, EPDM Clapper seal, Nitrile rubber bushing and seat O ring, S.S Shaft and EPDM diaphragm complete with 1. wet pilot basic trim asembly (horizontal mounting) 2. weather proof electric release trim assembly with two way solenoid valve. 3. Drain and drip trim 4. Test and alarm trim The cost shall be inclusive of flanges of appropriate class, PTFE gasket, washers, nut and bolts, including 24V DC power and control wiring upto panel & ON/OFF arrangement and all other associated works complete as required. 80 mm dia Makes: SANT / LEADER / ZOLOTO
Providing, fixing, jointing, testing and commisioning of Deluge valve Station (with bypass valve arrangement) flanged ductile iron body Aluminium bronze Clapper and Latch, EPDM Clapper seal, Nitrile rubber bushing and seat O ring, S.S Shaft and EPDM diaphragm complete with 1. wet pilot basic trim asembly (horizontal mounting) 2. weather proof electric release trim assembly with two way solenoid valve. 3. Drain and drip trim 4. Test and alarm trim The cost shall be inclusive of flanges of appropriate class, PTFE gasket, washers, nut and bolts, including 24V DC power and control wiring upto panel & ON/OFF arrangement and all other associated works complete as required. 150 mm dia Makes: SANT / LEADER / ZOLOTO
Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required. (Application : For Basement Zoning ) make:HD / TYCO / VIKING
Supply, installation, Testing and Commisioning of active fire barrier automatic drop down fire curtains, as per UL 10D. Active fire curtain barrier assemblies shall comprise of a fire resistant fabric which is wound on to a steel roller, which is powered by an internal electric DC motor, enclosed within a galvanized mild steel box 200*200/400mm 1.5mm thickness, including a conjoined bottom bar for entire length to suit the deflection performance requirements of the project and the desired ceiling configuration in fitted to the bottom edge of the fabric curtain. 1. Curtain fabric – min 120 minutes fire rating, Valmiera stainless steel reicement fabric 44152. 2.The fabric material is tested as part of the complete assembly, complete as either a single construction or as an overlapped and conjoined construction separately in the orientation and standard use of the application and installed on a steel mild steel barrel 100mm dia 1.6mm thickness in accordance with the fire resistance test in accordance with UL 10D.. 3.The galvanised steel side Guides should be of dimensions 100*53mm made of 2mm thickness 4.GFS Electric motor – Motor shall contain the necessary drive mechanism, a mechanical epicyclip gearbox retarder, and automatic overload protection, linked to an internal 24V dc electromagnetic brake with regenerative braking system. Additionally, motors are tested for reliability, durability and self-closing with a closing speed of 0.15m/s to 0.61m/s as per UL 10D. 5. Control Panel: Each system should have individual Panel having inbuilt batteries for minimum 2 hours backup, if required provision of split drop & delay drop to be inbuilt. 6. BMS: FC Panel to be connected with BMS via soft integration RS485 if required. Make supplied should have a UL This shall be integrated with the electrical, BMS, FIre/ Smoke detection system, etc, to ensure complete functionality. The entire system to be designed and executed as per the UL code provisions and tolerances. Contractor to produce design & shop drawings for approval as per Project Consultant / Engineer-in-charge. The work shall be guaranteed for all material & constructional defects. The rate shall include for Design, fabrication, submission & approval of design & shop drawings prior to supply & installation of the Fire Curtains as per design intent drawings. The clear openable size for the Fire curtain as per drawings. Respective Technical Test Certifications and other documents must be submitted to Consultant for approval as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge .Size : 5000mm(w)X 2600mm(H) MAKE: ORIENT FIRE , BLE & U S SMOKE AND FIRE CURTAINS
Supply, installation, Testing and Commisioning of active fire barrier automatic drop down fire curtains, as per UL 10D. Active fire curtain barrier assemblies shall comprise of a fire resistant fabric which is wound on to a steel roller, which is powered by an internal electric DC motor, enclosed within a galvanized mild steel box 200*200/400mm 1.5mm thickness, including a conjoined bottom bar for entire length to suit the deflection performance requirements of the project and the desired ceiling configuration in fitted to the bottom edge of the fabric curtain. 1. Curtain fabric – min 120 minutes fire rating, Valmiera stainless steel reicement fabric 44152. 2.The fabric material is tested as part of the complete assembly, complete as either a single construction or as an overlapped and conjoined construction separately in the orientation and standard use of the application and installed on a steel mild steel barrel 100mm dia 1.6mm thickness in accordance with the fire resistance test in accordance with UL 10D.. 3.The galvanised steel side Guides should be of dimensions 100*53mm made of 2mm thickness 4.GFS Electric motor – Motor shall contain the necessary drive mechanism, a mechanical epicyclip gearbox retarder, and automatic overload protection, linked to an internal 24V dc electromagnetic brake with regenerative braking system. Additionally, motors are tested for reliability, durability and self-closing with a closing speed of 0.15m/s to 0.61m/s as per UL 10D. 5. Control Panel: Each system should have individual Panel having inbuilt batteries for minimum 2 hours backup, if required provision of split drop & delay drop to be inbuilt. 6. BMS: FC Panel to be connected with BMS via soft integration RS485 if required. Make supplied should have a UL This shall be integrated with the electrical, BMS, FIre/ Smoke detection system, etc, to ensure complete functionality. The entire system to be designed and executed as per the UL code provisions and tolerances. Contractor to produce design & shop drawings for approval as per Project Consultant / Engineer-in-charge. The work shall be guaranteed for all material & constructional defects. The rate shall include for Design, fabrication, submission & approval of design & shop drawings prior to supply & installation of the Fire Curtains as per design intent drawings. The clear openable size for the Fire curtain as per drawings. Respective Technical Test Certifications and other documents must be submitted to Consultant for approval as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge .Size : 8000mm(W)X 2600mm(H) MAKE: ORIENT FIRE , BLE & U S SMOKE AND FIRE CURTAINS
Supply, installation, Testing and Commisioning of active fire barrier automatic drop down fire curtains, as per UL 10D. Active fire curtain barrier assemblies shall comprise of a fire resistant fabric which is wound on to a steel roller, which is powered by an internal electric DC motor, enclosed within a galvanized mild steel box 200*200/400mm 1.5mm thickness, including a conjoined bottom bar for entire length to suit the deflection performance requirements of the project and the desired ceiling configuration in fitted to the bottom edge of the fabric curtain. 1. Curtain fabric – min 120 minutes fire rating, Valmiera stainless steel reicement fabric 44152. 2.The fabric material is tested as part of the complete assembly, complete as either a single construction or as an overlapped and conjoined construction separately in the orientation and standard use of the application and installed on a steel mild steel barrel 100mm dia 1.6mm thickness in accordance with the fire resistance test in accordance with UL 10D.. 3.The galvanised steel side Guides should be of dimensions 100*53mm made of 2mm thickness 4.GFS Electric motor – Motor shall contain the necessary drive mechanism, a mechanical epicyclip gearbox retarder, and automatic overload protection, linked to an internal 24V dc electromagnetic brake with regenerative braking system. Additionally, motors are tested for reliability, durability and self-closing with a closing speed of 0.15m/s to 0.61m/s as per UL 10D. 5. Control Panel: Each system should have individual Panel having inbuilt batteries for minimum 2 hours backup, if required provision of split drop & delay drop to be inbuilt. 6. BMS: FC Panel to be connected with BMS via soft integration RS485 if required. Make supplied should have a UL This shall be integrated with the electrical, BMS, FIre/ Smoke detection system, etc, to ensure complete functionality. The entire system to be designed and executed as per the UL code provisions and tolerances. Contractor to produce design & shop drawings for approval as per Project Consultant / Engineer-in-charge. The work shall be guaranteed for all material & constructional defects. The rate shall include for Design, fabrication, submission & approval of design & shop drawings prior to supply & installation of the Fire Curtains as per design intent drawings. The clear openable size for the Fire curtain as per drawings. Respective Technical Test Certifications and other documents must be submitted to Consultant for approval as directed by engineer in charge. As per specification, data sheet and directed by Engineer in charge .Size : 9000mm(W)X 2600mm(H) MAKE: ORIENT FIRE , BLE & U S SMOKE AND FIRE CURTAINS
Supply, installation, Testing and Commisioning of Firex FB 250 Barrier system, 2 hour rating Above Fire Curtains (Mineral wool board fire barrier) 2 hour fire rating to BS:476 PART-20 Tested & certified to meet UL 1479 & IS : 12458. High Density Firex Coated Mineral Wool Boards 50mm Thickness : 100mm – 2 hour rated. Density 150 Kgs /cubic meter. Over coated with FM approved water immersion /weathering resistant FIREX EC 43 coating. Specifically designed for sealing around cable & service penetrations in walls and below panels. Firex FB 250 System consists of very high density fire & heat resistant mineral wool boards, coated with water resistant, Firex intumescent coating, affixed with Firex expanding sealant, which transforms into a hard ceramic during a fire to prevent the passage of fire and smoke and the transfer of heat. Firex FB 250 Barrier system make:ORIENT FIRE , BLE & U S SMOKE AND FIRE CURTAINS
Supply, Installation, Testing and Commissioning of Fire Pump Test Flow Meter Flow Meter 150MM (Digital Type and BMS compatible) suitable for flanged end installation capable to withstand system pressure. Measurements shall be done in both flow directions, with high measurement accuracy over a wide range of flow rates 0.1 to 10 m/s. The minimum required conductivity of the measured medium is 20μS/cm. The Flow Meters and the accessories shall be suitable for continuous operation under an ambient temperature of 0-55°C and Relative Humidity of 0-95%. All accessories required for mounting/erection of these instruments shall be furnished as necessary for completeness of the system. As per specification, data sheet and directed by Engineer in charge . MAKE: FORBES MARSHALL / EUREKA / GERAND
Supply and fixing of Thermal Insulation with Rock/Glass Wool with Aluminum cladding (Density -96 Kg/m3 thickness -50mm) for Exhaust pipe, As per specification, data sheet and directed by Engineer in charge . MAKE: JINDAL, HINDALCO, BALCO)
Earth work excavation including all soils for trench, Pole Pit and Earth Pit As per specification, data sheet and directed by Engineer in charge .
Design, fabrication, assembling, wiring, supply, testing at works, packaging, forwarding to site, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - FIRE PUMP PANEL Incomer: 1 No. 800A 50KA 4P ACB . Metering for Incomer: 1 No. Multifunction meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 800/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 set - Earth leakage relay. Bus bar: 1 set -800A, 4Wire, 25KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. Outgoings: 5 Nos. MCCB suitable for 110KW motor with Star Delta Starter with all accessories & relays & contactors with 1 No. ON status LED indicating lamp, 5 Nos. MPCB suitable for 7.5KW motor with DOL Starter with all accessories & relays & contactors with 1 No. ON status LED indicating lamp, 3No. 40a DP MCB with backfuse All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required & as directed by Engineer In Charge and as per aproved make. Makes: Motor Control Centre (Fire Pump Panel): GLOBUS / ELLINS / PRAGATI; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; Current Transformers: KALPA / VOLTAMPS / KAPPA; Protection Relays: ABB / SIEMENS / SCHNEIDER; Indicating Lamps: L&T / TEKNIC; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON; Power Contactors: ABB / SIEMENS / SCHNEIDER; Over Load Relay: LK / SIEMENS
Supply, Installation, testing & Commissioning of MPCB/MCCB/ MCB Isolators as per technical Specifications complete with all necessory accessories required to complete the job including structural supports for fire fighting works MCCB isolator starter panel with Star Delta Starter for 1 nos. of 3 Phase 7.5Kw motor with Powder coated M.S enclosure (isolator starter panel shall be IP 66 rating.) Makes: ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Power Contactors: ABB / SIEMENS / SCHNEIDER
Supply, Installation, testing & Commissioning of Remote on off push button for booster pumps with Powder coated M.S enclosure Makes: Push Buttons: SIEMENS / TEKNIC
Supply, laying and dressing of 3.5Core 185Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning complete for firefighting works & as directed by Engineer In Charge and as per aproved make. Make-KEI / POLYCAB / HAVELLS / RR KABEL
Supply, laying and dressing of 3Core 10Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required for firefighting works & as directed by Engineer In Charge and as per aproved make. Make-Polycab/KEI/RR Kabel /Havells
Supply & making of Cable end termination of the 3.5Core 185Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required for firefighting works & as directed by Engineer In Charge and as per aproved make. Make-DOWELLS / MULTI)
Supply & making of Cable end termination of the 3Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as required for firefighting works & as directed by Engineer In Charge and as per aproved make. Makes: DOWELLS / MULTI)
Supply, Instalaltion, Termination, Testing and comissioning of ISI Certified (for Signal & Field devices, Third Party Integration etc....) ATSC, PVC insulated, 2Cx1.5sqmm armored, Tinned Copper, twisted, shielded, PE insulated, Cable with proper ferrules, lugs, and other necessary accessories. The spec shall meet the system manufacturer specifications including all charges complete etc, as directed by Engineer in Charge/ departmental authorities as required,as per specifications & as directed by Engineer In Charge and as per approved make. Makes:POLYCAB / RR KABEL / KEI / HAVELLS
Supply and laying of 50 mm x 6mm GI Flat(2.5 Kgs /mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as requireda & as directed by Engineer In Charge and as per aproved make for fire fighting works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 6mm GI Flat (1.18Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required & as directed by Engineer In Charge and as per aproved make for fire fighting works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 8 SWG Copper wire(0.1155Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required as required & as directed by Engineer In Charge and as per aproved make for fire fighting works. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply, Installation, testing and commissioning of 2kg Cylinder filled with UL Listed & FM Approved Clean Agent - Grenoz® FK-5-1-12 (Non-HFC), Self activating Automatic Fire Suppression System for Panel Protection, Direct Low Pressure Valve with integrated ball valve and NRV for Pressure Gauge and Pressure Switch, Big Dial Pressure Gauge approx. 30mm dial size, UL Listed Pressure Switch with set pressure suitable to generate alarm in the event of clean agent discharge or pressure drop. Cylinder shall be made of Mild Steel CR2 grade conforming to IS 513, Internal and External cylinder surface shall be Pure Polyester Anti-corrosion Powder Coated with min DFT 50 micron. Service Pressure shall be of 15 bar, Hydropressure Test of 35 bar and Burst Pressure greater than 55 bar. Mounting Arrangement shall be MS with black powder coating. Fittings shall include Straight Connector with double locking seals and End of Line Adaptor with Big Dial Pressure Gauge suitable for Clean Agent. Fittings shall be of Double locking seals and easy push-in connection type as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of 3kg Cylinder filled with UL Listed & FM Approved Clean Agent - Grenoz® FK-5-1-12 (Non-HFC), Self activating Automatic Fire Suppression System for Panel Protection, Direct Low Pressure Valve with integrated ball valve and NRV for Pressure Gauge and Pressure Switch, Big Dial Pressure Gauge approx. 30mm dial size, UL Listed Pressure Switch with set pressure suitable to generate alarm in the event of clean agent discharge or pressure drop. Cylinder shall be made of Mild Steel CR2 grade conforming to IS 513, Internal and External cylinder surface shall be Pure Polyester Anti-corrosion Powder Coated with min DFT 50 micron. Service Pressure shall be of 15 bar, Hydropressure Test of 35 bar and Burst Pressure greater than 55 bar. Mounting Arrangement shall be MS with black powder coating. Fittings shall include Straight Connector with double locking seals and End of Line Adaptor with Big Dial Pressure Gauge suitable for Clean Agent. Fittings shall be of Double locking seals and easy push-in connection type. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of 4kg Cylinder filled with UL Listed & FM Approved Clean Agent - Grenoz® FK-5-1-12 (Non-HFC), Self activating Automatic Fire Suppression System for Panel Protection, Direct Low Pressure Valve with integrated ball valve and NRV for Pressure Gauge and Pressure Switch, Big Dial Pressure Gauge approx. 30mm dial size, UL Listed Pressure Switch with set pressure suitable to generate alarm in the event of clean agent discharge or pressure drop. Cylinder shall be made of Mild Steel CR2 grade conforming to IS 513, Internal and External cylinder surface shall be Pure Polyester Anti-corrosion Powder Coated with min DFT 50 micron. Service Pressure shall be of 15 bar, Hydropressure Test of 35 bar and Burst Pressure greater than 55 bar. Mounting Arrangement shall be MS with black powder coating. Fittings shall include Straight Connector with double locking seals and End of Line Adaptor with Big Dial Pressure Gauge suitable for Clean Agent. Fittings shall be of Double locking seals and easy push-in connection type. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of 6kg Cylinder filled with UL Listed & FM Approved Clean Agent - Grenoz® FK-5-1-12 (Non-HFC), Self activating Automatic Fire Suppression System for Panel Protection, Direct Low Pressure Valve with integrated ball valve and NRV for Pressure Gauge and Pressure Switch, Big Dial Pressure Gauge approx. 30mm dial size, UL Listed Pressure Switch with set pressure suitable to generate alarm in the event of clean agent discharge or pressure drop. Cylinder shall be made of Mild Steel CR2 grade conforming to IS 513, Internal and External cylinder surface shall be Pure Polyester Anti-corrosion Powder Coated with min DFT 50 micron. Service Pressure shall be of 15 bar, Hydropressure Test of 35 bar and Burst Pressure greater than 55 bar. Mounting Arrangement shall be MS with black powder coating. Fittings shall include Straight Connector with double locking seals and End of Line Adaptor with Big Dial Pressure Gauge suitable for Clean Agent. Fittings shall be of Double locking seals and easy push-in connection type. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of UL Listed Nonconductive Blend of Special Modified Polymer Tube - Red Color, with activation temperature of 138deg C at 15 bar. OD X ID - 6mm X 4mm. Min Bending Radius - 100mm. Tube shall detect Fire and forms nozzle for clean agent discharge. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of UL Listed Hooter cum Strobe for generating alarm in the event of discharge or pressure drop. Red Color standalone Hooter cum Strobe shall be provided for each Monitoring Panel. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, testing and commissioning of 4 Zone Monitoring Panel for Cylinder pressure monitoring. Panel shall be IP 65 rated and shall be made of ABS material with compact design. 4 Inputs for Cylinders, 1 Output for Hooter, 1 Potential Free Contact Relay, inbuilt battery backup shall be provided with each monitoring panel. LED indications for System ON, Battery Low, Zone Open & Zone Fire. Control Buttons for Silent, Reset and Test. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, testing and commissioning of Installation of panel protection system including above components shall be done by authorized installation team of OEM. Testing and commissioning shall be done, including leakage tests. Consumables for installation shall be of high grade material. as required and as directed by Engineer In Charge and as per aproved make. Approved makes -CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of VdS Approved/ UL & FM APPROVED IG541 Cylinder - with Constant Flow Technology, 300 Bar. (OEM Factory Filled); and with Safety Bust Disc Assembly. Complete with Low Pressure switch, Pressure gauge. as required and as directed by Engineer In Charge and as per aproved make. 140Ltr cylinder with IG541 Agent ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Pressure Regulator (Constant Discharge Technology) for each cylinder to reduce the pressure from 300bar to 60bar before the manifold as required and as directed by Engineer In Charge and as per aproved make. Make :CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Flexible Discharge Hose with Check valve as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved/ UL & FM APPROVED Electrical Actuator as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Manual actuator with lever as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX / SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Pneumatic Actuator valves with actuation hose , Tees, Elbows & with required accessories as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Discharge Pressure Switch, Shall be install on the Discharge piping after Manifold as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, testing and commissioning of VdS Approved// UL & FM APPROVED Nozzles , 360 Deg / 180 Deg Throw, selection as per approved hydraulic flow calculations. as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, installation, testing and commissioning of Piping Sch 80 seamless with all required fittings, accessories, painting etc complete as per approved hydraulic flow calculations. as required and as directed by Engineer In Charge and as per aproved make. Make : CEASEFIRE / MINIMAX /SAFEX
Supply, installation, testing and commissioning of Cylinder Manifold supports and fittings including any special tool to rest any components within the clean agent system. as per approved hydraulic flow calculations. as required and as directed by Engineer In Charge and as per aproved make. ( Make: CEASEFIRE / MINIMAX /SAFEX
Supply, Installation, Testing and Commissioning of Electric Traction Passenger Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms • Rated capacity :- 15 Passenger/1020 Kg • Floors :- B+G+2 floor (4 Stops) • Travel :- 15-20 mtrs • Location of Lift Machine:- MRL • Rated speed :- 1.0/1.25 mps • Shaft Size :- 2580 mm x 3050 mm • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Service Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms • Rated capacity :- 15 Passenger/1020 Kg , • Floors :- B+G floor (2 Stops), • Travel :- 10-15 mtrs, Location of Lift Machine:- MRL, • Rated speed :- 1.0/1.25 mps • Shaft Size :- 2400 mm x 2000 mm • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable • Door type :- COPO / TOPO Doors with frame having clear opening of 800/900/100 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Telugu &English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audiovisual indication at all landings, • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class, ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge, • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Passenger Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms, • Rated capacity :- 15 Passenger/1020 Kg, • Floors :- B+G+3 floor (5 Stops), • Travel :- 20 to 25 mtrs, • Location of Lift Machine:- MRL, • Rated speed :- 1.0/1.25 mps, • Shaft Size :- 2580 mm x 3050 mm, • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable, • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Passenger Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms • Rated capacity :- 15 Passenger/1020 Kg, • Floors :- Ground+7 F (8 Stops) , • Travel :- 30-35 mtrs, • Location of Lift Machine:- MRL, • Rated speed :- 1.0/1.25 mps, • Shaft Size :- (2700 mm x 3400 mm) • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable, • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings, • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable, • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge, • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Passenger Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms, • Rated capacity :- 15 Passenger/1020 Kg, • Floors :- Ground+8 F (9 Stops) , • Travel :- 32-37 mtrs, • Location of Lift Machine:- MRL, • Rated speed :- 1.0/1.25 mps, • Shaft Size :- (2580 mm x 3300 mm) • Material (Car) :- High End finishes., • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor, • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings, • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge, • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Service/Fire Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms • Rated capacity :- 15 Passenger/1020 Kg • Floors :- Ground+8 F (9 Stops) • Travel :- 32-37 mtrs • Location of Lift Machine:- MRL • Rated speed :- 1.25 mps • Shaft Size :- (2580 mm x 3350 mm) • Material (Car) :- Metal finish to cabin align with surrounding materials- Durable • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. . Make: Mitsubishi/Otis/Schindler/TKE/KONE
Supply, Installation, Testing and Commissioning of Electric Traction Passenger Lift as per Technical specification, NBC, NEC, IS codes and CEIG/Lift inspector requirment norms • Rated capacity :- 15 Passenger/1020 Kg • Floors :- Ground+6 F (7 Stops) • Travel :- 25-30 mtrs • Location of Lift Machine:- MRL • Rated speed :- 1.25 mps • Shaft Size :- (2580 mm x 3100 mm) • Material (Car) :- Metal finish to cabin align with surrounding materials - Durable • Door type :- COPO / TOPO Doors with frame having clear opening of 900/1000 mm wide x 2000mm high made from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audiovisual alarm, VAS in Telugu & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port, control panel duly wired with proper size & strength copper wire for power & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire landing, • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for 60 days with 18" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge • Lift Machine of Gearless PMSM of suitable kW with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. This includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking,traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. For Full Collective control system.General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge.Warrantee: - Job covers two years of warrantee for all the Lift parts with Annual Maintenance as per the maintenance schedule during contract DLP period. . Make: Mitsubishi/Otis/Schindler/TKE/KONE
• Supply of Escalator Units -Design, manufacture, and supply of heavy‑duty indoor escalators suitable for continuous operation, designed in accordance with EN 115‑1:2017 + A1:2024 and IS 17900/IS4591/EN 115 compliance, with 30° inclination, speed of 0.5m/s,, 1000 mm step width, parallel arrangement, three (3) flat steps at landings, aluminium steps, 10 mm safety glass balustrades (900 mm height), complete with truss, drive motor, step chain, handrails, comb plates, skirt panels, control equipment, and all standard safety devices, suitable for vertical rise of 6000 mm and operating on 3 × 380 V, 50 Hz / 220 V power supply. • Installation & Commissioning – Hoisting, positioning, alignment, and fixing of escalator truss within the designated pit and structural openings, including interface with civil works. Installation of escalator components including aluminium steps, handrails, safety glass balustrades, skirt panels with anti‑friction coating, aluminium comb plates, ribbed aluminium access covers, and decking. Testing, adjustment, and commissioning of the complete escalator system, including all mandatory safety devices (emergency stop switches, step sag switches, skirt safety devices, handrail entry switches, anti‑climb and anti‑ride barriers, passenger fall‑protection barriers), in full compliance with applicable standards. • Electrical and Auxiliary Works – Supply and installation of local escalator control panel, internal wiring, earthing, and termination for power supply. Coordination for main power availability up to the escalator control panel. Provision for handrail lighting (continuous white LED type). No BMS integration or remote monitoring shall be included unless specified separately... • Maintenance It including routine inspections, preventive maintenance, lubrication, adjustments, functional checks of safety devices, and breakdown support to ensure safe and uninterrupted operation as per contract documents . Make: Mitsubishi/Otis/Schindler/TKE/KONE
• Supply of Escalator UnitsDesign, manufacture, and supply of heavy‑duty indoor escalators suitable for continuous operation, designed in accordance with EN 115‑1:2017 + A1:2024 and IS 17900/IS4591/EN 115 compliance,, with 30° inclination, 1000 mm step width, speed of 0.5m/s, parallel arrangement, three (3) flat steps at landings, aluminium steps, 10 mm safety glass balustrades (900 mm height), complete with truss, drive motor, step chain, handrails, comb plates, skirt panels, control equipment, and all standard safety devices, suitable for vertical rise of 4000 mm and operating on 3 × 380 V, 50 Hz / 220 V power supply. • Installation & Commissioning – Hoisting, positioning, alignment, and fixing of escalator truss within the designated pit and structural openings, including interface with civil works. Installation of escalator components including aluminium steps, handrails, safety glass balustrades, skirt panels with anti‑friction coating, aluminium comb plates, ribbed aluminium access covers, and decking. Testing, adjustment, and commissioning of the complete escalator system, including all mandatory safety devices (emergency stop switches, step sag switches, skirt safety devices, handrail entry switches, anti‑climb and anti‑ride barriers, passenger fall‑protection barriers), in full compliance with applicable standards. • Electrical and Auxiliary Works – Supply and installation of local escalator control panel, internal wiring, earthing, and termination for power supply. Coordination for main power availability up to the escalator control panel. Provision for handrail lighting (continuous white LED type). No BMS integration or remote monitoring shall be included unless specified separately.. . • Maintenance It including routine inspections, preventive maintenance, lubrication, adjustments, functional checks of safety devices, and breakdown support to ensure safe and uninterrupted operation as per contract documents . Make: Mitsubishi/Otis/Schindler/TKE/KONE
PUMP -Tertiary Chilled Water Pumps Set (Variable speed) HORIZONTAL SPLIT CASE - CENTRIFUGAL PUMPSETS - FOR COMFORT COOLING Supply, Installation, Testing, Commissioning & Handing over of Horizontal split case, Centrifugall pump Single Stage, double suction impeller, double volute casing, inline design, with horizontally mounted motor and spacer coupling, Pumps with flexible / rubber bellows suitable for variable flow chilled water recirculation system.Impellers shall be made of cast silicon bronze enclosed double suction type with smooth surface for minimum friction loss.Pump Shaft shall be made of Stainless Steel and protected by renewable shaft sleevs. Coupling shall be of rigid spacer type.The pump housing shall be with a replaceable bronze wearing ring to reduce the amount of liquid running from the discharge side of the impeller to the suction side. The motor shall be of TEFC Sq.Cage flange mounted, totally enclosed fan-cooled motors with IP 54 enclosure class 'F' insulation, suitable for 415V, 3ph, 50hz power connection.RPM not exceeding 1500 RPM. Motor efficiency shall be of MINIUMUM IE4. Pump motors shall be suitable for VFD driven variable flow chilled water system, Pump performance shall be tested as per ISO 9906 / Hydraulic Institute standards. Pumps shall be considered with the necessary supports, accessories and as per technical specification & data sheet required as directed by Engineer In Charge/ Departmental Authorities. Type - Horizontal split case inline pumps with motor mounted vertical Housing - Cast Iron Impeller - Lead free cast [ Stainless Steel -AISI 316/CF8M] Flow rate - 5875 LPM Head - 52 mtrs Total Pumps - ( 4 W + 1S) Make. Make- GRUNDFOS / WILO / XYLEM
TFA UNITS- TAG NO -TFA-BSF-Z1-B5 & B6 AHU RM -04,TFA-BSF-Z2-B5 & B6 AHU RM -05,TFA-BSF-Z4-B5 & B6 AHU RM -07 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 20 TR /3300cfm, ESP-0.6mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room., Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent, AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories.AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615), Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge . AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton /Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TFA-BSF-Z3-B5 & B6 AHU RM -06, Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 25 TR /4000cfm ESP-0.6mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation., All AHU shall be having euro vent . Fan certifications shall be Eurovent, AHU coil shall have copper header AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 ESP-0.6mmwc as per specification, data sheet and as directed by Engineer In Charge . AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TAG NO -TFA-GF-Z1-B4-KITCHEN-03, Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 28 TR /4500cfm, ESP-0.6mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent. AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator. AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line. • Casing Strength Classification : D1. • Casing Air Leakage : L1. • Filter Bypass Leakage : F8. • Thermal Transmittance : T3. • Thermal Bridging Factor : TB2. • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge . - AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TFA-TF-Z1-COURT RM AHU RM -01,TFA-TF-Z1-COURT RM AHU RM -02,TFA-TF-Z2-COURT RM AHU RM -03,TFA-TF-Z2-COURT RM AHU RM -04 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 63 TR /10250cfm, ESP-0.6mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved. Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header. AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line. • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge . - AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TAG NO -TFA-TF-Z3-COURT RM AHU RM -05,TFA-TF-Z3-COURT RM AHU RM -06 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units. Capacity- 80 TR /13000cfm, ESP-0.6mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent, Fan certifications shall be Eurovent, AHU coil shall have copper header, AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615), Flexible/ rubber bellows shall be provided for AHU Chilled water line, • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge . AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TFA-TF-Z4-COURT RM AHU RM -07,TFA-TF-Z4-COURT RM AHU RM -06, Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 100 TR /16000cfm, ESP-0.6mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent. Fan certifications shall be Eurovent, AHU coil shall have copper header, AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615), Flexible/ rubber bellows shall be provided for AHU Chilled water line, • Casing Strength Classification : D1. • Casing Air Leakage : L1. • Filter Bypass Leakage : F8. • Thermal Transmittance : T3. • Thermal Bridging Factor : TB2. • Air Handling Unit Performance as per EN 13053. as per specification, data sheet and as directed by Engineer In Charge . - AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TFA-8F-Z4-B1-KITCHEN-02, Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 15 TR /2000cfm, ESP-0.6mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved. Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions.TFA shall have demand control ventilation..All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header , AHU coil shall be AHRI certified. AHU supply duct shall be with sound attenuator. AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line. • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge . AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
TFA UNITS- TAG NO -TFA-GR-Z1-B3-SHARED KITCHEN-01, Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 53 TR /8500cfm, ESP-0.6mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions.TFA shall have demand control ventilation. All AHU shall be having euro vent, Fan certifications shall be EuroventAHU coil shall have copper header, AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615), Flexible/ rubber bellows shall be provided for AHU Chilled water line, • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge . AHU :CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens; Air Filter:Thermadyne /Camfil/AAF; VFD Drive - Danfoss / ABB / HONEYWELL; UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z1-B1-08,AHU-GR-Z2-B2-19,AHU-GR-Z3-B3-26,AHU-1F-Z3-B4-59 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 16000cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.All AHU shall be having euro vent Fan certifications shall be Eurovent. AHU coil shall have copper header. AHU coil shall be AHRI certified. AHU supply duct shall be with sound attenuator. AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1. • Filter Bypass Leakage : F8. • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z1-B2-09 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 21000cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent, Fan certifications shall be Eurovent, AHU coil shall have copper header, AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1,• Casing Air Leakage : L1 , • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z1-B3-10,AHU-1F-Z4-B3-68 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units OF Capacity- 10500cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z1-B4-11 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 7500cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-GR-Z1-B4-11 Capacity- 7500cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z1-B6-17 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 7500cfm, ESP-37.5mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent, AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line. • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-4F-Z1-COURT-28-154 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 7500cfm ESP-30mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z1-B5-12,AHU-1F-Z3-B1-56 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 12000cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615), Flexible/ rubber bellows shall be provided for AHU Chilled water line, • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-2F-Z1-COURT 43-77,AHU-2F-Z2-COURT-42-88,AHU-2F-Z3-COURT-52-99 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 2700cfm ESP-20mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-2F-Z4-COURT-51-108,AHU-4F-Z1-COURT-26-151,AHU-4F-Z1-COURT-27-153,AHU-4F-Z1-COURT-28-155,AHU-4F-Z1-COURT-29-157,AHU-4F-Z2-COURT-23-162,AHU-4F-Z2-COURT-22-164,AHU-4F-Z2-COURT-21-166,AHU-4F-Z2-COURT-20-168,AHU-4F-Z3-COURT-19-171,AHU-4F-Z3-COURT-18-173,AHU-4F-Z3-COURT-17-175,AHU-4F-Z4-COURT-32-182,AHU-4F-Z4-COURT-31-184,AHU-4F-Z4-COURT-30-186,AHU-6F-Z1-COURT-06-211,AHU-6F-Z1-COURT-07-213,AHU-6F-Z1-COURT-08-215,AHU-6F-Z1-COURT-09-217,AHU-6F-Z2-COURT-03-222,AHU-6F-Z2-COURT-02-224,AHU-6F-Z3-COURT-16-231,AHU-6F-Z3-COURT-15-233,AHU-6F-Z4-COURT-12-240,AHU-6F-Z4-COURT-11-242,AHU-6F-Z4-COURT-10-244 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 3000cfm ESP-20mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-2F-Z1-COURT 44-79,AHU-2F-Z1-COURT 45-81,AHU-2F-Z1-COURT 46-83,AHU-2F-Z1-COURT 47-85,AHU-2F-Z2-COURT-41-90,AHU-2F-Z2-COURT-40-92,AHU-2F-Z2-COURT-39-94,AHU-2F-Z2-COURT-38-96,AHU-2F-Z3-COURT-35-101,AHU-2F-Z3-COURT-36-103,AHU-2F-Z3-COURT-37-105,AHU-2F-Z4-COURT-50-110,AHU-2F-Z4-COURT-49-112,AHU-2F-Z4-COURT-48-114 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units. Capacity- 3500cfm ESP-20mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved. Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent. Fan certifications shall be Eurovent. AHU coil shall have copper header. AHU coil shall be AHRI certified. AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053. as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-4F-Z1-COURT-25-149 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 4100cfm ESP-20mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation..All AHU shall be having euro vent. Fan certifications shall be Eurovent. AHU coil shall have copper header . AHU coil shall be AHRI certified. AHU supply duct shall be with sound attenuator. AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1, • Casing Air Leakage : L1, • Filter Bypass Leakage : F8, • Thermal Transmittance : T3, • Thermal Bridging Factor : TB2, • Air Handling Unit Performance as per EN 13053, as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-4F-Z2-COURT-24-160,AHU-4F-Z3-COURT-34-177,AHU-4F-Z4-COURT-33-180,AHU-6F-Z1-COURT-05-209,AHU-6F-Z2-COURT-04-220,AHU-6F-Z3-COURT-14-235,AHU-6F-Z4-COURT-13-238 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 4500cfm ESP-20mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection.AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation..All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-GR-Z2-B6-23 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 7200cfm ESP-37.5mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-GR-Z2-B6-23 Capacity- 7200cfm ESP-37.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z4-B5-34,AHU-1F-Z3-B6-65,AHU-1F-Z4-B6-75 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 8000cfm ESP-37.5mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- AHU-GR-Z3-B5-28 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 8200cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-2F-Z1-COURT 43-76,AHU-2F-Z1-PASSAGE-09-86,AHU-2F-Z7-COURT-42-87,AHU-2F-Z2-PASSAGE-10-97,AHU-2F-Z3-COURT-52-98,AHU-2F-Z3-PASSAGE-11-106,AHU-2F-Z4-COURT-51-107,AHU-2F-Z4-PASSAGE-12-115,AHU-4F-Z1-COURT-25-148,AHU-4F-Z1-PASSAGE-01-158,AHU-4F-Z2-COURT-24-159,AHU-4F-Z2-PASSAGE-02-169,AHU-4F-Z3-PASSAGE-03-178,AHU-4F-Z4-PASSAGE-04-187,AHU-6F-Z1-PASSAGE-01-218,AHU-6F-Z2-PASSAGE-02-229,AHU-6F-Z3-PASSAGE-03-236,AHU-6F-Z4-PASSAGE-04-245 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 8500cfm ESP-30mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified, AHU supply duct shall be with sound attenuator, AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615, Flexible/ rubber bellows shall be provided for AHU Chilled water line, • Casing Strength Classification : D1, • Casing Air Leakage : L1 , • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z1-B2-37 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 8500cfm ESP-37.5mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- (1W-CHW-Coil + 1Stand By-DX -Coil) TAG NO - AHU-6F-Z2-COURT-01-228 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 8500cfm ESP-20mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Additionally stand by Dx Tyep Coil required and velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z1-B6-45,AHU-1F-Z2-B6-55 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 9000cfm ESP-37.5mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615). Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO -AHU-2F-Z1-COURT 45-80,AHU-2F-Z1-COURT 46-82,AHU-2F-Z1-COURT 47-84,AHU-2F-Z2-COURT-40-91,AHU-2F-Z2-COURT-39-93,AHU-2F-Z2-COURT-38-95,AHU-2F-Z3-COURT-36-102,AHU-2F-Z3-COURT-37-104,AHU-2F-Z4-COURT-49-111,AHU-2F-Z4-COURT-48-113,AHU-4F-Z1-COURT-26-150,AHU-4F-Z1-COURT-27-152,AHU-4F-Z1-COURT-29-156,AHU-4F-Z2-COURT-23-161,AHU-4F-Z2-COURT-22-163,AHU-4F-Z2-COURT-21-165,AHU-4F-Z2-COURT-20-167,AHU-4F-Z3-COURT-19-170,AHU-4F-Z3-COURT-18-172,AHU-4F-Z3-COURT-17-174,AHU-4F-Z3-COURT-34-176,AHU-4F-Z4-COURT-33-179,AHU-4F-Z4-COURT-32-181,AHU-4F-Z4-COURT-31-183,AHU-4F-Z4-COURT-30-185,AHU-6F-Z1-COURT-05-208,AHU-6F-Z1-COURT-06-210,AHU-6F-Z1-COURT-07-212,AHU-6F-Z1-COURT-08-214,AHU-6F-Z1-COURT-09-216,AHU-6F-Z2-COURT-04-219,AHU-6F-Z2-COURT-03-221,AHU-6F-Z2-COURT-02-223,AHU-6F-Z3-COURT-16-230,AHU-6F-Z3-COURT-15-232,AHU-6F-Z3-COURT-14-234,AHU-6F-Z4-COURT-13-237,AHU-6F-Z4-COURT-12-239,AHU-6F-Z4-COURT-11-241,AHU-6F-Z4-COURT-10-243 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 9000cfm ESP-30mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- (1W-CHW-Coil + 1Stand By-DX -Coil) TAG NO -AHU-6F-Z2-COURT-01-225,AHU-6F-Z2-COURT-01-227 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 9000cfm ESP-30mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Additionally stand by Dx Tyep Coil required and velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- (1W-CHW-Coil + 1Stand By-DX -Coil) TAG NO - AHU-6F-Z2-COURT-01-226 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 9000cfm ESP-20mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity, Additionally stand by Dx Tyep Coil required and velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-2F-Z1-COURT 44-78,AHU-2F-Z2-COURT-41-89,AHU-2F-Z3-COURT-35-100,AHU-2F-Z4-COURT-5O-109 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 9500cfm ESP-30mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-3F-Z1-B1-124,AHU-3F-Z2-B1-129,AHU-3F-Z3-B1-136,AHU-3F-Z4-B1-143 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 10000cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .(AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z2-B5-22,AHU-2F-Z8-B2-119,AHU-2F-Z12-B2-123 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 11500cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z4-B6-35,AHU-2F-Z7-B1-118 Capacity- 11000cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z2-B5-22,AHU-2F-Z8-B2-119,AHU-2F-Z12-B2-123 Capacity- 11500cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z3-B4-27,AHU-2F-Z5-B2-116,AHU-2F-Z9-B2-120,AHU-2F-Z10-B1-121 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 12500cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG No- AHU-2F-Z6-B1-117,AHU-2F-Z11-B1-122 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 13000cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z3-B6-29, AHU-1F-Z4-B1-66 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 13500cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z2-B1-18 Capacity- 13600cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z2-B1-46 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 14000cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z3-B1-24,AHU-1F-Z1-B1-36,AHU-1F-Z3-B3-58 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 15000cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z3-B2-57 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 15500cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- AHU-GR-Z2-B3-20,AHU-GR-Z4-B3-32,AHU-1F-Z2-B4-49,AHU-1F-Z4-B4-69 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 16500cfm ESP-45mmwc. Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z2-B4-21,AHU-GR-Z4-B1-30 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 17000cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-1F-Z1-B4-39 Capacity- 17500cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z1-B5-40,AHU-1F-Z2-B3-48,AHU-1F-Z3-B5-60,AHU-1F-Z4-B5-70 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 18000cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .(AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z4-B4-33,AHU-1F-Z1-B3-38,AHU-1F-Z2-B2-47 Capacity- 18500cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-1F-Z2-B5-50 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 19000cfm ESP-45mmwg . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-1F-Z4-B2-67 Capacity- 21500cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- TAG NO - AHU-GR-Z3-B2-25 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 22000cfm ESP-45mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z4-B2-31 Capacity- 24000cfm ESP-45mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- TAG NO - AHU-3F-Z1-B1-UPS & BATTERY-01-125,AHU-3F-Z1-B1-UPS & BATTERY-02-127,AHU-3F-Z2-B1-UPS & BATTERY-01-132,AHU-3F-Z2-B1-UPS & BATTERY-01-134,AHU-3F-Z4-B1-UPS & BATTERY-01-144,AHU-3F-Z4-B1-UPS & BATTERY-01-146,AHU-5F-Z1-B1-UPS & BATTERY-01-188,AHU-5F-Z2-B1-UPS & BATTERY-01-194,AHU-5F-Z2-B1-UPS & BATTERY-02-196 ,AHU-5F-Z3-B1-UPS & BATTERY-01-200,AHU-5F-Z3-B1-UPS & BATTERY-02-202 ,AHU-5F-Z4-B1-UPS & BATTERY-01-204,AHU-5F-Z4-B1-UPS & BATTERY-02-206,AHU-7F-Z1-B1-UPS & BATTERY-01-246,AHU-7F-Z1-B1-UPS & BATTERY-02-248,AHU-7F-Z2-B1-UPS & BATTERY-01-252,AHU-7F-Z1-B1-UPS & BATTERY-02-254,AHU-7F-Z3-B1-UPS & BATTERY-01-258,AHU-7F-Z3-B1-UPS & BATTERY-02-260,AHU-7F-Z4-B1-UPS & BATTERY-01-262,AHU-7F-Z4-B1-UPS & BATTERY-02-264 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of capacity Capacity- 1800cfm ESP-12.5mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- TAG NO - AHU-3F-Z3-B1-UPS & BATTERY-01-139,AHU-3F-Z3-B1-UPS & BATTERY-01-141 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units of Capacity- 1800cfm ESP-20mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- TAG NO - AHU-5F-Z2-ELV-192,AHU-5F-Z3-ELV-198 ,AHU-7F-Z2-ELV-250,AHU-7F-Z3-ELV-256 Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units Capacity- 2000cfm ESP-12.5mmwc . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 as per specification, data sheet and as directed by Engineer In Charge .(AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-1F-Z1-B5-41,AHU-1F-Z1-B5-43,AHU-1F-Z2-B5-51,AHU-1F-Z2-B5-53,AHU-1F-Z3-B5-61,AHU-1F-Z3-B5-63,AHU-1F-Z4-B5-71,AHU-1F-Z3-B5-73,AHU-5F-Z1-B1-UPS & BATTERY-02-190 Capacity- 2100cfm ESP-12.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-3F-Z2-B1-ELV-02-130 Capacity- 2400cfm ESP-12.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-3F-Z3-B1-ELV-01-137 Capacity- 2400cfm ESP-20mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-BS-Z1-LIFT LOBBY-01-03 Capacity- 3000cfm ESP-15mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-BS-Z1-FOOD & BEVERAGE-01-02,AHU-BS-Z2-DRIVERS LOUNGE-01-04 Capacity- 3200cfm ESP-15mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-BS-Z1-STAFF & CHANGING ROOM-01-05 Capacity- 3500cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z1-B5-13,AHU-GR-Z1-B5-15 Capacity- 3700cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-BS-Z1-STAFF & CHANGING ROOM-01-01 Capacity- 4000cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-BS-Z4-SECURITY BMS ROOM-01-06 Capacity- 4500cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-8F-Z2-B1-270,AHU-8F-Z2-B1-271,AHU-8F-Z3-B1-273,AHU-8F-Z3-B1-274,AHU-8F-Z4-B1-276 Capacity- 2500cfm ESP-15mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-8F-Z1-266,AHU-8F-Z1-268 Capacity- 2600cfm ESP-17.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-8F-Z2-B1-272 Capacity- 3200cfm ESP-15mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-8F-Z1-267 Capacity- 6000cfm ESP-20mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-8F-Z4-B1-275 Capacity- 8000cfm ESP-20mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS- Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted chilled water based double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ}. Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-8F-Z2-B1-269 Capacity- 11000cfm ESP-37.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO -AHU-3F-Z1-B1-UPS & BATTERY-01-126,AHU-3F-Z1-B1-UPS & BATTERY-02-128,AHU-3F-Z2-B1-UPS & BATTERY-01-133,AHU-3F-Z2-B1-UPS & BATTERY-01-135,AHU-3F-Z4-B1-UPS & BATTERY-01-145,AHU-3F-Z4-B1-UPS & BATTERY-01-147,AHU-5F-Z1-B1-UPS & BATTERY-01-189,AHU-5F-Z2-B1-UPS & BATTERY-01-195,AHU-5F-Z2-B1-UPS & BATTERY-02-197,AHU-5F-Z3-B1-UPS & BATTERY-01-201,AHU-5F-Z3-B1-UPS & BATTERY-02-203,AHU-5F-Z4-B1-UPS & BATTERY-01-205,AHU-5F-Z4-B1-UPS & BATTERY-02-207,AHU-7F-Z1-B1-UPS & BATTERY-01-247,AHU-7F-Z1-B1-UPS & BATTERY-02-249,AHU-7F-Z2-B1-UPS & BATTERY-01-253,AHU-7F-Z1-B1-UPS & BATTERY-02-255,AHU-7F-Z3-B1-UPS & BATTERY-01-259,AHU-7F-Z3-B1-UPS & BATTERY-02-261,AHU-7F-Z4-B1-UPS & BATTERY-01-263,AHU-7F-Z4-B1-UPS & BATTERY-02-265 Capacity- 1800cfm ESP-12.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-3F-Z3-B1-UPS & BATTERY-01-140,AHU-3F-Z3-B1-UPS & BATTERY-01-142 Capacity- 1800cfm ESP-20mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-5F-Z2-ELV-193,AHU-5F-Z3-ELV-199,AHU-7F-Z2-ELV-251,AHU-7F-Z3-ELV-257 Capacity- 2000cfm ESP-12.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-1F-Z1-B5-42,AHU-1F-Z1-B5-44,AHU-1F-Z2-B5-52,AHU-1F-Z2-B5-54,AHU-1F-Z3-B5-62,AHU-1F-Z3-B5-64,AHU-1F-Z4-B5-72,AHU-1F-Z3-B5-74,AHU-5F-Z1-B1-UPS & BATTERY-02-191 Capacity- 2100cfm ESP-12.5mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-GR-Z1-B5-14,AHU-GR-Z1-B5-16 Capacity- 3700cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
CEILING SUSPENDED AHU UNITS-(DX TYPE) Supply, installation, testing & commissioning of Factory Built, Ceiling Suspended/Floor Mounted Dx type double skin type Air Handling Units . Panels consisting of hot dip G.I. Casing, complete DIDW centrifugal fan/ Plug fan section & Motor shall be VFD compatible suitable for static pressure as detailed below, cooling coil section with hydrophilic Aluminum finned copper tube cooling coil, filter sections with 50 mm thk.,mixing box, air pre -filters, package with TEFC motor suitable for operation on 415 (+/-) 10%, 50 Hz, A.C Supply insulated drain pan and drain connections ( VFD cost for AHU shall be quoted seperately as per BOQ). Casing - Double Skin Casing of thermal break profile with 45+-5mm thick with 0.8 mm pre - coated and pre -plastisised GI for outer skin and 0.8 mm plain GI for Inner Skin encasing with 120 GSM Zinc coating, insulated by puf insulation with density of 40Kg/m3.and complete with inspection doors and marine light, limit switch including control wiring as required. Access doors(Hinged Type Access door) for both motor and filters section to be provided. Coil - The coil shall be of Copper construction with Aluminum fins. The drain pan shall be of SS304 as per manufacturer standard and shall be insulated. A secondary inclided drain pan shall also be provided extending at least 100mm after the main drain pan. Coil shall be selected for maximum at 500FPM velocity.velocity Coil To be compatible as per Refrigerant R410a (VRF/VRV) . Vendor to consider VRV AHU kit and controller also. Fan - DIDW centrifugal type backward curve/ Forward Curve centrifugal fan OR Backward curved type Plug Fan suitable for static pressure as detailed below. The motor shall be IE4 efficiency suitable for 3 phase supply. All AHU VFDs shall be provided with open protocol to communicate with third party BMS system with necessary enclosure and interconnecting cables/wires from VFD to AHU with necessary cable tray, saddles etc.Fan outlet velocity shall be 10 m/s. The fans below 6000 CFM shalll be Forward curved and above 6000 CFM shall be backward curved Filter - Each unit shall be provided with a factory assembled filter section containing washable synthetic type air filters having GI frame. Filter media and frame shall be rust proof and corrosion resistant.The filter shall have minimum 90% efficiency down to 10 microns. Pre filter of 50mm thick washable synthetic fiber(MERV 8). Fine / bag filter of MERV 14 grade shall be provided. Velocity across the filter shall not exceed 500FPM. Pre commisioning filter to be considered. AHU Noise level shall be less than 55 dba at 1mt inside AHU room. Supply connection - Supply flanges shall be provided for duct connection. AHU outlet will be fire retardant canvass cloth with provision of gauge for the measurement. All the AHU's dimensions should be as per the site conditions and to the available AHU room dimensions. TFA shall have demand control ventilation.. All AHU shall be having euro vent Fan certifications shall be Eurovent AHU coil shall have copper header AHU coil shall be AHRI certified AHU supply duct shall be with sound attenuator AHU shall be with the necessary supports and required accessories. AHU shall be with UVGI lamp, limit switch and inspection door. UVGI lamp capacity shall be 7.5 watts/ sq.ft of coil surface area. Motor shall be - IE4 motor (As per IS 12615) Flexible/ rubber bellows shall be provided for AHU Chilled water line • Casing Strength Classification : D1 • Casing Air Leakage : L1 • Filter Bypass Leakage : F8 • Thermal Transmittance : T3 • Thermal Bridging Factor : TB2 • Air Handling Unit Performance as per EN 13053 TAG NO - AHU-BS-Z4-SECURITY BMS ROOM-01-07 Capacity- 4500cfm ESP-10mmwc as per specification, data sheet and as directed by Engineer In Charge .( AHU Make: CARRIER / VTS / SYSTEMAIR/DAIKINFAN : KRUGER / GREENHECK / SYSTEMAIR; Motor :ABB/Crompton/Siemens; (Air Filter Make: AAF / CAMFIL / THERMADYNE); VFD Drive - Danfoss / ABB / HONEYWELL; ( UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
FAN COIL UNIT-CHW Supply, Installation, Testing & Commissioning of FCUs with a) 3 speed thermostat of make as approved by the architect/consultant b) Supporting frame and support. c) Full size S.S drain pan, double skin with insulation. FCU Noise level shall be less than 35 dBA at 1mtr Note :- Contractor to submit the Intent to Clients regarding the No of FCUs to be procured based on the approved shop dwg with the Left , Right configuration of pipe connection for ordering of the FCUs. Please Refer attached Techanical specification for the detailed FCU shall be with three speed and airflow and static pressure shall be selected for the medium speed 1.0 TR 400 cfm as per specification and as directed by Engineer In Charge and as per aproved make. Make- MITSUBISHI / CARRIER / TRANE / DAIKIN)
FAN COIL UNIT-CHW Supply, Installation, Testing & Commissioning of FCUs with a) 3 speed thermostat of make as approved by the architect/consultant b) Supporting frame and support. c) Full size S.S drain pan, double skin with insulation. FCU Noise level shall be less than 35 dBA at 1mtr Note :- Contractor to submit the Intent to Clients regarding the No of FCUs to be procured based on the approved shop dwg with the Left , Right configuration of pipe connection for ordering of the FCUs. Please Refer attached Techanical specification for the detailed FCU shall be with three speed and airflow and static pressure shall be selected for the medium speed 1.5 TR 600 cfm as per specification and as directed by Engineer In Charge and as per aproved make. Make- MITSUBISHI / CARRIER / TRANE / DAIKIN)
FAN COIL UNIT-CHW Supply, Installation, Testing & Commissioning of FCUs with a) 3 speed thermostat of make as approved by the architect/consultant b) Supporting frame and support. c) Full size S.S drain pan, double skin with insulation. FCU Noise level shall be less than 35 dBA at 1mtr Note :- Contractor to submit the Intent to Clients regarding the No of FCUs to be procured based on the approved shop dwg with the Left , Right configuration of pipe connection for ordering of the FCUs. Please Refer attached Techanical specification for the detailed FCU shall be with three speed and airflow and static pressure shall be selected for the medium speed 2.0 TR 800 cfm as per specification and as directed by Engineer In Charge and as per aproved make. Make- MITSUBISHI / CARRIER / TRANE / DAIKIN)
FAN COIL UNIT-CHW Supply, Installation, Testing & Commissioning of FCUs with a) 3 speed thermostat of make as approved by the architect/consultant b) Supporting frame and support. c) Full size S.S drain pan, double skin with insulation. FCU Noise level shall be less than 35 dBA at 1mtr Note :- Contractor to submit the Intent to Clients regarding the No of FCUs to be procured based on the approved shop dwg with the Left , Right configuration of pipe connection for ordering of the FCUs. Please Refer attached Techanical specification for the detailed FCU shall be with three speed and airflow and static pressure shall be selected for the medium speed 4.0 TR 1600 cfm as per specification and as directed by Engineer In Charge and as per aproved make. Make- MITSUBISHI / CARRIER / TRANE / DAIKIN)
CHEMICAL DOSING SYSTEM Design, engineering, selection, supply, installation, testing and commissioning of complete automatic chemical dosing system for chilled water system covering tertiary pumps at secondary side of plate heat exchanger (PHE) and entire CHW piping network inside the building, it shall be closed loop CHW, corrosion inhibitor + biocide, required of no dosing points and intigrate with Makeup water tank complete as per specification and as directed by Engineer in charge. Make : NALCO / ION EXCHANGE / INCHEM CORPORATION
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 600 mm dia C Class MS pipes conforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 600 mm dia minimum 10mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 400 mm dia C Class MS pipes conforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 400 mm dia minimum 8mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 350 mm dia C Class MS pipes conforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 350 mm dia minimum 8mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 300 mm dia C Class MS pipes conforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 300 mm dia minimum 8mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 250 mm dia C Class MS pipesconforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 250 mm dia minimum 6.3mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 200mm dia C Class MS pipess conforming to IS 3589 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 200 mm dia minimum 6.3mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of 150 mm dia C Class MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 150 mm dia minimum 5.4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 100 mm dia minimum 5.4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 80 mm dia minimum 4.8mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 65 mm dia minimum 4.5mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 50 mm dia minimum 4.5mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 40 mm dia minimum 4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 32 mm dia minimum 4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 25 mm dia minimum 4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 20 mm dia minimum 4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
C-CLASS MS PIPES Providing , laying, testing & Commissioning of following classes MS pipes conforming to IS 1239 including necessary accessories &supports- fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. including PUF blocks of 160 kg/ m3 density for supporting the pipes including transportaiton and painting with two coats of red oxide paint and one coat of post office red enamel paint /zinc chromate primer and all labour charges and cost of all accessories etc., complete.. Piping passing through building expansion joints shall have the flexible connection for the pipe connection. pipe shall have metal expansion joint 15 mm dia minimum 4mm thickness as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: TATA STEEL,JINDAL,SAIL )
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 600 dia Nominal Bore-50 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of 40 mm thick insualtion for 400 Dia MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 400 dia Nominal Bore-40 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 350 dia Nominal Bore-40 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 300 dia Nominal Bore-40 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation / factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 250 dia Nominal Bore-32 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 200 dia Nominal Bore-32 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 150 dia Nominal Bore-32 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber/XLPE. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 100 dia Nominal Bore-32 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 80 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 65 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 50 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 40 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 32 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 25 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 20 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Nitrile Rubber Insulation factory fitted GC cloth for the piping- Supply, installation Testing and commissioning of insualtion for MS pipe, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber. The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 15 dia Nominal Bore-25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved ( Make: ARMACELL / K-FLEX / AEROFOAM) Adhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply & installation Testing and commissioning of aluminium cladding (embossed sheet) 26G with necessary accessories. for AHU/ PHE room CHW piping as per specification and as directed by Engineer In Charge and as per approved Make- ARMACELL,K-FLEX,AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
BAll VALVES Supply, Installation, Testing and Commissioning of following sizes ball valve.(Body design condition PN-16) SITC of Ball valve Gunmetal screwed end complete with necessary supports-flanges,gaskets,bolts,nuts etc,ball (SS-304) and SS spindle Confirming to class 1 of IS 778/ equiv.Valve should be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 20mm Dia as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: VICTAULIC / ZOLOTO / AUDCO
BAll VALVES Supply, Installation, Testing and Commissioning of following sizes ball valve.(Body design condition PN-16) SITC of Ball valve Gunmetal screwed end complete with necessary supports-flanges,gaskets,bolts,nuts etc,ball (SS-304) and SS spindle Confirming to class 1 of IS 778/ equiv.Valve should be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 25mm Dia as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: VICTAULIC / ZOLOTO / AUDCO
BAll VALVES Supply, Installation, Testing and Commissioning of following sizes ball valve.(Body design condition PN-16) SITC of Ball valve Gunmetal screwed end complete with necessary supports-flanges,gaskets,bolts,nuts etc,ball (SS-304) and SS spindle Confirming to class 1 of IS 778/ equiv.Valve should be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 32mm Dia as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: VICTAULIC / ZOLOTO / AUDCO
BAll VALVES Supply, Installation, Testing and Commissioning of following sizes ball valve.(Body design condition PN-16) SITC of Ball valve Gunmetal screwed end complete with necessary supports-flanges,gaskets,bolts,nuts etc,ball (SS-304) and SS spindle Confirming to class 1 of IS 778/ equiv.Valve should be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 40mm Dia as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: VICTAULIC / ZOLOTO / AUDCO
BAll VALVES Supply, Installation, Testing and Commissioning of following sizes ball valve.(Body design condition PN-16) SITC of Ball valve Gunmetal screwed end complete with necessary supports-flanges,gaskets,bolts,nuts etc,ball (SS-304) and SS spindle Confirming to class 1 of IS 778/ equiv.Valve should be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 50mm Dia as per specification and as directed by Engineer In Charge and as per aproved make. ( Make: VICTAULIC / ZOLOTO / AUDCO
Supply, Installation, Testing and Commissioning of following sizes ball valve with Y-strainer.(Body design condition PN 16) SITC of ball valve set with strainer ball screwed end complete with necessary supports-flanges,gaskets, bolts nuts etc.ball (SS-304) Conforming to class 2 of IS 778 /equiv.Valves shall be suitable for PN 16 Operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 25 mm dia. as per specification and as directed by Engineer In Charge . ( Make: SANT / VTM VALVES / LEADER)
Supply, Installation, Testing and Commissioning of following sizes ball valve with Y-strainer.(Body design condition PN 16) SITC of Ball valve and strainer set complete with necessary accessories &supports- flanges,gaskets,bolts,nuts etc,Valve body shall be ASTM A 351 Gr. CF8 & ball (mirror finished) SS-304 confirming to class 2 of IS 778 /equiv. Valves shall be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 32mm dia. as per specification and as directed by Engineer In Charge . ( Make: SANT / VTM VALVES / LEADER)
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 25mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 32mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 40mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 50mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 65mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 80mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 100mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves ( With Nitrile rubber insulation-32mm) for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 150mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves ( With Nitrile rubber insulation-32mm) for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 200mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, testing and commissioning of Manual Balancing Valve necessary accessories & supports- SITC of screw type Balancing valves ( With Nitrile rubber insulation-32mm) for sizes upto 80 mm dia confirming to BS:5154/equivalent and Cast iron flanged for sizes 100 mm & above complete with matching flanges,bolts,nuts and gaskets,etc.as specified. Manual double regulation balancing type with indicator scale from 0(full shut) to full open with integer setting position. Valves shall have 2 body plugs and one set of pressure test cocks. The test cocks shall be long enough to protrude out of the pipe insulation. These valves shall have the built in pressure drop measuring facility to compute flow rate across the valve. The valves shall be screwed or flanged in accordance with the Specification of the pipework into which they are installed. Valves shall be suitable for PN 16 operating pressure. Valve shall be with Test Ports. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 250mm dia. as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 100 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 80 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 65 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 50 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 40 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 32 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, installation and testing of UPVC Drain Piping with 9mm Nitrile Rubber class "O" Insulation covered with interwoven glass cloth protection. Necessary pipe fittings(Including enlarger, bends, T Joints etc) has to be considered to connect the UPVC drain pipe to cast iron floor trap (agri 4 Kg/cm2)( Type B) 25 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- ASTRAL / SUPREME / FINOLEX Insulation Make: ARMACELL / K-FLEX / AEROFOAM
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 250 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 250 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 200 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 200 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 150 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 150 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 100 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 100 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
SITC of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves 80 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 80 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 65 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 65 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Manually operated Butterfly valves complete with Nitrile rubber insulation - Butterfly Valve (Manual) with C.I body SS disc nitrile sheet & O- ring & PN-16 pressure rating for chilled water circulation as specified Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves 65 mm shall have crank arm wheel handle gear mechanism with position indicator and adjustable stop provided general opreation.for all over7 feet or higher the floor and exposed to view. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 50 mm dia Nominal Bore as per specification and as directed by Engineer In Charge .( Make: VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation Testing Commissioning of Motorised Butterfly valves complete with Nitrile rubber insulation - Motorized on/off Butterfly Valves with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating for isolation of pump. Complete with actuator of thr required torque The actuator shall be IP 55 Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. valves shall have provision of 1-Ph Supply and ON/OFF feedback provision Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 250 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
Supply, Installation Testing Commissioning of Motorised Butterfly valves complete with Nitrile rubber insulation - Motorized on/off Butterfly Valves with extended neck/spindle, matching flanges, hot dipped galvanized bolts and nuts including insulation. Valves should be rated for PN 16 - pressure rating for isolation of pump. Complete with actuator of thr required torque The actuator shall be IP 55 Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. valves shall have provision of 1-Ph Supply and ON/OFF feedback provision Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 200 dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
Supply, Installation Testing Commissioning of Non Return valves complete with Nitrile rubber insulation mating flange joints as specified. Non return valve of Ductile CI Body flanged ends Valves shall be with necessary accessories &supports, adhesive etc- All check valve shall be cast iron flange with dual plate, Broze trim, rubber face. Valve shall be non slaming type to prevent water hammer either by providing spring or accumulator Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) All check valve shall be cast iron flange with dual plate, Broze trim, rubber face. Valve shall be non slaming type to prevent water hammer either by providing spring or accumulator Valves shall be suitable for PN 16 operating pressure. 250mm NR valve as per specification and as directed by Engineer In Charge . Make-VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Icluding matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 250mm `Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Icluding matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure. Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 200mm `Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 32mm thickness All flanges shall be of ANSI 16.5 (PN 16) 150mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 100mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 80mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 65mm Y' strainers aas per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Icluding matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 50mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 40mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 32mm Y' strainers as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make- SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 25mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Supply, Installation, Testing, Commissioning of `Y' strainers complete with Nitrile rubber insulation mating flange joints as specified. Y Strainer of Ductile CI Body flanged ends. Including matching flangs,gaskets,nut bolts.All flanges shall be of ANSI16.5(PN-16) . Permanant magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non magnetic SS sheet with perforation.All flanges shall be supplied with mating flanges Valves shall be with necessary accessories &supports, adhesive etc- Valves shall be suitable for PN 16 operating pressure Valves shall be with matching flanges ,gaskets and fastners duely insulated with nitrile rubber insulation of 25mm thickness All flanges shall be of ANSI 16.5 (PN 16) 20mm Y' strainers as per specification and as directed by Engineer In Charge . Make-SANT / VTM VALVES / LEADER)
Thermowells with thermometer SITC of Industrial Stem Type (150 mm Length) Thermometers complete with thermo wells,greystone fittings, all accessories as per specifications and any other item required to make the system complete.Mercury fill, Brass body /stem. - Temp.- 0 deg to 50 deg C- stem length shall be minimum 80mm scale length shall be 225mm. as per specification and as directed by Engineer In Charge .( Make: BAUMER / HONEYWELL / FIEBIG
Pressure indicator SITC of Industrial Type 100 mm Dial Pressure Gauges complete with syphons, gauge cocks, fittings, all accessories as per specifications and any other item required to make the system complete. Glyserin fill with cold brass body as per specification and as directed by Engineer In Charge . ( Make: BAUMER / HONEYWELL / FIEBIG)
Supply, Installation, testing and commissioning of 25mm shut off valves as per specification and as directed by Engineer In Charge . Make-VICTAULIC / ZOLOTO / AUDCO
Supplly, Installation, Testing, Commissioning of 15 mm automatic air vents with valves up to 100 mm pipe size. &25 mm automatic air vents with valves above 100 mm pipe size Auto air vent shall be desinged to vent automatically with float principle. AAV shall have bronze body, SS float and non ferrous internal parts suited for 1035 kPa working pressure. Automatic air vent with ball valve for isolation with necessary fittings, accessories. as per specification and as directed by Engineer In Charge . Make- LEADER / SANT / ZOLOTO
Supplly, Installation, Testing, Commissioning of 25mm automatic air vents with valves Auto air vent shall be desinged to vent automatically with float principle. AAV shall have bronze body, SS float and non ferrous internal parts suited for 1035 kPa working pressure. Automatic air vent with ball valve for isolation with necessary fittings, accessories. For larger pipe sizes air vents shall be fitted on air bottles adequately sized for the pipe it is venting.25mm gate valves as per specification and as directed by Engineer In Charge . Make- LEADER / SANT / ZOLOTO
Supply, Installation, Testing, Commissioning of 25mm gate valves as per specification and as directed by Engineer In Charge . Make- VICTAULIC / ZOLOTO / AUDCO)
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 32mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP54 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 100mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP54 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 80mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP54 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V 65mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP54 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V 50mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP54 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 40mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP42 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 32mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make- BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP42 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 25mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
Supply, Installation, Testing , Commissioning of PRESSURE INDEPENDENT CONTROL VALVE 2 way Modulating Balancing Cum Flow Control Valves with Nitrile rubber insulation 25mm thickness Supply, Installation, testing and commissioning of Pressure independent type 2 way modulating Control valves in a single Unit of Valve. PN16 Rating. Cast Iron body, Flanged Ends Conection Duly mounted with Modulating actuator IP42 Type suitable for 24V AC. and should have the below mentioned features. 1. Diff Pressure should be of Diaphragm with Spring self adjusting table. 2. Manual Over ride to the Actuator should be possible for Manual Opening Or Closing of Valve if required. 3. Actuator Should be Linear Operational, Electricaly operated and not thermal actuator. Valves shall be suitable for PN 16 operating pressure. Valves shall be with necessary accessories &supports, adhesive etc- PICV valve shall have voltage step-down from 230 to 24 V. 20mm dia Nominal Bore as per specification and as directed by Engineer In Charge . Make-BELIMO / DANFOSS / HONEYWELL
BTU METER Supply, installation, testing an commissioning of 600mm Dia/ 10300 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow.BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge . ( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 500mm Dia/ 7000 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 450mm Dia/ 3468 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 150mm Dia/ 710 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow.BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 100mm Dia/ 258 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow.BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 80mm Dia/ 128 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow.BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 65mm Dia/ 66 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow.BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 50mm Dia/ 40 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 40mm Dia/ 22 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
BTU METER Supply, installation, testing an commissioning of 32mm dia / 14 gpm BTU meter which shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include matched pair temperature sensor with the necessary accessories for installing the sensorsShall have the features of Battery Backup Minimum 10 Years, Data logging for Minimum 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, M-BUS O/P card. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. BTU Meter shall BMS compatible. as per specification and as directed by Engineer In Charge .( Make: HONEYWELL / IPRO / SIEMENS)
CLOSED EXPANSION TANK Supply, installation, testing an commissioning of Water Expansion / Make Up tank made out of 6 mm thick mild steel plates, fabricated using all welded joints complete with necessary connections for piping with vent, man hole cover, make up connection with gate valve, quick fill connection valve, float valve, drain connection with valve, overflow connection, fittings, insulation, all accessories as per specifications and any other item required to make the system complete. Closed Expansion Tank( 1 OR MORE) with Membrane, without insulation, valves & fittings ( ENTIRE SET) , for sutable 4300 TR,PN-16 as per specification and as directed by Engineer In Charge . Make-Anergy/Kaizen/ Sevcon
Supply, installation, testing an commissioning of Safety Valve, PN-16, (1 N0. Required per expansion Tank ) as per specification and as directed by Engineer In Charge . Make- Anergy/Kaizen/ Sevcon
Pressurization Unit - Supply, Installing, Testing and commissioning of Pressurizing unit consisting of Inline vertical multistage, centrifugal clear water pumps (1W+1S) with S.S. 304 casing, S.S. 304 impeller and S.S. 316 shaft, CI Base,TEFC motor (with mechanical seal) with control panel and Set of accessories such as pressure switches, suction and discharge pipe manifolds, pressure gauges, valves etc. conforming to the specifications. This Shall Include Control panel, Set of accessories such as pressure switches, suction and discharge pipe manifolds, pressure gauges, valves etc. Pressurizatin unit suitable for chilled water pump head 52m as per specification and as directed by Engineer In Charge and as per approved Make-Anergy/Kaizen/ Sevcon
Supply, installation, testing& commissioning of 24G, GSS Ducting with required angle flanges & installation materials such as heavy duty supports by anchor fasteners etc as required asper IS 655 /SMACNA Standards. Makes: As per list of recommended brands.24G(Make-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing& commissioning of GSS Ducting with required angle flanges & installation materials such as heavy duty supports by anchor fasteners etc as required asper IS 655 /SMACNA Standards. Makes: As per list of recommended brands.22G(Make-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing& commissioning of GSS Ducting with required angle flanges & installation materials such as heavy duty supports by anchor fasteners etc as required asper IS 655 /SMACNA Standards. Makes: As per list of recommended brands.20G(Make-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing& commissioning of GSS Ducting with required angle flanges & installation materials such as heavy duty supports by anchor fasteners etc as required asper IS 655 /SMACNA Standards. Makes: As per list of recommended brands.18G(Make-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, fabrication and erection of 2hr (GI with intumscent coating) Fire Rated coating on Ducting and Plenum boxes for temperature 250 deg. C generally as applicable. The fire rating ducting shall have integrity, stabality and insulation. Duct to maintain minimum of 75% cros-sectional area along it whole length when tested for 2 hrs. when tested in accordance with BS 476 Part 6, 7, 20,24 / ISO 6944-1 Ducting passing through building expansion joints shall have the flexible connection and as per specification and as directed by Engineer In Charge . Make- Feukem/Paramount/Pidilite
Supply & Installation of Factory Pre-cut SMART Pre-Insulated ECO+ PIR Panels complete CFC & HCFC Free 20mm thick with FSK Reinforced Aluminium foil on one side and 80 micron Embossed Aluminium foil (Anti microbial, Anti fungal, Anti corrosion and UV Protection coating) on the other side and close cell not less than 95% Rigid Cellular foam insulation of thickness as specified below and material shall be Class O as per BS 476 Part 6 & Part 7 with 2 hours fire rating, with Density of 46kg/m3 and should have Thermal Conductivity 0.021 W/mK , Water absorption shall be not more than 0.03% as per EN 13403 standard and panel should be GreenPro & GRIHA certifed. The ductwork should be capable of handling pressures upto 2000 Pascals. The joint between the ducts shall be with Polymer slide in type joint between the ducts and all other polymer accessories to be of the same manufacturer. Measurement would be done on outer to outer. Supporting of Threaded Rod (6mm) & C Channel/ Wire supporting of reputed make recommended by Manufacturer to be provided. 20 mm Thickness (Internal Ducting) as per specification and as directed by Engineer In Charge and as per approved Make-DUCTOFAB,ZECO,ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing & commissioning of GSS CIRCULAR / spiral Ducting )- Supply, installation, testing & commissioning of 24G factory fabricated 120 GSM GSS Ducting with required TDC/TDF flanges, Guide vanes,reinforcement/stiffeners & installation materials such as heavy duty supports by anchor fasteners,Gaskets, Sealants etc as required asper SMACNA Standards GSS ducting complete with elbows turning vanes neoprene /PVC gaskets, GI fully threaded rods, GI supports / Hangers etc. All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class Ducting passing through building expansion joints shall have the flexible connection. as per specification and as directed by Engineer In Charge and as per approved Make-DUCTOFAB,ZECO,ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing & commissioning of GSS CIRCULAR / spiral Ducting )- Supply, installation, testing & commissioning of 22G factory fabricated 120 GSM GSS Ducting with required TDC/TDF flanges, Guide vanes,reinforcement/stiffeners & installation materials such as heavy duty supports by anchor fasteners,Gaskets, Sealants etc as required asper SMACNA Standards GSS ducting complete with elbows turning vanes neoprene /PVC gaskets, GI fully threaded rods, GI supports / Hangers etc. All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class Ducting passing through building expansion joints shall have the flexible connection. as per specification and as directed by Engineer In Charge and as per approved Make-DUCTOFAB,ZECO,ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing & commissioning of GSS CIRCULAR / spiral Ducting )- Supply, installation, testing & commissioning of 20G factory fabricated 120 GSM GSS Ducting with required TDC/TDF flanges, Guide vanes,reinforcement/stiffeners & installation materials such as heavy duty supports by anchor fasteners,Gaskets, Sealants etc as required asper SMACNA Standards GSS ducting complete with elbows turning vanes neoprene /PVC gaskets, GI fully threaded rods, GI supports / Hangers etc. All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class as per specification and as directed by Engineer In Charge and as per approved Make-DUCTOFAB,ZECO,ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply, installation, testing & commissioning of GSS CIRCULAR / spiral Ducting )- Supply, installation, testing & commissioning of 18G factory fabricated 120 GSM GSS Ducting with required TDC/TDF flanges, Guide vanes,reinforcement/stiffeners & installation materials such as heavy duty supports by anchor fasteners,Gaskets, Sealants etc as required asper SMACNA Standards GSS ducting complete with elbows turning vanes neoprene /PVC gaskets, GI fully threaded rods, GI supports / Hangers etc. All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class as per specification and as directed by Engineer In Charge and as per approved Make-DUCTOFAB,ZECO,ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Supply installation, testing and commissioning of 26G aluminum cladding( Embossed sheet Cladding) over insulated air-conditioning ducts, wherever exposed to atmosphere, complete in all respects as per specifications, drawings and directions of Engineer-in-ChargeMake- Nalco/National/Jindal/TataAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount.
Supply, fabrication and erection of air outlet collar connection for circular and spiral as required. as per specification and as directed by Engineer In Charge and as per approvedMake-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount.
Supply, installation, testing & commissioning of Wire mesh Bird screen-as specified. 20 G as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB / ZECO / ASAWA
Supply, Installation, Testing, Commissioning of Pressure Relief damper as specified. 20G as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER,SYSTEMAIR,TROX
Supply, Installation, Testing, Commissioning of Manual Volume control dampers as specified. Manual control opposed blade Volume control damper in 16G construction as specified, Al dampers (Low leakags), with TDF flange- within ducts to be provided with suitable links, levers and quadrants for manual control of volume of air flow. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make- AIRMASTER,SYSTEMAIR,TROX
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. Up to 0.36 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 0.37 to 0.6 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 0.61 to 0.9 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 0.91 to 1.2 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 1.21 to 1.5 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 1.51 to 1.9 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of Motorized Volume control dampers with actuator as specified. Supply, installation, testing & commissioning of multi blade, opposed blade type aerofoil sections motorised vcd dampers with spring return actuator. VCD in 16G construction as specified, Al dampers ( Low leakags), with TDF flange- It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection. Actuators for the above volume control dampers-- Contacts shall be provided in the actuator to receive signals for opening and closing the damper Power for the actuator shall be derived from LCP of the AHU by the Contractor. It shall have position feed back switch to communicate to BMS and shall work on 230V, 1ph power supply. 1.9 to ABOVE Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved DAMPERS Make: AIRMASTER / SYSTEMAIR / TROX (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, Installation, Testing, Commissioning of GI Fusible link Fire dampers 500 mm long with sleeve as per UL 555 Standard,Minimum width of damper shall be 225 mm. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Motorized Fire Damper Supply, Installation, testing and commissioning of UL 555 S Certified Fire & Smoke dampers The damper shall have ON/Off position feed back to communicate to BMS. The damper shall work on 230V , 1Ph power supply and shall be rated for 250 deg C for 2 hrs. It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection for tripping of AHU fan motor.the vendor should furnish the UL test certificate at the time of delivery For Fire damper access door shall be provided. Up to 0.36 Sqm. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Motorized Fire Damper Supply, Installation, testing and commissioning of UL 555 S Certified Fire & Smoke dampers The damper shall have ON/Off position feed back to communicate to BMS. The damper shall work on 230V , 1Ph power supply and shall be rated for 250 deg C for 2 hrs. It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection for tripping of AHU fan motor.the vendor should furnish the UL test certificate at the time of delivery For Fire damper access door shall be provided. 0.37 to 0.6 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Motorized Fire Damper Supply, Installation, testing and commissioning of UL 555 S Certified Fire & Smoke dampers The damper shall have ON/Off position feed back to communicate to BMS. The damper shall work on 230V , 1Ph power supply and shall be rated for 250 deg C for 2 hrs. It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection for tripping of AHU fan motor.the vendor should furnish the UL test certificate at the time of delivery For Fire damper access door shall be provided. 0.61 to 0.9 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Motorized Fire Damper Supply, Installation, testing and commissioning of UL 555 S Certified Fire & Smoke dampers The damper shall have ON/Off position feed back to communicate to BMS. The damper shall work on 230V , 1Ph power supply and shall be rated for 250 deg C for 2 hrs. It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection for tripping of AHU fan motor.the vendor should furnish the UL test certificate at the time of delivery For Fire damper access door shall be provided. 0.91 to 1.2 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aprovedFIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Motorized Fire Damper Supply, Installation, testing and commissioning of UL 555 S Certified Fire & Smoke dampers The damper shall have ON/Off position feed back to communicate to BMS. The damper shall work on 230V , 1Ph power supply and shall be rated for 250 deg C for 2 hrs. It shall be complete with control panel, actuator, sensor and inter-locking / wiring / connection for tripping of AHU fan motor.the vendor should furnish the UL test certificate at the time of delivery For Fire damper access door shall be provided. 1.21 to 1.5 Sqm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply Air Grill with VCD - Supply, Installation, testing and commissioning of continuous/discrete supply air grilles extruded aluminium, 'powder coated as specified (EP-0 DEG, EP-15 DEG as required )and complete with i) Face bars horizontal/vertical, adjustable/non-adjustable. ii) 20mm margins with PVC gasket iii) Sidewall or linear as shown in drgs. Linear supply air Grill with Volume control damper 150mm Wide as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Return Air Grill without VCD - Supply, Installation, testing and commissioning of continuous/discrete air grilles extruded aluminium, 'powder coated as specified (EP-0 DEG, EP-15 DEG as required )and complete with i) Face bars horizontal/vertical, adjustable/non-adjustable. ii) 20mm margins with PVC gasket iii) Sidewall or linear as shown in drgs. Linear supply air Grill with Volume control damper as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of powder coated opposed blade collar dampers as specified of Aluminium construction Collar dampers as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Modulinear Slot type diffusers with 'hit and miss dampers. 150 wide - 3 slots as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Modulinear Slot type diffusers with 'hit and miss dampers. 150 wide - 2 slots as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Modulinear Slot type diffusers with 'hit and miss dampers. 3-slot Supply grille with hit & miss damper as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Modulinear Slot type diffusers with 'hit and miss dampers. 2-slot Supply grille with hit & miss damper as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Modulinear Slot type Plenum Boxin G.I. Construction - 24 G with 6 mm Nitrile Close cell insulation - suitable for diffusers (without Flexible duct) as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Supply underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (300 x 300 /Diffuser:225 x 225/Neck : 150 x 150 mm) s.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Supply underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (375 x 375 / Diffuser:300 x 300/Neck : 225 x 225 mm) s.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Supply underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (450 x 450 / Diffuser:375 x 375/Neck : 300 x 300 mm) s.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Supply underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (525 x 525 /Diffuser:450 x 450/Neck : 375 x 375 mm) s.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Supply underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (600 x 600 / Diffuser:525 x 525/Neck : 450 x 450 mm) s.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Return underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (300 x 300 /Diffuser:225 x 225/Neck : 150 x 150 mm) r.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Return underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (375 x 375 / Diffuser:300 x 300/Neck : 225 x 225 mm) r.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Return underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (450 x 450 / Diffuser:375 x 375/Neck : 300 x 300 mm) r.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Return underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (525 x 525 /Diffuser:450 x 450/Neck : 375 x 375 mm) r.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning for Return underfloor diffuserSupply and return Air diffusers shall be with plennum Box and necessary supports and accessories. The floor diffusercore incorporates a large number of support ribs for structural integrity capable of witestand a point load at the center for up adjustecd to provide vertical and horizontal supply air discharge ,in a swirl patten. (600 x 600 / Diffuser:525 x 525/Neck : 450 x 450 mm) r.a.diffuseras required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 150 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 200 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make- AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 250 / 280 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 315 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 350 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Adjustable Jet Nozzle with Swirl plate. Supply, Installation, testing and commissioning of Adjustable Jet Nozzle with & Swirl unit for two-step reduction of the throw distance due to air control blades . Flange, face cover ring, swirl unit , V-0,& Spherical nozzle casing made of galvanised sheet steel. cap should made of ABS plastic, UL 94, flame retardant, with unique saw tooth edges,, air regenerated noise measured should be according to EN ISO 5135. The Sound power level shall be less than 40dBof the 400 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-AIRMASTER / SYSTEMAIR / TROX
Supply, Installation, testing and commissioning of Kitchen Exhuat duct-kitchen ducting shall be air and water tight welded construction black steel sheet 16G in acccorancae with BS1449 part 1 Grade CR4GP duct shalll be painted from outside with 2 coats of heat resistance galvanic paint after manufacturing. Ductwork shall be with angle flange and having the access door for cleaning. All ducting shall be with necessory supports and accessories Ducting passing through building expansion joints shall have the flexible connection. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWAAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Flexible Duct Supply, Installation, testing and commissioning of insulated(TF quality) flexible duct of following dia with necessary clamping arrangements and supports. Flexible duct should fire sustain 200 °C for minimum 2 hours. (Class ‘O’ Fire category) Note: Universal clamp should be provided to fix the flexible duct in the spigots and covered with tape. Flexible duct length shall not beyond 2meter. ( with necessory supports arrangement) 450 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB,ZECO,ASAWA
Flexible Duct Supply, Installation, testing and commissioning of insulated(TF quality) flexible duct of following dia with necessary clamping arrangements and supports. Flexible duct should fire sustain 200 °C for minimum 2 hours. (Class ‘O’ Fire category) Note: Universal clamp should be provided to fix the flexible duct in the spigots and covered with tape. Flexible duct length shall not beyond 2meter. ( with necessory supports arrangement) 300 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB,ZECO,ASAWA
Flexible Duct Supply, Installation, testing and commissioning of insulated(TF quality) flexible duct of following dia with necessary clamping arrangements and supports. Flexible duct should fire sustain 200 °C for minimum 2 hours. (Class ‘O’ Fire category) Note: Universal clamp should be provided to fix the flexible duct in the spigots and covered with tape. Flexible duct length shall not beyond 2meter. ( with necessory supports arrangement) 250 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB,ZECO,ASAWA
Flexible Duct Supply, Installation, testing and commissioning of insulated(TF quality) flexible duct of following dia with necessary clamping arrangements and supports. Flexible duct should fire sustain 200 °C for minimum 2 hours. (Class ‘O’ Fire category) Note: Universal clamp should be provided to fix the flexible duct in the spigots and covered with tape. Flexible duct length shall not beyond 2meter. ( with necessory supports arrangement) 200 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB,ZECO,ASAWA
Flexible Duct Supply, Installation, testing and commissioning of insulated(TF quality) flexible duct of following dia with necessary clamping arrangements and supports. Flexible duct should fire sustain 200 °C for minimum 2 hours. (Class ‘O’ Fire category) Note: Universal clamp should be provided to fix the flexible duct in the spigots and covered with tape. Flexible duct length shall not beyond 2meter. ( with necessory supports arrangement) 150 mm dia as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB,ZECO,ASAWA
Duct Thermal Insulation Nitrile Rubber Insulation factory fitted GC cloth for the ducting- Supply, installation Testing and commissioning of insualtion for ducting, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Closed Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 25 mm thickness as per specification and as directed by Engineer In Charge and as per aproved Make:ARMACELL / K-FLEX / AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Duct Acoustic Insulation Nitrile Rubber Insulation factory fitted GC cloth for the ducting- Supply, installation Testing and commissioning of insualtion for duct, Class O. Thermal insulation shall be applied as per given in the specification. Nitrile rubber shall be with necessary required accessories, supports,adhesive. Insulation material shall be Open Cell Microcellular Elastomeric Nitrile Rubber The Density of Material shall be between 40 to 60 Kg/m3. for Nitrile rubber Thermal conductivity of elastomeric nitrile rubber shall not exceed 0.036 W/m deg K at an average temperature of 0 deg C. The insulation shall have fire performance such that it passes minimum fire rating Class 1 as per BS 476 Part 7 for surface spread of flame and also pass Fire Propagation requirement as per BS476 Part 6 to meet the Class ‘O’ Fire classification as per 1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations 1990. Water vapour permeability shall not exceed 0.024 Perm inch (2.48 x 10-14 Kg/m.s.Pa) i.e. Moisture Diffusion Resistance Factor or ‘µ’ value should be minimum 7,000. Material should have FM Global (Factory Mutual) USA approval for fire behavior Insulation material shall have Ultra-Fresh® anti-microbial protection, which is EPA (Environmental Protection Agency), USA approved(or equivalent), as an integral part of insulation that cannot be washed off or worn off as per ASTM G-21. It shall give enhanced level of protection against harmful Microbes such as bacteria, mold, mildew and fungi Should also pass Smoke Toxicity of the product according to DIN 5510 Part 2 appendix 2 Should have VOC emission Class A+ as per ISO 16000 Insulation products shall be free from CFC/HCFC, Formaldehyde, Dust & Fibres Material should have low temperature flexibility conforming to ASTM D 1056 -07 Ozone resistance as per ASTM D 1171-99(07) 19 mm thickness as per specification and as directed by Engineer In Charge and as per aproved Make:ARMACELL / K-FLEX / AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Firber Glass ( Mineral wool) Thermal Insulation Supply, Installation, testing and commissioning of Duct Thermal Insulation applied outside of the duct work of resin bonded semi rigid Fiber Glass/ Miniral wool with one side factory laminated Alu glass foil sheet ( non tearable) Aluminium sheet on one side as vapor barrier. Fiber glass (Miniral wool)should confirm to BS:476 Part 4 & 5.(Non-Combustible) Thermal conductivity of the insulation material shall not exceed 0.033 W/m K and thermal resistance should be 1.51Sq.mt K/W at 25 deg C mean temperature NOTE-Insulation price includes required adhesives, all required accessories, supports, tape etc. Insulation shall be fire rated. The material should be ASTM E84 and NFPA 90A &90B compliant Supply and return Ducts – Thickness 25mm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make : ARMACELL / K-FLEX / AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
Underdeck insulation generally as specified and complete with all necessary elements. Supply, Installation, testing and commissioning of Underdeck insulation material shall be Closed Cell Elastomeric Nitrile Rubber foam . Density of the nitrile rubber shall be 40-60 Kg/m3. Thermal conductivity as per ASTM C 518 of the insulation material shall not exceed 0.0352 W/moK at an average temperature of 10oC. The insulation shall have fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame as per BS 476 and alsopassFirePropagationrequirementasperBS476Part6tomeettheClass‘O’Firecategoryasper1991 Building Regulations (England & Wales) and the Building Standards (Scotland) Regulations1990 The insulation material shall also be fire rated for Class V 0 as per UL 94. Water diffusion factor shall not be less than µ>7000 for plain sheets. Material should be FM approved. NOTE-Insulation price includes required adhesives, all required accessories, supports, tape etc. Underdeck insulation Thickness-25mm Thick as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make : ARMACELL / K-FLEX / AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
ROOM ACOUSTIC INSULATION- Supply, Installation, testing and commissioning of acoustic lining on wall and ceiling of AHU rooms with 25mm thick 50mm Rigid Board of Glass wool one side aluminum faced. with 600mm x 600mm perforated sheet and other side black glass cloth lamination, density 70 to 80 kg/cu.m. Insulation shall be fire rated. NOTE-Insulation price includes required adhesives, all required accessories, supports, tape etc.The surface shall have a frame work of 22 gauge The application of the acoustic insulation shall be as follows: 1. Fix U clamp on the wall made out of 1mm thick G.I with fasteners or rawl plug. 2. Fix pre-fabricated compressed GI clip having a thickness of 0.6 mm and fix in to the U clamp by friction fit method horizontally over wall at an interval of 600 mm to fix the pre-fabricated perforated aluminium panels. 3. Fix cut panels of fiberglass wool panel of appropriate density and thickness in between the frame and followed by a layer of R.P. tissue and finally finished with modular type 26 SWG aluminium perforated panels of dimensions 600 x 600 mm aluminium sheet having a minimum perforations of 20%. The ends of the panels wherever it is open shall be finished with GI C channel of suitable sizes to avoid the fiber glass erosion/migration to the AHU air. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-ARMACELL / K-FLEX / AEROFOAMAdhesive for duct and pipe insulation :Napco/Foster/Armaflex 520/ Pidilite SR 998/Paramount
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fan outlet velocity shall be 10 m/s/ As per data sheet Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag -EX-BS-22 ( Normal mode) Capacity- 800 CFM Static Pressure- 0.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved (( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fan outlet velocity shall be 10 m/s/ As per data sheet Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z01-EL RM09-54,EX-BS-Z01-EL RM09-55,EX-BS-Z01-EL RM10-56,EX-BS-Z01-EL RM12-57 ( Normal and Fire mode) Capacity- 800 CFM Static Pressure- 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fan outlet velocity shall be 10 m/s./As per data sheet Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-CONT RM-26 ( Normal and Fire mode) Capacity- 1200 CFM Static Pressure- 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor r NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-TR-TE-66,EX-TR-TE--67,EX-TR-TE-68,EX-TR-TE-69 ( Normal) Capacity- 1200 CFM Static Pressure- 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z01-EL RM01-42,EX-BS-Z01-EL RM02-43,EX-BS-Z02-EL RM03-44,EX-BS-Z02-EL RM04-45,EX-BS-Z03-EL RM05-46,EX-BS-Z03-EL RM06-47,EX-BS-Z03-EL RM07-48,EX-BS-Z03-EL RM08-49( Normal and Fire mode) Capacity- 1500 CFM Static Pressure- 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) Smoke Extraction fans motor shall be Fire rated motor All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-CORR02-31 ( Normal and Fire mode) Capacity- 2500 CFM Static Pressure- 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-ELV TRENCH-23 ( Normal and Fire mode) Capacity- 3100 CFM Static Pressure- 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-CORR01-27( Normal and Fire mode) Capacity- 3500 CFM Static Pressure- 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TR-Z01-EL RM13-58,EX-TR-Z02-EL RM14-59,EX-TR-Z03-EL RM15-60,EX-TR-Z04-EL RM16-61,EX-TR-Z01-ELV RM01-62,EX-TR-Z02-ELV RM02-63,EX-TR-Z03-ELV RM03-64,EX-TR-Z04-ELV RM04-65 ( Normal and Fire mode) Capacity- 5000 CFM Static Pressure- 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-ELE TRENCH-24,EX-BS-CONS HTPL RM-25 ( Normal and Fire mode) Capacity- 7000 CFM Static Pressure- 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z01-ELPL RM- 50,EX-BS-Z02-ELPL RM-51,EX-BS-Z03-ELPL RM-52,EX-BS-Z03-ELPL RM-53( Normal and Fire mode) Capacity-7500 CFM Static Pressure- =1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-BS-HTPL RM-30 ( Normal and Fire mode) Capacity-8000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-CONS HTPL RM-25 ( Normal and Fire mode) Capacity-8500 CFM Static Pressure- =1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-SE-ZN03-140 ( Fire mode) Capacity- 10000 CFM Static Pressure- = 3inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-FF-SE-Z6-102,EX-FF-SE-Z12-108( Fire mode) Capacity-10500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-1F-SE-Z01-B6-112( Fire mode) Capacity-10500 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-12 ( Normal and Fire mode) Capacity- 11000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-LTPL RM-28( Normal and Fire mode) Capacity- 11000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-Fan- EX-FF-SE-Z5-101,EX-FF-SE-Z10-106,EX-FF-SE-Z11-107,EX-3F-SE-Z01-108,EX-3F-SE-Z02-109,EX-3F-SE-Z04-111 ( Fire mode) Capacity- 11000 CFM Static Pressure- = 2.0 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW ( Or VFD as specified in data sheet ) Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-1F-SE-Z02-B6-113,EX-1F-SE-Z03-B6-114,EX-1F-SE-Z04B6-115 ( Fire mode) Capacity- 11000 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-14( Normal and Fire mode) Capacity- 11500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z9-105 ( Fire mode) Capacity- 11500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z7-103,EX-FF-SE-Z8-104( Fire mode) Capacity- 12000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW ( Or VFD as specified in data sheet ) Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-3F-SE-Z03-110( fire mode) Capacity- 12500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-BS-10 ( Normal and Fire mode) Capacity- 14000 CFM Static Pressure- =1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z1-B2-86( Fire mode) Capacity- 14500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-21 ( Normal and Fire mode) Capacity- 15000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z3-B1-93,EX-FF-SE-Z4-B3-99 ( Fire mode) Capacity- 15000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-BS-07 ( Nornal & Fire mode) Capacity- 16000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-SE-Z01-B6-112,EX-GR-SE-Z03-B5-118,EX-GR-SE-Z04B5-119 ( Fire mode) Capacity- 16000 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z1-B1-85,EX-FF-SE-Z2-B1-89,EX-FF-SE-Z4-B1-97 ( Fire mode) Capacity- 17500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-20( Normal and Fire mode) Capacity- 18000 CFM Static Pressure- = 1.6 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-06 ( Normal and Fire mode) Capacity- 18500 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-3F-SE-PASSAGE-142,EX-3F-SE-PASSAGE-143,EX-3F-SE-PASSAGE-144,EX-3F-SE-PASSAGE-145,EX-5F-SE-PASSAGE-146,EX-5F-SE-PASSAGE-147,EX-5F-SE-PASSAGE-148,EX-5F-SE-PASSAGE-149,EX-7F-SE-PASSAGE-150,EX-7F-SE-PASSAGE-151,EX-7F-SE-PASSAGE-152,EX-7F-SE-PASSAGE-153 (Fire mode) Capacity- 19000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-TRANS RM-29 ( Normal and Fire mode) Capacity- 20000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z1-B3-71,EX-GF-SE-Z1-B4-72( Fire mode) Capacity- 20000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z3-B2-94( Fire mode) Capacity- 21000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-SE-ZN01-138( Fire mode) Capacity- 21000 CFM Static Pressure- = 3 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z2-B4-92,EX-FF-SE-Z4-B4-100 ( Fire mode) Capacity- 21500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z3-B3-95 ( Fire mode) Capacity- 23000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 Kw Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-SE-Z02-B6-113 ( Fire mode) Capacity-23000 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-TRANS RM-29 ( Normal and Fire mode) Capacity- 24000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z4-B1-81,EX-FF-SE-Z1-B4-88,EX-FF-SE-Z2-B3-91,EX-FF-SE-Z3-B4-96 ( Fire mode) Capacity- 24000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-SE-Z02-B5-117 ( Fire mode) Capacity- 24000 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-GF-SE-Z3-B4-80 (Fire mode) Capacity- 24500 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-11 ( Normal and Fire mode) Capacity- 25000 CFM Static Pressure- =1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z1-B1-69,EX-GF-SE-Z3-B1-77,EX-FF-SE-Z2-B2-90 (Fire mode) Capacity- 25000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No - EX-BS-05 ( Normal and Fire mode) Capacity-25500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EEX-GF-SE-Z2-B1-73 ( Fire mode) Capacity- 26000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-FF-SE-Z1-B3-87( Fire mode) Capacity- 28000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-1F-SE-Z03-B5-118 (Fire Mode) Capacity- 28000 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z3-B3-79 ( Fire mode) Capacity- 28500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-1F-SE-Z01-B5-116,EX-1F-SE-Z02-B5-117,EX-1F-SE-Z04B5-119 (Fire mode) Capacity- 28500 CFM Static Pressure- = 2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-TF-SE-ZN04-141 (Fire mode) Capacity- 28500 CFM Static Pressure- = 3 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No - EX-GF-SE-Z4-B3-83(Fire mode) Capacity- 30000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-SE-Z01-B5-116 (Fire mode) Capacity- 30000 CFM Static Pressure- =2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-17( Normal and Fire mode) Capacity- 30500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-19 ( Normal and Fire mode) Capacity- 30500 CFM Static Pressure- =1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Tag No- EX-GR-SE-Z03-B6-114,EX-GR-SE-Z04B6-115( Fire mode) Capacity- 30500 CFM Static Pressure- =2.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z4-B4-84,EX-FF-SE-Z4-B2-98 (Fire mode) Capacity- 31000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-18 (Normal & Fire mode) Capacity- 31500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z2-B4-76 ( Fire mode) Capacity- 32000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z2-B2-74 ( Fire mode) Capacity- 33500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make KRUGER / GREENHECK / SYSTEMAIR). Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z2-B3-75 ( Fire mode) Capacity- 35000 CFM Static Pressure- = 2 inch WGG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-TF-SE-ZN02-139( Fire mode) Capacity- 35000 CFM Static Pressure- =3 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-09 ( Normal & Fire mode) Capacity- 36000 CFM Static Pressure- =1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z4-B2-82 ( Fire mode) Capacity- 36000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-BS-13 ( Normal & Fire mode) Capacity- 38500 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z1-01 (normal & fire mode) Capacity- 39000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z1-02 ( FIRE mode) Capacity- 39000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-08 ( Normal & Fire mode) Capacity- 40000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-DG RM-32 TO 41 ( Normal & Fire Mode) Capacity- 40000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-15,EX-BS-16 ( Normal & Fire Mode) Capacity- 40500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z1-B2-70 ( FIRE mode) Capacity- 46000 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GF-SE-Z3-B2-78 ( FIRE mode) Capacity- 47500 CFM Static Pressure- =2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z2-03 ( Normal & Fire mode) Capacity- 49500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-BS-Z2-04( fire mode) Capacity- 49500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-TF-SE-ZN01-120,EX-TF-SE-ZN01-121,EX-TF-SE-ZN01-122,EX-TF-SE-ZN01-123,EX-TF-SE-ZN02-124,EX-TF-SE-ZN02-125,EX-TF-SE-ZN02-126,EX-TF-SE-ZN02-127,EX-TF-SE-ZN03-128,EX-TF-SE-ZN03-138,EX-TF-SE-ZN03-129,EX-TF-SE-ZN03-130,EX-TF-SE-ZN03-131,EX-TF-SE-ZN04-132,EX-TF-SE-ZN04-133,EX-TF-SE-ZN04-134,EX-TF-SE-ZN04-135,EX-TF-SE-ZN04-136( fire mode) Capacity- 57000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-ZN01-B3-KITCHEN-01( normal mode) Capacity- 27000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-ZN01-B4-KITCHEN-02( normal mode) Capacity- 14000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-8F-ZN03-KITCHEN-03( normal mode) Capacity- 7000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
JET FANS FOR BASEMENT as per below description and the tender technical specifications Design (Including CFD Analysis) Supply, installation, testing & commissioning of Axial type Jet fan complete fan including each component shall be fire rated and designed to with stand minimum 250° C temperatures for 2 hrs tested in accordance with EN 12101-3:2015. in the event of fire. Fan motor shall be two speed 2P/4P , high efficiency and low noise design. Sound levels @ 3m from fan shall not exceed levels of 68/50 dba. Each fan shall be of circular design with impeller not more than 355 mm in dia and with a thrust not less than 48 N @ high speed & 12 N @ low speed to cover an area of apprx 600sqm. Test Certificates to be produced prior to delivery of the units. The fan shall incorporate factory mounted silencers at the inlet and the outlet alongwith guide vanes to straighten air flow & all accessories like mounting brackets etc. Steel Protection guards to be provided at inlet and outlet for each fan along with air deflector at outlet. Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE2 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT 3). Total height of fan including silencer & supports shall not exceed 550mm. 4) For protection of cable trays & equipment from the wall & ceiling slab painting work contractor should be wrap all the equipments after installation with polythin marerial. Fan Tag No- JET-BS-Z1-01_05,JET-BS-Z2-06_12 ( Normal & Fire mode) Capacity- 4224/2149 CFM / CFM Static Pressure- = 0.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-Z01-EL RM09-54,SA-BS-Z01-EL RM09-55,SA-BS-Z01-EL RM10-56,SA-BS-Z01-EL RM12-57( normal& fire mode) Capacity- 600 CFM Static Pressure- = 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/ SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-22( normal mode) Capacity- 650 CFM Static Pressure- = 0.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-CONT RM-26 ( normal & fire mode) Capacity- 1000 CFM Static Pressure- = 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-Z01-EL RM01-42,SA-BS-Z01-EL RM02-43,SA-BS-Z02-EL RM03-44,SA-BS-Z02-EL RM04-45,SA-BS-Z03-EL RM05-46,SA-BS-Z03-EL RM06-47,SA-BS-Z03-EL RM07-48,SA-BS-Z03-EL RM08-49 ( normal & fire mode) Capacity- 1200 CFM Static Pressure- = 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-ELV TRENCH-23( normal & fire mode) Capacity- 2500 CFM Static Pressure- = 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-CORR02-31( normal & fire mode) Capacity- 2500 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW ( Or VFD as specified in data sheet ) Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-CORR01-27( normal & fire mode) Capacity- 3500 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-TR-Z01-EL RM13-58,SA-TR-Z02-EL RM14-59,SA-TR-Z03-EL RM15-60,SA-TR-Z04-EL RM16-61,SA-TR-Z01-ELV RM01-62,SA-TR-Z02-ELV RM02-63,SA-TR-Z03-ELV RM03-64,SA-TR-Z04-ELV RM04-65( normal & fire mode) Capacity- 4000 CFM Static Pressure- = 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-ELE TRENCH-24( normal & fire mode) Capacity- 5500 CFM Static Pressure- = 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-Z01-ELPL RM-50,SA-BS-Z02-ELPL RM-51,SA-BS-Z03-ELPL RM-52,SA-BS-Z03-ELPL RM-53( normal & fire mode) Capacity- 6000 CFM Static Pressure- = 1 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-HTPL RM-30( normal & fire mode) Capacity- 6500 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-LTPL RM-28( normal & fire mode) Capacity- 8500 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- SA-BS-14( normal & fire mode) Capacity- 10000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-12( normal & fire mode) Capacity- 10500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-10( normal & fire mode) Capacity- 13500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-20( normal & fire mode) Capacity- 14500 CFM Static Pressure- = 1.6 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-21( normal & fire mode) Capacity- 15000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-07( normal & fire mode) Capacity- 15500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-06( normal & fire mode) Capacity- 17500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-LC-19+20-94,SA-4TH-LC-21+22-95,SA-4TH-LC-29+30-99( fire mode) Capacity- 21000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-11( normal & fire mode) Capacity- 23000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-05( normal & fire mode) Capacity- 24000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-LC-17+18-93,SA-4TH-LC-23+24-96,SA-4TH-LC-25+26-97,SA-4TH-LC-27+28-98,SA-4TH-LC-31+32-100( fire mode) Capacity- 24000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-17(normal & fire mode) Capacity- 25500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-09,SA-BS-19(normal & fire mode) Capacity- 29000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-T-LL-01-82,SA-T-LL-02-83,SA-T-LL-03-83,SA-T-LL-04-84(fire mode) Capacity- 21500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-18(normal & fire mode) Capacity- 30500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag NoSA-BS-ST-02-67,SA-BS-ST-04-69,SA-BS-ST-06-71,SA-BS-ST-08-73(fire mode) Capacity- 31000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-ST-10-86,SA-4TH-ST-11-87,SA-4TH-ST-14-90,SA-4TH-ST-15-91(fire mode) Capacity- 31500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-08(normal & fire mode) Capacity- 32500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-ST-09-85,SA-4TH-ST-12-88,SA-4TH-ST-13-89,SA-4TH-ST-16-92(fire mode) Capacity- 33000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-T-LC-03+04-75,SA-T-LC-07+08-77,SA-T-LC-11+12-79,SA-T-LC-15+16-81(fire mode) Capacity- 34000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-13(normal &fire mode) Capacity- 35500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-ST-01-66,SA-BS-ST-03-68,SA-BS-ST-05-70,SA-BS-ST-07-72(normal &fire mode) Capacity- 37000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-T-LC-01+02-74,SA-T-LC-05+06-76,SA-T-LC-09+10-78,SA-T-LC-13+14-80 (fire mode) Capacity- 36000 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-Z1-01 (normal & fire mode) Capacity- 39000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-Z1-02 (fire mode) Capacity- 39000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-15 (normal & fire mode) Capacity- 39500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-DG RM-32 TO 41 (normal & fire mode) Capacity- 40000 CFM Static Pressure- = 0.8 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-16 (normal & fire mode) Capacity- 40500 CFM Static Pressure- = 2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-LL-06-102,SA-4TH-LL-07-103,SA-4TH-LL-10-106,SA-4TH-LL-11-107 ( fire mode) Capacity- 29000 CFM Static Pressure- = 1.6 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-4TH-LL-05-101,SA-4TH-LL-08-104,SA-4TH-LL-09-105,SA-4TH-LL-12-108(fire mode) Capacity- 30500 CFM Static Pressure- = 1.6 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Fans for Basement 2 Vane Axial Fan(ceiling suspended) -Smoke spill Fans for Basement Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-Z2-03(normal &fire mode) Capacity- 49500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, testing & commissioning of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be VFD as specified in data sheet Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-SA-BS-Z2-04(fire mode) Capacity- 49500 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved make ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
Supply and installation of CO SENSOR & DETECTOR, CO detector to be installed flush mounted hard wired to Panels, Each Sensor shall have Output Terminals: (Screw Type) 1. 24 V AC/DC 2. Power grounding 3. O/P 1 Linear signal CO transmitter 4. O/P 2 Linear signal CO2 transmitter (Built in option) 5. O/P 3 – Gas alarm (NC) 6. Jumpers to choose between open or 10V signal; voltage or current outputs 7. Jumper for configuring the linear output 0% or 20 % start point. 8. UART port Sensor Electrical/Mechanical/Dimensions: Power Input 24 VAC/VDC±20%, 50 Hz (half-wave rectifier input);Power Consumption < 3 Watts average; Wiring Connections max 1.5 mm2 wires for screw terminal (main terminal) and spring loaded terminal; UART connector 5-pin, 2.54 mm pitch & slide connector CO Measurement : Operating Principle Gas sensitive thick film material (MMOS) internally compensated for temperature and humidity variations, with active carbon filter with Automatic Baseline Correction (ABC) 3 Accuracy 4± 10 ppm: Measurement ranges 0 to 200 ppm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-HONEYWELL / RESIDEO / GREYSTONE)
Cabinet Fan-(Floor Mounted Cabinet Fan),KITCHEN FA FAN FOR GROUND FLOOR Design (Including CFD Analysis)Supply, installation, commissioning & testing of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- FA-GR-ZN01-B3-KITCHEN-01-A,FA-GR-ZN01-B3-KITCHEN-01-B ( Normal mode) Capacity- 8500CFM ESP- = 1.2 inch WG as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make AHU :CARRIER,VTS,SYSTEMAIR/DAIKIN(FAN :KRUGER,GREENHECK,SYSTEMAIRMotor :ABB/Crompton/SiemensAir Filter:AAF,CAMFIL,THERMADYNEUVGI-lamps : UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
Cabinet Fan-(Floor Mounted Cabinet Fan),KITCHEN EA FAN FOR GROUND FLOOR Design (Including CFD Analysis) Supply, installation, commissioning & testing of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-GR-ZN01-B4-KITCHEN-02 ( Normal mode) Capacity- 9000CFM ESP- = 1.2 inch WG as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make AHU :CARRIER,VTS,SYSTEMAIR/DAIKINFAN :KRUGER,GREENHECK,SYSTEMAIRMotor :ABB/Crompton/SiemensAir Filter:AAF,CAMFIL,THERMADYNEUVGI-lamps : UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
Cabinet Fan-(Floor Mounted Cabinet Fan),KITCHEN EA FAN FOR EIGHT FLOOR Design (Including CFD Analysis) Supply, installation, commissioning & testing of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) `2)CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No- EX-8F-ZN03-KITCHEN-03 ( Normal mode) Capacity- 4500CFM ESP- = 1.2 inch WG as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved AHU :CARRIER,VTS,SYSTEMAIR/DAIKINFAN :KRUGER,GREENHECK,SYSTEMAIRMotor :ABB/Crompton/SiemensAir Filter:AAF,CAMFIL,THERMADYNEUVGI-lamps : UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, commissioning & testing and CFD analysis of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-ZN01-TOILET -01,EX-TF-ZN03-TOILET -03(normal mode) Capacity- 11000 CFM Static Pressure- = 1.5 inch WG` as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, commissioning & testing and CFD analysis of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-ZN02-TOILET -02,EX-TF-ZN04-TOILET -04(normal mode) Capacity- 12000 CFM Static Pressure- = 1.5 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, commissioning & testing and CFD analysis of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-ZN01&02-TOILET -05,EX-TF-ZN 03&04-TOILET -06(normal mode) Capacity- 3500 CFM Static Pressure- = 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
VENTILATION AND EXHUST SYSTEM FANS Design (Including CFD Analysis) Supply, installation, commissioning & testing and CFD analysis of VENTILATION & EXHAUST SYSTEMS in accordance with and meeting the intents of the specifications, drawings and data sheets complete with: i) Vane Axial /Tube Axial / Centrifugal / Cabinet Inline / Propeller Fan with drive motors as specified in Fan Data Sheet. ii) Mild steel mounting frame iii) Vibration mounts. iv) Fire rated Flexible Canvass connections v) Filters with necessary frames wherever necessary. vi) 8 Rmt . Of necessary elctrical cabling including necessary cable terminations and frames wherever necessary. necessary earthing fromIsolator panel to FAN viii) Required Earthing of motor and unit. viii ) All VFDs shall be provided with open protocol to communicate with third party BMS system. viii ) All Motors shall be VFDs compatible. Note:- Starter shall be star delta for 5.5 KW and above and DOL starter for less than 5.5 KW Vane Axial Fan(ceiling suspended) -Smoke spill Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans Motor shall be - IE4 motor (As per IS 12615) All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor NOTE:- 1) REFER THE TECHNICAL DATASHEET FOR THE EQUIPMENT SCHEDULED (Annexure1) 2) CONTRACTOR/SUPPLIER SHALL TAKE THE PRIOR APPROVAL FROM THE CONSULTANT/ SITE INCHAREGE/CLIENT BEFORE PROCUREMENT OF THE UNIT Fan Tag No-EX-TF-ZN01&02-TOILET -05,EX-TF-ZN 03&04-TOILET -06(normal mode) CaFan Tag No-EX-TF-ZN 01&04-TOILET -07,EX-TF-ZN 02&03-TOILET -08(normal mode) Capacity- 5000 CFM Static Pressure- = 1.2 inch WG as per specification, data sheet and as directed by Engineer In Charge and as per approved ( Make: KRUGER / GREENHECK / SYSTEMAIR) Motor :ABB/Crompton/SiemensVFD-DANFOSS / ABB / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 300 x 250 /50 CFM to 230 CFM as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 500 x 350 /70 cfm to 360 Cfm as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 550 x 400 / 100 cfm to 560 Cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750 x 350 / 140 cfm to 710 Cfm as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750x450 /185 cfm to 925 Cfm- as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750x450 /290 cfm to 1450 Cfm- as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750x450 /420 cfm to 2100 Cfm- as per specification , and as directed by Engineer In Charge and as per aproved make. Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750x450 /560 cfm to 2900 Cfm- as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator:BELIMO / SIEMENS / HONEYWELL
RECTANGULAR VARIABLE AIR VOLUME BOX Supply, Installation, Testing & Commissioning of Pressure Independent type Variable Air Volume boxes(AHRI 880 certified & labled), BMS Communicable, Single Duct Rectangular VAV Terminal unit with 22 galvanised steel, Open cell insulation with circular inlet, high5 accuracy multipoint airflow sensor. It has Spigot round damper with elastomeric gasket and rectangular outlet with flanged connection of 40 mm flange VAV Box includes following accessories: - 1) Built-in Controller and Actuator 2) BMS Communication over BACNet MS/TP - 3) Digital Room Thermostat 4) Step Down Transformer - 5) Internal Wiring All VAV terminals with DDC controller must be single OEM. VAV should be with internal acoustic lining. 750x450 /850 cfm to 3700 Cfm- as per specification , and as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
BMS INTEGRATION FOR VAV The Master Controller shall be able to communicate with VAV boxes and enable the output to IBMS for integration. as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make:SCHNEIDER-EcoStruxure,JOHNSON CONTROLS,HONEYWELL TREND
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 200 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 250 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 300 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 500 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 650 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 850 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
CAV Constant Volume Flow Limiters,should be Mechanically System Powered with High-quality plastic control damper and casing (UL 94 V1),conforming to DIN 4102, fire rating class B2,stainless steel leaf spring & silicon free oscillation damper ,It should be Factory Calibrated and can be Adjusted at Site with Independent of orientalion in installation.Contorl range should be ± 10 % of Set Flow. CAV boxes shall be AHRI certified. VAV should be with internal acoustic lining. 1600 cfm as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-DUCTOFAB / ZECO / ASAWA. Actuator: BELIMO / SIEMENS / HONEYWELL
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm - 4500 / 5500 cfm( 27 TR) Tag No : HRW1 as per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm - 5000 / 4000 cfm(31 TR) Tag No : HRW 2 aas per specification, data sheet and as directed by Engineer In Charge and as per approved (HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm -4500 / 3000 cfm (28 TR) TAG NO : HRW3 as per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm - 5600 / 3500 cfm( 35 TR) TAG NO : HRW 4 aas per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm - 4800 / 3500 cfm( 30 TR) TAG NO ; HRW 05 as per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm - 5300 / 4000 cfm( 33TR)CC TAG NO :HRW 06 as per specification, data sheet and as directed by Engineer In Charge and as per approved make HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm -5000 / 4000 cfm(32 TR) TAG NO :HRW 7 as per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
HEAT RECOVERY SYSTEM. Supply , Installation , Testing and commissioning of Energy recovery system including I) Energy recovery cassetes as required, with dessicant wheels. ii) Supply and exhaust fans fan motor assemblies with all accessories. iii) Double skin Body iv)Unit Control centre for entire unit with VFD's and Bypass starters, control circuit fusing etc. with required cabling and control wiring. v) Pre filters on both supply and exhaust inlet side vi) Isolator panel with starter and accessories as specified vii) Required Earthing of motor and unit. Note:- In case the total supply air is to be divided into exhaust air part and supplement air part then the same can be done and vendor to quote as package with all add on fans, ducting,controls,electrical, bms etc., & no extra payment shall be made for that. Eurovent certification is required for the HRW units Coil to be Eurovent certified. Motor shall be - IE4 motor (As per IS 12615) Supply/Return Air Cfm -5200 / 4000 cfm(33 TR) TAG NO :HRW 8 as per specification, data sheet and as directed by Engineer In Charge and as per approved HRW Unit : FLAKT WOODS / CARRIER / SYSTEMAIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens (Air Filter Make: AAF / CAMFIL / THERMADYNE) UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
Dry Type Electrostatic Air cleaner scrubber Supply, Installation, testing & commissioning of Dry type scrubber for kitchen Installation, Testing & Commissioninghen Exhaust application with all accessories as specified in specification. Dry scrubber – Electrostatic Air cleaner as per specifications,suitable for following capacities. The Air filtration efficiency should be between 90 to 95% & units shall be staked one above other or side by side as per site requirement. Finishing - Powder coated, Dark Blue Operating voltage - 220 Vac+/-10%, 50 Hz (Single phase) Features - Short circuit, arc protection with auto power restore for power pack Efficiency - Upto 95%, meets NIOSH 5026 Oil Mist Test Particle Size - Collects particles as small as 0.01 microns Motor - Sealead ball bearings UL, single phase Cell - Ionizing voltage - 12 KVdc Collector voltage - 6 KVdc One cell comprising of 9 ionizing wires and 25 collection plate Controls - Auto cut-off when door is opened. Indicator lights for fault, normal or wash function. Pre-filter - Aluminium mesh, washable Dry contact for BMS. NOTE- 1. Electrical static air cleaner shall be suitable for outdoor installation and shall have IP 5 protection.Scrubber 9000cfm 2. Fan Shall be fire rated for 2 hrs @ 250 Deg C and 30 Min for @ 300 Deg C and Motor Shall be Flame proof Type. TAG NO : EX-DS-GR-ZN01-B3-KITCHEN-01 TOTAL CFM : 27000 ( 9000 X 3 NOS) as per specification, data sheet and as directed by Engineer In Charge and as per approved Dry Scrubber - NUTECH / ULTRAPURE / AQUA AIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens/KECAir Filter:AAF / CAMFIL / THERMADYNEUVGI-lamps :NUTECH / ULTRAPURE / AQUA AIR
Dry Type Electrostatic Air cleaner scrubber Supply, Installation, testing & commissioning of Dry type scrubber for kitchen Installation, Testing & Commissioninghen Exhaust application with all accessories as specified in specification. Dry scrubber – Electrostatic Air cleaner as per specifications,suitable for following capacities. The Air filtration efficiency should be between 90 to 95% & units shall be staked one above other or side by side as per site requirement. Finishing - Powder coated, Dark Blue Operating voltage - 220 Vac+/-10%, 50 Hz (Single phase) Features - Short circuit, arc protection with auto power restore for power pack Efficiency - Upto 95%, meets NIOSH 5026 Oil Mist Test Particle Size - Collects particles as small as 0.01 microns Motor - Sealead ball bearings UL, single phase. Cell - Ionizing voltage - 12 KVdc Collector voltage - 6 KVdc One cell comprising of 9 ionizing wires and 25 collection plate Controls - Auto cut-off when door is opened. Indicator lights for fault, normal or wash function. Pre-filter - Aluminium mesh, washable Dry contact for BMS. NOTE- 1. Electrical static air cleaner shall be suitable for outdoor installation and shall have IP 5 protection.Scrubber 7000cfm+ 2. Fan Shall be fire rated for 2 hrs @ 250 Deg C and 30 Min for @ 300 Deg C and Motor Shall be Flame proof Type. TAG NO : EX-DS-GR-ZN01-B4-KITCHEN-02 TOTAL CFM : 14000 ( 7000 X 2 NOS) as per specification, data sheet and as directed by Engineer In Charge and as per approved Dry Scrubber - NUTECH / ULTRAPURE / AQUA AIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens/KECAir Filter:AAF / CAMFIL / THERMADYNEUVGI-lamps :NUTECH / ULTRAPURE / AQUA AIR
Dry Type Electrostatic Air cleaner scrubber Supply, Installation, testing & commissioning of Dry type scrubber for kitchen Installation, Testing & Commissioninghen Exhaust application with all accessories as specified in specification. Dry scrubber – Electrostatic Air cleaner as per specifications,suitable for following capacities. The Air filtration efficiency should be between 90 to 95% & units shall be staked one above other or side by side as per site requirement. Finishing - Powder coated, Dark Blue Operating voltage - 220 Vac+/-10%, 50 Hz (Single phase) Features - Short circuit, arc protection with auto power restore for power pack Efficiency - Upto 95%, meets NIOSH 5026 Oil Mist Test Particle Size - Collects particles as small as 0.01 microns Motor - Sealead ball bearings UL, single phase. Cell - Ionizing voltage - 12 KVdc Collector voltage - 6 KVdc One cell comprising of 9 ionizing wires and 25 collection plate Controls - Auto cut-off when door is opened. Indicator lights for fault, normal or wash function. Pre-filter - Aluminium mesh, washable Dry contact for BMS. NOTE- 1. Electrical static air cleaner shall be suitable for outdoor installation and shall have IP 5 protection.Scrubber 7000cfm 2. Fan Shall be fire rated for 2 hrs @ 250 Deg C and 30 Min for @ 300 Deg C and Motor Shall be Flame proof Type. TAG NO : EX-DS-8F-ZN03-KITCHEN-03 TOTAL CFM : 7000 as per specification, data sheet and as directed by Engineer In Charge and as per approved Dry Scrubber - NUTECH / ULTRAPURE / AQUA AIRFAN : KRUGER / GREENHECK / SYSTEMAIRMotor :ABB/Crompton/Siemens/KECAir Filter:AAF / CAMFIL / THERMADYNEUVGI-lamps :NUTECH / ULTRAPURE / AQUA AIR
OZONATOR FOR STP Design, Size, supply, installation, and commissioning of duct-mounted STP room at basement area Exhaust air foul odour, microorganism, and pollutant destruction system using Generation lV high concentration "Electro-Chemical Oxidant" spray with high efficiency "Bipolar Oxygen Ions technique" Ozone generator working on capture and treat technique. The entire odour control system has to be installed out of the duct, and the only odour destructor with riders is to be injected using flexible tubing that does not exceed 15 mm in the duct carrying STP room exhaust air. The MOC of the unit should be Stainless steel 304 grade with built-in PLC and BMS integration. The Oxidation reactor should have a minimum life of 15,000 hours. Odour control vendor should have minimum 10 years of working experience in odour control application. The system/ technology should be without any consumables other than electricity. The unit should be CE certified. The Manufactuer must have ISO 9001-2015. Certification. as per specification, data sheet and as directed by Engineer In Charge and as per approved make 47000 CFM as per specification and as directed by Engineer In Charge and as per aproved make. Make - Eltech Ozone/Chemtronic/Sahora
PAC UNITS Supply Installation Testing & Commisioning of of Dual Fluid Type (DX + CW) Precision Air Conditioning Unit complete with Fixed Scroll Compressor, with Heater and Humidifer . Unit should be bottom discharge with Fan Section below False Floor with auto modulating PIDV valve. Refrigerant should be Eco-Friendly- R407c. Unit should have with Backward curved plug fan with direct driven EC Motor (Electronically Commutated) . Indoor unit shall be provided with all necessary accessories including unit base anti vibration mount etc.indoor unit frame shall be made up of 50mm of box section with adjustable screw at bottom. Unit shall be compatable for the BMS system. Pre commissioning filter for testing and commissioning PAC unit mounting stand shall be MS coated and height shall be match to the raised floor height of the server room Noise level shall be 65dB( A) at 1.5 meter distance. Inside design condition - 22 deg. +/- 1 deg. C & Relative humidity 50% -/+ 5 % Chilled Water Inlet / Outlet Temperature - 6/14.5⁰C Dual Fluid Type (DX +CW ) PAC Unit with EC Motor with Fixed Scroll Compressor with Fan Section below False Floor with PIDV. (With Heater & Humidifer ) Cap. - 7.5 TR Bottom Discharge Airflow : 4500 CFM Ref : R407c supply Installation, Testing, Commissioning & Handling of units with Refrigerant Gas as per specification, data sheet and as directed by Engineer In Charge and as per approved make VERTIV / SCHNEIDER / DAIKIN
PAC UNITS Supply Installation Testing & Commisioning of Dual Fluid Type (DX + CW) Precision Air Conditioning Unit complete with Fixed Scroll Compressor, with Heater and Humidifer . Unit should be bottom discharge with Fan Section below False Floor with auto modulating PIDV valve. Refrigerant should be Eco-Friendly- R407c. Unit should have with Backward curved plug fan with direct driven EC Motor (Electronically Commutated) . Indoor unit shall be provided with all necessary accessories including unit base anti vibration mount etc.indoor unit frame shall be made up of 50mm of box section with adjustable screw at bottom. Unit shall be compatable for the BMS system. Pre commissioning filter for testing and commissioning PAC unit mounting stand shall be MS coated and height shall be match to the raised floor height of the server room Noise level shall be 65dB( A) at 1.5 meter distance. Inside design condition - 22 deg. +/- 1 deg. C & Relative humidity 50% -/+ 5 % Chilled Water Inlet / Outlet Temperature - 6/14.5⁰C Dual Fluid Type (DX +CW ) PAC Unit with EC Motor with Fixed Scroll Compressor with Fan Section below False Floor with PIDV. (With Heater & Humidifer ) Cap. - 6 TR Bottom Discharge Airflow : 3250 CFM Ref : R407c supply Installation, Testing, Commissioning & Handling of units with Refrigerant Gas as per specification, data sheet and as directed by Engineer In Charge and as per approved make : VERTIV / SCHNEIDER / DAIKIN
supply Installation, Testing, Commissioning with Refrigerant Gas . Refrigerant should be Eco-Friendly- R407c/R410a (For 6 TR & 7.5 TR) & VRV/VRF
Supply, installation and testing of Ø34.9 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø28.6 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø22.2 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø19.1 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø15.9 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø12.7 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø9.5 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
Supply, installation and testing of Ø6.4 mm- Refrigerant Piping consisting of copper tubes of wall thickness 20G inclusive of Suction Gas Piping & Fittings/Liquid Line Piping & Fittings, with class "O" nitrile rubber Insulation with finish as required. The piping to be mounted & supported properly with suitable size of clamp, M.S. hanger, tray etc., as required at site, The insulation shall be closed cell/cross linked elastomeric Nitrile rubber of thickness 13/19 mm. The insulation thickness upto 19.1 mm dia pipe shall be 13 mm and above 19.1 mm dia, the insulation thickness shall be 19 mm. Testing of refrigerant piping and procedure shall be done as per Manufacturer's recommendations, Makes:Totaline/Mandav/Mexico/Obo or its equivalent make as approved by the competent authority. Note: The rate is considered per pipe either Liquid or Suction only. Copper Pipe Make:Totaline/Mandav/Mexflow Insulation Make:ARMACELL,K-FLEX,AEROFOAM
GI 40mm Drain Piping with all fittings, accessories and required supports and with insulation of 25mm thick ( Nitrile rubber) Makes: GI Pipe: TATA / JINDAL STAR / JINDAL HISSAR; Insulation: ARMACELL / K-FLEX / AEROFOAM
GI 20mm Humidifier Piping with all necessary fittings and accessories and supports Makes: GI Pipe: TATA / JINDAL STAR / JINDAL HISSAR; Insulation: ARMACELL / K-FLEX / AEROFOAM
Supply air perforated Diffuser of 600 x 600 mm size and shall be provided with Volume control damper, aluminium construction . The construction of the grill shall be strudy to allow the movement of men and material over the grill. The sample shall be approved by consultants/ Architects/ clients before procurement. Make: AIRMASTER / SYSTEMAIR / TROX
Supply Installation Testing & Commisioning of Floor Insulation with 15 mm thick closed cell Nitrile rubber with Aluminium Foil and 2 coat of painting fixed to the floor with formaldehyde free adhesive and joints sealed with reinforce aluminium foil. Nitrile rubber shall be covered with thermal insulation protecting coating with alkali resistance glass fiber fabric of weight 200 gsm and 7 mil minimum thickness of reinforcement. the coating non volatile content shall be as per the gudeline of ASTM 1644-01. The coating flamability, surface burning charactoristics shall be as per ASTM E-84 and UL 723 Makes: ARMACELL / K-FLEX / AEROFOAM
Supply Installation Testing & Commisioningof Motorised fire and smoke Damper with motorized Actuator for PAC Unit. The damper shall be atleast 1.5 hr. The damper shall be UL 555 S, Class A certified. The damper shall be constructed out of 16G galvanised sheet steel it shall be complete with control panel , actuator sensors and inter loacking / wiring / connection for tripping of fan motor. The vendor should furnish the UL test certificate at the time of delivery and UL symbol should be there in all fire dampers.FIRE DAMPERS (UL 555/555S) Make: GREENHECK / AIRMASTER / SYSTEMAIR (DAMPER ACTUATORS Make: BELIMO / SIEMENS / HONEYWELL)
Supply, installation, testing and commissioning of Drain Pump Kit as per technical specificaition and as directed by Engineer in charge
Non Fire rated Sealant for non fire rated wall - Mastic compound sealant- Non fire rated wall shall be sealed with mastic compound sealant. Cutout opening shall have sleeve provision for duct annd pipes. opening, sleeve provision and closing of the opening shall be part of contracor's scope of work HILTI,FISCHER,3M
Fire Sealant- fire rated wall shall be with fire sealant . Fire sealant is intumescent sealant with mineral wool( make:HILTI / FISCHER / 3M
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 8 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 10 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 12 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 14HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 16 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 18 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 20 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 22 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
AIR COOLED VRV/VRF DX UNITS ( Stand By System for Critical Areas) Supply, installation, commissioning & testing of aircooled DX type VRV/VRF Condensing Unit for Heating and Cooling ( Vendor /OEM to be consider as per site weather condition ) with all accessories and consisting of: a) Inverter type Compressor (min two), condenser, fans , microprocesserbased inbuilt control unit etc., b) Necessary vibration isolators c) Painting of supports and pipes d) Pressure testing. e) Making openings in walls and Closing with necessary 'Civil Work finishing with suitable 2hr FR fire seal (HILTI / FISCHER / 3M) (need to necessarily included here). f) With necessary mounting steel structure, all accessories, anti corrosive painting, final finish painting, bolts, nuts, foundation bolts, civil foundation, anti vibration mounting pads,springs etc., and if any additional item required to cover the installtion of ODU to be included. g) Condenser, Noiseless fans, evaporator, Electronic Expansion Valve (EEV) etc., h) Microprocessor based control panel i) Central controller for remote on/off, status screen etc., j) Eco-friendly and IGBC approved Refrigerant to be used. k) suitable for mainly cooling and secondarily heating too when necessary. l) all wiring shall be FRLS m) refrigerants pipe & nitrile rubber insulation(class O) only to be on perforated powder coated MS cable trays both at bottom and removable cover laid in trench or in open as required. n) NC level not more than 60 db from 1 m from source o)First fill refrigerant gas charge (till handover to the client) for the given area including all required material, laboure etc., Note :Number of refrigerant piping circuit in between indoor and outdoor units are as per OEM. Contractor has to consider the circuit as per OEM and quote accordingly. Client will not pay any extra amount as per circuit. 24 HP as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes as per specification, and as directed by Engineer In Charge . Fan Coil Unit -1.3 TR (470 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes Fan Coil Unit -1.6 TR (470 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes Fan Coil Unit -2.0 TR (700 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes Fan Coil Unit -2.2 TR (700 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes Fan Coil Unit -2.6 TR (740 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
VRV INDOOR UNITS Supply, installation, commissioning & testing of VRV/VRF Indoor Unit including all accessories with vibration isolators & supporting frame work or stands finished with epoxy paint etc.,complete as required as per site. following and suitable for cooling :- All The Indoors should have drain pump except Highwall Units, low height FCU and Hidh Static Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes b) Indoor units of types mentioned below complete with cordless remote controller,Unit that are suspended should be installed using resilient hangers to prevent structure borne noise. FCU and Ductable should be with Corded remote. Cassette and Highwalls with Cordless Remotes Fan Coil Unit -3.2 TR (1130 cfm) as per specification, and as directed by Engineer In Charge and as per approved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
Supply and Installation of Ref Nets for Double ODU connections in Pair (Gas & Liquid) as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
Supply and Installation of Ref Nets for Triple ODU connections as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
Supply and Installation of Multi Connection Joint / Ref Nets for IDUs as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved make. Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
SITC of Interface adaptor for Bacnet including required cabling The HVAC Contractor should select the Interface adaptor for BACnet Gateway capable of controlling and monitoring 128 Indoor Units and 20 VRV Systems. Refer Monitor and Control Points as per list. Capable to monitor and control the parameters like ON/OFF Status, Error Code, Operation Mode (Status/setting), Airflow (status/setting),Setpoint, Measured Room Temperature, Filter Limit Sign, Air direction (Status/setting), etc… as required & as directed by complete etc. as required & as directed by Engineer In Charge and as per aproved Make-MITSUBISHI Electric / O GENERAL / LG / DAIKIN)
Supply of Advanced Oxidation PentagonPlasma (AOP) cells comprising of UVC lamp 254 NM on NANO metallic compound target Alumninum matrix cell duly enclosed by a poly casing tube, with the capability to produce plasma Hydroxyl oxidizers. The unit shall have inbuilt multipin Bi polar ion generator pins along with ultrasonic radio frequency waves for pest repellancy. The UV-C lamp will be a low-pressure mercury type and of such intensity as to provide minimum performance as listed below. The UV-C lamp will produce only Germicidal UV (by definition this means 99.99% UV-C energy). The life of the lamp shall be atleast 18000 hours. The cell will have built in LED indication system stating the operation of the 3 technologies the UV lamp, ionizer and pest repellant.The wattage of the lamp shall not be less than 21 watts upto 6500 CFM ,36 watts upto 20000 CFM and a minimum of 48 watts upto 28000 CFM or combination based on the application area. The system shall be capable of reducing microbial bacteria, virus and spores , VoC’, odors and particulates matter. The equipment shall have to GREENPRO,TUV,CE, ISO 13485, ROHS with 2014/35/EU Low Voltage Directive along with FDA compliance certifications. The AOP cell shall a microbiological testing report against Bacteriophage (MS-2 FDA) surrogate SARS Cov-2 with a minimum efficiency of 99 percent along with a Virology report from CCMB lab with an minimum efficiency of 99 percent against SARS COV2 within 45 minutes. The power / control cabling between the AOP cell and the power source / controls shall be included in the cost .The system shall be capable of reducing microbial bacteria, virus and spores, VoC’s, odors and particulate matter. The Pentagon cells should be selected by considering a load factor calculation for each specific area where the equipment is to be installed. Detailed selection chart to be furnished indicating the model number for each unit. Cells Should be complete with Transformers, control cabling and Plug Top & necessary power cable. Vendor to comply all Tender Specifications.The AOP cell should be mounted within the AHU or at supply air duct/plenum. CFM - UPTO 2000 as per specification, and as directed by Engineer In Charge . UV LAMP: NUTECH,ULTRAPURE,AQUA AIR
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - TERTIARY CHILLED WATER PUMP PANEL INCOMERS: 1 No. 800A 50kA 4P ACB WITH LSING PROTECTION. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 800A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 5 No.MCCB SUITABLE FOR 90KW MOTOR WITH VFD STARTER with 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 2 Nos MCCB SUITABLE FOR 90KW MOTOR WITHOUT VFD 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON; Contactors: SCHNEIDER / ABB / LAURITZ KNUDSEN; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-1 AHU PANEL-1 INCOMERS: 1 No. 400A 50kA TPN MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 400A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 18.5 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,5 Nos MPCB SUITABLE FOR 15KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 11KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 9.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,10 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,10 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-2 AHU PANEL-1 INCOMERS: 1 No. 400A 50kA TPN MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 400A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,7 Nos MPCB SUITABLE FOR 15KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 11KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,3 Nos MPCB SUITABLE FOR 9.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,7 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,6 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-3 AHU PANEL-1 INCOMERS: 1 No. 400A 50kA TPN MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 400A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,6 Nos MPCB SUITABLE FOR 15KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,5 Nos MPCB SUITABLE FOR 11KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 9.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,7 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,4 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-4 AHU PANEL-1 INCOMERS: 1 No. 400A 50kA TPN MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 400A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 18.5 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,6 Nos MPCB SUITABLE FOR 15KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 11KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 9.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,7 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,4 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-1 AHU PANEL-2 INCOMERS: 1 No. 250A 50kA FP MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22.5 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 No. MPCB SUITABLE FOR 22KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,10 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 Nos MPCB SUITABLE FOR 3.7KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,10 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-2 AHU PANEL-2 INCOMERS: 1 No. 200A 50kA FP MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 200A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,13 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,10 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 12 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-3 AHU PANEL-2 INCOMERS: 1 No. 200A 50kA FP MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 200A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,9 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,7 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 10 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-4 AHU PANEL-2 INCOMERS: 1 No. 250A 50kA FP MCCB. , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 22 KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 8KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 Nos MPCB SUITABLE FOR 7.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,11 Nos MPCB SUITABLE FOR 5.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,2 Nos MPCB SUITABLE FOR 4KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 Nos MPCB SUITABLE FOR 3.7KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,8 Nos MPCB SUITABLE FOR 2.2KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 11 Nos MPCB SUITABLE FOR 1.5KW MOTOR 1 set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-1 PRESS.I FAN & SMOKE EXTRACTION FAN PANEL(FIRE MODE) INCOMERS: 1 No. 1250A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 1250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 2 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,8 No MPCB SUITABLE FOR 22.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 4 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 10 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,4 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,2 No MPCB SUITABLE FOR 3.7 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 4 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 8No MPCB SUITABLE FOR1.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2No MPCB SUITABLE FOR0.37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-2 PRESS.I FAN & SMOKE EXTRACTION FAN PANEL(FIRE MODE) INCOMERS: 1 No. 1250A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 1250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 2 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,8 No MPCB SUITABLE FOR 22.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 10 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 10 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,5 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 4No MPCB SUITABLE FOR1.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2No MPCB SUITABLE FOR0.37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-3 PRESS.I FAN & SMOKE EXTRACTION FAN PANEL(FIRE MODE) INCOMERS: 1 No. 630A 35kA TPN MCCB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 2 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 4 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 11 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,4 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 4No MPCB SUITABLE FOR1.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2No MPCB SUITABLE FOR0.37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-4 PRESS.I FAN & SMOKE EXTRACTION FAN PANEL(FIRE MODE) INCOMERS: 1 No. 630A 50kA TPN MCCB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 2 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 4 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 11 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,4 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 4No MPCB SUITABLE FOR1.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2No MPCB SUITABLE FOR0.37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-1 Ventilation Panel INCOMERS: 1 No. 630A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 1 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 8 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 12 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,4 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 No MPCB SUITABLE FOR 9.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,3 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,6 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,2 No MPCB SUITABLE FOR 3.7 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 2 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-2 Ventilation Panel INCOMERS: 1 No. 630A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 20 No MPCB SUITABLE FOR 18.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 2 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,6 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,1 No MPCB SUITABLE FOR 3.7 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 6 No MPCB SUITABLE FOR 2.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 4No MPCB SUITABLE FOR 1.1 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 -BLOCK-3 Ventilation Panel INCOMERS: 1 No. 630A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 4 No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 6 No MPCB SUITABLE FOR 19 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 7 No MPCB SUITABLE FOR 15 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, 5 No MPCB SUITABLE FOR 9.2 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,3 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port,9 No MPCB SUITABLE FOR 5.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-4 Ventilation Panel INCOMERS: 1 No. 1250A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 1250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 19No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 13 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - SUBSTATION VENTILATION PANEL INCOMERS: 1 No. 1250A 50kA TPN EDO ACB , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , Bus bar: 1 set - 1250A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. OUTGOING: 19No.MPCB SUITABLE FOR 37 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 4 No MPCB SUITABLE FOR 11 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port , 1 No MPCB SUITABLE FOR 9.3 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port ,1 No MPCB SUITABLE FOR 7.5 KW MOTOR 1set - RYB LED type indicating lamps,1 No. KWH meter (KWH+KW) with RS - 485 port, as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of Local control panel for AHU with 16A FP MCB Isolator, VFD suitable for 1.5KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 16A FP MCB Isolator, VFD suitable for 2.2KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 32A TPN MCB Isolator, VFD suitable for 3.7KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 32A TPN MCB Isolator, VFD suitable for 5.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 32A TPN MCB Isolator, VFD suitable for 7.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 63A TPN MCB Isolator, VFD suitable for 9.3KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 63A TPN MCB Isolator, VFD suitable for 11KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 63A TPN MCB Isolator, VFD suitable for 15KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 63A TPN MCB Isolator, VFD suitable for 18.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 100A TPN MCB Isolator, VFD suitable for 22.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for AHU with 16A FP MCB Isolator, DOL starter suitable for 2.2KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for AHU with 32 FP MCB Isolator, DOL starter suitable for 5.5KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for AHU with 63 FP MCB Isolator, star delta starter suitable for 5.5KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of 100A FP MCCB Isolator suitable for 45KW motor (for PAC) (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of 63A FP MCCB Isolator suitable for 22KW motor (for PAC) (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, VFD suitable for 1.1KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, VFD suitable for 1.5KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, VFD suitable for 2.2KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, VFD suitable for 3.7KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, VFD suitable for 5.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, VFD suitable for 7.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, VFD suitable for 9.3KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, VFD suitable for 11KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, VFD suitable for 15KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, VFD suitable for 18.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; VFD: DANFOSS / ABB / HONEYWELL
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, DOL suitable for 1.1KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per aproved make. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, DOL suitable for 1.5KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per aproved make. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 16A FP MCB Isolator, DOL suitable for 2.2KW motor (IP-52) with powder coated MS enclosure with all necessary accessories required to complete the job as per specification including structural supports and as per specification,as required & as directed by Engineer In Charge and as per aproved make. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, DOL suitable for 3.7KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, DOL suitable for 5.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support. and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; DOL Starter (Contactor): SCHNEIDER / ABB / LAURITZ KNUDSEN
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 32A TPN MCB Isolator, star delta starter suitable for 7.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, star delta starter suitable for 9.3KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, star delta starter suitable for 11KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, star delta starter suitable for 15KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 63A TPN MCB Isolator, star delta starter suitable for 18.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 100A TPN MCB Isolator, star delta starter suitable for 30KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, installation, testing & commissioning of Local control panel for Vent. Fan with 100A TPN MCB Isolator, star delta starter suitable for 37.5KW motor (IP-52), with powder coated MS enclosure with all necessary accessories required to complete the job including structural support supports and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC Works. Makes: MCB Isolator: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+
Supply, laying and dressing, terimation & testing of 3.5Core 70Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing terimation & testing of 3.5Core 50Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3.5Core 35Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-POLYCAB / RR KABEL / KEI / HAVELLS
Supply, laying and dressing, terimation & testing of 4Core 16Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 4Core 10Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 4Core 6Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 2.5Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 4Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 6Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 10Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 16Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing , terimation & testing of 3Core 35Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, terimation & testing of 3Core 70Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3.5Core 70Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3.5Core 50Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3.5Core 35Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3.5Core 25Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 4Core 16Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 4Core 10Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 4Core 6Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 4Core 4Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3Core 25Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3Core 16Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3Core 10Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3Core 6Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply, laying and dressing, termination & testing of 3Core 4Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-KEI, HAVELLS, POLYCAB, RR KABEL
Supply & making of Cable end termination of the 3.5Core 70Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3C/3.5Core 50Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3C/3.5Core 35Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3.5Core 25Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 4Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 4Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 4Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 4Core 4Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 4Core 2.5Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & making of Cable end termination of the 3Core 4Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: REYCHEM / 3M / DENSONS
Supply & laying of 25X6 mm G.I. earthing strips for panels, AHuS, FANS, PUMPS, starter panels etc. along with Fixing accessories and as per specification,as required & as directed by Engineer In Charge and as per aproved make for HVAC works Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & laying of 8 SWG CU WIRE earthing strips for panels, AHuS, FANS, PUMPS, starter panels etc. along with Fixing accessories and as per specification,as required & as directed by Engineer In Charge and as per aproved make as per aproved make for HVAC works Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply,transporatation & installation of 300mm x 62.5mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 450mm x 62.5mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 750mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 900mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make PROFAB / APARNA ROLLFORM / GLOMETALPARNA ROLLFORM
Supply,transporatation & installation of 450mm x 50mm x 2.0mm of Hot Dipped Galvanized Iron Ladder Type cable trays with rungs at span of 250 mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with suspenders and etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 600mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron Ladder Type cable trays with rungs at span of 250 mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with suspenders and etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 750mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron Ladder Type cable trays with rungs at span of 250 mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with suspenders and etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-PROFAB / APARNA ROLLFORM / GLOMETAL
Supply,transporatation & installation of 900mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron Ladder Type cable trays with rungs at span of 250 mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with suspenders and etc., complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Make-PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, Installation, Testing and Commissioning of Indoor/outdoor as per site requirment floor mounted metal clad, 33 KV 800A VCB Panel with 1 Nos. VCBs suitable for 50Hz 3-phase system, suitable for 31.5kA/3sec short circuit withstand capacity & 31.5kA/1sec Internal Arc capacity . Switchgear Panel enclosure of sheet steel (preferably Aluzinc), dust tight, vermin proof, totally enclosed cubicle floor mounting, free standing type with single break, horizontally drawout type breaker with trip free mechanism as per latest standard i.e. IS/IEC 62271-200 as amended up to date and as per Technical specifications, IP4X for indoor VCB Panel & IP55 for outdoor VCB as applicable and with Type tested enclosure. Switchgear Panel shall be electrically & mechanically interlocked as per IEC 62271-1, full voltage insulated copper Busbar with heat shrinkable sleeving, complete with suitable metering & protection devices, breaker featured with mechanical ON-OFF indicator with hand trip device and all accessories such as shunt trip coil, motorized & manually operated spring charging mechanism, emergency trip push buttons, auxiliary switch of 2NO + 2NC, interconnections, space heaters, panel earthing etc. and equipped with following switchgear and accessories including connection suitable for 3x400sqmm XLPE 33kV cable (cable entry from bottom) to be connected through heat shrinkable jointing material etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make.All Bi-Directional multifunction meters true rms value sensing type with RS485 ports for communication in Modbus; power / energy meters (of accuracy class 0.2) for down loading data to PC. supply voltage monitoring relay for monitoring and control incoming 33KV supply with trip & alarm contacts with adjustable high & low value limits for voltage & frequency complete with suitable port for downloading historical data to PC. All VCBs with communicable protection relays with ports wired out and with 4NO + 4NC integral aux. contact plus cradle aux. contact wired out for monitoring of each type of fault trip, OPEN / CLOSE / CRADLE POSITION & relay trip settings from PC. All VCBs complete with T/N/C switches, lamp indications, shunt trip healthy check lamps, trfo. fault annunciators & hooter etc. each VCB panel comprising the following: ICOG- Nos. 800 Amp. VCB. 31.5KA, 3 Nos of dual core CT’s of 150/5 amp, 0.2S class 15 VA Burden , PT’s of 33 KV / √3 to 110 V / √3 , 50 VA or as per the arrived load demand & selected transformer and rating as directed by CPDCL or Engineer-In Charge for metering and class 5P10 for protection, 3 No. Cast Resin 33000V/v3/110V/v3/110V/v3 PT Class 0.2/3P accuracy and 30VA burden max with and protection fuses / MCB. 1 No. Digital voltmeter with selector switch, 1 No. Digital Ammeter with selector switch, 1 No. Microprocessor based numerical relays with O/L, E/F and S/C protection with Integrated Arc sensing feature alongwith trip/lockout / antipumping / aux. relays.1 No. Bi Directional multi function meter, Set of MCBs for Panel AC/DC, Set of MCBs for Main AC/DC,Set of Indication lamps LED types,TNC Switch, L-R Switch, Pushbuttons for ON-OFF,1 set of Mechanical & Electrical interlocking set Incomer Surge Protection Device (SPD) required, 1 set of earthing trunck,1 trolley for each 4 VCB as a Complementary,1 No. DC self power pack suitable for 3 trips with 110V output, complete etc for control circuit. as directed by Eingineer In Charge and as per aproved make. Note: The contractor or OEM is completely held responsible for replacing of spares or any required consumables during defects liability period as per detailed in technical specifications..33 KV HT PANEL (In addition to the above requirement the panel should be as per detailed technical specifications / Andhra Pradesh Central Power Distribution Company Limited). Makes:SCHNEIDER / ABB / SIEMENS)
Supply, installation, testing and commissioning of Indoor/outdoor as per site requirment floor mounted, dust, damp and vermin proof, cubicle, H. T. Metering Panel made out of 2 mm thick CRCA sheet steel complete with electronic trivector meter,CT’s of 150/5 amp, 0.2S class 15 VA Burden , PT’s of 33 KV / √3 to 110 V / √3 , 50 VA or as per the arrived load demand & selected transformer and rating as directed by CPDCL or Engineer-In Charge , conforming to relevant IS standard and complete as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make. CT’s, PT’s and trivector meter shall be got tested and approved from local electricity supply authority.The GA drawing also shall be got approved from State DISCOM authorities before fabrication.The unit shall have provision for sealing and Acrylic window shall be provided to facilitate meter reading. Supply & fixing of HT Meter Mounting Box as required as per APCPDCL Dept Norms with sealing arrangement, box sizing, window, TB, to accomidate HT Meter as per APCPDCL norms and HT meter specification, CT and PT ratio etc shall also be as per APCPDCL standards and requirements.33 KV APCPDCL /APSEB Metering Cubicle - Indoor Type (In addition to the above requirement the panel should be as per detailed technical specifications / Andhra Pradesh Central Power Distribution Company Limited). ( Makes- SCHNEIDER / ABB / SIEMENS)
Supply, Installation, Testing and Commissioning of total type tested Indoor type floor mounted metal clad, 33 KV 800A VCB Panel with 9 Nos. VCBs (2 INCOMERS + 1 BUS COUPLER + BUS RAISER+ 6 OUTGOINGS) suitable for 50Hz 3-phase system, suitable for 31.5kA/3sec short circuit withstand capacity & 31.5kA/1sec Internal Arc tested for all compartments. Switchgear Panel enclosure of sheet steel preferably Aluzinc, dust tight, vermin proof, totally enclosed cubicle floor mounting, free standing type with single break, horizontally drawout type breaker with trip free mechanism as per latest standard i.e. IS/IEC 62271-200 as amended up to date and as per Technical specifications, IP4X for VCB Panel & IP55 with Type tested enclosure. Switchgear Panel shall be electrically & mechanically interlocked as per IEC 62271-1 with OEM only, full voltage insulated copper Busbar with heat shrinkable sleeving, complete with suitable metering & protection devices, breaker featured with mechanical ON-OFF indicator with hand trip device and all accessories such as shunt trip coil, motorized & manually operated spring charging mechanism, emergency trip push buttons, auxiliary switch of 2NO + 2NC, interconnections, space heaters, panel earthing etc. and equipped with following switchgear and accessories including connection suitable for 3Cx400sqmm XLPE 33kV cable (cable entry from bottom) to be connected through heat shrinkable jointing material etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make. "All multifunction meters true rms value sensing type with RS485 ports for communication in Modbus; power / energy meters (of accuracy class 0.5) for down loading data to PC. Provision of supply voltage monitoring relay for monitoring and control incoming 33KV supply with trip & alarm contacts with adjustable high & low value limits for voltage & frequency complete with suitable port for downloading historical data to PC. All VCBs with communicable protection relays with ports wired out and with 4NO + 4NC integral aux. contact plus cradle aux. contact wired out for monitoring of each type of fault trip, OPEN / CLOSE / CRADLE POSITION & relay trip settings from PC. All VCBs complete with T/N/C switches, lamp indications, shunt trip healthy check lamps, trfo. fault annunciators & hooter etc.INCOMER : 2 Nos. each comprising the following, 1 No. 800 Amp. VCB. 31.5KA, 1 No. Integral Earth switch for line side earthing, 3 Nos of dual core CT’s of 150/5 amp, 0.2S class 15 VA Burden , PT’s of 33 KV / √3 to 110 V / √3 , 50 VA or as per the arrived load demand & selected transformer and rating as directed by CPDCL or Engineer-In Charge with and protection fuses / MCB,1 No. Digital voltmeter with selector switch,1 No. Digital Ammeter with selector switch.1 No. Microprocessor based numerical relays with O/L, E/F and S/C protection with Integrated Arc sensing feature alongwith trip/lockout / antipumping / aux. relays, 1 No. Multi-function meter, Set of MCBs for Panel AC/DC, Set of MCBs for Main AC/DC, Set of Indication lamps LED types,TNC Switch, L-R Switch, Pushbuttons for ON-OFF,1 set of Mechanical & Electrical interlocking set,Incomer Surge Protection Device (SPD) required,1 No. DC self power pack suitable for 3 trips with 110V output, BUS PT : BUS PT shall be 33KV/v3/110V/v3 for class 0.5 metering & CI-3P for protection 20VA burden each. The HT fuses of BUS PT shall be completely enclosed in epoxy housing. BUS COUPLER,1 No. 800 Amp. VCB. 31.5 KA as Bus coupler with protection as required, OUT GOING - 6 Nos each comprising the following:1 No. 800 Amp. VCB. 31.5KA,1 No. Integral Earth switch for line side earthing, 3 No.of Dual core CT’s of 150/5 amp, 0.2S class 15 VA Burden , PT’s of 33 KV / √3 to 110 V / √3 , 50 VA or as per the arrived load demand & selected transformer and rating as directed by CPDCL or Engineer-In Charge with and protection fuses / MCB,1 No. Digital voltmeter with selector switch,1 No. Digital Ammeter with selector switch,1 No. Microprocessor based numerical relays with O/L, E/F and S/C protection with Integrated Arc sensing feature alongwith trip/lockout / antipumping / aux. relays,1 No. Multi-function meter,Set of MCBs for Panel AC/DC,Set of MCBs for Main AC/DC,Set of Indication lamps LED types,TNC Switch, L-R Switch, Pushbuttons for ON-OFF,1 set of Mechanical & Electrical interlocking set,Incomer Surge Protection Device (SPD) required,1 No. DC self power pack suitable for 3 trips with 110V output, The instrument and relay panel fitted with,1 – Triple pole numerical I.D.M.T. over current & earth fault relay with two outer elements connected for over current the middle element for earth fault protection over current setting 50% - 200% Earth fault setting 20% - 80% and with instantaneous element on all 3 pole settings 500-2000% on over current and 200-800% on earth fault (50, 50 N & 51, 51N),1 – Master trip relay (86),1 – Trip circuit Supervision relay.(95),1 – Anti pumping relay (94),1 – Set of auxiliary relay for transformer fault ALARM for winding temperature,1 – no. circuit breaker control switch for electrical (T/N/C), 1 – Set of red / green indicating lamps for close and open position with MCB,1 – Amber indicting lamp for auto trip with MCB,1 – clear indicating lamp for trip circuit healthy with MCB,1 – 1 set of white indicating lamps one per phase with MCB,1 – Blue indicating lamp for spring charged with MCB,12 window annunciation panel,1 – Push button on front door for emergency trip,1 – Cable termination suitable for cable joint to receive 33 KV 3 core 400 sq.mm XLPE cable,REF relay protection and its associated works,1 set of earthing trunk,1 trolley for 4 VCB's as a Complementary,. complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Approved makes - SCHNEIDER / ABB / SIEMENS)
Supply,Installation, testing and commissioning of 3C X 400 Sq.mm. (E) XLPE HT cable insulated IS:7098/II/85 H.T.cable for working voltage 33 K.V.Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semiconducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanised flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable with cable route markers to be provided for every 20 mtrs etc complete as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make. complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make: KEI / RR KABEL / POLYCAB / HAVELLS)
Supply and Making heat shrinkable type indoor terminations kit of approved make suitable for XLPE insulated 33 KV cable, with required components, preparation of cable ends, testing etc. as required of 33KV,3C X 400 Sq.mm. (E) XLPE HT cable as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: REYCHEM, 3M, DENSONS)
Supply and Making heat shrinkable type outdoor type terminations of approved make suitable for XLPE insulated 33 KV cable, with required components, prepration of cable ends, testing etc. as required of 3C x 400 Sqmm (E) XLPE HT Cable size. Makes: REYCHEM, 3M, DENSONS)
Supply and Making heat shrinkable type Straight Through Joint kit of approved make suitable for XLPE insulated 33 KV cable, with required components, prepration of cable ends, testing etc. as required of 3C x 400 Sqmm (E) XLPE HT Cable size. Makes: REYCHEM, 3M, DENSONS)
Supply of Rubber hand gloves suitable for 33KV HT complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: Vidyut,Jyot, Crystal,Kavachh
Supply and Installation of Shock treatment chart both in Regional Language & English and framed with 5mm thick glass as required, complete with A1 size complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.
Supply and Installation of 33000V danger notice plate of 250 mm x 200mm, made of mild steel sheet of at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.
Supply and Installation of 415V danger notice plate of 200 mm x 150mm, made of mild steel sheet of at least 2mm thick & vitreous enamelled white on both sides and with inscription in signal red colour on front side as required complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.
Supply and Installation of PVC synthetic elastomer electrically insulated mat confirming to IS: 15652-2006 with Class C insulation having 3mm thickness upto 33KV
Supply and Installation of of 3.3kV class-A approved tested quality rubber mat of 2 mm thick and 2mtr x 1mtr, installed in front of the panels.Back side also if required. The items shall be as per Safety standard & supplied as per plant Safety Engineer instructions. Fixing of support for safety equipment shall be included in rate quoted.
Supply and Installation of Single Line Diagram on 5mm thick Aluminium sheet in A0 Size duly laminated.
Supply and Installation of Single Line Diagram on 5mm thick Aluminium sheet in A1 Size duly laminated.
Supply & fixing of First Aid box 18" x 12" x 8"
Supply ,Transportation of cast Resin (Dry Type) indoor type copper double wound2000kva 33KV/0.433 KV, Three Phase 50 Hz Transformers designed and manufactured as per IS 11171/IEC 60726 , ANSI and NEMA Standards with all standard fittings, connected Delta on Primary side and Star on Secondary side with additional neutral brought out on load side 33000/433V with HV ON load Tap changer (OLTC) with RTCC etc tap changing +5% to -15% temperature rise by the resistance 90 degrees with terminal arrangement Cable box on HV side and Bus duct on LV Side with off circuit Tap links etc.,, complete Makes: ( Make: SIEMENS / ABB / SCHNEIDER / VOLTAMP)
Design, Approval & Supply Installation Testing And commissioning of Aviation Lighting system in compliance with ICAO (International Civil Aviation Organisation) Norms prescribe Aviation Obstruction Lighting for any structure above 45metres in height, to be considered along with Local Aviation Dept applicable rule through Airports Authority of India to be considered) with the following but not limited to, Supply, installation, testing & commissiong of MEDIUM INTENSITY AVIATION WARNING LIGHT Medium Intensity LED based Aviation Warning Light, Type-‘A’, conforming to ICAO regulation, flashing white light for Night time use only for intensity 2,000 CD ± 25% , Cast Aluminum Body, for omni directional usage Horizontal 360 ˚, Vertical 3˚. Control Panel for operating above light, having following features: Potential free contact for lamp failure indication Input output surge protection Dusk-dawn operation will be controlled by photocell, IP 65 Weather protection. Max. Power -35W, Lens Material- Borosilicate glass, Burning Life -100000 hrs, weather RF suppresion Operational voltage: 230V AC, 50 Hz complete etc. as required & as directed by complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make- PHILIPS&HUGHEY / ORGA AVIATION / PYROTECH)
Supply Installation Testing And commissioning of Aviation light Control Panel for operating the above MI light having following features:-- i)Aviation Lighting control Panels DB with all necessary components (relays, push buttons, LV power sources units, electronics, photo sensors, MCBs, ELMCBs, Timers, Alarms etc.,) for integration, as below ii) with input & out put surge protection iii) potential free contact for lamp failure indication iv)photo cell for automatic dust to dawn operation for lamp v)wheather protection IP65 vi) operational voltage 230 V, AC 50hz vii) control and power cabling viii) complete automation and status indication and integration with the SCADA/BMS system IF REQUIRED ix) all Hot dip gavanised steel supports, angles etc., x) Liaise and obtain all necessary approval from Aviation Dept and AAI and other relevant authorities as and when required. xi) the entire system shall be maintenance free for a min period of 20 years including the LED flash lights xii) necessary structure with approved color painting and coding as per AAI and Aviation dept. Make- PHILIPS&HUGHEY / ORGA AVIATION / PYROTECH)
Supply Installation Testing And commissioning of 2000 kVA at 0.8 pf 415V 50Hz 3-Ø Prime rated DG Set as per latest CPCB norms complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled. Alternator: It shall be self regulated, self excited and confirms to IS: 13364/1992 or latest version with regulation of +5% from No load to full load, IP23, with standard Alternator Protection( Over voltage, over speed & under voltage). Diesel Engine: It shall have residential silencer, up to 10 M exhaust piping , electronic / Mechanical governor, Manual & electric Start, Batteries,battery charger , control panel (16 G) with MCCB/ACB (4P; 25/36/50 KA) with PLC based Engine controller supplied by OEM,, Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engine instruments panel and AVM, Controller should be microprocessor based with auto sync, load sharing and AMF logic, Including first oil & fuel fill. The diesel engine shall be capable of providing 10% over load for 1 Hr for every 12 Hrs of continuious running at full load. The DG set shall be supplied with initial filling of fuel, lube oil, coolant oil as per OEM specifications and shall be tested at site. Noise level should meet as per latest NBC norms. DG shall be have Energy metering. All insulations used shall be free of CFC and HCFCs.) complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.Engine Makes: CATERPILLAR, PERKINS, CUMMINS Alternator Make:LEROY-SOMER, STAMFORD Battery Make: EXIDE / AMARA RAJA BATTERIES
Supply, Installation, testing and commissioning of Isolator Panel with 1 x 3200A, FP ACB EDO Breaker with RYB, On, OFF, TRIP, Test, Service etc indicating lamps as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; LED Indicating Lamps: TEKNIC / SALZER / LK
Supply installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 4B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 as per final approved makes - DG Synchronizing Panel-1 & 2 DG Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSING) protection , 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 set - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link . DG Synchronising relay for synchronising of two DGs. DG Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V(LSING) , 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link. DG Synchronising relay for synchronising of two DGs. Bus Coupler : 1 No. - 6300A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V , 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link. Bus bar: 1 set - 6300A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. Outgoings: 5 Nos 3200A TPN 50KA ACB with O/C, S/C, E/F & U/V (LSING) protection , 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port. And as per drg no. SL-291-EL0-050. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved . Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, Installation, testing and commissioning of 1m x 1m acoustic panel for wall treatment made out of 100 mm thick rock wool with 64 kg/cm2 density, 22 SWG perforated GI sheet, chicken mesh & tissue on th rear complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make
Supply, Installation, testing and commissioning of 1m x 1m acoustic panel for ceiling treatment made out of 100 mm thick rock wool with 64 kg/cm2 density, 22 SWG perforated GI sheet, chicken mesh & tissue on th rear complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.
Supply, Installation of MS supports (including anchor fasterners & painting) for Hitech spring support for Silencer work complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make.. MAKE: SAIL,JINDAL,VIZAG
Supply, Installation, testing and commissioning of Acoustic double door of size 2.4 m height & 2 m wide including MS frame work complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required & as directed by Engineer In Charge and as per aproved make.
Supply, Installation, testing and commissioning of Acoustic single door of size 2.4 m height & 1.2 m wide including MS frame work complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make complete etc. as required & as directed by Engineer In Charge and as per aproved make.
Supply, Installation, testing and commissioning of of Hot air attenuators of size 1m dept x 1m long x 100 mm thick made out of 100 mm thick rock wool with 64 kg/cm2 density, 22 SWG perforated GI sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .
Supply, Installation, testing and commissioning of Fins/Rain louvers on Fresh air side made of 18 SWG MS sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications.
Supply, Installation and commissioning of Hot air ducting from radiator till Hot air attenuator area with 18 SWG GI sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .
Supply, Installation, testing and commissioning of Canvas cloth between radiator & ducting (for filling a maximum gap of 100 - 200 mm) complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .
Supply, Installation, testing and commissioning of MS supports (including anchor fasterners & painting) for Hot air ducting work complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .( Make: SAIL,JINDAL,VIZAG)
Supply, Installation, testing and commissioning of 250 mm dia 5 mm thick MS ERW Class B Exhaust pipe with accessories complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make. Makes: TATA / JINDAL / HISSAR/JINDAL STAR
Supply, Installation, testing and commissioning of Thermal insulation for 250 mm dia pipe with 50mm thick insulation of Mineral wool of 48 Kg. Cu.m density & covered with 24SWG Aluminium sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make( Make: JINDAL, HINDALCO, BALCO)
Supply, Installation, testing and commissioning of 450 mm dia 5 mm thick MS ERW Class B Exhaust pipe with accessories complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make.( Make: TATA / JINDAL / HISSAR/JINDAL STAR)
Supply, Installation, testing and commissioning of Thermal insulation for 450 mm dia pipe with 50mm thick insulation of Mineral wool of 48 Kg. Cu.m density & covered with 24SWG Aluminium sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make.( Make: JINDAL, HINDALCO, BALCO)
Supply, fabrication and installation of supports for silencer/ exhaust pipe, etc., made out of MS channels/angles including cutting, welding and fabrication to the required size and painting with one coats of primer and two coats of enamel paint complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .(each DG set exhaust pipe support is 6mtr in height)( Make: SAIL / JINDAL / VIZAG)
Supply, fabrication and installation of 6 meters/30mtr height exhaust stack structure made out of MS channels/angles including cutting, welding and fabrication to the required size and painting with one coats of primer and two coats of Aluminium paint. Including Lightning arrestor and aviation lamp complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications . Make: SAIL,JINDAL,VIZAG
Supply, Installation, testing & commissioning of 990 ltr day tank made out of 2 mm thick MS sheet complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications .
Supply, Installation, testing & commissioning of magnetic level switch with High & Low level provision complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Make-ABB, Honeywell, Siemens, Danfoss, Schneider Electric
Supply, Installation, testing & commissioning 40 mm dia MS fuel pipe with accessories, 1 coat of primer & 2 coats of enamel paint complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make. Makes: TATA / JINDAL / HISSAR/JINDAL STAR
Supply, Installation, testing & commissioning of 40 mm dia flanged end ball valve complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved make( Make: ZOLOTO / SANT / AUDCO
Supply & installation of steel support for mounting of day tanks and supports for fuel piping with accessories complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications. MAKE: SAIL / JINDAL / VIZAG
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 4B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. PCC-1 EB Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - Neutral CT & Restricted Earth fault protection Relay, 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 set - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. EB Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link,1 set - Neutral CT & Restricted Earth fault protection Relay,1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port ,1 set - 3200A ,15VA, CL 0.5, CT's for metering,1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link. 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec, EB Incomer: 3 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link,1 set - Neutral CT & Restricted Earth fault protection Relay,1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. Bus coupler: 2No. - 3200A 50KA FP EDO ACB Motorised (MP based release) . Bus bar: 5 set - 3200A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports with 5 sets of Surge protection device SPD 1+2. Outgoings: 1 Nos 3200A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 5 Nos 2500A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2500A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 4 Nos 2000A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 3 Nos 250A TPN 50KA MCCB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 1 Nos 100A TPN 50KA MCCB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 100A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. complete etc. as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 4B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. PCC-2 EB Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - Neutral CT & Restricted Earth fault protection Relay, 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 set - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. EB Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link,1 set - Neutral CT & Restricted Earth fault protection Relay,1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port ,1 set - 3200A ,15VA, CL 0.5, CT's for metering,1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link. 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec, EB Incomer: 3 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link,1 set - Neutral CT & Restricted Earth fault protection Relay,1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. Bus coupler: 2 No. - 3200A 50KA FP EDO ACB Motorised (MP based release) . Bus bar: 3set - 3200A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports with 5 sets of Surge protection device SPD 1+2. Outgoings: 1 Nos 3200A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 2Nos 2500A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2500A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps,6Nos 2000A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 4 Nos 250A TPN 50KA MCCB MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 1 Nos 100A TPN 50KA MCCB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 100A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 1 Nos 63A TPN 50KA MCCB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 63A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 4B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. PCC-3 Incomer1: 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - Neutral CT & Restricted Earth fault protection Relay, 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. Bus bar: 1 set - 3200A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports with 1 sets of Surge protection device SPD 1+2. . Outgoings: 3 Nos 3200A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 2 Nos 250A TPN 50KA MCCB MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 1 Nos 2000A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - APFC Panel-1 (850 KVAR) INCOMERS: 1 No. 2000A 50kA FP ACB with RHOM , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 No. APFC relay BUSBAR: 1 set - 2000A, 4Wire, 50KA, 415V, TP Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. OUTGOING: 7No. 200A 50kA TPN MCCB With 100KVAR capacitor bank and 200A contactor , 2 Nos 100A 50kA TPN MCCB With 50KVAR capacitor bank and 100A contactor, 2 Nos 63A 50kA TPN MCCB With 25KVAR capacitor bank and 63A contactor , MPP Heavy Duty Type Capacitor with 480V, as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON; Contactors: SCHNEIDER / ABB / LAURITZ KNUDSEN; Capacitors: SCHNEIDER / LK / ABB
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. shall be provided for each panel compartments. MAIN FIRE EMERGENCY PANEL EB Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - Neutral CT & Restricted Earth fault protection Relay, 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 1 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 set - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link , 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. EB Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V (LSIG) protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 2 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link,1 set - Neutral CT & Restricted Earth fault protection Relay,1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec. DG Incomer: 2 1 No. - 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C & E/F (LSIG) protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port ,1 set - 3200A ,15VA, CL 0.5, CT's for metering,1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link. 1 set - Neutral CT & Restricted Earth fault protection Relay , 1 set - Surge Pretection device (Type-1+2 protection) with surge current rating of 50 kA, 10/350MicroSec, Bus coupler: 1 No. - 3200A 50KA FP EDO ACB Motorised (MP based release) . Bus bar: 4 set - 3200A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports with 4 sets of Surge protection device SPD 1+2. Outgoings: 4 Nos 3200A TPN 50KA ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps, 1 Nos 200A TPN 50KA MCCB MP based with O/C, S/C, E/F & U/V protection ,1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 200A ,15VA, CL 0.5, CT's for metering, 1 set - RYB LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; Protection Relays: ABB / SIEMENS / SCHNEIDER; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - SUBSTATION LIGHTING & POWER PANEL Incomer: 1 No. 63A 35KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports.. Outgoings: 15 Nos 32A TPN 35KA MCB 1 no. ON LED type indicating lamps, 2 Nos 40A TPN 35KA MCCB 1 no. ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either end and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - SUBSTATION EMERGENCY LIGHTING PANEL Incomer-1: 1 No.40A 35KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No.40A 35KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports with Surge Protection Device SPD 2. Outgoings: 10 Nos 25A TPN 35KA MCB with 1 No. LED type indicating lamp. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - BLOCK-1 MAIN PANEL Incomer-1: 1 No. 250A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-2: 1 No. 2500A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2500A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-3: 1 No. 2500A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2500A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Bus bar: 1 set - 2500A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2 Bus-coupler: 1 No. 250A FP MCCB Outgoings: 4 Nos 800A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 400A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 400/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 315A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 315/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 10 Nos 250A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 100A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 63A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-1 NORMAL LIFT & ESCALATOR PANEL Incomer: 1 No. 250A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 250A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 1+2. Outgoings: 4 Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 80A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 9 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 7 Nos 25A TPN MCB. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-1 EMERGENCY LIFT PANEL Incomer: 1 No. 100A 15KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 150A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 2. Outgoings: 4 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 80A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 3 Nos 25A TPN MCB All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 FIRE EMERGENCY PANEL Incomer: 1 No. 1600A 35KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 1600A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus bar: 1 set - 1600A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 1 Nos 1250A FP 35KA ACB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 1250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 800A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps,1 Nos 250A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps,3 Nos 100A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 63A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps,4 Nos 40A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 SERVER ROOM UPS PANEL Incomer-1: 1 No. 630A 35KA TP+2N MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 600/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 630A 35KA TP+2N MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 600/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 630A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 100A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - ELV UPS PANEL (SIDE BUILDINGS) Incomer-1: 1 No. 100A 20KA TP+2N MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 21 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - ELV UPS PANEL (MAIN BUILDINGS) Incomer-1: 1 No. 100A 20KA TP+2N MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - SHARED KITCHEN PANEL Incomer: 1 No. 160A 20KA FP MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, FP Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 3 Nos 63A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 40A TPN MCB with 1 no. ON LED type indicating lamps, 1 Nos 32A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 25A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 20A TPN MCB with 1 no. ON LED type indicating lamps, 4 Nos 16A TPN MCB with 1 no. ON LED type indicating lamps, 7 Nos 10A TPN MCB with 1 no. ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either end and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - STAFF & ADVOCATE CANTEEN KITCHEN PANEL Incomer: 1 No. 160A 20KA FP MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, FP Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 3 Nos 63A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 40A TPN MCB with 1 no. ON LED type indicating lamps, 1 Nos 32A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 25A TPN MCB with 1 no. ON LED type indicating lamps, 2 Nos 20A TPN MCB with 1 no. ON LED type indicating lamps, 4 Nos 16A TPN MCB with 1 no. ON LED type indicating lamps, 6 Nos 10A TPN MCB with 1 no. ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB1-B1@GR Incomer-1: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 250A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 13 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 25A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 100A TPN MCCB with 1 set ON LED type indicating lamps, 1 Nos 160A TPN MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB1-B1@1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 8 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends amd as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB1-B1@2F Incomer-1: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 11 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. 1 Nos 63A TPN MCCB with 1 set ON LED type indicating lamps.. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB2-B1@GR Incomer-1: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 250A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 18 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 1 Nos 25A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 100A TPN MCCB with 1 set ON LED type indicating lamps, 1 Nos 160A TPN MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB2-B1@1F Incomer-1: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 14 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. 1 Nos 63A TPN MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@GR Incomer-1: 1 No. 80A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 80A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 80A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 16 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. 3 Nos 32A DP MCB with 1 set ON LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 11Nos 63A TPN MCB with 1 set ON LED type indicating lamps. 1 Nos 32A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@2F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 18 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 32A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 125A TPN MCCB with 1 set ON LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@5F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 8Nos 63A TPN MCB with 1 set ON LED type indicating lamps, 6 Nos 32A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 125A TPN MCCB with 1 set ON LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@7F Incomer-1: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 13 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, 1 Nos 32A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB1-B1@8F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 7 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB1-B1@GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 2 Nos 40A 2P MCCB with 1 set ON LED type indicating lamps, 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB1-B1@1F Incomer: 1 No. 32A 20KA 2P MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 5 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB1-B1@2F Incomer: 1 No. 32A 20KA 2P MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 5 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB2-B1@GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 1 Nos 40A 2P MCCB with 1 set ON LED type indicating lamps, 11 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB2-B1@1F Incomer: 1 No. 32A 20KA 2P MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 2. Outgoings: 08 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB1-B1@GF Incomer: 1 No. 40A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 12 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB1-B1@1F Incomer: 1 No. 40A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB1-B1@2F Incomer: 1 No. 40A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB1-B1@5F Incomer: 1 No. 40A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. 5 Nos 25A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB1-B1@7F Incomer: 1 No. 40A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 8 Nos 25A DP 20KA MCB with 1 no. ON LED type indicating lamps. 4 Nos 25A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB1-B1@GR Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 10 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB1-B1@1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB1-B1@2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB2-B1@GR Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 10 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps, 1 Nos 80A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB2-B1@1F Incomer: 1 No. 80A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 80/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 80A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB1-B1@GF Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB1-B1@1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB1-B1@2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB1-B1@5F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB1-B1@7F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 12 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 MB BF TO 3RD FLR COMP. UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 MB BASEMENT TO 3RD FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 MB 4TH TO 7TH FLR COMPUTER UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-1 MB 4TH TO 7TH FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - BLOCK-2 MAIN PANEL Incomer-1: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-2: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-3: 1 No. 250A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Bus-coupler: 1 No. 250A FP MCCB Bus bar: 1 set - 2000A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2 Outgoings: 3 Nos 800A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamp, 2 Nos 400A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 400/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 100A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 11 Nos 63A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 04 Nos 125A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 125/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps . 01 Nos 200A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 200/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps . 01 Nos 160A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 160/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-2 NORMAL LIFT & ESCALATOR PANEL Incomer: 1 No. 200A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 200/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 200A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 1+2. Outgoings: 2 Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 80A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 10 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 25A TPN MCB. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-2 EMERGENCY LIFT PANEL Incomer: 1 No. 100A 15KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 150A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 2. Outgoings: 4 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 80A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 3 Nos 25A TPN MCB All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-2 FIRE EMERGENCY PANEL Incomer: 1 No. 1600A 35KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 1600A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus bar: 1 set - 1600A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 1 Nos 1250A FP 35KA ACB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 1250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 400A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 400/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 250A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 100A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 63A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps 4 Nos 40A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB3-B2@GR Incomer-1: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 19 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 6 Nos 32A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 100A FP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB3-B2@1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 12 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. 1Nos 63A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps ,1 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB4-B2@GR Incomer-1: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 32A DP MCB with 1 set ON LED type indicating lamps, 2 Nos 125A FP MCCB with 1 set ON LED type indicating lamps All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB4-B2@1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 11 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB4-B2@2F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 11 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. 1 Nos 63A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB2-B2@GR Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 19 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB2-B2@1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 12 Nos 63 TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB2-B2@3F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 17 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB2-B2@5F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB2-B2@7F Incomer-1: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 250A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 250/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 250A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 21 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB3-B2@GF Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 1 Nos 40A 4P MCCB with 1 set ON LED type indicating lamps, 13 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB3-B2@1F Incomer: 1 No. 32A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB4-B2@GF Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 1 Nos 40A 2P MCCB with 1 set ON LED type indicating lamps, 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB4-B2@1F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB2-B2@GF Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 12 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB2-B2@1F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB2-B2@3F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 8 Nos 25A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB2-B2@5F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 8 Nos 25A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB2-B2@7F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 08 Nos 25A DP MCB with 1 set ON LED type indicating lamps. 02 Nos 25A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB3-B2@GR Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 15 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB3-B2@1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either endsand as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB4-B2@GR Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 12 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB4-B2@1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB4-B2@2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 08 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB2-B2@GR Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 80A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB2-B2@1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 8 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB2-B2@3F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB2-B2@5F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB2-B2@7F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 14 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-2 MB BASEMENT TO 3RD FLR COMPUTER UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-2 MB GR TO 3RD FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-2 MB 4TH TO 7TH FLR COMPUTER UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 150A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-2 MB 4TH TO 7TH FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set -63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set -63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set -63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 - BLOCK-3 MAIN PANEL Incomer-1: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-2: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-3: 1 No. 250A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Bus-coupler: 1 No. 250A FP MCCB Bus bar: 1 set - 2000A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2 Outgoings: 3 Nos 800A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 400A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 400/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 200A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 200/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps,3 Nos 160A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 160/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 125A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 125/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 100A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 11 Nos 63A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-3 NORMAL LIFT & ESCALATOR PANEL Incomer: 1 No. 200A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 200/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 200A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 1+2. Outgoings: 3 Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 80A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 10 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 6 Nos 25A TPN MCB. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-3 EMERGENCY LIFT PANEL Incomer: 1 No. 100A 15KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 2. Outgoings: 2 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 80A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps. 3 Nos 25A TPN MCB All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-3 FIRE EMERGENCY PANEL Incomer: 1 No. 1600A 35KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 1600A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus bar: 1 set - 1600A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 1 Nos 630A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 100A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 63A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 40A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB5-B3 @ GR Incomer-1: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 125A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB5-B3 @ 1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 9 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB5-B3 @ 2F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 6 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB5-B3 @ 3F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 7 Nos 32A TPN MCB with 1 set ON LED type indicating lamps ,1 Nos 63A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB6-B3 @ GR Incomer-1: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 100A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB6-B3 @ 1F Incomer-1: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 14Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 1 Nos 63A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB3-B3 @ GR Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 19 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB3-B3 @ 1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB3-B3 @ 3F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 18 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 125A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB3-B3 @ 5F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB3-B3 @ 7F Incomer-1: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 18 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB5-B3 @ GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 2 Nos 40A 2P MCCB with 1 set ON LED type indicating lamps, 8 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB5-B3 @ 1F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB5-B3 @ 2F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB6-B3 @ GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 1 Nos 40A 2P MCCB with 1 set ON LED type indicating lamps, 9 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB6-B3 @ 1F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB3-B3 @ GR Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB3-B3 @ 1F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB3-B3 @ 3F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB3-B3 @ 5F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB3-B3 @ 7F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB5-B3 @ GR Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB5-B3 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB5-B3 @ 2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB6-B3 @ GR Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB6-B3 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB3-B3 @ GR Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB3-B3 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB3-B3 @ 3F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB3-B3 @ 5F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB3-B3 @ 7F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-3 MB BASEMENT TO 3RD FLR COMPUTER UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-3 MB BASEMENT TO 3RD FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-3 MB 4TH TO 7TH FLR COMPUTER UPS PANEL Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-3 MB 4TH TO 7TH FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 - BLOCK-4 MAIN PANEL Incomer-1: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-2: 1 No. 2000A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 2000A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Incomer-3: 1 No. 250A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electro-Mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 250A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps. Bus-coupler: 1 No. 250A FP MCCB Bus bar: 1 set - 2000A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2 Outgoings: 3 Nos 800A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 160A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 160/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 3 Nos 200A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 200/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 100A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 125A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 125/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 13 Nos 63A FP 50KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-4 NORMAL LIFT & ESCALATOR PANEL Incomer: 1 No. 200A 20KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 200/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 200A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 1+2. Outgoings: 3 Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 60/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 80A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 9 Nos 40A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 5 Nos 25A TPN MCB. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments. - BLOCK-4 EMERGENCY LIFT PANEL Incomer: 1 No. 100A 15KA TPN MCCB, Metering for Incomer: 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 15KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. SPD 2. Outgoings: 3 Nos 63A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 2 Nos 80A FP 15KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 80/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 3 Nos 25A TPN MCB All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-4 FIRE EMERGENCY PANEL Incomer: 1 No. 1600A 35KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 1600A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus bar: 1 set - 1600A, 4Wire, 35KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 1 Nos 1250A FP 35KA ACB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 1250/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps,3 Nos 400A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 400/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 100A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 100/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 63A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 40A FP 35KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 40/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - SUB FIRE EMERGENCY PANEL Incomer-1: 1 No. 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electrical-mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link. Incomer-2: 1 No. 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electrical-mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 3200A 50KA FP ACB EDO TYPE (Motorised) MP based with O/C, S/C, E/F & U/V protection with Electrical-mechanical interlocking, 1 No. Multifunction meter (KWH+KW+A+V+F+MD with RS - 485 port , 1 sets - 3200A ,15VA, CL 0.5, CT's for metering , 1 set - RYB LED type indicating lamps, 1 set - Control MCB with Neutral link, 1 set - ON OFF TRIP LED type indicating lamps, 1 set - Control MCB with Neutral link Bus bar: 2 set - 3200A, 4Wire, 50KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 4 Nos 1600A 50KA FP ACB EDO Type (Motorised) MP based with O/C, S/C, E/F, & U/V protection 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 1600/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 4 Nos 800A 50KA FP ACB EDO Type (Motorised) MP based with O/C, S/C, E/F, & U/V protection 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 800/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, 1 Nos 630A 50KA FP MCCB MP based with O/C, S/C, E/F, & U/V protection 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 630/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB7-B4 @ GR Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 17 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 125A FP MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB7-B4 @ 1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 16 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB7-B4 @ 2F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 6 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. 1Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB8-B4 @ GR Incomer-1: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 16 Nos 32A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 125A FP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB8-B4 @ 1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 13 Nos 32A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-SB8-B4 @ 3F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 6 Nos 32A TPN MCB with 1 set ON LED type indicating lamp, 1Nos 63A FP 20KA MCCB with 1 no. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) with 1 set 63/5A 10VA CL 1.0 CT's for metering with 1 serRYB LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB4-B4@ GR Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB4-B4 @ 1F Incomer-1: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 12 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB4-B4 @ 3F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 15 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, 2 Nos 125A TPN MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB4-B4 @ 4F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 14 Nos 63A TPN MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - LIGHTING & POWER PANEL-MB4-B4 @ 7F Incomer-1: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 160A 20KA FP MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 160A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 1+2. Outgoings: 17 Nos 63A TPN MCB with 1 set ON LED type indicating lamps, All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB7-B4 @ GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 1 Nos 32A 2P MCCB with 1 set ON LED type indicating lamps, 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB7-B4 @ 1F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 11 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB8-B4 @ GR Incomer-1: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 32/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 32A 20KA 2P MCCB with Electrical-Mechanical interlocking, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 160/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 32A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 2 Nos 32A 2P MCCB with 1 set ON LED type indicating lamps, 10 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB8-B4 @ 1F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-SB8-B4 @ 2F Incomer: 1 No. 40A 20KA 2P MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB4-B4 @ GR Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 13 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB4-B4 @ 1F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 6 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB4-B4 @ 3F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB4-B4 @ 4F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - EMRG.LIGHTING PANEL-MB4-B4 @ 7F Incomer: 1 No. 40A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 40A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 25A DP MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB7-B4 @ GR Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 2 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps, 8 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB7-B4 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB7-B4 @ 2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB8-B4 @ GR Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 2 Nos 63A TP+2N MCCB with 1 set ON LED type indicating lamps, 8 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB8-B4 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-SB8-B4 @ 2F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB4-B4 @ GR Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB4-B4 @ 1F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 7 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB4-B4 @ 3F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 08 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB4-B4 @ 4F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 9 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - UPS PANEL-MB4-B4 @7F Incomer: 1 No. 63A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 10 Nos 63A TP+2N MCB with 1 set ON LED type indicating lamps. All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends.and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-4 MB BASEMENT TO 3RD FLR COMPUTER UPS PANEL Incomer-1: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 125A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 125/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 125A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be type tested IEC 61439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-4 MB BASEMENT TO 3RD FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FPN MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA FPN MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-4 MB 4TH TO 7TH FLR COMPUTER UPS PANEL Incomer-1: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 100A 20KA TP+2N MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 100/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus bar: 1 set - 100A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 4 Nos 63A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 60/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle formation, compartmentalized, Form 3B construction, free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. MP based release to be provided for above 250A breakers. The Panel shall be Partially type tested IEC 60439 Part 1 & 2 and Provision for gas flooding system shall be provided for each panel compartments.. - BLOCK-4 MB 4TH TO 7TH FLR EMER. LTG. UPS PANEL Incomer-1: 1 No. 63A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-2: 1 No. 63A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Incomer-3: 1 No. 63A 20KA FP MCCB, 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 63/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link Bus-coupler: 1 No. 63A FP MCCB Bus bar: 1 set - 63A, 4Wire, 20KA, 415V, TPN Aluminium busbars, interconnections with colour coded heat shrinkable sleeves and SMC Busbar supports. 1 set Surge Protection device SPD 2. Outgoings: 5 Nos 40A TP+2N MCCB with 1 No. Multifunction Meter (KWH+KW+A+V+F with RS - 485 port) , 1 set - 40/5A ,10VA, CL 1.0, CT's for metering , 1 set - RYB LED type indicating lamps , 1 set - Control MCB with Neutral link All panels shall be of Top / Bottom cable entry. Panels shall be extandable type on either ends. and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK; ACB / MCCB: ABB / SIEMENS / SCHNEIDER (MG) / LEGRAND; MCB / Isolator / RCCB: LEGRAND – DX3/EKINOX / SCHNEIDER-A9 / HAGER H3/NOVELLO+; Digital / Multifunction Meters: ELMEASURE / SCHNEIDER / SOCOMEC; CT / PT: KAPPA / AE / MECO; SPD / TVSS: SCHNEIDER / LEGRAND / SIEMENS; LED Indicating Lamps: TEKNIC / SALZER / LK; Busbar Supports: POWER MAT / SCHNEIDER / KRIPSON
Supply, installation, testing & commissioning of Adapter Box for Cable termination for feeder (Extension of Busbar for 20 nos. cable termination) and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 32A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 32A SP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 40A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 40A TP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 63A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 63A TP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 100A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 100A TP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 125A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 125A TP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 250A FP MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 250A TP+2N MCCB as per IS/ IEC 60947-2 (IP-42) for UPS with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 40A FP RCBO, 300mA (IP-42) for Escalator with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 40A FP RCBO, 300mA (IP-42) for Lifts with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 80A FP RCBO, 300mA (IP-42) for Lifts with powder coated MS enclosure with all necessary components required to complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Makes: LT Panel (IEC 61439): ABB / SIEMENS / SCHNEIDER / LEGRAND / LK
Supply, installation, testing & commissioning of 3.5Core 300Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS
Supply, installation, testing & commissioning of 3.5Core 240Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 185Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 150Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 120Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 95Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 70 Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 50 Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 35Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 25Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 240Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 95Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 70Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 50Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 35Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 25Sq.mm 1100 volt grade XLPE insulated PVC sheathed Aluminium conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 16Sq.mm 1100 volt grade XLPE insulated PVC sheathed Copper conductor armoured XLPE/PVC cables,IS 7098(Part 1) 1988, as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 1Core 95Sq.mm 1100 volt grade PVC sheathed Copper conductor umarmoured flexible cables,IS 7098(Part 1) 1988 as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 1Core 70Sq.mm 1100 volt grade PVC sheathed Copper conductor umarmoured flexible cables,IS 7098(Part 1) 1988 as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 1Core 35Sq.mm 1100 volt grade PVC sheathed Copper conductor umarmoured flexible cables,IS 7098(Part 1) 1988 as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 1Core 25Sq.mm 1100 volt grade PVC sheathed Copper conductor umarmoured flexible cables,IS 7098(Part 1) 1988 as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 300Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 240Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 150Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 120Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 95Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 35Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 3.5Core 25Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 25Sq.mm 1100 volt grade Aluminium conductor Fire Survival Cables, IEC 60331, cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 4Core 16Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331 ,armoured cables of including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved make. MAKE: POLYCAB / RR KABEL / KEI / HAVELLS
Supply, installation, testing & commissioning of 1Core 25Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331, umarmoured flexible cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of 1Core 16Sq.mm 1100 volt grade Copper conductor Fire Survival Cables, IEC 60331, umarmoured flexible cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 2C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning ofend Termination of 3C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 4C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 12C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 14C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 19C x 1.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 2C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 3C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 4C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 5C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 6C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 10C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of of 12C x 2.5 sq.mm Cu unarmoured Multistand XLPE/PVC cables as per specification in cable trays, shafts, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. Make-POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 300 Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core240 Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 185Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 150Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 120Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 95Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 70Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 50Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 35Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3.5Core 25Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 4Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping cu lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply & making of Cable end termination of the 3Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping CU lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete as per specification,as required & as directed by Engineer In Charge and as per approved make for HVAC works Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 240Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 95Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 70Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 50Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 35Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 25Sq.mm PVC insulated sheathed PVC/XLPE Aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 16Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 4Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3Core 10Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3Core 6Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 3Core 4Sq.mm PVC insulated sheathed PVC/XLPE Copper conductor armoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required & as directed by Engineer In Charge and as per approved Makes: ( Make: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 1Core 95Sq.mm PVC insulated sheathed Flexible Copper conductor Unarmoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 1Core 70Sq.mm PVC insulated sheathed Flexible Copper conductor Unarmoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 1Core 35Sq.mm PVC insulated sheathed Flexible Copper conductor Unarmoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 1Core 25Sq.mm PVC insulated sheathed Flexible Copper conductor Unarmoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of Cable end termination of the 1Core 16Sq.mm PVC insulated sheathed Flexible Copper conductor Unarmoured cables of 1100 volt grade including supplying and fixing of crimping aluminium lugs, double compression glands with suitable earth tag and earthing facility at both ends of cables etc. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 4C x 1.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 12C x 1.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 2C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 3C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 4C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 5C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 6C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 10C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply, installation, testing & commissioning of end Termination of 12C x 2.5 sq.mm Cu Armoured Multistand Cable with suitable lugs and glands complete etc as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and approved Makes: REYCHEM / 3M / DENSONS)
Supply & fixing of ISI, 20 outer dia,1.6 thickness MS conduit pipe as per lS-9537 Part ll including cost of all materials, accessories and all labour charges etc., complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make.( Make: BHARAT / GB / PRECISION)
Supply & fixing of ISI, 25 outer dia,1.6 thickness MS conduit pipe as per lS-9537 Part ll including cost of all materials, accessories and all labour charges etc., complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make.( Make: BHARAT / GB / PRECISION)
Supply & fixing of ISI, 32 outer dia,1.6 thickness MS conduit pipe as per lS-9537 Part ll including cost of all materials, accessories and all labour charges etc., complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make.( Make: BHARAT / GB / PRECISION)
Supply & fixing of ISI, 38 outer dia,1.6 thickness MS conduit pipe as per lS-9537 Part ll including cost of all materials, accessories and all labour charges etc., complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make.( Make: BHARAT / GB / PRECISION)
Supply & fixing of ISI, 50 outer dia,2.0 thickness MS conduit pipe as per lS-9537 Part ll including cost of all materials, accessories and all labour charges etc., complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make.( Make: BHARAT / GB / PRECISION)
Supply and Fixing of 20mm outer dia (1.40 to 1.55)mm thicknes medium grade with IS:9537 part 3 FRLS rigid P.V.C. pipe (ISI marked) concealed in wall/ceiling/cable trays with all required MS junction boxes and all accessories including masonary work for run of mains including all labour charges etc., complete. MAKES: ( Make: PRECISION / VIP / POLYCAB)
Supply and Fixing of 25mm outer dia (1.60 to 1.80)mm thicknes medium grade with IS:9537 part 3 FRLS rigid P.V.C. pipe (ISI marked) concealed in wall/ceiling/cable trays with all required MS junction boxes and all accessories including masonary work for light, bell, fan, and separate plug point with hot dip galvanized 20/18 SWG MS modular metal switch box with earthing terminal including all labour charges etc., complete MAKES: ( Make: PRECISION / VIP / POLYCAB)
Supply and Fixing of 32mm outer dia (1.90 to 2.10)mm thicknes medium grade with IS:9537 part 3 FRLS rigid P.V.C. pipe (ISI marked) concealed in wall/ceiling/cable trays with all required MS junction boxes and all accessories including masonary work for light, bell, fan, and separate plug point with hot dip galvanized 20/18 SWG MS modular metal switch box with earthing terminal including all labour charges etc., complete. MAKES: ( Make: PRECISION / VIP / POLYCAB)
Supply and fixing of 1 or 2 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and fixing of 3 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal. and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and fixing of 4 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal.and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and fixing of 6 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal.and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and fixing of 8 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal. and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and fixing of 12 Modular Hot Dip galvanized 18 SWG Module box with earthing terminal.and as directed by Engineer in Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Wiring with 2 runs of 22/0.3mm ( 1.5 Sq.mm) HFFR / ZHFR P.V.C. insulated 1100V grade as per IS : 694 / 1990 specification flexible copper cable (ISI marked) in existing pipe with 6A Modular switch (ISI marked) with cover plate, Ceiling rose/BH/ SBH, including all labour charges etc., complete for Light, Bell, Fan and Exhaust Fan points etc., complete. Make of wire: FINOLEX, RR KABEL, HAVELLS, POLYCAB Modular Switch Make: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Wiring with 3 runs of 22/0.3mm ( 1.5 Sq.mm) HFFR / ZHFR P.V.C. insulated 1100V grade as per IS : 694 / 1990 specification flexible copper cable (ISI marked) in existing pipe with 6A Modular switch (ISI marked) with cover plate, Ceiling rose/BH/ SBH, including all labour charges etc., complete For Stair Case points., complete (1.5 times of point wiring). (for Non Residential Building). Make of wire: FINOLEX, RR KABEL, HAVELLS, POLYCAB Modular Switch Make: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply and run of 1 of 22 /0.3mm (1.5 Sq.mm) HFFR / ZHFR P.V.C. insulated 1100V grade as per IS : 694 / 1990 specification flexible copper cable in existing pipe for earth continuity including all labour charges etc., complete. Make of wire: FINOLEX, RR KABEL, HAVELLS, POLYCAB
Supply, installation, testing and commissioning of 3200Amp, 160KA breaking capacity (100% Neutral busbar) sandwich busduct system made of CRCA sheet/Hot Galvanized steel encloserof thickness not less than 1.5mm having degree of protection of IP 55/IP 65 as per IEC/EN 61439-6, PVC/Plastic insulated reinforced with glass fibre four strip ALUMINIUM busbar in convenient sections including end cover units suitable for 415 volts 3 phase, 4 wire, 50 Hz A.C. system etc., with necessary joints, fire barrier at each floor, provision of tapping at each floor/every meter, continuous earthing with 2 no of aluminum strip of suitable size (one on each side0 including GI clamping brackets, angle iron brackets, steel fasteners, connecting to earth system as required . Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply, installation, testing and commissioning of 800Amp, 42/50KA KA breaking capacity (100% Neutral busbar) sandwich busduct system made of CRCA sheet/Hot Galvanized steel encloserof thickness not less than 1.5mm having degree of protection of IP 55/IP 65 as per IEC/EN 61439-6, PVC/Plastic insulated reinforced with glass fibre four strip ALUMINIUM busbar in convenient sections including end cover units suitable for 415 volts 3 phase, 4 wire, 50 Hz A.C. system etc., with necessary joints, fire barrier at each floor, provision of tapping at each floor/every meter, continuous earthing with 2 no of aluminum strip of suitable size (one on each side0 including GI clamping brackets, angle iron brackets, steel fasteners, connecting to earth system as required . Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of 3200 Amps Horizontal / Vertical bends for sandwitch Bus Duct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of 800 Amps Horizontal / Vertical bends for sandwitch Bus Duct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of 3200 Amps Copper Flexibles for three phases and neutral for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of 800 Amps Copper Flexibles for three phases and neutral for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of Flange End for 3200 Amps for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved make complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply and Fixing of Flange End for 800 Amps for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply, installation, testing & commissioning of 160A Tap Off Box with MCCB for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply, installation, testing & commissioning of 250A Tap Off Box with MCCB for sandwitch Busduct complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aprovedmake. Makes: SCHNEIDER,LEGRAND(Zucchini),LK)
Supply, installation, testing & commissioning of 6KVA 192/240 VDC with Isolation Transformer on line UPS as per IS 16242(Part-I):2014 and IEC 60240-1: 2008- with Single Phase input and output, 50 Hz, True sine wave unity Power factor and fully digital IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer.Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building. All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required & as directed by Engineer In Charge .MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 10.0 KVA 312/360 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave,unity Power factor, SCR based rectifier and fully digital IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer. Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building. s All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge .MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC. MAKE: MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 20.0 KVA 312/360 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave unity Power factor, SCR based rectifier and fully digital IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer. Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge . Makes-MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC)
Supply, installation, testing & commissioning of 30.0 KVA 360/384/480 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave,unity Power factor, SCR based rectifier and fully digital IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer. Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge and as per approved makeMITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC. MAKE: MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 40.0 KVA 360/384/480/504 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave, unity Power factor, SCR based rectifier and fully digital IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer. Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge .MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 60.0 KVA 480/504/528/600/720 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave,unity Power factor, SCR based rectifier and IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer.Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge .MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC. MAKE: MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 100.0 KVA 480/504/528/600/720 V DC on line UPS as per IEC62040-1 & IEC62040-3 with 3 Phase input and output, 50 Hz, True sine wave,unity Power factor SCR based rectifier and IGBT based inverter, with K13 transformer for voltage amplification and harmonics reduction UPS system, with internal isolation transformer.(3+1) configuration for 300kva load with continuous operation. Energy Efficiency Requirements for UPS as per Super ECBC/ECSBC building All UPS systems shall be suitable to operate on parallel redundant, standalone, hot standby mode, etc. The capacity of UPS system is as below : i) Input, output, static bypass and maintenance bypass breakers required. Separate termination panel with 4 breakers to be considered, if breakers are not in-built. Internal cabling between breaker panel and UPS to be considered by UPS vendor. ii) Standard communication features required. iii) Dust filter required for each UPS. iv) Pulse Width Modulation. v) Conformal coating of critical PCBAs. vi) Parallel redundant kit (1+1)for UPS required for UPS required.vii)Ups should be with double conversionkit for faster transfer time..viii)UPS sould be with Battery monitoring system. ix) Acoustic level should be less than 58dB at 1 mtr. distance,Complete and as per specifications,as required for critical IT & server application with no downtime & as directed by Engineer In Charge .MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC. MAKE: MITSUBISHI, SOCOMEC, SCHNEIDER, NUMERIC
Supply, installation, testing & commissioning of 12V, 65Ah SMF Battery bank to provide 90 min backup on each UPS of 6.0kva at full load at 0.8 pf and 1.75 V/cell ECV calculated by Watt/battery method. Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge and as per approved make EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of 12V 65Ah SMF Battery bank to provide 90 min backup on each UPS of 10.0kva at full load at 0.8 pf and 1.75 V/cell ECV calculated by Watt/battery method. Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge and as per approved make EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of 12V, 120Ah SMF Battery bank to provide 90 min backup on each UPS of 20.0kva at full load and 1.75 V/cell ECV calculated by Watt/battery method.Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge and as per approved make EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of minimum 42 no. of 120Ah SMF 12V Battery bank to provide 90 min backup on each UPS of 30.0kva at full load at 0.8 pf and 1.75 V/cell ECV calculated by Watt/battery method. Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 15 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved make, as required & as directed by Engineer In Charge and as per aproved make. EXIDE, AMARA RAJA BATTERIES. MAKE: EXIDE / AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of 12V, 65Ah SMF Battery bank to provide 15 min backup on each UPS of 40.0kva at full load and 1.75 V/cell ECV calculated by Watt/battery method. Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 15 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV.Complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved make, as required & as directed by Engineer In Charge and as per aproved make. EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of minimum 48 no. of 150Ah 12V SMF Battery bank to provide 90 min backup on each UPS of 40.0kva at full load at 0.8 pf and 1.75 V/cell ECV calculated by Watt/battery method. Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 15 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV.Complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make. and as per aproved make, as required & as directed by Engineer In Charge and as per aproved make. EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of 12V, 65Ah SMF Battery bank to provide 15 min backup on each UPS of 60.0kva at full load and 1.75 V/cell ECV calculated by Watt/battery method.Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge and as per approved make EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of minimum 60 no. of 150Ah 12V SMF Battery bank to provide 90 min backup on each UPS of 60.0kva at full load at 0.8 pf and 1.75 V/cell ECV calculated by Watt/battery method.Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge . EXIDE, AMARA RAJA BATTERIES
Supply, installation, testing & commissioning of 12V, 120Ah SMF Battery bank to provide 15 min backup on each UPS of 100.0kva at full load and 1.75 V/cell ECV calculated by Watt/battery method.Vendor to submit battery sizing sheet with all parameters mentioned clearly. i) MS insulated open type racks for batteries with battery interlinks duly connected. ii) DC cable between UPS and battery : 15 mtr +ve, 15 mtr -ve per run x no of battery banks. Vendor to furnish the cable details to withstand max discharge current at full load and ECV of battery at the end of 90 min. iii) DC MCCB with UV trip coil and aux contacts for battery protection and isolation. The breaker should be rated such that it can withstand the max discharge current from battery at full load and ECV. complete and as required & as directed by Engineer In Charge and as per approved make, as required & as directed by Engineer In Charge . EXIDE, AMARA RAJA BATTERIES
Supply,Transportation, installation, testing and commissioning of earthing as per IS 3043 with copper earth plate of size 600 x 600 x 3.15 mm by embodying 3 to 4 mtr below the ground level with 40mm dia 'B' Class G.I Pipe by exacavating a pit to a depth of 3 to 4 Mtr as per National Electric Code and earth connection from electrode Copper strip of 25mm x 5mm x 200mm length to be bolted with nut bolts to G.I.pipe including 25mm x 3mm copper strip of 6Mtrs length connected from plate to Copper strip including filling with 20Kg Salt and 40Kg Charcoal or 40Kg including all accessories like nuts bolts reducer,nipple, wire meshed funnel and CC finished chamber covered with hinged type with CI cover ,CI frame of size 300 X 300 mm ,testing earth resistance as required etc., Chamber is raised by 150mm from the FGL. A proper permanent identification tag/label/earth cable marker shall be provided for each electrode / pit to indicate the Earth pit no:, Earth resistance measured value with date and next renewal shall be marked on CI plate. (for Lifts), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply,Transportation, installation, testing and commissioning of independent earthing for Important equipment with 100mm dia Heavy gauge C.I ( Cast iron ) pipe with Flange 2.5m long enclosed in C.C/ brick masonry chamber of 450m x 450m x 400mm with R.C.C. Slab cover duly providing staggered holes filling with salt and charcoal from the bottom of the pipe giving earth connection from electrode through G.I strip of 40 x 6mm x 200mm length with all accessories and labour charges complete, as per IS specifications 732/1982 (Part II). Chamber is raised by 150mm from the FGL. A proper permanent identification tag/label/earth cable marker shall be provided for each electrode / pit to indicate Earth pit no:, Earth resistance measured value with date and next renewal shall be marked on CI plate. (5 X'Mer+4 DG Set and HT) , as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply,Transportation, installation, testing and commissioning of earthing as per IS 3043 with copper earth plate of size 600 x 600 x 3.15 mm by embodying 3 to 4 mtr below the ground level with 40mm dia 'B' Class G.I Pipe by exacavating a pit Providing earthing as per IS 3043 with copper earth plate of size 600 x 600 x 3.15 mm by embodying 3 to 4 mtr below the ground level with 40mm dia 'B' Class G.I Pipe by excavating a pit to a depth of 3 to 4 Mtr in all soils for Sophisticated Electronic equipment as per National Electric Code and earth connection from electrode Copper strip of 25mm x 5mm x 200mm length to be bolted with nut bolts to G.I. pipe including 25mm x 3mm copper strip of 6Mtrs length connected from plate to Copper strip including filling with 20Kg Salt and 40Kg Charcoal or 40Kg bentonite powder including all accessories like nuts bolts reducer, nipple, wire meshed funnel and CC finished chamber covered with hinged type with CI cover ,CI frame of size 300 X 300 mm ,testing earth resistance as required etc., complete (5 X'fer+4 DG Set and HT) Chamber is raised by 150mm from the FGL. A proper permanent identification tag/label/earth cable marker shall be provided for each electrode / pit to indicate Earth pit no:, Earth resistance measured value with date and next renewal shall be marked on CI plate., as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 8 SWG Copper wire(0.1155Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 3mm Copper Flat (0.663Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 40 mm x 6mm Copper Flat(1.9 Kgs/Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 50 mm x 6mm Copper Flat (2.680Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 3mm GI Flat(0.656 Kgs/Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 25mm x 6mm GI Flat (1.18Kgs/1Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 40 mm x 6mm GI Flat(1.6 kgs/Mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 50 mm x 6mm GI Flat(2.5 Kgs /mtr) Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 75 mm x 10mm Copper Flat Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection,sleeves with color code etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply and laying of 75 mm x 10mm GI Flat Earth wire/Strip in horizontal /Vertical run in Ground/surface/Recess including, revitting,soldering,saddles,making connection etc as required, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 75x 10 mm CU with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 75x 10 mm GI with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 65x 10 mm GI with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 40x 6 mm GI with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 25x 6 mm GI with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & fixing of 1Mtr length EARTH BUS of 25x 6 mm Cu with required insulators in main LT panel room for earthing connectivity, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - CAPE / OBO BETTERMANN / ASHLOK
Supply & Fixing of 1C 95Sq.mm Cu Flexible Cable (For 100kVA UPS Earthing), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 70Sq.mm Cu Flexible Cable (For 60kVA UPS Earthing), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 50Sq.mm Cu Flexible Cable (For 50kVA UPS Earthing), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 35Sq.mm Cu Flexible Cable (For 30,40kVA UPS Earthing), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 25Sq.mm Cu Flexible Cable (For 5kVA to 20kVA UPS Earthing), as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 16Sq.mm Cu Flexible Cable , as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 10Sq.mm Cu Flexible Cable , , as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply & Fixing of 1C 6Sq.mm Cu Flexible Cable , as required & as directed by Engineer In Charge and as per aproved make. Approved makes - POLYCAB / RR KABEL / KEI / HAVELLS
Supply and Installation of 10 mm copper bonded Round steel solid Conductor for Foundation earthing(In floor) meet the requirements of IS/ IEC 62305 and IEC 62561-2 complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved make., DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply and installation of corrosion tape for conductor oin soil to meet the requirement of IS/IEC-62305., as required & as directed by Engineer In Charge and as per aproved make. DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply, Installation, testing & commissioning of Exothermic Welding - Including welding mould and other accessories for welding confirms the requirements of IEEE 837:2014 , as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply, Installation, testing & commissioning of Rust resistant non corossive 10 mm dia Copper Bonded Steel round conductor used for Earth termination inside the concrete ( In structural Column )., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply, Installation, testing & commissioning of Bonding clamp for interconnecting Round Conductor with reinforcement rebar at every 3.5 Mtr inside the concrete to meet the requirements of IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply, Installation, testing & commissioning of stainless steel Straight Connector for interconnecting 10 mm dia copper bonded round conductor at straight connection, as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of stainless steel Earth stud of dimension 69 x 69 mm integrated inside concrete and should be tested for electrical resistivity, salt spray and humidity test & short circuit to meet the requirements of IS/IEC 62305 and IEC 62561- 1&2.5., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of 10mm stainless steel Straight Connector for integrated down conductor and should be tested for electrical resistivity, mechanical load to meet the requirement for IS/IEC - 62305 and IEC 62561-1&2., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of 10 mm copper bonded Solid Steel Round Conductor with average coating thickness minimum of 100µm for Type-B Earthing and should be tested for Tensile strength, Electrical Resistance, salt mist, Bend & Adhesion to meet the requirements of IS/ IEC 62305 and IEC 62561-1&2., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of D-clamp for interconnecting 10 mm Round Conductor at every 3mtr with reinforcement rebar inside the concrete to meet the requirements of IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of stainless steel Straight Connector for interconnecting 10 mm dia copper bonded round conductor at straight connection, as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of MS Cross Connector for 10 mm Copper round conductor at cross junction., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning and installation of Fascade stud (strike pad) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination. Cross sectional area of conductor should be 50 mm²., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Nylon Conductor Holder for Parapet wall for holding 8 mm dia Aluminium alloy round Conductor., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply,Installation, testing & commissioning of Stainless steel Cross Connector for 8 mm dia Aluminium alloy round conductor at tee & cross junction., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Earthing stud & suitable Clamp of dimension 69 x 69 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Expansion joint with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations.Expansion joint should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305.Tested for Electrical, Mechanical and chemical as per IEC 62561., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of connecting point made of stainless steel for terminating 10mm copper conductor., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of D-clamp for interconnecting 10 mm Round Conductor at every 3mtr with reinforcement rebar inside the concrete to meet the requirements of IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of 18 mm copper bonded Solid Steel Round Conductor with minimum coating thickness 70µm as integrated down conductor. Material should be tested Tensile strength, Electrical Resistance, salt mist, Bend & Adhesion to meet the requirements of IS/ IEC 62305 and IEC 62561-1&2., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Stainless steel SS 304 Grade Folding Clamp as per sheet profile for 8 mm dia Aluminium alloy Solid Round Conductor for horizontal Air terminal above metal sheet to meet the requirements for IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of 18mm stainless steel Straight Connector at every 5 Mtr of integrated down conductor and should be tested for electrical resistivity, mechanical load to meet the requirement for IS/IEC - 62305 and IEC 62561-1&2., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of MS cross connector for 18 mm round conductor at cross junction., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of Vertical airterminal with corner protecting measure along with suitable mounting arrangements to protect the corners and edges of terrace area and to avoid side flashes., as required & as directed by Engineer In Charge and as per aproved make.DEHN,OBO BETTERMANN,CAPE ELECTRIC
Supply ,Installation, testing & commissioning of air termination rod of 4 mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends(Tappered Type). The rod shall be mounted with stone and fixing accessories ., as required & as directed by Engineer In Charge and as per aproved make. Approved makes - DEHN / OBO BETTERMANN / CAPE ELECTRIC Test Parameter for 4 mtr vertical air terminal a)ELectrical Resistivity b) Tensile Strength c) Condition of Salt Mist Tested as per IEC 62561-2.
Supply ,Installation, testing & commissioning of Earthing stud with fixing clamp accessories of dimension 69 x 99 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305., as required & as directed by Engineer In Charge and as per aproved make. Approved makes - DEHN / OBO BETTERMANN / CAPE ELECTRIC
Supply ,Installation, testing & commissioning of a stainless steel earthing stud of dimension 100 mm x 75 mm with a Two-point copper leading terminal of length 1 meter each with suitable clamping and connecting accessories used in the structural steel ring earthing system to meet the requirements of IS/IEC 62305, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - DEHN / OBO BETTERMANN / CAPE ELECTRIC
Supply ,Installation, testing & commissioningof Cu Earthing stud with fixing clamp accessories of dimension 150 x 75 mm used in structural steel ring earthing system to meet the requirements of IS/IEC 62305. Rated Current : Irms-50 KA per sec; Ipeak- 110 KA per sec, as required & as directed by Engineer In Charge and as per aproved make. Approved makes - DEHN / OBO BETTERMANN / CAPE ELECTRIC
Operation & Maintenance during defects liability period of 24 months for O&M of 33 KV Substation/Electrical and Mechanical Maintencance inAssembly Building a HT Panels, Transformers, LT Panels, Diesel Generator Sets, AC Units, Plumbing System and Fresh Air & Exhaust fans etc complete for 2 shifts in 24 Hours cycle with the following Personnel: Deployment per shift: 1. Licensed Shift Engineer(ELE)-1 2. Licensed Diploma Engineer-1 3. Electrical Technician-1 4. Mechanical Technician-1 5. Airconditioning Tehnician-1 6. Helper(ELE)-1 Total for one Shift 6 Persons. For 2 shifts (2x6) 12 Persons
Operation of VIP Lifts during defects liability period of 24 months in Assembly Building for 2 shifts with the following Personnel: Deployment per shift: 1. Lift Operators-12 Persons Total for one Shift 6 Persons. For 2 shifts (2x6) 12 Persons
Supply, installation, testing & commissioning of 150mm x 50mm x 1.6mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete and as required & as directed by Engineer In Charge and as per approved . Make:PROFAB / APARNA ROLLFORM / GLOMETAL .
Supply, installation, testing & commissioning of 900mm x 50mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete and as required & as directed by Engineer In Charge and as per approved . Make:PROFAB / APARNA ROLLFORM / GLOMETAL .
Supply, installation, testing & commissioning of 900mm x 75mm x 2.0mm of Hot Dipped Galvanized Iron perforated cable trays without cover, including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/Wall with suspenders etc., complete and as required & as directed by Engineer In Charge and as per approved . Make:PROFAB / APARNA ROLLFORM / GLOMETAL .
Supply, installation, testing & commissioning of 150mm x 50mm x 2.0mm of Hot Dipped Galvanized Iron Ladder Type cable trays with rungs at span of 250 mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with suspenders and etc., complete and as per specifications,as required & as directed by Engineer In Charge . . Make:PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, installation, testing & commissioning of the 100x38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supply, installation, testing & commissioning of the 150mm x 38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aprovedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, installation, testing & commissioning of the 300mm x 38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aprovedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, installation, testing & commissioning of the 100mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aprovedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, installation, testing & commissioning of the 150mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aprovedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supply, installation, testing & commissioning of the 300mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete and as required, as per specifications & as directed by Engineer In Charge and as per aprovedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supplying & Installation of 172mm x 52mm G.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying & Installation of 222mm x 52mmG.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying & Installation of 372mm x 52mm G.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways complete and as required, as per specifications & as directed by Engineer In Charge and as per aproved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supply, install, test and commissioning of 8 LOOP addressable peer to peer Networkable analogue addressable type fire alarm control panel with minimum 1500 Character / 240X64 Pixel / 7inch Touchscreen graphic LCD display. The panel should be equipped with sufficient numbers of loop with 20% spare capacity, with each networkable intelligent fire alarm Control Panel having SLC with capacity of min 250 detectors/ devices in any combination (Min 120 Detector) with key pad, dual flash-based microprocessor technology, inbuilt USB Port for upload and down load the configuration tools, RS232 serial port for direct PC or modem connection, inbuilt NAC's, min 20 programmable Zonal LEDs and operates on 240V AC + 10% with 50 Hz with built in charger. The panel shall have fire, fault relays, option of BMS integration MODBUS/ BACKNET, graphical software for provision of TCP/ IP modules, Remote Access, Class 'X' wiring with provision of both class 'A' and class 'B' wiring in the SLC circuit, userfriendly with communication facility to monitor & control the FACPs from a single window. The panel shall be suitable for minimum of 5000 event record facility, event fetch from FACP facility and the single panel shall be suitable for min 2000 fire zones and 200 Panels/ Nodes in one network with all other accessories required to successfully run the system. The panel shall be completed as per UL and FM/EN54 & VDS standards (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design) as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, install, test and commissioning of 10 LOOP addressable peer to peer Networkable analogue addressable type fire alarm control panel with minimum 1500 Character / 240X64 Pixel / 7inch Touchscreen graphic LCD display. The panel should be equipped with sufficient numbers of loop with 20% spare capacity, with each networkable intelligent fire alarm Control Panel having SLC with capacity of min 250 detectors/ devices in any combination (Min 120 Detector) with key pad, dual flash-based microprocessor technology, inbuilt USB Port for upload and down load the configuration tools, RS232 serial port for direct PC or modem connection, inbuilt NAC's, min 20 programmable Zonal LEDs and operates on 240V AC + 10% with 50 Hz with built in charger. The panel shall have fire, fault relays, option of BMS integration MODBUS/ BACKNET, graphical software for provision of TCP/ IP modules, Remote Access, Class 'X' wiring with provision of both class 'A' and class 'B' wiring in the SLC circuit, userfriendly with communication facility to monitor & control the FACPs from a single window. The panel shall be suitable for minimum of 5000 event record facility, event fetch from FACP facility and the single panel shall be suitable for min 2000 fire zones and 200 Panels/ Nodes in one network with all other accessories required to successfully run the system. The panel shall be completed as per UL and FM/EN54 & VDS standards (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design) as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Network Active Repeater Panel with 1500 Character / 240X64 Pixel / 7inch Touchscreen. The LCD shall Display all events / detectors, devices status of complete systems in the networked. as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Analogue Addressable loop powered Sounder & Beacon with inbuilt isolator and having Min 15 distinct sound patterns/ multitone to indicate Exit doors and direct occupants for safe and fast evacuation and 100dB output with minimum 1Hz Frequency flash rate designed for IP65 requirements and approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Junction Box, Glands and other mounting accessories for proper installation.as required,as per specifications & as directed by Engineer In Charge and as per approved make Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Dust and Vermin proof (Resettable) addressable analogue Manual call boxes along with Isolators inbuilt having front reset mechanism with 170° viewable LED and can be viewed from the distance of 7 M. also have inbuilt isolator having operating temperature from -40°C-70°C to initiate audio visual alarm in case of Human detection of fire. The manual call point must be indoor type with IP 44 rating. The call point must be resettable type without break glass.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Optical smoke detector with LED with standard base having capacity of min 126 address combination. Operating temperature -40°C to 70°C &Humidity 0-95%. The detector should have polling 360-degree viewable LED with 5 class approved response modes all approved with the relevant standards, drift compensation and transient rejection. The detector shall have facility to mount in different comprehensive environment like Hostile environment, precious storage, Warehouse and normal working environments. The detector should have a self-locking mechanism and requires a special tool to remove this detector. The detector should have a hard address inside the base. The detector must have nonvolatile memory to write the installation date & site codes. The detector should be made of fire-retardant material & should be melt above 100-degree C. The detectors must be openable for the cleaning of dust whenever required. All the other specs should be as per the specification attached.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, instllation, testing and commissioning of intallegent analogue addressable photo electric smoke detector including cost of base plate etc., complete as per specification with required fittings and accessories. The detector shall self test feature to test the detectory remotely. The remote testing shall be done by generating actual smoke within detector chamber. (For above false ceiling)as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply and installation of intelligent analogue addressable rate of rise cum fixed temparature heat detectors including the cost of base plate. 75mm dia MS outlet box for fixing of the detector base, mounting accessories etc., complete as per specifications and as required & as directed by Engineer In Charge and as per aproved make. Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Analogue Addressable Multi-sensor (Smoke & Heat) detector with LED with standard base having capacity of min 126 address combination. Operating temperature -40°C to 70°C & Humidity 0-95%. The detector should have polling 360-degree viewable LED with 5 class approved response modes all approved with the relevant standards, drift compensation and transient rejection. The detector should trigger heat alarm as per the A1R class requirement. The detector shall have facility to mount in different comprehensive environment like Hostile environment, Parking Garage, Precious storage, Ware house and normal working environments. The detector should have a self-locking mechanism and requires a special tool to remove this detector. The detector should have a hard address inside the base. The detector should be made of fire-retardant material & should be melt above 100-degree C. The detectors must be open for the cleaning of dust whenever required. The detector must have 4 nonvolatile memories to write the installation date & site codes as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Addressable Multicirteria (Smoke + Heat + CO + IR) Detector. The detector shall have four sensing elements viz. Photo electric smoke, Heat, Carbon Monoxide & Infra Red Flame detection combined in a single detector. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with userfriendly rotary decimal switches. The internal CO Sensor should be replaceable upon EOL. It should be possible to generate 2 distinctive tones if the CO concentration reaches 2 definite userdefined levelsas required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, install, test and commissioning of Analogue addressable Control (Input/Output) module with inbuilt relay and isolator with LED indicator, approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Junction Box and other mounting accessories for proper installation. In case of Manufacturer with single Input or Output module need to supply One quantity of each for line item.( For MCP)as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Addressable Relay Module for AHU / Access Control / Lifts / Staircase Pressurization / Fire Suppression/Public Address System & other Third Party Outputs. The relay module shall provide DPDTcontact rated at 24V DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with userfriendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. Complete with Cable lugs at Ends, cable compression glands, cable tags and Ferruling, back box etc. . as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply and Installation of Intelligent analogue addressable monitor modules including the cost of mounting accessories complete as per specifications and as required.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Loop isolation module which consists of LED. This LED shall be mounted with in a round polycarbonate encloser. Isolator Base for Isolators.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Response Indicator with LED for above false ceiling detectors. Complete with Cable lugs at Ends,cable tags and Ferruling, back box etc.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Addressable Beam Detector. The beam detector shall be used for High Ceiling application with a detection range upto 100 mtrs having 4 manual & 2 auto sensitivity settings. The beam detector shall be True addressable installed on the SLC circuite & communicate directly with the panel without any interface module. Complete with Cable lugs at Ends, cable compression glands, cable tags and Ferruling, back box etc. as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Graphics UserInterface for Monitoring & Control of complete Fire, Voice Evacuation & Telephone Talkback System. The GUI based main network software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems, and / or sensors’ locations. It shall have the facility to change the sensitivity of any detector. The software shall be capable of monitoring 200 Nodes with 100 MB baud Transmission rate on Fibre Optics Network and 12 MB baud Transmission on cable and 2,50,000 network points. The software shall provide the facility to Monitor, Control all the Digital PAVA as well as 2 way communication from main control room using voice signals over Fire Network along with the Fire detection signal. The Graphic workstation shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of GUI. as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Workstation for GUI Supply, Transportation and installation of Desktop with fully loaded software as desired, with the following configuration. 1. Processor: Intel® Core™ i7-12th Generation or Higher version Processor with Intel® HD Graphics 770 (2.9 GHz base frequency, up to 4.9 GHz with Intel® Turbo Boost Technology, 25 MB L3 cache, 12 cores 20 threads) Intel Q670 Chipset 2. Memory: 8 GB DDR4-3200 MHz SDRAM (1 x 8 GB) memory slots 2 DIMM 3. Hard drive 512GB SSD (Hard Drive 2 nd 1 TB 7200 SATA HDD ) 4. 1 audio line in; 1 audio line out; 1 HDMI; 1 RJ-45; 1 VGA; 4 USB 3.0; 4 USB 2.0 5. Operating Systems: Windows 11 Pro professional 64 bit with product key License. 6. communications (intel Wi-Fi & Blue tooth) 7. Preloaded with latest version of Antivirus Symantec/ McAfee / NOD32 / e-Trust / Avast Internet Security / Kaspersky / Quick heal / eScan / Msecure with following features: Antivirus, Antispyware, intrusion Prevention Browserprotection with single management console with 3 year subscription with support updates and patches. 8. Accessories: With required connecting cables and driver media should be supplied. 9. Warranty: 3 Year Standard On-Site Comprehensive Hardware Warranty (including O.S support, Spares- Parts/Service/Labour/On-site) as required,as per specifications & as directed by Engineer In Charge . Makes:HP, DELL
Supply, Installation, Testing & Commissioning of MODbus Interface Gateway for communication with BMS / Other Utilities. MODbus shall support 22500 data points. MODbus Gateway shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of MODbus Gateway.as required,as per specifications & as directed by Engineer In Charge . Makes: NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning 24VDC Power Supply Unit for Notification Devices (i.e sounder cum strobe & directional sounder). PSU shall be monitored by FACP. PSU shall have inbuilt battery charger & shall have provision to provide sufficient battery backup for 4 hours in alarm condition. MAKE: NOTIFIER, BOSCH, EDWARDS
Supply, Installation, Testing & Commissioning of Short wave length laserbased Absolute Smoke Detection system with single pipe inlet aspiration detector for Up to 1000 m2 (10000 sq. ft.) coverage; 100m linear pipe & 130m branched pipe; Wide sensitivity range; 4 alarm levels; High efficiency aspirator; Clean air barrier optics protection; Easy to replace air filter with memory; 7 programmable relays; AutoLearn; Referencing; Event log. Alarm Threshold Setting Range: (0.005%–20% obs/m), TCP/IP & WiFi connectivity support for central monitoring & monitoring of Andriod/iOS tablets/smartphones, LED display, support for inclusion of analytics for notification regarding dust, diesel & PVC wire burning. The unit shall be seamlessly integrated with fire alarm control panel so that it can be control and monitor from fire panel.as required,as per specifications & as directed by Engineer In Charge . Make-NOTIFIER, BOSCH, EDWARDS)Approvals-UL
Supply, Installation, Testing & Commissioning of Sampling point with capillary as required,as per specifications & as directed by Engineer In Charge . Make-NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Sampling Pipe - Smooth bore UPVC or CPVC or ABS Pipe 25mm Outer Dia & 19 to 21mm Inner Dia with all required bends joints & accesories as required,as per specifications & as directed by Engineer In Charge . (approx qty of pipe) Make-NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of High level interface to integrate VESDA system with fire alarm system seamlessly as required,as per specifications & as directed by Engineer In Charge . Make-NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, Testing & Commissioning of Power supply unit with 230VAC input and 24 VDC output, support battery backup in case of AC mains failure & have built in charging circuit for batteries and with battery cabinet for mounting batteries. The power supply unit has AC input LED indication - supports 6 Nos of 12V, 12AH batteries (2 nos of batteries inside the power supply unit & 4 Nos of batteries in the battery cabinet)as required,as per specifications & as directed by Engineer In Charge . Make-NOTIFIER, BOSCH, EDWARDS)
Supply, Installation, testing & Commissioning of EN54-16 Certified IP Amplifer 600W Class-D Amplifier and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection,monitoring functions, and 2 Ethernet (RJ45) A and B for redundant installations and four local analog inputs (program / priority) of configurable sensitivity. Unit shall have following features & shall comply to technical specifications. -The IP Amplifier shall be able to connect directly over Ethernet without using any additional interface.as required,as per specifications & as directed by Engineer In Charge . Makes - NOTIFIER / BOSCH
Supply, Installation, testing & Commissioning of IP based Networkable Touch screen call station for selection of zones, supervision of system status, setting of scheduled broadcasts. The call station shall be truly IP based & do not require any server interface for system operation with the following functions: . Built-in monitoring loudspeaker . Detachable goose-neck microphone . LCD touchscreen display . Audio input as required,as per specifications & as directed by Engineer In Charge . Makes - NOTIFIER / BOSCH
Supply and Fixing of Ceiling Recessed mount Speakers with 6W impedance with power taps of 1.5W/3W/6W etc., complete. as required,as per specifications & as directed by Engineer In Charge . Makes - NOTIFIER / BOSCH
Supply and Fixing of Ceiling Surface mount Speakers+ back box with 6W impedance with power taps of 1.5W/3W/6W etc., complete. as required,as per specifications & as directed by Engineer In Charge . Makes - NOTIFIER / BOSCH
Supply, Installation, Testing and Commissioning of speakers with following specifications:12W Wall mount box Speaker+Back box if required, rated power: 12W, Tapings 100 volt line : 12/6/9WTransformer Impedance, Ohms , 100V : 1.67k/3.33k/6.66k, Frequency Response : 55-15,000 Hz SPL at 1kHz (1W/1M) : min 85dB, Color / Finish : White RAL9016 / Black. as required,as per specifications & as directed by Engineer In Charge . Makes - NOTIFIER / BOSCH .
Supply, Installation, Testing & Commissioning of IP based Central Monitoring Software for system falut monitoring from central location. Includes workstation with 21 inch LCD monitor as required,as per specifications & as directed by Engineer In Charge . Makes - HP,DELL .
Supply, Installation, testing & Commissioning of 19'' PA Rack to install head equipment like controller & amplifiers. The rack shall be floor mounted & have glass door with trolley wheels. Cooling fan on the top & cable manager, dress plates etc. ( Contractor shall furnish the quantity of required PA rack sizing based on OEM recomendation as required,as per specifications & as directed by Engineer In Charge . Make: VALRACK / RITTAL / NETRACK
TALK BACK SYSTEM CONSULE-- SITC OF MicroController Based 16 Zone Selector with Following features, (a) Feather type key pads to select the zones. (b) Moulded plastic attractive enclosure. (c )Backlight Liquid Crystal Display(LCD) (d) Userfriendly interactive display. (e) Announcement selector - PTT Switch. (f) Listen selector switch. (g) All Call switch to select all zones simultaneously for announcement (h) Built in Buzzer (i) Call station number indication software Controller Unit with (a) Builtin Power supply. (b) Zone Selector Switching Circuit (c)Terminal blocks to terminate zones ,wires, amplifier wires etc., (d) Builtin Power Supply for TB Speaker (e) CALL Monitoring Circuit (f) Additional terminal blocks for CALL & Mic signal as required,as per specifications & as directed by Engineer In Charge . Gooseneck Microphone ( Fitted in the Console ) Makes-NOTIFIER,BOSCH
TALK BACK SPEAKERS- SITC OF 6W Rated Power, 9W Maximum Power, 100V Input Line, Microphone, Call Switch, Enclosure. The cost shall include the mounting accessories. as required,as per specifications & as directed by Engineer In Charge . Makes-NOTIFIER, BOSCH)
Supply, Instalaltion, Termination, Testing and comissioning of ISI Certified (for Signal & Field devices, Third Party Integration etc....) ATSC, PVC insulated, 2Cx1.5sqmm armored, Tinned Copper, twisted, shielded, PE insulated, Cable with proper ferrules, lugs, and other necessary accessories. The spec shall meet the system manufacturer specifications including all charges complete etc., as directed by Engineer in Charge/ departmental authorities as required,as per specifications & as directed by Engineer In Charge . Makes: FINOLEX / HAVELLS / POLYCAB
With Fire Survival Cable:-Supply installation, testing and commissioning of Points wiring for signal initiating devices,control,monitor,& fault isolator (From connector box) ,speaker cabling,amlifire cabling,talk back system cabling consisting of GI JB's, pull boxes etc.& Fire survial cable equivalent to Ramfirecro-F3 Silicon Rubber insulated , Halogen Free Fire Survival cable, LPCB approved and BS 6360 compliant, of 2c 1.5 sqmm shielded & twisted Copper Multistranded for FA system with RED color, collective screen etc., (Signal,supervised power, voice, strobes,telephonic & spare) with all necessary accesssories for laying fixing, mounting,terminating etc., 1) Each signal loop shall be in independent conduits. 2) Where control & other elements form part of the detector base, separate points shall not be measured as required,as per specifications & as directed by Engineer In Charge . Makes:FINOLEX / HAVELLS / POLYCAB
Supply installation testing and commissioning of Points wiring for fire alarm signal & field devices cabling with 2Cx1.5Sq.mm FRLS shielded & twisted Copper Multistranded wires having fire retarding low smoke insulation in 25mm dia. in the existing PVC conduits in concealed/surface including all saddle ,spacers, bends, junction boxes etc. 1) Each signal loop shall be in independent conduits as required,as per specifications & as directed by Engineer In Charge . Make:FINOLEX / HAVELLS / POLYCAB
Supply installation testing and commissioning of Points wiring for speaker cabling, amplifier cabling with 2Cx1.5Sq.mm FRLS shielded & twisted Copper Multistranded wires having fire retarding low smoke insulation in 25mm dia in the existing PVC conduits in concealed/surface including all saddle ,spacers, bends, junction boxes etc. 1) Each signal loop shall be in independent conduits as required,as per specifications & as directed by Engineer In Charge . Make:FINOLEX / HAVELLS / POLYCAB
Supply and Fixing of 20mm dia 1.95-2.1mm thick Heavy grade with IS:9537 part 3 rigid P.V.C. pipe (ISI MARK) concealed in wall with all required accessories accessories such as junction boxes, conduit , bends, elbows and ceiling rose, with all necessary fixing accessories like mounting screws .clamps etc. including all labour charges etc., complete for DATA / Telephone / ACS / CCTV / FAVA and as directed by Engineer In Charge. Makes: PRECISION / VIP / POLYCAB
Supply and Fixing of 20mm dia 1.95-2.1mm thick Heavy grade with IS:9537 part 3 rigid P.V.C. pipe (ISI MARK) concealed in wall with all required accessories accessories such as junction boxes, conduit , bends, elbows and ceiling rose, with all necessary fixing accessories like mounting screws .clamps etc. including all labour charges etc., complete and as required & as directed by Engineer In Charge and as per aproved make. Makes: PRECISION / VIP / POLYCAB)
Supply, laying, testing & commissioning of 4C x 0.75 sq.mm Cu XLPE/PVC insulated & PVC sheathed unarmoured control cables of 1.1 KV grade with copper conductor as per IS 7098 Part-I -1988 etc complete as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and as required,as per specifications & as directed by Engineer In Charge . Makes:POLYCAB / RR KABEL / KEI / HAVELLS)
Supply, laying, testing & commissioning of 8C x 0.75 sq.mm Cu XLPE/PVC insulated & PVC sheathed unarmoured control cables of 1.1 KV grade with copper conductor as per IS 7098 Part-I -1988 etc complete as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and as required,as per specifications & as directed by Engineer In Charge . Makes:POLYCAB / RR KABEL / KEI / HAVELLS)
Supply and Fixing of 20mm dia 1.95-2.1mm thick Heavy grade with IS:9537 part 3 rigid P.V.C. pipe (ISI MARK) concealed in wall with all required accessories accessories such as junction boxes, conduit , bends, elbows and ceiling rose, with all necessary fixing accessories like mounting screws .clamps etc. including all labour charges etc., complete and as required & as directed by Engineer In Charge and as per aproved make. Makes: PRECISION / VIP / POLYCAB)
Supply, installation, testing and commissioning of Cat 6a , 4 Pair UTP LSZH Cable for data points from floor network switches to each data points as per drawings as required,as per specifications & as directed by Engineer In Charge, for ELV, CCTV, ACS, FAPA, etc complete. Makes: PANDUIT, STL, SYSTIMAX)
Supply, installation, testing and commissioning of Cat 6A I/O modjack(RJ45) for Voice as required,as per specifications & as directed by Engineer In Charge . Makes: PANDUIT, STL, SYSTIMAX)
Supply, installation, testing and commissioning of Single faceplate for I/O (For Data & Voice) as required,as per specifications & as directed by Engineer In Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply, installation, testing and commissioning of Dual module faceplate for I/O (For Data & Voice) as required,as per specifications & as directed by Engineer In Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply, installation, testing and commissioning of Quad module faceplate for I/O (For Data & Voice) as required,as per specifications & as directed by Engineer In Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply, installation, testing and commissioning of GI Back Box for I/O as required,as per specifications & as directed by Engineer In Charge . Makes: LEGRAND (ARTIOR/MYRIUS) / SCHNEIDER-UNICA / CRABTREE (MURANO/APOGEE)
Supply, installation, testing and commissioning of Cat6A 7ft Patch Cord ( Fieldside ) for Voice as required & as directed by Engineer In Charge and as per aproved make. Makes: PANDUIT, STL, SYSTIMAX)
Supply, laying ,testing and commissioning of 4-pair, Cat6 Solid (Third party ETL Intertek tested up to 600 MHZ ) to support 1Gbps with Cross (+) filler pair separator & PVC sheath 23 AWG, STP/UTP Cable , Meets or exceeds ANSI/TIA-568.2-D and UL Listed &RoHS Compliant in the existing raceways /PVC conduits including making connections to information outlets and patch panels with ferruling at both ends for identification with necessary tools for punching stripping crimping and testing required etc., complete. Makes: PANDUIT / STL / SYSTIMAX
Supply, installation, testing and commissioning of Cat6A I/O modjack(RJ45) for Data as required & as directed by Engineer In Charge and as per aproved make. Makes: PANDUIT / STL / SYSTIMAX
Supply, installation, testing and commissioning of Cat6A 7ft Patch Cord ( Fieldside ) for Data as required & as directed by Engineer In Charge and as per aproved make. Makes: PANDUIT, STL, SYSTIMAX)
Supply and Fixing of 25mm outer dia (1.60 to 1.80)mm thicknes medium grade with IS:9537 part 3 FRLS rigid Surface P.V.C. pipe (ISI marked) on wall/ceiling/cable with all required PVC Junction Boxes confirms to IS : 3419 and all accessories fixing on chromium plated metallic base saddles for run of mains including all labour charges etc., complete. DATA / Telephone / ACS / CCTV / FAVA/ Rodent control etc., complete. Makes: PRECISION / VIP / POLYCAB)
Supply and Fixing of 20mm outer dia (1.40 to 1.55)mm thicknes medium grade with IS:9537 part 3 FRLS rigid P.V.C. pipe (ISI marked) concealed in wall/ceiling/cable with all required MS junction boxes and all accessories including masonary work for DATA / Telephone / ACS / CCTV / FAVA/ Rodent control run of mains including all labour charges etc., complete.. Makes: PRECISION / VIP / POLYCAB)
Supply installation testing and commisioning Outdoor, steel tape armoured multimode glass Fiber Optic Cable as per latest ammendments of TIA /EIA 568B.3 , GR 20 CORE/ UEC 794-1/ EN 187000 Standards in existingMSPVC Conduits/ hume pipe including making terminations to active passive equipments with ferruling at both ends for identification with necessorry tools for Terminations and testing required as required & as directed by Engineer In Charge and as per aproved make.6 Core Multimode Outdoor Armoured Fiber Optic Cable FOR DATA AND VOICE NETWORKING SYSTEM & Security system Makes: PANDUIT, STL, SYSTIMAX
Supply installation testing and commissioning Outdoor, steel tape armoured Single mode [9/125um] glass Fiber Optic Cable as per latest amendments of TIA /EIA 568B.3 , GR 20 CORE/ UEC 794-1/ EN 187000 Standards in existing MSPVC Conduits/ hume pipe including making terminations to active passive equipment with ferruling at both ends for identification with necessary tools for Terminations and testing required as required & as directed by Engineer In Charge and as per aproved make.6 Core Single Mode Outdoor Armoured Fiber Optic Cable FOR DATA AND VOICE NETWORKING SYSTEM& Security System Makes: PANDUIT, STL, SYSTIMAX
Supply installation testing and commisioning Outdoor, steel tape armoured multimode glass Fiber Optic Cable as per latest ammendments of TIA /EIA 568B.3 , GR 20 CORE/ UEC 794-1/ EN 187000 Standards in existingMSPVC Conduits/ hume pipe including making terminations to active passive equipments with ferruling at both ends for identification with necessorry tools for Terminations and testing required as required & as directed by Engineer In Charge and as per aproved make.12 Core Multimode Outdoor Armoured Fiber Optic Cable FOR DATA AND VOICE NETWORKING SYSTEM & Security System Makes: PANDUIT, STL, SYSTIMAX
Supply installation testing and commissioning Outdoor, steel tape armoured Single mode [9/125um] glass Fiber Optic Cable as per latest amendments of TIA /EIA 568B.3 , GR 20 CORE/ UEC 794-1/ EN 187000 Standards in existing MSPVC Conduits/ hume pipe including making terminations to active passive equipment with ferruling at both ends for identification with necessary tools for Terminations and testing required as required & as directed by Engineer In Charge and as per aproved make.12 Core Single Mode Outdoor Armoured Fiber Optic Cable FOR DATA AND VOICE NETWORKING SYSTEM & Security System Makes: PANDUIT, STL, SYSTIMAX
Supply, installation, testing & commissioning of Microprocessor based Master Controller with 16X2 LCD DISPLAY capable of operating in 4 ultrasonic frequency band spectrums. The controller should support upto 20 transducers in dedicated connection & 24 transducers in single loop @300 sq.ft each for Room Void Area & 150 sq.ft each for Ceiling & Floor Void each and networkable on RS 485 having facility to support Hardwired Third Party BMS integration via Modbus & potential free NO-NC contacts. The system shall use UL and CE approved transformers for power supply as required & as directed by Engineer In Charge and as per aproved make. ( Make: LG, SAMSUNG)
Supply, Installation, Testing & Commissioning of Transducer (Each transducer should cover an area upto 300 sq.ft in Room Void and 150 sq.ft in Ceiling & Floor Void. Looping permitted. Transducer produce high decibel sound waves at very high frequency not less than 20 Khz.) for Ceiling , above celling with all required mounting/fixing accessories, termination etc.as required & as directed by Engineer In Charge and as per aproved make Make-Maser/R-scat/Earth innovations
Supply, Installation, Testing & Commissioning of Bracket ( MS Powder Coated ) for installtion of each controller along as required,as per specifications & as directed by Engineer In Charge .
Supply, laying, testing & commissioning of 2C x 0.75 sq.mm Cu XLPE/PVC insulated & PVC sheathed unarmoured control cables of 1.1 KV grade with copper conductor as per IS 7098 Part-I -1988 etc complete as required and as directed by Engineer In Charge/departmental authorities as per detailed technical specifications and as required,as per specifications & as directed by Engineer In Charge . Makes:POLYCAB / RR KABEL / KEI / HAVELLS)
Supplying, fabricating, laying and connecting the 100x38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc completeas required,as per specifications & as directed by Engineer In Charge and as per approved make Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying, fabricating, laying and connecting the 150mm x 38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete as required,as per specifications & as directed by Engineer In Charge and as per approvedMakes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supplying, fabricating, laying and connecting the 300mm x 38mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete as required,as per specifications & as directed by Engineer In Charge and as per approved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying, fabricating, laying and connecting the 100mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc completeas required,as per specifications & as directed by Engineer In Charge and as per approved make . Makes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supplying, fabricating, laying and connecting the 150mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete as required,as per specifications & as directed by Engineer In Charge and as per approved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supplying, fabricating, laying and connecting the 300mm x 25mm GI Raceways of 2.0mm. thick with top cover and required hard ware etc complete aas required,as per specifications & as directed by Engineer In Charge and as per approved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL
Supplying & Installation of 172mm x 52mm G.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways as required,as required,as per specifications & as directed by Engineer In Charge and as per approved make Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying & Installation of 222mm x 52mmG.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways as required,as required,as per specifications & as directed by Engineer In Charge and as per approved make Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Supplying & Installation of 372mm x 52mm G.I. Junction box of 2mm thick for direct acces to cables at the inter section of Raceways as required,as per specifications & as directed by Engineer In Charge and as per approved Makes: PROFAB / APARNA ROLLFORM / GLOMETAL)
Design, Supply, Installation, Testing and Commissioning (SITC) of 185 KLD Sewage Treatment Plant based on MBBR Technology with 55 KLD Ultra Filtration (UF) System, complete with all mechanical, electrical, piping, instrumentation, controls and accessories required for satisfactory operation. The system shall include coarse and fine bar screens, raw sewage transfer pumps (1 Working + 1 Standby), air blowers (1W+1S), aeration grids for raw sewage tank, MBBR bio media, aeration grid / diffusers for MBBR tank, alum dosing system with tank and dosing pump, aeration grid for sludge tank, sludge recirculation pumps (1W+1S), filter feed pumps (1W+1S), pressure sand filter, activated carbon filter, water softener suitable for inlet hardness 300 mg/l and outlet hardness < 50 mg/l, sludge dewatering centrifuge with feed pump, tubular settlers for secondary clarifier, interconnecting piping and fittings, anoxic mixer, ozonation system, hypochlorite dosing system, electrical control panel with instrumentation, cables and cable trays, inlet and outlet electromagnetic flow meters, oil skimmer, and Ultra Filtration (UF) system of min 55 KLD capacity including circulation pump, feed pumps (1W+1S) and backwash pumps (1W+1S) complete with UF membranes, valves, piping, instruments and controls. The scope shall include interconnecting pipelines, valves, supports, electrical wiring, control panels, instrumentation, testing, commissioning, trial run and performance testing, including all accessories required for complete functioning of the STP system. All equipment shall be from approved makes such as Lubi / Xylem / KSB / Kirloskar for pumps; Airvak / Everest / Usha / Akash for blowers; Tata / Pentair / Hydropure for filtration systems; E Dose / Sintex for dosing systems; Aquateck / Cooldeck for tube settlers; Amsons / Scaler for ozonation; Aster / Shenitec / Kamstrup for flow meters; Veolia / Hitech / Dow for UF membranes; and other reputed fabricated makes as specified. The STP shall be designed to treat 185 KLD sewage and produce treated water meeting CPCB / State Pollution Control Board discharge standards suitable for reuse in flushing, gardening and cooling tower make:THERMAX/ION EXCHANGE
Design, Supply, Installation, Testing and Commissioning (SITC) of complete Water Treatment Plant (1 Stream) suitable for treatment of local tanker water considering worst inlet water quality and producing treated water conforming to IS 10500:2012 drinking water standards, comprising of raw water transfer pumps (12.5 m³/hr at 35 m head – 2 Nos., 1W+1S) with TEFC motors, Pressure Sand Filter (12.5 m³/hr) and Activated Carbon Filter (14 m³/hr) with FRP vessels (42"×72"), water softening unit with resin media, multiport valve and 500 L brine tank (OBR 1,40,000 L, inlet hardness 350 ppm), UV sterilization system (0–14 m³/hr), complete with UPVC Sch-40 interconnecting piping, valves, fittings, supports, MCC / power & control panel (IP55, BMS compatible), cables, cable trays, instruments, accessories, testing, commissioning and trial run, all complete as required for satisfactory operation of the system.make:THERMAX/ION EXCHANGE
Development of BIM Model – LOD 350 for Architecture and MEPF & ELV services, and LOD 400 for key spaces/details
Development of BIM Model and extraction of coordinated GFC drawings for Architecture and MEPF & ELV services, including review of MEPF & ELV shop drawings
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
MEP High Court Bid Document.pdf
TENDER_DOCUMENT • 2.37 MB
HC BOQ final.xlsx
TENDER_DOCUMENT • 0.34 MB
HC MEP BOQ.pdf
TENDER_DOCUMENT • 1.11 MB
SL-291 SINGLE LINE SCHEMATIC DIAGRAM - VENTILATION PANEL SL-291-EL0-060.pdf
TENDER_DOCUMENT • 2.26 MB
SL-291 _ AMARAVATI HIGH COURT FA SCHEMATICS FIRE A SCHEMATIC.pdf
TENDER_DOCUMENT • 1.93 MB
SL-291 _ AMARAVATI HIGH COURT - SINGLE LINE SCHEMATIC DIAGRAM - AHU PANEL SL-291-EL0-056.pdf
TENDER_DOCUMENT • 1.34 MB
SL-291 _ AMARAVATI HIGH COURT EARTHING SYSTEM SCHEMATIC DIAGRAM SL-291-EL0-051.pdf
TENDER_DOCUMENT • 0.72 MB
SL-291 _ AMARAVATI HIGH COURT PA SCHEMATIC PUBLIC A SCHEMATIC.pdf
TENDER_DOCUMENT • 1.39 MB
SL-291 _ AMARAVATI HIGH COURT SCHEMATIC DIAGRAM - TERTIARY CHILLED WATER PUMP PANE SL-291-EL0-059.pdf
TENDER_DOCUMENT • 0.25 MB
SL-291 _ AMARAVATI HIGH COURT TYP.SINGLE LINE DIAGRAM-1.pdf
TENDER_DOCUMENT • 7.20 MB
SL-291 _ AMARAVATI HIGH COURT- SINGLE LINE SCHEMATIC DIAGRAM - PLUMBING PANEL SL-291-EL0-058.pdf
TENDER_DOCUMENT • 0.69 MB
SL-291-DRC-99.pdf
TENDER_DOCUMENT • 4.62 MB
SL-291-DRC-99A.pdf
TENDER_DOCUMENT • 2.48 MB
SL-291-FF-99.pdf
TENDER_DOCUMENT • 1.98 MB
SL-291-FF-99A.pdf
TENDER_DOCUMENT • 1.41 MB
SL-291-MH-099-HC BASEMENT FLOOR HVAC LAYOUT SL-291-MH-099.pdf
TENDER_DOCUMENT • 3.07 MB
SL-291-MH-100-HC GROUND FLOOR HVAC LAYOUT SL-291-MH-100.pdf
TENDER_DOCUMENT • 10.66 MB
SL-291-WS-99.pdf
TENDER_DOCUMENT • 0.96 MB
SL-291 - AHU DATA SHEET _DX TYPE.pdf
TENDER_DOCUMENT • 0.59 MB
SL-291 - AHU DATA SHEET_CHW TYPE.pdf
TENDER_DOCUMENT • 1.46 MB
SL-291 - AHU-TOILET EX AND KITCHEN FA FAN DATA SHEET.pdf
TENDER_DOCUMENT • 0.46 MB
SL-291 - Heat Recovery data sheet.pdf
TENDER_DOCUMENT • 0.67 MB
SL-291 - KITCHEN DRY SCRUBBER & EX FA DATA SHEET.pdf
TENDER_DOCUMENT • 0.02 MB
SL-291 - PUMPS DATA SHEET.pdf
TENDER_DOCUMENT • 0.50 MB
SL-291 - VENTILATION FAN DATA SHEET.pdf
TENDER_DOCUMENT • 1.00 MB
HIgh court lift-_D2E_VT schematic.pdf
TENDER_DOCUMENT • 0.66 MB
High Court-Escalator scheme.pdf
TENDER_DOCUMENT • 0.04 MB
High_Court-ELV_Tech_Spec.pdf
TENDER_DOCUMENT • 1.67 MB
High_Court-Fire_fighting_technical_specification.pdf
TENDER_DOCUMENT • 0.68 MB
High_Court-HVAC_TECHNICAL__SPECIFICATION-15.04.2026.pdf
TENDER_DOCUMENT • 1.91 MB
High_Court-PLUMBING_WORKS_-_13.04.2026.pdf
TENDER_DOCUMENT • 1.23 MB
High_Court_-ELECTRICAL_SPECS.pdf
TENDER_DOCUMENT • 3.52 MB
Lift_D2E_VT Specification_Amravathi.pdf
TENDER_DOCUMENT • 0.98 MB
Design_Specification.pdf
TENDER_DOCUMENT • 0.09 MB
High Court, Amaravati. - MEP DBR - R4.pdf
TENDER_DOCUMENT • 2.79 MB
Preferred Makes for MEP works.pdf
TENDER_DOCUMENT • 0.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .