| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.9 LAccepted-AOC | L1 | Accepted-AOC OK | |
| 2 | L2₹39.2 L+₹31,700 (0.82%)Rejected-AOC | L2 | Rejected-AOC OK | |
| 3 | L3₹41.0 L+₹2.1 L (5.42%)Rejected-AOC | L3 | Rejected-AOC OK | |
| 4 | L4₹41.6 L+₹2.7 L (7.06%)Rejected-AOC 20 8 EWS PREETAM NAGAR COLONY ALLAHABAD | PRAYAGRAJ | UTTAR PRADESH | 211001 | L4 | Rejected-AOC OK | |
| 5 | L5₹42.0 L+₹3.1 L (8.05%)Rejected-AOC | L5 | Rejected-AOC OK |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
7 Sept 2021, 6:00 pmClosed
GE WEST BAREILLY
GE WEST BAREILLY
REPAIR/MAINT OF LT PANEL, LT FEEDER PILLER BOX, LT SWITCH GEAR AND ALLIED WORKS AND IMPROVEMENT TO E/S INSTALLATION UNDER GE (W) BAREILLY.
2021_MES_468814_1
8952/C/E8
Open Tender
Civil Works
Item Rate
180 days
GE WEST BAREILLY
SCANNED COPY OF ENLISTMENT LETTER IN MES IN RELEVANT CLASS CATEGORY SCANNED COPY OF APPLICATION ON LETTER HEAD OF FIRMSCAN COPY OF DD OF RS 500.00 IN FAVOUR OF GE WEST BAREILLY FROM ANY NATIONALISED OR SCHEDULED BANK SCANNED COPY OF REGISTRATION
6 documents required · 6 mandatory
₹500
Yes
GE WEST BAREILLY
₹80,000
Yes
18 Sept 2021
17 Aug 2021
9 Sept 2021
17 Aug 2021
7 Sept 2021
1 Sept 2021
17 Aug 2021 - 31 Aug 2021
Amount
M & L fabrication of MS busbar chamber of nominal dimension 900 mm x 600 mm x 400 mm duly provided with aluminimum busbar of size 50 mm x 6mm fixed on porcelain insulators TPN type out door weather/vermin proof with both way opening duly provided with neoprene rubber gasket along the doors openings pedestal type duly painted powder coated on CRCA steel sheet encloser with one No incommer MCCB 250 Amp 25 KA incl making connection /thimbles complete all as sepcified and directed
All as per Item Ser No 01 here-in-before but of size 600 mm x 600 mm x 300 mm and without MCCB.
M&L for preparing old painted surface of LT Panel board indoor/outdoor type of any size but not less than 1.2 x 1 x .4 mtr by cleaning removing of the old paint by scrathing with wire brush/sand paper etc and including minor repair to panel in different location where required with arc/gas welding with replacement of hinges and place the door in original position denting/patching of broken/rusted surfaces etc and apply two coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed by Engr-in- charge.
S&F in repair MCCB 415 Volts 4 pole 500 Amps 50 Hz 50 KA alongwith spreader terminal with adjustable thermal setting including lugs/thimbles of suitable size in existing panels complete all as specified and directed by Engr-in-Charge. Make L&T/Legrand /Indoasian/C&S. Note :- Necessary addition /altration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
All as per Item Ser No 7 here-in-before but of MCCB 400 Amps 4 pole 50 Hz 415 V, 36 KA
All as per Item Ser No 7 here-in-before but of MCCB 250 Amps 4 pole 50 Hz 415 V, 25 KA
All as per Item Ser No 7 here-in-before but of MCCB 200 Amps 4 pole 50 Hz 415 V, 25 KA
All as per Item Ser No 7 here-in-before but of MCCB 160 Amps 4 pole 50 Hz 415 V, 25 KA
All as per Item Ser No 7 here-in-before but of MCCB 125 Amps 4 pole 50 Hz 415 V, 16 KA
All as per Item Ser No 7 here-in-before but of MCCB 100 Amps 4 pole 50 Hz 415 V, 16 KA
S&F in replacement Isolator 4 pole 100 Amps, 415 Volts complete all as specified and directed by Engr-in-Charge. Make : L&T/Legrand /C&S.
All as per Item Ser No 14 here-in-before but 63 Amps, complete all as specified and directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles complete all as specified and directed.
Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed.
Removing of excavated soft/loose soil not exc 50 m & depositing where as directed at a level n.exc 1.5 m above from starting point completed all as specified and directed.
Taking out old defective cable from trenches/ floor/road/wall/pipe/pole /service connections of any size , testing with LT magger , seggregating the serviceable part of cables and store for relaying complete all as specified & directed. Note : Excavation and earth work will be paid and measured sepertely in relevant item.
Supply and laying in replacement of OH ACSR Conductor / XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor 1100 volt grade, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe of cross sectional area 240 Sq mm 3.5 core all as specified and directed. Note :- Rate deemed to be inclusive of connection including cable glands and lugs.
All as per Ser item No 25 here-in-before but 185 Sq mm 3.5 core
All as per Ser item No 25 here-in-before but 150 Sq mm 3.5 core
All as per Ser item No 25 here-in-before but 120 Sq mm 3.5 core
All as per Ser item No 25 here-in-before but 95 Sq mm 3.5 core
All as per Ser item No 25 here-in-before but 25 Sq mm 4 core
Relaying only serviceable LT UG Cable obtained from Srl item No 25 of any size and discription including necessary cable lugs. Note :- All relevent items like excavation, earth work tc shall be paid and measured seperatly.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches, punning complete all as specified and directed Note:- Punning thickness of 18 cm will be considered for payment.
M & L for brick protection to cable using old size sub class 'B' bricks, laid flat/lengthwise perpendicular to the axis of cable all as specified & directed.
M&L Cutting of floor/wall/road/footpath for removal of LT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable and all as specified & directed.
M&L for Boring of holes under road /pavement/hard standing or any other situation by mannual means for 100/80 mm bore at the depth not less than 1 mtr below ground level for crossing the cable and making good both the ends all as specified and directed. Note :- GI pipe shall be measure and paid separately under respective item.
S&F in repair machine pressed precast interlocking paver block with grey cement and pigment any shape and size confirming to IS 15658-2006 of 80 mm thickness M- 40 Grade over and including 20 mm thick sand filling complete all as specified and directed.
M&L for PCC (1:3:6) type C2 using (40 mm graded aggregate in foundation, filing and mass concrete complete all as specified and directed.
S & F in replacement GI pipe light grade of following dia for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. (a) 50 mm dia
(b) 80 mm dia
(c) 100 mm dia
S&F in repair loop-in-loop out box of size 30x20x20cm made out from 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door and locking arrangements with slanting cover on top and provision of 4 Nos aluminium bus bar of size 25mm x 2mm-4 Nos fixed on insulator and one MCB of capacity 6 Amps complete fixed on pole with and including suitable size MS flat iron clamps, nuts,bolts & washers etc complete all as specified and directed
M&L for spraying chemical (Roundup) on area to remove unwanted vegitation / grass at E/M installations / 2 pole/ 4 pole structures complete all as specified and directed. Note : Labour and equipments to spray chemical on required area are inclusive in quoted rate.
Dismantling and taking down of LED/Street light/ Bollard Light of any cap any size any make complete all as specified and as dierected.
Supply and fix new generation energy saving & environmental friendly long life versatile pressure die- cast aluminium IP 66 roadway luminaire with high power LED as light source and electronic driver of following capacity including necessary connections from Junction box to Light alongwith necessary conduit pipe and 2.5 sqmm aluminum conductor complete all as specified and as directed. Make : Crompton/C&S/Polycab (a) 60 Watt
(b) 72 Watt
(c) 90 Watt
S&F in replacement light fitting JETAIRIS Energy saving environmental friendly, exclusive innovative designed, long life versatile pressure die cast aluminium IP-66 flood light luminaire with high power LED 150 W. Make : Havells or equivalent
All as per Item Ser No 43 but rectangular flood light LED 120W.
S& F in replacement LED Bollard light 8 watt in cylindrical shape with opal acrylic diffuser and IP65 protection, all as per directed by Engr In Charge
Supply ,fixing ,commisioning and testing of Nature timer switch control Street Lights complete with MCB, Power and Panel duly complete with wiring Model : SWADEEP-02EC 12KW3P, three phase, max load 12KW or equivalent of other make complete all as specified and directed.
Lopping / prooning of tree branches upto the extend to obtain clearance all around the LT/HT over head lines conductor upto 3 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed. Note:- (a) Tools & plants including safety measures equipments like belt, ladder & ropes etc shall be arranged by the contractor at own cost. (b) Contractor supervisor will take proper shut down before starting the work and clear it before resuming power supply, however full assistance will be provided by MES Staff.
M&L for earthing complete with galvanised iron steel earth plate of size 600 x 600 x 3.15 mm thick burried directly in ground (earth pit not less 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below ground level connected to thick electrode and 32x6 mm GI strip as earthing by means of nuts bolts check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore (medium grade) and connected to main switch board or main control board as directed and including concrete pit in PCC (1:3:6) type C1 precast RCC cover slab 54 x 54 cm x 5 cm with reinforcement with 8 mm TMT bars @ 150 C/C with one handle and funnel for watering charcoal or coke and salt in alternate layers & necessary earth work in soft/loose soil complete all as shwon in electrical plate No 5 of SSR Part-I including testing on completion all as specified and directed.
S&F electric shock treatment chart of size approx 3ft x 2ft & 6 mm thick plywood with teak wood frame and covered with glass complete all as specified and directed.
S&F of notice board of size approx 4 ft x 3 ft duly fixed with 6 Nos clips for display of instructions with aluminum frame including covered with plastic laminated sheet complete all as specified and directed.
S&F fire retardant/ extinguishing Electric Insulated Synthetic mat" INSULATICA 2000" of size 2 mtr x 1 mtr x 2 mm thick ± 10% conforming to BIS : DOC.NO ETD-02(5229) P DT D30/06/03, meeting requirements of IS:3043,IS:5216 (Part-1,2&3), IS-8437 and IEC 479 Pub-1, 61111 & 61112, Tested for break down strength,Tensile/ Elongation, Ageing properties, Insulations Resistance, effects of Acid-Alkaline, Diesel and Transformer oil, Leakage Current Test, FireTest etc having Min, width of 1000mm ± 20mm.All alllied material such as Pu-Resin, Chemi Bound (Hardner), Spl PVC Adhesive, Liquid Primer etc as per site requirement, suitable for 11000 Volts complete all as specified and directed .
Supply only cable twin core PVC insulated and unsheathed multistranded aluminium conductor of size 2.50 Sqmm complete all as specified and directed.
S&F in repair off load change over switch three phase, Four pole with enclosure capacity 400 Amps with side handle operated complete all as specified and directed by Engineer-in-charge.
All as per Ser item No 53 here-in-before but capacity 200 Amps complete all as specified and directed
S&F in replacement 1100 volts grade PVC insulated aluminium conductor screened served with inner sheathed in service connection flat twin core cable of size 10 sqmm complete all as specified and directed.
All as per Ser item No 55 here-in-before but 06 sqmm complete all as specified and directed
Supply only LT PVC electrical insulation tape roll 25 mtr x 17 mm long (Pack of 10 taps) multicolour ISI marked.
Note : (i) Complaints pertaining to LT External Electric Supply shall be resolved by the contractor immediatelly after getting complaints. In case of failure on the part of contractor to resolve to the complaints within stipulated time, a penalty of Rs 1000/- per day per complaint shall be imposed from the contractor. (ii) A register shall be maintained to record all orders & instructions and their complaints and is to be signed by the contractor/his representative and the Engineer-in-charge/JE E/M concerned. (iii) Work done register to be maintained by the contrator. A separate Docket complaints slip book shall maintained by the contractor to note the complaints/jobs and get it signed by the user after completion of work and submits to the JE-in-Charge.
Ishtiaq and Sons
M/S HINA ELECTRICALS
Mohit Enterprises
R.S ENGINEERING TRADERS
M/S Gupta and Company
prabhave traders
M/S ARORA ENTERPRISES
M/S Gupta Builders
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .