| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.6 LAccepted-AOC 141 SHANTI NAGAR MODEL TOWN MODEL TOWN PANIPAT HARYANA 132103 | PANIPAT | HARYANA | 132103 | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹46.9 L+₹1.3 L (2.94%)Rejected-Finance 20 SC BOSE COLONY GALL NO 2 DEFENCE LAB ROAD RATNADA JODHPUR 342001 | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹50.3 L+₹4.7 L (10.3%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTERS SARU SECTION ROAD JAMNAGAR 381008 | JAMNAGAR | 381008 | L3 | Rejected-Finance Not lowest | |
| 4 | L4₹51.5 L+₹6.0 L (13.1%)Rejected-Finance | L4 | Rejected-Finance Not lowest | |
| 5 | L5₹51.9 L+₹6.4 L (14.0%)Rejected-Finance V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | L5 | Rejected-Finance Not lowest |
Tender Value
₹49.2 L
EMD Value
₹98,500
Closing Date
9 Apr 2024, 6:00 pmClosed
GE AF BARODA
GE AF BARODA DARJIPURA POST VADODARA 390022
PROVISION OF STANDBY DG SET AT HARNI, SPECIAL REPAIR/ REPLACEMENT OF BER DG SET AT OLD STP DARJIPURA AND JAKATNAKA PUMP HOUSE AND PROVISION OF STABILIZED COMMERCIAL POWER SUPPLY AT AF STATION VADODARA
2023_MES_626102_3
8846/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF BARODA
AS PER TENDER DOCUMENTS AND NIT
4 documents required · 4 mandatory
₹500
GE AF BARODA
₹98,500
Yes
7 Jun 2024
21 Mar 2024
11 Apr 2024
21 Mar 2024
9 Apr 2024
28 Mar 2024
Amount
Disconnecting and taking out exsting U/S DG set 30 KVA and depositing to E/M store yard complete all as specified and directed.
Disconnecting and taking out exsting U/S DG set 62.5 KVA and depositing to E/M store yard complete all as specified and directed.
Supply, installation, testing and commissioning of Silent type Diesel Engine Generating set 415 volts 30 KVA (CPCB-II compliant) or nearest higher size available, 3 phase 0.8 power factor, 50 Hz, 1500 RPM self excited self regulated brushless AC generator installed including control panel, suitable for ambient condition at Baroda and as per latest CPCB Norms of Govt of India and confirming to condition under ISO 3046, IS 10002, BS 5514/5000 with capacity of 10% overloading for one hour in every twelve hour duration and including the following accessories :-
(a) Alternator :- Synchronous alternator rated at 30 KVA suitable for continuous operation at 1500 RPM generating 415 volts at 0.8 p. f (lag) suitable for 50 Hz, three phase, 4 wire system. The alternator shall be brushless,single bearing type,self excited & self regulated with an AVR .The alternator will be suitable for tropical climate and shall generally confirm to IS: 4722 : 2001 The salient features of the alternators are :- (i) +-1% voltage regulation (max) in static conditions. (ii) IP: 23 protections with class ‘H’ insulation. · (iii) Permanent lubricating bearing. · (iv) Permissible overload of 10% for one hour in 12 hours of operation.
(b) Diesel Engine: - Adequate capacity of Diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe medium grade. Lowest exhaust emmissions control device to meet the next genration (CPCB-II compliant). Turbo charger type exhaust manifold. (v) Silencer : Residential type vi) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electric operated/ (as recommended by OEM) for 1% speed /frequecy regulation with Fuel filters and Fuel hoses.
vii) Lub oil System :- Lubricating oil filter, Lubricating oil pump viii) Air Intake System :- Air intake Manifold, Air cleaner dry type ix) Governer mechanical type x) Starting System :- Electric Self starter with and including battary charging alternator 12 Volts DC. xi) Batteries :- Battery of maintenance free of capacity 12 V, 88 AH- 01 No complete with copper conductor multistranded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolyte all as specified. (xii) Start and stop push button (xiii) Ignition key / Switch (xiv) Radiator with blower fan & first fill of coolant oil (xv) Corrosion inhibitor coolant (xvi) Direct fuel injection system through governer mechanical type
xvii) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xviii) Coupling arrngement : - Flexible coupling xix) Accessories :- AVM Pads built- in or separtely mounted to manufactrer base frames.
xx) Base Frame : - Base frame is fabricated either in ISMC channel or in sheet metal. The base frame will be primer coated and painted. The base frame is rugged in construction and designed for mounting Diesel engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. xxi) MS/Steel flexible pipe line to and from the fuel tank to the DG Set. xxii) Battery Charger shall be provided as per manufacturer guidelines. xxiii) 1 No battery of 12 V in charged condition with its leads.
(c) ACOUSTIC ENCLOSURE : Acoustic enclosure shall be and fabricated out of 14 / 16 SWG CRCA steel after 9 tank surface pre-treatment and pure polyster powder coated in fully automatic process . The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Excellent UV resistence High retention of surface finish in outdoor installation and corrosive envirement. Canopy panel and doors shall have inside lining of FIRE-RETARDANT foam as acoustic material & Rock wool for hot zone.Adequate hinged doors shall be provided to canopy, one door shall have glass window for control panel visibility. (i) Manufactured by OEM suitable for 30 KVA DG Set. (ii) It Should be as per latest rules,CPCB norms and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battery should be inside the enclosure. (iv) Fuel tank :-Daily service fuel tank of 8 hours of continuous operation, fabricated form 14 SWG sheet metal complete with drain, inlet and outlet connection and fuel gauge.
(v) Construction Details/specification are as follows : - (aa) Outer body :- CRCA Sheet of 14/ 16SWG mm thick. (ab) Doors :- CRCA sheet of 14/16 SWG (ac) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level. vi) The acoustic should be composite in construction and fully assembled integral unit. vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably internally illuminated by CFL/FTL Lamp fittings. ix) The noise level should be 75 dB at 1m under free field conditions. x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The base frame should be painted with epoxy based black shade. Note :- (i) The complete DG Set shall be procured from authorised OEM of the manufacturer of engine. A certificate in this connection shall be submitted to the GE. (ii) Circulation system to achieve desired inside temperature of acoustic enclosure, if required shall be provided as per OEM recommendation.
(iii) The quoted rate shall deemed to be inclusive of 12 hours test run at site as specified in PS and IS requirements in presence E/M Offr detailed by accepting officer, all testing arrangements/ equipments shall be made available by the contractor for tests. (iv) The quoted rate shall be deemed to be inclusive of first fill of lubricant oil, DHPP for 12 hours testing and final successful acceptance test. (v) Anything missed out above but technically required for efficient working of DG Set is deemed to be included in quoted rates. vi) Design / drawing of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/ panel board manufacturer / supplier & is to be got approved from Engr-in-charge/GE before placing final order to the manufacturer.
vii) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc can be done of both SEB mains & DG mains. viii)The quoted rate shall be deemed to be inclusive of first fill of engine oil & final successful acceptance test.
D) Inbuilt Control Panel chamber/Generator Monitoring Panel :- Control panel shall be fabricated from 16/14 SWG sheet dust and vermin proof with internal wiring and powder coated after seven tank treatment process and have following protection system :- (i) Microprocessor based generator set monitoring and control system fully configurable, consists of LCD display and to monitor operator interface, fault history, alternator data, Engine data, porvision for service adjustement and caliberation of DG control functions, Engine controls, engine protective functions, alternative protective functions etc, Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display (ii) MCCB 63 Amp 25 KA Adustable type -1 Nos (iii) Instrument fuses and control wiring. (iv) Indication lamps for set running (DG ON) and load on. (v) Bus bar including suitable capacity CTs, cable etc. Note:- The contractor shall arrange for artificial load resistive for testing of DG Set at site and the cost is deemed to be included in the quoted rates.
MAKES :- Make of Engine : CUMMINS/KIRLOSKAR GREEN/ASHOK LEYLAND/GREAVES COTTON Make of Alternator : KIRLOSKAR ELECTRIC/ALSTOM/CROMPTON GREAVES/SIEMENS Make of Battery : Exide/AMCO/AMARON.
Supply, installation, testing and commissioning of Silent type Diesel Engine Generating set 415 volts 100 KVA (CPCB-II compliant) or nearest higher size available, 3 phase 0.8 power factor, 50 Hz, 1500 RPM self exicited self regulated brushless AC generator installed including control panel, suitable for ambient condition at Baroda and as per latest CPCB Norms of Govt of India and confirming to condition under ISO 3046, IS 10002, BS 5514/5000 with capacity of 10% overloading for one hour in every twelve hour duration and including the following accessories :- (a) Alternator :- Synchronous alternator rated at 100 KVA suitable for continuous operation at 1500 RPM generating 415 volts at 0.8 p. f (lag) suitable for 50 Hz, three phase, 4 wire system. The alternator shall be brushless,single bearing type,self excited & self regulated with an AVR .The alternator will be suitable for tropical climate and shall generally confirm to IS: 4722 : 2001 The salient features of the alternators are :- (a) +-1% voltage regulation (max) in static conditions. (b) IP: 23 protections with class ‘H’ insulation. · (c) Permanent lubricating bearing. · (d) Permissible overload of 10% for one hour in 12 hours of operation.
(b) Diesel Engine: - Adequate capacity of Diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe medium grade. Lowest exhaust emmissions control device to meet the next genration (CPCB-II compliant). Turbo charger type exhaust manifold.
(v) Silencer : Residential type vi) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electric operated/ (as recommended by OEM) for 1% speed /frequecy regulation. Fuel filters Fuel hoses vi) Lub oil System :- Lubricating oil filter Lubricating oil pump vii) Air Intake System :- Air intake Manifold Air cleaner dry type viii) Governer mechanical type ix) Starting System :- Electric Self starter with and including battary charging alternator 12 Volts DC. x) Batteries :- Battery of maintenance free of capacity 12 V, 100 AH- 01 No complete with copper conductor multistranded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolyte all as specified. (xi) Start and stop push button (xii) Ignition key / Switch (xiii) Radiator with blower fan & first fill of coolant oil (xiv) Corrosion inhibitor coolant (xv) Direct fuel injection system through governer mechanical type
xii) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xiii) Coupling arrngement : - Flexible coupling xiv) Accessories :- AVM Pads built- in or separtely mounted to manufactrer base frames. xv) Base Frame : - Base frame is fabricated either in ISMC channel or in sheet metal. The base frame will be primer coated and painted. The base frame is rugged in construction and designed for mounting Diesel engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator.
xvi) MS/Steel flexible pipe line to and from the fuel tank to the DG Set. xvii) Battery Charger shall be provided as per manufacturer guidelines. xviii) 1 No battery of 12 V in charged condition with its leads. (c) ACOUSTIC ENCLOSURE : Acoustic enclosure shall be powder coated weather proof outdoor type and fabricated out of 14/16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven-tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE-RETARDANT foam as acoustic material & Rock wool for hot zone.Adequate hinged doors shall be provided to canopy, one door shall have glass window for control panel visibility. (i) Manufactured by OEM suitable for 62.5 KVA DG Set. (ii) It Should be as per latest rules,CPCB norms and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battery should be inside the enclosure. (iv) Fuel tank :-Daily service fuel tank of 8 hours of continuous operation, fabricated form 14 SWG sheet metal complete with drain, inlet and outlet connection and fuel gauge.
(v) Construction Details/specification are as follows : - (aa) Outer body :- CRCA Sheet of 14/16 SWG . (ab) Doors :- CRCA sheet of 14/16 SWG . (ac) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level. vi) The acoustic should be composite in construction and fully assembled integral unit.
vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably internally illuminated by CFL/FTL Lamp fittings. ix) The noise level should be 75 dB at 1m under free field conditions. x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The base frame should be painted with epoxy based black shade. Note :- (i) The complete DG Set shall be procured from authorised OEM of the manufacturer of engine. A certificate in this connection shall be submitted to the GE. (ii) Circulation system to achieve desired inside temperature of acoustic enclosure, if required shall be provided as per OEM recommendation.
(iii) The quoted rate shall deemed to be inclusive of 12 hours test run at site as specified in PS and IS requirements in presence E/M Offr detailed by accepting officer, all testing arrangements/ equipments shall be made available by the contractor for tests. (iv) The quoted rate shall be deemed to be inclusive of first fill of lubricant oil, DHPP for 12 hours testing and final successful acceptance test. (v) Anything missed out above but technically required for efficient working of DG Set is deemed to be included in quoted rates. vi) Design / drawing of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/ panel board manufacturer / supplier & is to be got approved from Engr-in-charge/GE before placing final order to the manufacturer. vii) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc can be done of both SEB mains & DG mains. viii)The quoted rate shall be deemed to be inclusive of first fill of engine oil & final successful acceptance test.
(d) Inbuilt Control Panel chamber/Generator Monitoring Panel :- Control panel shall be fabricated from 16/14 SWG sheet dust and vermin proof with internal wiring and powder coated after seven tank treatment process and have following protection system :- (i) Microprocessor based generator set monitoring and control system fully configurable, consists of LCD display and to monitor operator interface, fault history, alternator data, Engine data, porvision for service adjustement and caliberation of DG control functions, Engine controls, engine protective functions, alternative protective functions etc, Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display (ii) MCCB 160 Amp 35 KA Adustable type -1 Nos (iii) Instrument fuses and control wiring. (iv) Indication lamps for set running (DG ON) and load on. (v) Bus bar including suitable capacity CTs, cable etc.
Note:- The contractor shall arrange for artificial load resistive for testing of DG Set at site and the cost is deemed to be included in the quoted rates. MAKES :- Make of Engine : CUMMINS/KIRLOSKAR GREEN/ASHOK LEYLAND/GREAVES COTTON Make of Alternator : KIRLOSKAR ELECTRIC/ALSTOM/CROMPTON GREAVES/SIEMENS Make of Battery : Exide/AMCO/AMARON.
Material and labour for making DG set platform suitable DG set 100 KVA size 5 mtr x 3 .5 Mtr and Height 900mm from ground level GL including excavation in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in cm 1:6, PCC 1:2:4 type B1 in copping, plaster 10mm thick in cm 1:6 om brick /complete surface PCC 1:4:8 type B1 sub base 75mm thick, as in flour RCC 1:2:4 type B1 250mm thick floor with 10mm dia bar using extra cement returning filling and removal on surplus soil, 3 coats of white washing on cement work for including ramp/ steps of suitable DG set complete all as specified and as directed.
Supply, installation, testing and commissioning of Silent type Diesel Engine Generating set 415 volts Not less than 62.5 KVA (CPCB-II Complaint) or nearest higher size available, 3 phase 0.8 power factor, 50 Hz, 1500 RPM self exicited self regulated brushless AC generator installed including control panel, suitable for ambient condition at Baroda and as per latest CPCB Norms of Govt of India and confirming to condition under ISO 3046, IS 10002, BS 5514/5000 with capacity of 10% overloading for one hour in every twelve hour duration and including the following accessories :- (a) Alternator :- Synchronous alternator rated at 62.5 KVA suitable for continuous operation at 1500 RPM generating 415 volts at 0.8 p. f (lag) suitable for 50 Hz, three phase, 4 wire system. The alternator shall be brushless,single bearing type,self excited & self regulated with an AVR .The alternator will be suitable for tropical climate and shall generally confirm to IS: 4722 : 2001 The salient features of the alternators are :- (a) +-1% voltage regulation (max) in static conditions. (b) IP: 23 protections with class ‘H’ insulation. · (c) Permanent lubricating bearing. · (d) Permissible overload of 10% for one hour in 12 hours of operation.
(b) Diesel Engine: - Adequate capacity of Diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven.
iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe medium grade. Lowest exhaust emmissions control device to meet the next genration (CPCB-II compliant). Turbo charger type exhaust manifold. (v)Silencer : Residential type vi) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electric operated/ (as recommended by OEM) for 1% speed /frequecy regulation. Fuel filters Fuel hoses
vi) Lub oil System :- Lubricating oil filter Lubricating oil pump vii) Air Intake System :- Air intake Manifold Air cleaner dry type viii) Governer mechanical type ix) Starting System :- Electric Self starter with and including battary charging alternator 12 Volts DC. x) Batteries :- Battery of maintenance free of capacity 12 V, 100 AH- 01 No complete with copper conductor multistranded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolyte all as specified. (xi) Start and stop push button (xii) Ignition key / Switch (xiii) Radiator with blower fan & first fill of coolant oil (xiv) Corrosion inhibitor coolant (xv) Direct fuel injection system through governer mechanical type
xii) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xiii) Coupling arrngement : - Flexible coupling xiv) Accessories :- AVM Pads built- in or separtely mounted to manufactrer base frames.
xv) Base Frame : - Base frame is fabricated either in ISMC channel or in sheet metal. The base frame will be primer coated and painted. The base frame is rugged in construction and designed for mounting Diesel engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. xvi) MS/Steel flexible pipe line to and from the fuel tank to the DG Set. xvii) Battery Charger shall be provided as per manufacturer guidelines. xviii) 1 No battery of 12 V in charged condition with its leads.
(c) ACOUSTIC ENCLOSURE : Acoustic enclosure shall be powder coated weather proof outdoor type and fabricated out of 14/16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven-tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE-RETARDANT foam as acoustic material & Rock wool for hot zone.Adequate hinged doors shall be provided to canopy, one door shall have glass window for control panel visibility. (i) Manufactured by OEM suitable for 62.5 KVA DG Set. (ii) It Should be as per latest rules,CPCB norms and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battery should be inside the enclosure. (iv) Fuel tank :-Daily service fuel tank of 8 hours of continuous operation, fabricated form 14/16 SWG sheet metal complete with drain, inlet and outlet connection and fuel gauge. (v) Construction Details/specification are as follows : - (aa) Outer body :- CRCA Sheet of 14/16 SWG .
(ab) Doors :- CRCA sheet of 14/16 SWG . (ac) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level. vi) The acoustic should be composite in construction and fully assembled integral unit. vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably internally illuminated by CFL/FTL Lamp fittings. ix) The noise level should be 75 dB at 1m under free field conditions. x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The base frame should be painted with epoxy based black shade. Note :- (i) The complete DG Set shall be procured from authorised OEM of the manufacturer of engine. A certificate in this connection shall be submitted to the GE. (ii) Circulation system to achieve desired inside temperature of acoustic enclosure, if required shall be provided as per OEM recommendation.
(iii) The quoted rate shall deemed to be inclusive of 12 hours test run at site as specified in PS and IS requirements in presence E/M Offr detailed by accepting officer, all testing arrangements/ equipments shall be made available by the contractor for tests. (iv) The quoted rate shall be deemed to be inclusive of first fill of lubricant oil, DHPP for 12 hours testing and final successful acceptance test. (v) Anything missed out above but technically required for efficient working of DG Set is deemed to be included in quoted rates. vi) Design / drawing of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/ panel board manufacturer / supplier & is to be got approved from Engr-in-charge/GE before placing final order to the manufacturer.
vii) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc can be done of both SEB mains & DG mains. viii)The quoted rate shall be deemed to be inclusive of first fill of engine oil & final successful acceptance test.
(d) Inbuilt Control Panel chamber/Generator Monitoring Panel :- Control panel shall be fabricated from 16/14 SWG sheet dust and vermin proof with internal wiring and powder coated after seven tank treatment process and have following protection system :- (i) Microprocessor based generator set monitoring and control system fully configurable, consists of LCD display and to monitor operator interface, fault history, alternator data, Engine data, porvision for service adjustement and caliberation of DG control functions, Engine controls, engine protective functions, alternative protective functions etc, Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display (ii) MCCB 100 Amp 25 KA Adustable type -1 Nos (iii) Instrument fuses and control wiring. (iv) Indication lamps for set running (DG ON) and load on. (v) Bus bar including suitable capacity CTs, cable etc.
Note:- The contractor shall arrange for artificial load resistive for testing of DG Set at site and the cost is deemed to be included in the quoted rates. MAKES :- Make of Engine : CUMMINS/KIRLOSKAR GREEN/ASHOK LEYLAND/GREAVES COTTON Make of Alternator : KIRLOSKAR ELECTRIC/ALSTOM/CROMPTON GREAVES/SIEMENS Make of Battery : Exide/AMCO/AMARON.
Material and labour for making DG set platform suitable DG set up to 62.5 KVA size 5 mtr x 3 Mtr and Height 0.6 Mtr from ground level GL including excavation in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in cm 1:6, PCC 1:2:4 type B1 in copping, plaster 10mm thick in cm 1:6 om brick /complete surface PCC 1:4:8 type B1 sub base 75mm thick, as in flour RCC 1:2:4 type B1 250mm thick floor with 10mm dia bar using extra cement returning filling and removal on surplus soil, 3 coats of white washing on cement work for fixing transformer including ramp of suitable DG set complete all as specified and as directed.
Supply, installation, testing and commissioning of factory made, outdoor type, AMF Panel board, suitable for 30 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12 V,15 A all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description complete all as specified and as directed.
(o) Neutral link rated current 15 A -01 No (p) Aux supply 12 V DC , voltage sensing relay 415 VAC. - 02 Nos (q) 12 V, 15 Amp battery charger for charging the DG set battery with 2.5 sqmm control cable Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete. (b) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 900mm above ground level, all as directed by Engineer in Charge. (c) AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as directed by Engg-in- Charge.
Supply, installation, testing and commissioning of factory made, outdoor type, AMF Panel board, suitable for 62.5 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12 V,15 A all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description complete all as specified and as directed.
(h) Aux control relay with socket 3 C/O 12 VDC, 30 A - 04 Nos (j) Digital type DC Voltmeter, 0 to 30 VDC - 01 Nos (k) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted - 01 No (l) Miniature circuit breaker , 1 pole 6 Amps with over load & short circuit protection , short circuit strength 10 kA - 06 Nos. (m) Miniature circuit breaker , 1 pole 10 /16 Amps with over load & short circuit protection , short circuit strength 10 KA. - 02 Nos (n) Neutral link rated current 15 A -01 No (o) Aux supply 12 V DC , voltage sensing relay 415 VAC. - 02 Nos (p) 12 V, 15 Amp battery charger for charging the DG set battery with 2.5 sqmm control cable Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete.(b) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 1.2m above ground level, all as directed by Engineer in Charge. (c) AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as specified and directed
Supply, installation, testing and commissioning of factory made, outdoor type, AMF Panel board, suitable for 100 KVA DG set confirming to IS-5039, cubical type base mounting with IP-54 protection, made out of 3.15 mm thick CRCA sheet , 415 Volt, 3 phase , 50 Hz supply mounted on and including MS angle section 40 x 40 x 5 mm frame with front and back openable, double door with provision of locking arrangement dust & vermin proof , gasket, TPN bus bar shall be insulated with colour coated heat shrinkable sleeves and shall be mounted on proper insulator, gland, welding hinges of dust proof, overall powder coated complete including taking down old AMF panel , Controller with battery charger 12 V,15 A all as specified and directed & Consisting of the following equipment connecting up incoming and out going cables complete with glands and lugs and chamber painted with two coats of aluminium paint over a coat of red oxide primer including mounting the chamber with suitable size of bolts/ nuts including taking down existing unserviceable chamber of any description complete all as specified and as directed.
(j) push button with element PB1 - Engine start PB2 - Engine stop PB3 - DG contactor ON PB4 - DG contactor OFF PB5 - Mains contactor ON PB6 - Mains contactor OFF (k) Aux control relay with socket 3 C/O 12 VDC, 30 A - 04 Nos (l) Digital type DC Voltmeter, 0 to 30 VDC - 01 Nos (m) Electronic type Hooter, supply voltage 12 V DC 96 Sqmm flush mounted - 01 No (n) Miniature circuit breaker , 1 pole 6 Amps with over load & short circuit protection , short circuit strength 10 kA - 09 Nos . (o) Miniature circuit breaker , 1 pole 10 /16 Amps with over load & short circuit protection , short circuit strength 10 KA. - 02 Nos
(p) Neutral link rated current 15 A -01 No (q) Aux supply 12 V DC , voltage sensing relay 415 VAC. - 02 Nos (r) 12 V, 15 Amp battery charger for charging the DG set battery with 2.5 sqmm control cable Note :- (a) Quoted rate includes excavation, earth work and PCC work and connection & testing complete. (s) PCC 1:3:6 platform with angle iron frame for mounting AMF panel 900mm above ground level, all as directed by Engineer in Charge. (t) AMF Panel should be mounted on platform of PCC (1:3:6) and supported by Angle sections complete all as directed by Engg-in- Charge.
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 250 Amps complete all as specified and directed
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 200 Amps complete all as specified and directed
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32x6 mm main earthing lead by means of galvanized bolts, nuts and washers with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed
Supply and fixing of GI 40mm dia light grade protection pipe complete all as specified and directed.
Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in soft/loose soil including taking out faulty cable/cable, cable covers and GI pipe complete all as specified and directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed.
M&L for sand cushioning with using clean dry and natural river sand including gently punning below/around cable complete all as specified and directed. Note: Depth of the sand shall be measured after punning.
Supply and laying unreinforced precast concrete cable cover factory made embossed the mark “LT CABLE” LV type1 flat size 250 x 150 x 40 mm laid in trenches complete all as specified and directed.
Material and labour for boring of roads/ hard cemented surface for insertion of 50 mm dia G I pipe and including PCC for laying of cable all as specified and directed.
Supply and fixing of Galvanised steel tubes, light grade 50mm dia for cable protection laid in pole coping , on wall/ under the road complete all as specified and directed Note : Cost of Bends under the coping, breaking of Exsiting PCC for laying of pipe is deemed to be included with unit rate of item.
Supplying, laying and testing of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of size 95 Sqmm, 3.5 Core, including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and Covers shall be measured and paid separately.
Supplying, laying and testing of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of size 70 Sqmm, 3.5 Core, including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and Covers shall be measured and paid separately.
Supplying, laying and testing of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of size 50 Sqmm, 3.5 Core, including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and Covers shall be measured and paid separately.
Supplying, laying and testing of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of size 35 Sqmm, 3.5 Core, including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and Covers shall be measured and paid separately.
Supplying, laying and testing of cable XLPE Insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor, laid in trenches/duct or fied to wall/passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of size 25 Sqmm, 3.5 Core, including disconnnecting/taking out existing unsv/damaged old LT UG cable complete all as specified and directed :- Notes : Earthwork, Sand and Covers shall be measured and paid separately.
Supply and fix IP 43 VTPN DB With MCCB Incomer Distribution Board Loadline DBs are fitted with Bus Bars, Neutral Links, Blanking Plates 04 way, 415 volts, 50 Hz, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting with one MCCB as incommer 100 Amps complete all as specified and directed. Make. Havells/Schneider /Seimens /Legrand. (Note : Extra MCCB SP/TP shall be measured and paid separately under respective items of BOQ.
S & F MCB DB 12 way sheet metal enclosure SPN 240 volts, 50 Hz, with IP-42 protection, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting complete all as specified and directed. Note : Copper thimble shall be used for connection of cable .
S&F Cable jointing kit for 1100V (Earthed) grade cable for straight through joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 35 to 95 sqmm including disconetion of cables from old LT pannel and connection to new Lt pannel with suitable Lugs complete all as specified and directed
Supply, installation, commissioning and testing factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door type size not less then 1500mm (L) x 1400 H x 500 D platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Amps meter with Suitable cable alley and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron 4 Nos each Suitable long welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC 1:2:4 B2 of Suitable size the ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm. Front and back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising complete all as specified and directed:-
Supply and fix MCCB four pole 63 amps FP 415 Volts breaking capacity 20 KA as per IEC 60947-2 complete all as specified and directed
Supply and fix MCB, single pole and neutral link (double pole) 240 volts 40 to 63 Amps capacity B seriesfixed in DB's complete all as specified and directed
Supply and fix MCB, single pole 240 volts 6 to 32 Amps capacity B series fixed in DB's complete all as specified and directed
Supply and fix MCB, single pole 240 volts 40 to 63 Amps capacity B series fixed in DB's complete all as specified and directed
Supply, install, testing and commissioning of 30 KVA STATIC FREQUENCY CONVERTER or Static AC power source out put volatge 220V 3 phase AC specification mentioned as under:- (a) INPUT : 340 TO 460V, 47 TO 53 Hz, 3 phase 4 Wire AC (b) OUTPUT : 220V±1%, 50 Hz ±0.5%, 3 Phase 4 Wire AC (c) RATING : 30 KVA/24KW (d) OUTPUT VOLTAGE : 220V for 3 phase (P – P) (e) LINE & LOAD REGULATION : ±1% (f) OUTPUT VOLTAGE DISTORTION : < 3% FOR LINEAR LOAD (g) INVERTER TECHNIQUE : IGBT BASED PWM (h) OUTPUT OVERLOAD CAPACITY : 150% FOR 10 SECONDS (j) TRANSIENT RESPONSE FOR 100% STEP LOAD : ±8% (k). RECOVERY TO REGULATION BAND : WITHIN 100 MILLI SECONDS (l) GALVANIC ISOLATION : INPUT AND OUTPUT ISOLATED BY INBUILT DOUBLE WOUND ISOLATION TRANSFORMER (m) ENCLOSURE PROTECTION CLASS : IP21 (n) Ambient temprature : upto 45 degree C
(o) PROTECTIONS : INPUT OVER/UNDER VOLTAGE, PHASE FAIL, OUTPUT OVERLOAD, OUTPUT OVER/UNDER,VOLTAGE, DC OVER/UNDER VOLTAGE, HIGH SPEED, FUSES FOR SEMI CONDUCTOR DEVICES & OVERHEAT (p) FRONT PANEL LCD DISPLAY TO SHOW : INPUT VOLTAGES (R, Y, B), OUTPUT VOLTAGES (U, V, W),OUTPUT CURRENT (U, V, W) AND OUTPUT FREQUENCY. (q) LED INDICATIONS TO INDICATE: MAINS ON, OUTPUT ON & FAULT. NATURE OF FAULT WILL BE DISPLAYED IN TEXT FORM ON LCD. complete all as specified and directed.
M&L for providing earthing complete with copper earth plate electrode 60 x 60cm x 3.15mm thick buried directly in ground (Earth pit not less than 3.25 meters deep below ground level) with top edge of the plate not less than 2.5 meters below normal ground level, including providing The chemical should be tested and certified by any international accredited laboratory. The earthhencing compound should be tested referring to protocol IS 1350/&/EC62321/111/54/CDV. The PH value of compound should be between 7 to 8. The content of mercury (Hg) & Hexacromium should be below detection level. The electrode should be tested for salt spray test as per BIS117-09 for corrosion for minimum 500Hrs. including testing on completing, connected to copper earth lead 32x6mm (copper strip) upto 7.5 meter long by means of bolts,nuts check nuts and washers of all galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-1 and connected to and including phophor bronze or copper strip 50x6mm 70mm long 3way test point including necessary excavation/ earth work in any type of soil/rock strata, PCC 1:3:6 type C1 cement concrete 1:2:4 type B1 reinforced with welded steel wire fabric (AMP) not less than 4 KG per Sqm funnel with wire mesh and watering pipe 20 mm dia bore (GI Medium grade), PCC pit with 50mm thick PCC cover etc. including testing on completing including GI protection pipe 40mm dia medium grade for earthing lead complete all as specified and directed including demolition of old unservicable earthing.
Plain cement concrete 1:2:4 ( nominal mix ) type B-1 (using 20 mm graded crushed stone aggregates) as in copings and the like including weathering, slightly rounded or chamfered angles and throating including necessary formwork where required complete all as specified and directed.
Supply and fix copper strip 32 mm x 6 mm complete with new porceline insulator by means of screws of suitable size for isolation of strip complete all as specified and directed.
M K ENGINEERS CO.
M/s SK Traders
KAVYA ENTERPRISES
Electromech Engineers
M/s super construction
Chakshu Enterprise
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .