Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.8 LAccepted-AOC | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹24.8 L+₹3.2 L (14.8%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L2 | Rejected-Finance HIGHEST | |
| 3 | L3₹25.3 L+₹3.7 L (17.1%)Rejected-Finance | L3 | Rejected-Finance HIGHEST | |
| 4 | L4₹26.9 L+₹5.4 L (24.8%)Rejected-Finance 0 NEAR SHIV MANDIR KALYANIPURA KRIPAL NAGAR AJMER RAJASTHAN 305001 UDYAM RJ 01 0091182 | AJMER | RAJASTHAN | 305001 | L4 | Rejected-Finance HIGHEST | |
| 5 | L5₹30.3 L+₹8.8 L (40.7%)Rejected-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L5 | Rejected-Finance HIGHEST |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
17 Sept 2020, 6:00 pmClosed
SHRI T C SHISHODIYA, DCWE(C)
MULTAN LINE ARMY AREA JODHPUR-342010 (RAJ)
Repair and Maintenance and Calibration of 33 KV and 11 KV Switch Gears, RMU, Outdoor CTs and PTs at Army Area Jodhpur
2020_MES_369807_1
CWE (A) JODH-70 OF 2020-21
Open Tender
Civil Works
Item Rate
150 days
Army Area Jodhpur
4 documents required · 4 mandatory
₹500
GE(Army) Utility
₹60,000
Yes
16 Feb 2021
17 Aug 2020
18 Sept 2020
17 Aug 2020
17 Sept 2020
3 Sept 2020
Amount
Cleaning, servicing and testing complete HT 33 KV switch yard, various equipment, over head line, CT, PT, Isolator, DO fuse etc complete way at Power House all as specified and directed by EIC for the following :- (a) line isolator, 33 KV (Horizontal type) :- Servicing of line isolator (Horizontal break outdoor type) including cleaning of contact (knife) by CTC liquid, proper lubrication greasing on contacts & moving rod / handle for proper function of moveable rod for smooth ON / OFF position and checking the incoming and outgoing connection (terminal lugs to be replaced if required) and testing with following. (i) Carrying out Insulation testing between phase to phase& phase to earth shall be carried out all as directed by Engr-in-Charge.
M&L for General Servicing & Testing 33 KV Outdoor Circuit Breaker including indoor control panel (Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination, repair/testing of AC/DC wiring from Outdoor VCB to Indoor control panel for smoothly operation etc). complete all as specified and directed by Engr-in-Charge on site.
M&L for General Servicing & Testing 11 KV Flusarc Circuit Breaker, CT and PT (Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ) complete all as directed by Engr-in-Charge.
M&L for General Servicing & Testing 11 KV FBX RMU (01 incomer 02 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination) Make: Schneider Type : FBX-E / 12-21/M+T2+T2+T2+Xb,630 A. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV RMU (01 incomer 03 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination) with replacement of unserviceable/damaged wiring and making connection of AC/DC supply complete all as directed by Engr -in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV RMU (01 incomer 02 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ), 630 Amp complete all as directed by Engr-in-Charge. Note : Complete breaker (Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV RMU (02 incomer 03 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ), 630 Amp complete all as directed by Engr-in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV RMU (02 incomer 02 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ), 630 A complete all as directed by Engr-in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV RMU (02 incomer 04 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ), 630 Amp complete all as directed by Engr-in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General Servicing & Testing 11 KV FBX RMU (01 incomer 02 out going) ( Cleaning, IR Value check, CRM test , Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination), 630 Amp complete all as directed by Engr-in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
M&L for General servicing and testing of 11KV VCB ( Ceaning, IR Value chech, CRM test and open / close time test rackin /rackout Electrical and mechanical operation check incuding secondary injection test on overcurrernt and earth fault relay and time coordination) complete all as directed by Engr-in-Charge. Note : Complete breaker ( Incoming and outgoing) considered as one complete Job.
Material and labour for repair/ replacement of defective control wiring of current transformers , ampere meter, voltmeter, potential transformers, circuits of indoor/Outdoor type 33/11 KV VCB'S using 2.5 sqmm copper flexible PVC insulated wire and suitable size of copper lugs and thimbles and connector all as directed at site by Engr-in-Charge. Note : Complete breaker (Incoming and outgoing) considered as one complete Job.
Material and labour for replacement of U/S Bekalite base and fuse grip 32 Amps incl fuse link suitable for control wiring of 11 KV VCB'S. Make : As per Sample
Material and labour for replacement of U/S breaker control switch suitable for 11 KV RMU/VCB.
Material and labour for replacement of 3 pole, 2 NO/2NC of 45 A of auxilary contactor 110 Volt DC supply used for protection of earth fault and over current relay . Make : Siemens, L&T, Schneider.
supply and fixing in repair of LED type indicator lamp (Red/Blue/Yellow) suitable for 110 Volt DC in OCB's/VCB's.
Material and labour for replacement of unserviceable tripping/ closing coil 24/110 Volt DC Supply suitable for 11 KV OCB/VCB/RMU.
All as per item No 18 above but for 33 KV OCB/VCB/RMU of any Make .
M & L for replacement of maintenance free battery 12 Volts, 20 AH complete connected in series suitable for battery bank. Make -Exide or Amaron
Surface excavation not exceeding 30 cm and averaging 15 cm in depth for levelling and cleaning of area at Sub Stn including removing of shrubs and bushes in soft/loose soil all as directed at site.
Material and labour in replacement of unserviceable end jointing kit, outdoor type heat shinkable, 120 - 185 Sqmm, 3.0 Core suitable for 33 KV 3 Core, XLPE electric cable complete all as specified and directed: (Make: Reychem/Birla 3M/M seal)
All as per item No 22 above but indoor type
All as per item No 22 above but straight through type
Dismantling of Unserviceable steel structure, cross arms , bracings , supports, clamps from Two/Four pole structure at various locations all as directed.
Supplying, fabricating & fixing structural mild steel channel, angle iron, flat iron and brackets etc for fabrication of cross arms, bracings, supports, D-clamps, stiffeners, eye hooks, bolts, pole clamps and plates including nuts, bolts and washers, welding cold or hot drilling holes for insulators bolts in any shape or size, and febrication of 33 KV tower as per existing height as indicated or directed and inclusive of one red oxide prime coat, one under coat and one finishing coat of aluminium paint complete (Insulators to be measured and paid for separately under respective items).
Material and labour in replacement of Set of ring core protection (Cl.5P10) CTs capable of handling 2.5 VA burden, CTR 40-20/1A, set of three for 33 KV RMU complete all as directed by Engr-in-Charge. (Location -Ajmer line & Shikargarh Power House 33 KV RMU)
Material and labour in replacement of existing unserviceable Bus bar of 33 KV outdoor type RMU, set of three complete with 36 KV insulation Boot, earthing connection etc complete all as specified and directed by Engr-in-Charge. (Location - Shikargarh Power House 33 KV RMU, Make Schneider). Note : Contractor should visit the site to know the exact scope of the job for above item of BOQ before quoting rates. No claim arising out of any error or inaccuracy in understanding the scope of work shall be entertained.
Material and labour in replacement of existing unserviceable end termination jointing boots of 33 KV RMU indoor type, set of three complete with 36 KV insulation complete all as specified and directed by Engr-in-Charge.
Material and labour in replacement of Set of ring core protection (Cl.5P10) CTs capable of handling 2.5 VA burden, CTR 100-50/1A, set of three for 11 KV RMU complete all as directed by Engr-in-Charge.
Material and labour for repair/rewinding of spring charging motor for Indoor/outdoor type, 33 KV, VCB,operated on 230 volts AC/ DC complete all as specified and directed by EIC.
Material and labour for repair/rewinding of spring charging motor for Indoor/outdoor type, 11 KV, VCB,operated on 230 volts AC/ DC complete all as specified and directed by EIC.
M & L for replacement of battery charger 24 Volts output 5 Amps, Input 88V - 265 Volts AC complete all as directed by Engr-in-Charge. Make - Alan or equivalent
M&L for interchanging of existing unserviceable relay at CPH 11 KV & 33 KV RMU feeder from another existing RMU at CPH power house complete with wiring and testing all as directed by Engr-in-Charge.
Material and labour in replacement of old unserviceable LA station class heavy duty, gap less confirming to IS 3070 having having system voltage 33 KV highest system voltage 36 KV, system fault level 25 KA, LA rated voltage 42 KV, maximum continuous operationg voltage 36 KV rms, nominal discharge current 10 KAp, rated frequency 50Hz complete with all fittings suitable for 33 KV, 3 phase, earth distribution system complete all as specified. Make:-/Oblum/JB/Pactil.
Supply, installation, testing and commissioning in replacement of outdoor type oil cooled single phase Current Transformer (CT) set of three with double wound, dual ratio C.T.'s 60-30A/5-5A suitable for 33 KV 3 phase system 15 VA burden for protection (class 5P10) 15 VA burden for metering (accuracy class 0.2) as per IS: 2705-1992 complete with necessary connections etc as required complete all as specified and directed.Make: CG/KAPPA/Heptacare Power.
All as per item No 36 above but dual ratio CT 150-75A/5-5A suitable for 33 KV system.
Supply, installation, testing and commissioning in replacement of outdoor type oil cooled single phase HT Potential Transformer (PT) set of three suitable for 33 KV / 110 Volt outdoor type, 3 Phase system, 15 VA burden for protection (accuracy class 0.1) as per IS: 2705-1992 complete with necessary connections etc as required complete all as specified and directed.Make: CG/KAPPA/Heptacare Power.
Supply and fix in replacement of 33 kv RMU PT fuse 0.5 Amps AVT type complete all as directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5m wide and n.exc. 1.5m in depth for laying of cable and foundation in soft/loose soil complete all as specified and directed.
Removing excavated material (soil/rock) and depositing at a distance not exceeding 50m where directed.
Returning filling in and well ramming in layers n. exc. 25cm including spreading, leveling and watering all as specified and directed.
M&L for river sand cushioning to underground cable for cushioning 8cm below the cable and 15cm above cable all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1, flat size 300 mm x 180 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables for protection.
Re-laying of 40 to 50mm thick roughly hammer dressed stone slab 25 to 30cm wide and not less than 60cm long laid dry and abuting each other with gap between adjacent slab not exceeding 10mm over U/G cable for cable all as directed.
M&L for Auguring/ Driling /Boring of holes under road, pavement, hard standing by trenchless technology by mannual /machine, including fixing of HDPE pipe of 100 mm bore dia complete all as specified and directd by EIC.
M&L for GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall including claps, nut bolt etc all as specified and directed of size 100 mm. Make: Prakash surya/ Jindal/ TATA.
M&L for Trimming and pruning of one tree complete cutting of all branches of any dia but not exceeding 3" up to a safe distance from the over head lines complete all as directed at site and disposal of branches/bushes to a distance and clearing the site all as directed by AGE EM-III. NOTE:- 1. The necessary man power, tool & plant, cutting tools and JCB required for cutting/pruning of branches is deemed to incl in the rate quoted for the job. 2. Proper shut down will be taken by the authorised rep only.
Supply, fixing and lay in replacement of XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor HT 11 KV (E) volts grade cross sectional 95 sq mm 3.0 core, laid in trenches/ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable OH conductor all as specified and directed. Make : Havells/Finolex/Polycab.
Material and labour for end jointing kit, indoor type heat shinkable, 95 sqmm to 120 Sqmm, 3 core suitable for 11 KV (E), XLPE insulated electric power cable complete all as specified and directed. Make : Raychem, Birla 3M, M-seal.
All as per item No 50 above but outdoor type.
All as per item No 50 above but straight through.
M&L for filling of new transformer oil up to minimum level, dielectric strength of oil should not be less than 50KV at 2.5mm. Gap Make: SAVITA
Supply & Fix Post type, porcelain , vitreous, white , green & brown insulator including one galvanised iron long steel spindle, two galvanised iron washer and one galvanised iron nut, working pressure 33000 Volts and of size 290 mm dia x 290 mm height. ISI marked.
Repairing of damaged/unserviceable gang operate devices 33 KV male & female contacts, flexible jumpers, MS jumper carrier and back connector plate incl cleaning and greasing of complete contacts of GOD unit, DO fuse unit and reluging of aluminium conductors connected to top & bottom contacts of GOD and DO units incl. welding and threading of operating rod mechanism complete making serviceable all as directed by Engr-in-Charge. Note:- (i) Necessary parts like knife, male/female contacts and aluminium conductor for jumpering, GI pipe and handle will be Measured and paid separately against respective item. (ii) Rates for Welding machine, threading arrangements, grease, jumper and binding wire deemed to be included in quoted rates.
Supply and fix female contact / fix contact assembly complete suitable for 33 KV GOD horizontal type.
Supply and fix male contact / moving contact pipe assembly complete suitable for 33 KV GOD Horizontal type.
Supply, install, testing and commissioning in replacement of 2 kVA UPS (Inverter) with battery bank for 60 minutes backup at 100 % load as per design & specifications for Substation critical components, Industrial type online UPS with static switches for bypass etc including maintenance free batteries of 12 Volts 180 AH of suitable numbers ad directed for output supply of 230 Volts with battery bank & UPS stand/box as per specified and directed by Engr -in-Charge. Make : - Exide, Amron, SF Sonic, Luminus.
Material and Labour in replacement of maintenance free dry type batteries 2 Volts 110 AH connected in series with suitable copper connector for output voltage 110 Volts DC and wiring connection etc complete internal wiring with copper multistrandard wire of suitable size with lugs/thimbles or critical components complete all as per specified and directed by Engr -in-Charge. Make : - Exide, Amron.
Material and Labour in replacement of Battery Bank stand/rack with door suitable to carry for 55 Nos batteris load/weight complete all as per specified and directed by Engr -in-Charge.
Supply and laying & testing LT cable XLPE insulated screened PVC bedded, galvenised steel strip or wire armoured electric power cable (heavy duty) 1100 Voltts grade with stranded copper conductor of following sizes : - Make: Havells/Polycab/KEI/Finolex (a) 2.5 Sqmm 4 Core
All as per item No 62 above but 2.5 Sqmm 8 Core
All as per item No 62 above but 2.5 Sqmm 12 Core
All as per item No 62 above but 2.5 Sqmm 16 Core
Supply and laying & testing cable XLPE insulated screened PVC bedded, galvenised steel strip or wire armoured electric power cable (heavy duty) 1100 Voltts grade with stranded aluminium conductor of size 10 sqmm 2 Core. Make: Havells/Polycab/KEI/Finolex.
Material and Labour for painting of 33/11 KV main receiving stations yard which includes maximum 12 Nos of steel tubular pole's, complete structure of VCBs, CT & PTs structures, complete busbar structure, channels of 11 mtr poles structure, GOD structures, with stay wire, clamps, nuts and bolts with two coats of aluminium paints of max hight up to 10 mtr from ground level incl painting of PCC platforms/copping with two coats of synthetic enamel paint after cleaning the surface thoroughly of colour complete all as specified and directed by Engr-in-Charge at site. (Location : CPH, Ajmer Line PH, Mini Market PH & Shikargarh Power House).
M&L for Earthing complete with galvanized steel earth plate electrodes 600x600x6 mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to galvanised iron earthing strip 32mm x6mm thick by means of bolt nuts check nuts and washers of galvanized iron or steel all as specified & shown in electrical plate No.3 of MES SSR part-I 2009 connected to earth test point as specified and testing on completion including provision of 40 mm dia light grade pipe up to 7.5 mtr length as protection & watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of soil incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, all as directed at site. NOTE:- Rate included for excavation & earth work in any type of strata as shown in electrical plate No 3.
M&L for Earthing complete with copper earth plate electrodes 600x600x3.15 mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to copper earthing strip 20mm x 3mm thick by means of bolt nuts check nuts and washers complete all as specified & shown in electrical plate No.3 of MES SSR part-I 2009 connected to earth test point as specified and testing on completion including provision of 40 mm dia light grade pipe up to 7.5 mtr length as protection & watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of soil incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, all as directed at site. NOTE:- Rate included for excavation & earth work in any type of strata as shown in electrical plate No 3.
Shri Electrical Enterprises
SHISHODIA ENTERPRISES
M/S JAGDAMBA ENTERPRISES
SANJOLI CONSTRUCTION COMPANY
Pioneer Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .